ii UDC2500 Universal Digital Limit ControllerProduct Manual 3/07
About This Document
Abstract
This document provides descriptions and procedures for the Installation, Configuration, Operation, and Troubleshooting of
your UDC2500 Controller.
Symbol Definitions
The following table lists those symbols used in this document to denote certain conditions.
Symbol Definition
This CAUTION symbol on the equipment refers the user to the Product Manual for
additional information. This symbol appears next to required information in the manual.
WARNING
PERSONAL INJURY: Risk of electrical shock. This symbol warns the user of a
potential shock hazard where HAZARDOUS LIVE voltages greater than 30 Vrms, 42.4
Vpeak, or 60 VDC may be accessible. Failure to comply with these instructions
Protective Earth (PE) terminal. Provided for connection of the protective earth (green
or green/yellow) supply system conductor.
Functional earth terminal. Used for non-safety purposes such as noise immunity
improvement. NOTE: This connection shall be bonded to protective earth at the source
of supply in accordance with national local electrical code requirements.
Earth Ground. Functional earth connection. NOTE: This connection shall be bonded to
Protective earth at the source of supply in accordance with national and local electrical
code requirements.
Chassis Ground. Identifies a connection to the chassis or frame of the equipment shall
be bonded to Protective Earth at the source of supply in accordance with national and
local electrical code requirements.
3/07 UDC2500 Universal Digital Limit ControllerProduct Manual iii
Figure 5-6 Wiring Connections for 0 to 10 Volts___________________________________________ 76
Figure 5-7 Wiring Connections for 0 to 20 mA or 4 to 20 mA Inputs___________________________ 77
Figure 6-1 Wiring Connections for Calibrating Auxiliary Output______________________________ 84
Figure 8-1 UDC2500 Exploded View __________________________________________________ 101
3/07 UDC2500 Universal Digital Limit ControllerProduct Manual ix
1.1 Overview
Function
UDC2500 Limit Controllers accept input signals from any of several types of external
sensors such as Thermocouples (T/Cs) and Resistance Temperature Detectors (RTDs). It
conditions these signals, as necessary, to derive the equivalent Process Variable (PV)
value that drives various circuits in the controller.
The equivalent PV signal is compared with the Limit control set point and any error
signal from the differential amplifier de-energizes the coil of an electromechanical,
single-pole, dual-throw (SPDT) limit output relay.
When de-energized, the output relay “Locks Out” and remains that way until the PV
input signal drops below the High Limit Set Point or goes above the Low Limit Set Point
and the controller is reset manually via the keyboard or from a remote location (Contact
Input Option).
Introduction
1 Introduction
The contact of the output relay terminates at the rear terminal of the controller to which
you make the appropriate field wiring connections.
A flashing “LIMIT” in the lower display indicates that the output relay is de-energized.
Features
• 90 – 264 Vac or 24 Vac/dc Power Supply
• Input/Output Isolation
• Isolated Auxiliary Current Output / Digital Inputs
• Modbus® RS-485 or Ethernet TCP/IP Communications
High Limit Controller
When the PV input signal is below the limit set point, the output relay energizes. If the
PV signal exceeds the limit set point, the output relay de-energizes and the flashing
“LIMIT” display is turned on.
When the PV signal returns to a value below the limit set point, the controller can be
reset manually using the RESET key or Contact Input Option.
Low Limit Controller
When the PV input signal is above the limit set point, the output relay energizes. If the
PV signal falls below the limit set point, the output relay de-energizes and the flashing
“LIMIT” display is turned on.
3/07 UDC2500 Universal Digital Limit ControllerProduct Manual 1
Introduction
When the PV signal returns to a value above the limit set point, the controller can be reset
manually using the RESET key or Contact Input Option.
Easy to read displays
The dedicated vacuum fluorescent displays with multi-language prompts make the
operator interface easy to read, understand and operate. Programmed sequences of
displays assure quick and accurate entry of all configurable parameters.
Easy to operate
Simple keystrokes let you select input and range configuration, set the operating
parameters that meet you process control needs now, and change them later to meet new
ones.
Mount anywhere
This instrument is intended for industrial control applications. It must be panel mounted
with the wiring terminals enclosed within the panel. The instrument is environmentally
hardened and, when suitably enclosed, can be mounted anywhere in plant or factory, on
the wall, or even on the process machine itself. The front face is NEMA3 and IP55 rated
and can be easily upgraded to NEMA4X and IP66 for the most severe hose-down
applications. It withstands ambient temperatures up to 55°C (133°F) and resists the
effects of vibration and shock.
Figure 1-1 UDC2500 Operator Interface
2 UDC2500 Universal Digital Limit ControllerProduct Manual 3/07
1.1.1 Function of keys
Table 1-1 shows each key on the operator interface and defines its function.
Key Function
• Places the controller in the Configuration Set Up group select mode.
SetupSetup
FunctionFunctionFunction
Sequentially displays Set Up groups and allows the FUNCTION key to
display individual functions in each Set Up group.
• Used in conjunction with the SET UP key to select the individual functions of
a selected Configuration Set Up group.
• Used during field calibration procedure.
Introduction
Table 1-1 Function of Keys
Lower
Lower
Lower
Display
Display
Display
Reset
Reset
Reset
Select
Select
Select
M-A
M-A
M-A
SP
SP
SP
Run
Run
Run
Hold
Hold
Hold
• Selects an operating parameter to be shown in the lower display.
MAN-AUTO This function is not available on the Limit Controller.
RESET Reset the Limit Relay.
This key does not function on the Limit Controller
• Acknowledges a latched alarm 1.
• Acknowledges Diagnostic Messages.
• Increases the selected parameter value.
• Decreases the selected parameter value.
3/07 UDC2500 Universal Digital Limit ControllerProduct Manual 3
Introduction
1.2 Process Instrument Explorer Software
Overview
Process Instrument Explorer lets you configure your instrument on a desktop/laptop or
Pocket PC. For details see Process Instrument Explorer manual #51-52-25-131.
Features
• Create configurations with intuitive software program running on either a Pocket
PC, a Desktop or a laptop computer. ·
• Create/edit configurations live, just connect software to controller via comm port.·
• Create/edit configurations offline and download to controller later via comm. port.·
• Port types available on every UDC2500:·
o infrared,·
o RS 485,
o Ethernet.·
• Same port types on UDC3200 and UDC3500 allow interconnectivity.
• This software is available in English, Spanish, Italian, German and French.
Figure 1-2 Screen capture of Process Instrument Explorer running on a Pocket
PC
4 UDC2500 Universal Digital Limit ControllerProduct Manual 3/07
Infrared communications
The infrared connection provides a non-intrusive wireless connection with the instrument
and maintains NEMA4X AND IP66 integrity.
No need to get access to the back of the controller to communicate with the instrument,
no need to take your screw driver to wire the communication cable, no wiring mistake
possible. You can now duplicate an instrument’s configuration, upload or download a
new configuration in a matter of seconds, just by pointing your Pocket PC in the direction
of the instrument.
It takes just a few seconds to upload a configuration from an instrument. You can then
save the configuration file onto your PC or pocket PC for review, modification or
archiving. Furthermore, this software also gives you important maintenance information
on the controller: instantly, get information on the current operating parameters, digital
inputs and alarm status, identify internal or analog input problems.
Question: What if I have several controllers on the same panel? How can I be sure I am
communicating with the correct one?
Answer: The infrared port of the controller is normally “off”. You activate the infrared
port by pressing any controller’s key. You can now communicate. After 4 minutes, the
port will be shut down again. Also, in the Communications Group “IR ENABLE” may be
disabled to prohibit IR communications.
Introduction
Figure 1-3 Depiction of infrared communications
3/07 UDC2500 Universal Digital Limit ControllerProduct Manual 5
Introduction
1.3 CE Conformity (Europe)
This product is in conformity with the protection requirements of the following European
Council Directives:
Directive. Conformity of this product with any other “CE Mark” Directive(s) shall not be
assumed.
Product Classification: Class I: Permanently connected, panel-mounted Industrial
Control Equipment with protective earthing (grounding) (EN61010-1).
Enclosure Rating: This controller must be panel-mounted with the rear terminals
enclosed within the panel. The front panel of the controller is rated at NEMA4X and IP66
when properly installed.
Installation Category (Overvoltage Category): Category II (EN61010-1)
Pollution Degree: Pollution Degree 2: Normally non-conductive pollution with
occasional conductivity caused by condensation. (Ref. IEC 664-1)
EMC Classification: Group 1, Class A, ISM Equipment (EN61326, emissions), Industrial
Equipment (EN61326, immunity)
Method of EMC Assessment: Technical File (TF)
73/23/EEC, the Low Voltage Directive, and 89/336/EEC, the EMC
Declaration of Conformity: 51453655
Deviation from the installation conditions specified in this manual, and the special
conditions for CE conformity in Subsection
with the Low Voltage and
ATTENTION
EMC Directives.
2.1, may invalidate this product’s conformity
The emission limits of EN61326 are designed to provide reasonable protection
against harmful interference when this equipment is operated in an industrial
environment. Operation of this equipment in a residential area may cause harmful
interference. This equipment generates, uses, and can radiate radio frequency
energy and may cause interference to radio and television reception when the
equipment is used closer than 30 meters (98 feet) to the antenna(e). In special
cases, when highly susceptible apparatus is used in close proximity, the user may
have to employ additional mitigating measures to further reduce the
electromagnetic emissions of this equipment.
WARNING
If this equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
6 UDC2500 Universal Digital Limit ControllerProduct Manual 3/07
2.1 Overview
Introduction
Installation of the UDC2500 consists of mounting and wiring the controller according to
the instructions given in this section. Read the pre-installation information, check the
model number interpretation (Subsection
selections, then proceed with installation.
What’s in this section?
The following topics are covered in this section.
2.1 Overview 7
Installation
2 Installation
2.3), and become familiar with your model
TOPIC See Page
2.2 Condensed Specifications 8
2.3 Model Number Interpretation 11
2.4 Control and Alarm Relay Contact Information 13
2.5 Mounting 14
2.6 Wiring 16
2.7 Wiring Diagrams
Composite Wiring Diagram
AC Line Voltage
Input 1 Connections
18
18
19
20
Relay Output
Electromechanical
Solid State
Open Collector
RS-422/485 Communications Option
Ethernet Communications Option
Auxiliary Output and Digital Inputs Option
Transmitter Power using Open Collector Output
Transmitter Power using Auxiliary Output
21
21
22
22
23
24
24
25
2.8 Limit Control Application Diagram25
3/07 UDC2500 Universal Digital Limit ControllerProduct Manual 7
Installation
Pre-installation Information
If the controller has not been removed from its shipping carton, inspect the carton for
damage then remove the controller.
• Inspect the unit for any obvious shipping damage and report any damage due to
transit to the carrier.
• Make sure a bag containing mounting hardware is included in the carton with the
controller.
• Check that the model number shown on the inside of the case agrees with what you
have ordered.
2.2 Condensed Specifications
We recommend that you review and adhere to the operating limits listed in Table 2-1
when you install your controller.
Table 2-1 Condensed Specifications
Analog Inputs
Analog Input Signal
Failure Operation
Stray Rejection Common Mode
Digital Inputs (One)
(Optional)
Accuracy:
± 0.25% of full scale typical (± 1 digit for display)
Can be field calibrated to ± 0.05% of full scale typical
16-bit resolution typical
Sampling Rate: Both inputs are sampled six times per second
Temperature Stability: ± 0.01% of Full Scale span / ˚C change—typical
Input Impedance:
4-20 Milliampere Input: 250 ohms
0-10 Volt Input: 200K ohms
All Others: 10 megohms
AC (50 or 60 Hz): 120 dB (with maximum source impedance of 100 ohms) or ± 1 LSB (least
significant bit) whichever is greater with line voltage applied.
DC: 120 dB (with maximum source impedance of 100 ohms) or a ±1 LSB whichever is
greater with 120 Vdc applied.
DC (to 1 KHz): 80 dB (with maximum source of impedance of 100 ohms) or ±1 LSB
whichever is greater with 50 Vac applied.
Normal ModeAC (50 or 60 Hz): 60 dB (with 100 % span peak-to-peak maximum)
+30 Vdc source for external dry contacts or isolated solid state contacts. Digital Inputs are
isolated from line power, earth ground, analog inputs and all outputs except for the Second
Current Output.
8 UDC2500 Universal Digital Limit ControllerProduct Manual 3/07
Zero-crossing type SPST solid state contacts consisting of a triac N.O. output. Internally
socketed.
Resistive Load: 1.0 amp @ 25°C and 120 or 240 Vac, 0.5 amp @ 55°C and 120 or 240 Vac
Inductive Load: 50 VA @ 120 Vac or 240 Vac
Minimum Load: 20 milliamps
Open Collector Outputs (One or Two)
Socketed assembly replacing a relay. Opto-isolated from all other circuits except current
output and not from each other. Internally powered @ 30 Vdc.
Note: Applying an external power supply to this output will damage the instrument.
Maximum Sink Current: 20 mA
Short-circuit current limit: 100 mA
One or two SPDT Electromechanical relays.
Up to four setpoints are independently set as high or low alarm, two for each relay. Setpoint
can be on Process Variable, Deviation, PV Rate, Communication Shed or Thermocouple
Health. A single adjustable hysteresis of 0.0 to 100.0% is provided.
Alarm Relay Contacts Rating: Resistive Load: 5 amps at 120 Vac or 240 Vac or 30 Vdc
Analog Inputs: are isolated from all other circuits at 850Vdc for 2 seconds, but not from each
other.
Analog Outputs: are isolated from all other circuits at 850Vdc for 2 seconds.
AC Power: is electrically isolated from all other inputs and outputs to withstand a HIPOT
potential of 1900Vdc for 2 seconds per Annex K of EN61010-1.
Relay Contacts: with a working voltage of 115/230 Vac, are isolated from each other and all
other circuits at 345Vdc for 2 seconds.
Baud Rate: 4800, 9600,19,200 or 38,400 baud selectable
Data Format: Floating point or integer
Length of Link:
2000 ft (600 m) max. with Belden 9271 Twinax Cable and 120 ohm termination resistors
4000 ft. (1200 m) max. with Belden 8227 Twinax Cable and 100 ohm termination resistors
Link Characteristics: Two-wire, multi-drop Modbus RTU protocol, 15 drops maximum or up
to 31 drops for shorter link length.
Type: 10Base-T
Length of Link: 330 ft. (100 m) maximum
Link Characteristics: Four-wire, single drop, five hops maximum
IP Address: IP Address is 10.0.0.2 as shipped from the Factory
Recommended network configuration: Use Switch rather than Hub in order to maximize
UDC Ethernet performance
Type: Serial Infrared (SIR)
Length of Link: 3 ft. (1 m) maximum for IrDA 1.0 compliant devices
Baud Rate: 19,200 or 38,400 baud selectable
20 VA maximum (90 to 264 Vac)
15 VA maximum (24 Vac/dc)
10A maximum for 4 ms (under operating conditions), reducing to a maximum of 225 mA (90
to 264 Vac operation) or 750 mA (24 Vac/dc operation) after one second.
CAUTION
power is supplied. Otherwise, the instruments may not start up normally due to voltage drop
from the inrush current.
= 0.4): 3 amps @ 130 Vac or 250 Vac
When applying power to more than one instrument, make sure that sufficient
3/07 UDC2500 Universal Digital Limit ControllerProduct Manual 9
Installation
Weight
3 lbs. (1.3 kg)
Environmental and Operating Conditions
Parameter Reference Rated Operative
Ambient Temperature
Relative Humidity
Vibration
Frequency (Hz)
Acceleration (g)
Mechanical Shock
Acceleration (g)
Duration (ms))
Line Voltage (Vdc)
Line Voltage (Vac)
90 to 240 Vac
24 Vac
Frequency (Hz)
(For Vac)
25 ± 3 °C
77 ± 5 °F
10 to 55* 10 to 90* 5 to 90* 5 to 95*
0
0
0
0
+24 ± 1 22 to 27 20 to 27 - -
120 ± 1
240 ± 2
24 ± 1
50 ± 0.2
60 ± 0.2
15 to 55 °C
58 to 131 °F
0 to 70
0.4
1
30
90 to 240
20 to 27
49 to 51
59 to 61
Limits
0 to 55 °C
32 to 131 °F
0 to 200
0.6
5
30
90 to 264
20 to 27
48 to 52
58 to 62
Transportation and
Storage
–40 to 66 °C
–40 to 151 °F
0 to 200
0.5
20
30
- -
- -
- -
- -
- -
* The maximum moisture rating only applies up to 40 °C (104 °F). For higher temperatures, the RH specification is
derated to maintain constant moisture content.
10 UDC2500 Universal Digital Limit ControllerProduct Manual 3/07
Installation
2.3 Model Number Interpretation
Introduction
Write your controller’s model number in the spaces provided below and circle the corresponding
items in each table. This information will also be useful when you wire your controller.
KEY NUMBER - UDC2500 Single Loop Controller
Digital Controller for use with 90 to 264Vac PowerDC2500
Digital Controller for use with 24Vac/dc PowerDC2501
TABLE I - Specify Contro l Output and/or AlarmsSelection
Description
Selection
Availability
Availability
DC2500 2501
Output #1
Output #2 and Alarm
#1 or Alarms 1 and 2
TABLE II - Communications and Software Selections
Communications
Software Selections
Reserved
Infrared interface
TABLE III - Input 1 can be changed in the field using external resistorsSelecti o n
Input 1
Input 2
Electro Mechanical Relay (5 Amp Form C)
Solid State Relay (1 Amp)
Open Collector transistor output
No Additional Outputs or Alarms
One Alarm Relay Only
E-M Relay (5 Amp Form C) Plus Alarm 1 (5 Amp Form C Relay)
Solid State Relay (1 Amp) Plus Alarm 1 (5 Amp Form C Relay)
Open Collector Plus Alarm 1 (5 Amp Form C Relay)
None
Auxiliary Output/Digital Inputs (1 Aux and 1 DI or 2 DI)
RS-485 Modbus Plus Auxiliary Output/Digital Inputs
CE, UL and CSA (Standard)
CE, UL, CSA and FM
None
Stainless Steel Customer ID Tag - 3 lines w/22 characters/line
None
None
None
TABLE V - Product Manuals
Product Information on CD - All Languages0 _
English Manual (51-52-25-127)E _
Manuals
Certificate
French Manual (51-52-25-127-FR)F _
German Manual (51-52-25-127-DE)G _
Italian Manual (51-52-25-127-IT)I _
Spanish Manual (51-52-25-127-SP)
None
Certificate of Conformance (F3391)
3/07 UDC2500 Universal Digital Limit ControllerProduct Manual 11
Installation
Limit Controller Restrictions/Comments:
1. FM approved units with communications are limited to read only.
2. FM approved units are restricted to TC and RTD type inputs.
3. UL listed for regulatory use only.
b
c
II
Input 2 Not Available with Limit Model
_ L _
Figure 2-1 Model Number Interpretation
12 UDC2500 Universal Digital Limit ControllerProduct Manual 3/07
2.4 Limit and Alarm Relay Contact Information
Limit Relay
ATTENTION
The Limit relay is designed to operate in a Failsafe mode. This results in momentary
(5 seconds maximum) limit action when power is initially applied, until the unit completes selfdiagnostics. If power is lost to the unit, the Limit Control Relay will still function.
Table 2-2 Limit Relay Contact Information
Installation
Power
Off
On
Alarm Relays
ATTENTION
Alarm relays are designed to operate in a failsafe mode (that is, de-energized during alarm
sate). This results in alarm actuation when power is OFF or when initially applied, until the unit
completes self diagnostics. If power is lost to the unit, the alarms will de-energize and thus the
alarm contacts will close.
Power
Limit
Control
Relay
Wiring
N.O. Open Open
N.C. Closed
N.O. Closed Open
N.C. Open
Variable NOT in Limit State Variable in Limit State Unit
Relay
Contact
Indicators Relay
Contact
Off
Closed
Off
Closed
Table 2-3 Alarm Relay Contact Information
Alarm Relay
Wiring
Variable NOT in Alarm State Variable in Alarm State Unit
Relay
Contact
Indicators Relay
Contact
Indicators
Off
On
Indicators
Off
On
3/07 UDC2500 Universal Digital Limit ControllerProduct Manual 13
N.O. Open Open
N.C. Closed
N.O. Closed Open
N.C. Open
Off
Closed
Off
Closed
Off
On
Installation
2.5 Mounting
Physical Considerations
The controller can be mounted on either a vertical or tilted panel using the mounting kit
supplied. Adequate access space must be available at the back of the panel for installation
and servicing activities.
• Overall dimensions and panel cutout requirements for mounting the controller are
shown in
• The controller’s mounting enclosure must be grounded according to CSA standard
C22.2 No. 0.4 or Factory Mutual Class No. 3820 paragraph 6.1.5.
• The front panel is moisture rated NEMA3 and IP55 rated and can be easily upgraded
to NEMA4X and IP66.
Overall Dimensions
mm
inches
Figure 2-2.
Max. panel thickness
19,1
.75
9,0
0,35
92,0 + 0,8
-0,00
3,62 + 0,03
-0,00
Panel
Cutout
92,0 + 0,8
-0,00
3,62 + 0,03
-0,00
Figure 2-2 Mounting Dimensions (not to scale)
17,9
0,70
113,1
4,45
90,6
3,57
108,6
4,28
14 UDC2500 Universal Digital Limit ControllerProduct Manual 3/07
Mounting Method
Before mounting the controller, refer to the nameplate on the outside of the case and
make a note of the model number. It will help later when selecting the proper wiring
configuration.
Attach screws and
washers here for
water protection
Installation
Mounting Clips
Mounting Procedure
Step Action
Mark and cut out the controller hole in the panel according to the dimension
1
information in
Orient the case properly and slide it through the panel hole from the front.
2
Remove the mounting kit from the shipping container and install the kit as follows:
3
•For normal installation two mounting clips are required. Insert the prongs of the
clips into the two holes in the top and bottom center of the case (
•For water-protected installation four mounting clips are required. There are two
options of where to install the mounting clips: 1) Insert the prongs of the clips into
the two holes on the left and right side of the top and bottom of the case or 2) on
the center on each of the four sides (
•Tighten screws to 2 lb-inch (22 N•cm) to secure the case against the panel.
CAUTION: Over tightening will cause distortion and the unit may not seal properly.
For water-protected installations, install four screws with washers into the four
4
recessed areas in the corners of the bezel (
through the center piercing the elastomeric material and then tighten screws to 5 lb-in
(56 N•cm).
Figure 2-3 Mounting Method
Table 2-4 Mounting Procedure
Figure 2-2.
Figure 2-3).
Figure 2-3).
Figure 2-3). Push the point of the screw
3/07 UDC2500 Universal Digital Limit ControllerProduct Manual 15
Installation
2.6 Wiring
2.6.1 Electrical Considerations
Line voltage wiring
This controller is considered “rack and panel mounted equipment” per EN61010-1,
Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory
Use, Part 1: General Requirements. Conformity with 72/23/EEC, the Low Voltage
Directive requires the user to provide adequate protection against a shock hazard. The
user shall install this controller in an enclosure that limits OPERATOR access to the rear
terminals.
Mains Power Supply
This equipment is suitable for connection to 90 to 264 Vac or to 24 Vac/dc 50/60 Hz,
power supply mains. It is the user’s responsibility to provide a switch and non-time delay
(North America), quick-acting, high breaking capacity, Type F (Europe), 1/2A, 250V
fuse(s), or circuit-breaker for 90-264 Vac applications; or 1 A, 125 V fuse or circuit
breaker for 24 Vac/dc applications, as part of the installation. The switch or circuitbreaker shall be located in close proximity to the controller,
OPERATOR. The switch or circuit-breaker shall be marked as the disconnecting device
for the controller.
CAUTION
When applying power to multiple instruments, make certain that sufficient current is
supplied. Otherwise, the instruments may not start up normally due to the voltage drop
caused by the in-rush current.
Applying 90-264 Vac to an instrument rated for 24 Vac/dc will severely
damage the instrument and is a fire and smoke hazard.
within easy reach of the
Controller Grounding
PROTECTIVE BONDING (grounding) of this controller and the enclosure in which it is
installed shall be in accordance with National and Local electrical codes. To minimize
electrical noise and transients that may adversely affect the system, supplementary
bonding of the controller enclosure to a local ground, using a No. 12 (4 mm
2
) copper
conductor, is recommended.
Control/Alarm Circuit Wiring
The insulation of wires connected to the Control/Alarm terminals shall be rated for the
highest voltage involved. Extra Low Voltage (ELV) wiring (input, current output, and
low voltage Control/Alarm circuits) shall be separated from HAZARDOUS LIVE (>30
Vac, 42.4 Vpeak, or 60 Vdc) wiring per Permissible Wiring Bundling,
16 UDC2500 Universal Digital Limit ControllerProduct Manual 3/07
Table 2-5.
Electrical Noise Precautions
Electrical noise is composed of unabated electrical signals which produce undesirable
effects in measurements and control circuits.
Digital equipment is especially sensitive to the effects of electrical noise. Your controller
has built-in circuits to reduce the effect of electrical noise from various sources. If there
is a need to further reduce these effects:
• Separate External Wiring—Separate connecting wires into bundles
(See Permissible Wiring Bundling through separate conduit metal trays.
Use Suppression Devices—For additional noise protection, you may want to add
suppression devices at the external source. Appropriate suppression devices are
commercially available.
ATTENTION
For additional noise information, refer to document number 51-52-05-01, How to Apply Digital Instrumentation in Severe Electrical Noise Environments.
Permissible Wiring Bundling
Installation
Table 2-5) and route the individual bundles
Table 2-5 Permissible Wiring Bundling
Bundle No. Wire Functions
1
2 Analog signal wire, such as:
3
• Line power wiring
• Earth ground wiring
• Line voltage control relay output wiring
• Line voltage alarm wiring
• Input signal wire (thermocouple, 4 to 20 mA, etc.)
• 4-20 mA output signal wiring
Digital input signals
• Low voltage alarm relay output wiring
• Low voltage wiring to solid state type control circuits
• Low voltage wiring to open collector type control circuits
3/07 UDC2500 Universal Digital Limit ControllerProduct Manual 17
Installation
A
2.7 Wiring Diagrams
Identify Your Wiring Requirements
To determine the appropriate diagrams for wiring your controller, refer to the model
number interpretation in this section. The model number of the controller can be found on
the outside of the case.
Wiring the Controller
Using the information contained in the model number, select the appropriate wiring
diagrams from the composite wiring diagram below. Refer to the individual diagrams
listed to wire the controller according to your requirements.
uxiliary Output
and Digital Inputs
Terminals
See Figure 2-17
AC Line Voltage
Terminals
See Figure 2-5
Outputs 3 and 4
Terminals
See Figures 2-8
through 2-14
See Figures 2-15 and 2-16
L1
L2/N
4
5
6
7
8
9
Communications
Terminals
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Limit Relay
Terminals
See Figures 2-8
through 2-14
Not
Used
Input #1
Terminals
See Figure 2-6
xxxx
Figure 2-4 Composite Wiring Diagram
18 UDC2500 Universal Digital Limit ControllerProduct Manual 3/07
Installation
A
1
3
C/DC
Line
Voltage
1
PROTECTIVE BONDING (grounding) of this controller and the enclosure in which it is
2
Ground
Neutral
Hot
10
L1
11
L2/N
4
5
6
7
8
9
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
installed, shall be in accordance with National and local electrical codes. To minimize
electrical noise and transients that may adversely affect the system, supplementary
bonding of the controller enclosure to local ground using a No. 12 (4 mm
2
) copper
conductor is recommended. Before powering the controller, see “Prelimnary Checks”
in this section of the Product Manual.
2
It is the user’s responsibility to provide a switch and non-time delay (North America),
quick-acting, high breaking capacity, Type F (Europe), 1/2A, 250V fuse(s), or circuitbreaker for 90-264 Vac applications; or 1 A, 125 V fuse or circuit breaker for 24 Vac/dc
applications, as part of the instal lat ion.
3
CAUTION
Applying 90-264 Vac to an instrument rated for 24 Vac/dc will severely
damage the instrument and is a fire and smoke hazard.
xxxx
Figure 2-5 Mains Power Supply
3/07 UDC2500 Universal Digital Limit ControllerProduct Manual 19
Installation
Ω
Input #1
Millivolt or Volts
–
Xmitter
+
RTD
Power
Supply
250
except 0-10 Volts
25
2627+
R
–
source
mV or
Volt
source
+
–
Thermocouple Differential
Use Thermocouple
25
1
–+
26
27
extension wire only
R
+
–
+
–
2
–
+
Thermocouple
Use Thermocouple
extension wire only
3
25
R
26
+
–
27
0-10 Volts Milliamps
25
26
27
R
+
–
+
1
100K
0–10
Volt
source
1
2
3
2
1
100K
3
–
The 250 ohm resistor for milliamp inputs or the voltage divider for 0-10 Volt inputs are supplied
with the controller when those inputs are specified. These items must be installed prior to start
up when the controller is wired. For 0-20 mA applications, the resistor should be located at the
transmitter terminals if Burnout detection is desired.
Splice and tape this junction between the two thermocouples. This junction may be located
anywhere between the thermocouples and the instrument terminals, it does not need to be close
to the other thermocouple junctions. Both thermocouples must be of the same type. For best
accuracy, the two thermocouples should be matched or, preferably, made from the same batch
of wire.
This controller does not produce a steady current for burnout detection. For that reason, when a
thermocouple is used in parallel with another instrument, it may be desirable to configure the
burnout selection for this controller to “NOFS” and use the burnout current from the other
instrument to also drive this controller.
25
R
+
26
27
–
25
R
26
+
–
27
xxxx
Figure 2-6 Input 1 Connections
20 UDC2500 Universal Digital Limit ControllerProduct Manual 3/07
Loading...
+ 114 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.