Standard Supply Each Unipoint controller is supplied complete with DIN rail socket, power connector,
Shipping Details Shipping carton dimensions: H197mm (7.8") x W275mm (10.8") x D36mm (1.4")
gas type stickers and instruction manual.
Approximate weight: 420g (14.8oz)
Find out more
Contact Honeywell Analytics:
www.honeywellanalytics.com
www.honeywell.com
Americas
Honeywell Analytics Inc.
405 Barclay Blvd.
Lincolnshire, IL 60069
USA
Tel: +1 847 955 8200
Toll free: +1 800 538 0363
Fax: +1 847 955 8210
detectgas@honeywell.com
Europe, Middle East, Africa
Life Safety Distribution AG
Wilstrasse 11-U31
CH-8610 Uster
Switzerland
Tel: +41 (0)44 943 4300
Fax: +41 (0)44 943 4398
gasdetection@honeywell.com
Asia Pacific
Honeywell Analytics Asia Pacific
#508, Kolon Science Valley (I)
187-10 Guro-Dong, Guro-Gu
Seoul, 152-050
Korea
Tel: +82 (0)2 2025 0307
Fax: +82 (0)2 2025 0329
analytics.ap@honeywell.com
Please Note:
While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions.
Data may change, as well as legislation, and you are strongly advised to obtain copies of the most recently issued regulations,
standards, and guidelines. This publication is not intended to form the basis of a contract.
Technical Services
ha.us.service@honeywell.com
Honeywell Analytics Lines of Business
Commercial
Vulcain-brand gas detection from standalone units to fully engineered, multipoint systems, all offering cost-effective
regulatory compliance
Renowned Sieger and Manning gas
detection systems with advanced
electrochemical, infrared and open path
sensing technologies
» Applications: oil and gas, cold storage,
water/wastewater treatment,
chemicals, engine rooms, plastics
and fibers, agriculture, printing and
light industrial
laboratories
High Tech/Government
A complete portfolio of gas and chemical
detection instrumentation including
infrared spectroscopy (MST) with no cross
interference, to Chemcassette paper-
based solutions (MDA Scientific) offering
detection down to parts per billion
» Applications: semiconductor
manufacturing and nanotechnology,
aerospace propulsion and safety,
specialty chemicals industry, research
laboratories, emergency response
Portables
Single or multi-gas Lumidor and other
premium detectors with compact,
lightweight designs ranging from
simple alarm only units to advanced,
fully configurable and serviceable
instruments
24/7 global network includes
post-sales service and Systems
Integration teams
» Emergency call out, service
contracts, on/off-site repair, training
and commissioning
» Complete range of spares,
consumables and accessories
HWA6167
Zareba Unipoint controller
The Zareba Unipoint,
a simple DIN rail
mounted controller
Unipoint DIN controller
Typical Applications
• Small and medium integrated systems
• Custom control cabinets and panels
• Unmanned equipment rooms
• Boiler Houses
• HVAC systems
• Analyzer houses
• Car Parks
• Crane cabs
• Laboratories
User Friendly
• Ultra-clear backlit display
• System status codes
• Built-in audiovisual alarms
• Intuitive menu system
• Simple pushbutton operation
• Remote accept, reset and inhibit inputs
Easy to Install
• TS35 (‘top hat’) DIN rail mounting
• Removable terminal connectors.
• Easy access to all terminals
• Additional units clip together
Comprehensive Operation
• 3 wire mV bridge, 2 and 3 wire 4-20mA inputs
• DC operation
• 3 x alarm relays
• 1 x system fault relay
• Field inhibit input (mA versions)
Flexible Operation
• Fully user programmable scale, units
and calibration
• Relays configurable as energized, de-energized,
latching or non-latching, alarm relay on/off delay
• Compatible with a wide range of gas detectors
The Zareba Unipoint is a simple
DIN rail mounted controller offering
integrators a flexible and low cost solution
to incorporate flammable, toxic or oxygen
gas detection into their control systems.
Unipoint can be easily installed into any plastic
or metal enclosure for use indoor or outdoors
and even in potentially explosive atmospheres.
With the addition of one of the Zareba range of
flammable, toxic or oxygen detectors, systems
may be configured to monitor gases in a wide
range of applications from car parks and boiler
houses to analyzer shelters or crane cabs in
offshore facilities.
Two versions of Unipoint are available; one
for mV bridge, catalytic bead type, flammable
gas detector and the other for any 2 or 3 wire
4-20mA type gas detector. Each Unipoint is
easily installed onto the DIN rail via a special
socket (provided) that also interconnects power
to adjacent units. With removable terminal
connectors individual Unipoint controllers can be
easily changed without disturbing other devices.
By clipping together multiple Unipoints small
to medium sized monitoring solutions can be
realized. Each unit includes built-in audiovisual
alarms, three programmable alarm relays and
a fault relay. Gas concentration and system
status is displayed on the backlit LCD and each
controller is fully user programmable via an
intuitive, push button operated menu system.
Configuration menus can be password protected
to prevent unauthorized access. In addition
remote inputs allow accept, reset and inhibit of
alarms without the need to open the enclosure
that the Unipoint is mounted in.
Unipoint’s uncomplicated design makes it
ideal for applications where a simple method
of integrating gas detectors into a 3rd party
control system is required or as part of a small
standalone gas detection solution. All Honeywell
Analytics gas detectors and third party detectors
may be used with Unipoint subject to overall
power requirements.
Installation details
Dimensions
Installation
Electrical
DIN rail
1" = 25.4mm
Terminal detail
1
+
2
S
3
-
NO
4
C
5
NC
6
R
7
I
8
C
9
NO
10
C
11
NC
12
NO
13
C
14
NC
15
NO
16
C
17
NC
18
Max number of controllers
on one power rail
Detector
type
Max number
of controllers
3 wire mV8
2 wire mA8
3 wire mA4
wiring of power rail in parallel allows larger
systems to be constructed
Detector
Fault
Reset
Inhibit
Common
Alarm 1
Alarm 2
Alarm 3
Type of DetectorOutput to Detector Recommended Detector
3 wire mV bridge2.4-8.6V, 200mA constant current. Max cable loop
Signalpoint or Sensepoint Flammable
resistance 28 Ohms.
*The detector supply voltage is 1.5Vdc less than the supply to the controller
Controller Power Consumption
Unipoint VersionController StatusRelaysPower
FaultAlarm
Normal operation, no faults, no alarms. Zero cable resistanceEnergizedDe energized2.4W
mV
Normal operation, no faults, no alarms. Max loop cable resistance (28 ohms)EnergizedDe energized3.6W
All alarms, no faults. Max cable resistance (28 ohms)EnergizedEnergized4.8W
mA
1
includes power to detector 2 excludes power to 3 wire mA detector. All controllers with default configuration.
Normal operation, no faults, no alarms. Inclusive of 2 wire signal loop currentEnergizedDe energized1.8W
All alarms, no faults. Inclusive of 2 wire signal loop currentEnergizedEnergized3.0W
1
1
1
2
2
Technical summary
Gas Label Area
Gas Reading
Event Code
Power LED
Fault/
Inhibit LED
Alarm LED
Cancel
Detector Wiring Schematics
3 wire mV (e.g. Signalpoint and Sensepoint Flammable)
2 wire mA (e.g. Signalpoint and Sensepoint Toxic and Oxygen)
Measurement
Units
Up
Enter
Down
General Specification
Use The Zareba Unipoint controller provides integrators with a flexible and low cost solution to the
User interface
OperationTwo pushbuttons for normal operation of resetting alarms and initiating self diagnostic test of system.
Backlit DisplayUnits of measure, digital gas reading and event code
Other IndicationUltra-bright steady/flashing LEDs subject to condition; alarm (red), power (green), fault (amber).
Termination
Environmental
IP Rating Indoor, IP3x, to BS EN 60529:1992 (controller to be installed in suitable enclosure)
Weight 225g (7.94 oz) - Controller only
Operating Temp Range -10°C to +40°C / 14°F to 104°F
Operating Humidity Range 10 to 90%RH (non condensing)
Operating Pressure Range 90-110kPa
Storage -25°C to +60°C / -13°F to +140°F, 20 to 80%RH (non condensing)
Inputs
Supply Nominal 24Vdc (18-32Vdc). Max power mV = 4.8W (including power to detector), mA= 3.0W
Detector Type
Detector Supply
Outputs
Relays
Rating
Default Setting
User Configurable Options
Approvals
EMC/RFIEN50270
Electrical SafetyEN61010, UL61010b
PerformanceATEX measuring function EN61779 (Independent accreditation expected late 2005)
Other
many applications requiring flammable, toxic or oxygen gas detection to be incorporated into
their control systems. Unipoint is designed to use industry standard DIN rail allowing it to be
easily installed into many different types of plastic or metal, indoor or outdoor, hazardous or non
hazardous area enclosures. It is designed for use with any mV flammable gas detector as well
as any 2 or 3 wire 4-20mA gas detector (subject to overall power requirements).
Four buttons for user programmable functions via intuitive menu
In-built audible alarm 63dB at 0.3 meters
Easily accessible plug in screw type terminals. Terminals accept maximum wire diameter 1.5mm
(16 AWG)
(excluding power to 3 wire detector)
3 wire mV bridge
e.g. Sensepoint or
Signalpoint flammable
gas detectors
2.4-8.6V, 200mA constant
current. Maximum loop
resistance: 28 Ohms
Alarm 1
SPCO/3A,
240Vac/28Vdc
(non inductive load)
Non Latching
Normally
de-energized
Energize on alarm
Factory setting
10%FSD
Latching/
non-latching
Energized/
de-energized
Alarm trip point
Rising/falling
Alarm on / off delay
(0 to 900 seconds)*
CE, TUV
2 wire, 4-20mA, loop
powered e.g. Sensepoint
or Signalpoint toxic or
oxygen gas detectors
Input (18-32Vdc)-1.5Vdc,
30mA max
Alarm 2
SPCO/3A,
240Vac/28Vdc
(non inductive load)
Non Latching
Normally
de-energized
Energize on alarm
Factory setting
25%FSD
Latching/
non-latching
Energized/
de-energized
Alarm trip point
Rising/falling
Alarm on / off delay
(0 to 900 seconds)*
3 wire, 4-20mA, source
output e.g. Sensepoint
Plus and Pro flammable,
toxic and oxygen gas
detectors
Input (18-32Vdc)-1.5Vdc,
0.5A max
Alarm 3
SPCO/3A,
240Vac/28Vdc
(non inductive load)
Latching
Normally
de-energized
Energize on alarm
Factory setting
50%FSD
Latching/
non-latching
Energized/
de-energized
Alarm trip point
Rising/falling
Alarm on / off delay
(0 to 900 seconds)*
2
Fault
SPCO/3A,
240Vac/28Vdc
(non inductive load)
Non Latching
Normally
energized
De-energize on
fault/power loss
Latching/
non-latching
Energized/
de-energized
3 wire mA (e.g Sensepoint Plus and Pro all versions)
* Functionality only implemented in units supplied with software version 5V0. Available late 2005.