Honeywell UDC120L Product Manual

59339-1
HONEYWELL UDC120L MICRO-PRO
UNIVERSAL LIMIT CONTROLLER PRODUCT MANUAL (51-52-25-132-EN)
CAUTION: Installation should be only performed by
technically competent personnel. Local Regulations regarding electrical installation & safety must be observed.
1. INSTALLATION
Installing Option Modules
CPU PCB
Option Module 1
(Fixed Limit Relay)
Option Module 2
Mounting Struts
Option Module A
Option Module 3
PSU PCB
To access module A, first detach the PSU and CPU boards from the front by lifting first the upper, and then lower mounting struts. Gently separate the boards.
a. Plug the required option modules into the correct connectors, as shown below. b. Locate the module tongues in the corresponding slot on the opposite board. c. Hold the main boards together while relocating back on the mounting struts. d. Replace the instrument by aligning the CPU and PSU boards with their guides in the housing, then slowly push the instrument back into position.
Note: Option modules are automatically detected at power up.
Option Module Connectors
Option Slot 1
(Fixed Limit
Relay)
Option Slot 2
Connecto
r
PL4A
Option Slot A
Connectors PL5 & PL6
Option Slot 3
Connector PL4B
Panel-Mounting
The mounting panel must be rigid, and may be up to 6.0mm (0.25inch) thick For n multiple instruments mounted side-by-side, cut-out is 48n-4mm
Mounting Panel
Instrument
Housing
Ratchets
Gasket
Slide mounting clamp over the instrument housing towards rear face of mounting panel until the tongues engage in ratchets and instrument is clamped in position.
Hold instrument firmly in position (apply pressure to bezel only)
CAUTION: Do not remove the panel gasket; it is a seal against dust and
moisture.
Rear Terminal Wiring
USE COPPER CONDUCTORS (EXCEPT FOR T/C INPUT)
Single Strand wire gauge: Max 1.2mm (18SWG)
Actual connections required depend on the options fitted.
CAUTION: Check information label on housing for correct operating
voltage before connecting supply to Power Input Fuse: 100 – 240V ac – 1amp anti-surge 24/48V ac/dc – 315mA anti-surge
2. SELECT MODE
Select mode is used to access the configuration and operation menu functions. It can be accessed at any time by holding down and pressing . In select mode, press or to choose the required mode, press to enter. An unlock code is required to prevent unauthorised entry to Configuration, & Setup modes. Press or to enter the unlock code, then press to proceed.
Note: At first power-up the message !"#" $"%& is displayed, (see section 6). Access to other menus is denied until configuration mode is completed
Mode Upper
Display
Lower
Display
Description Default
Unlock
Codes
Operator
'(#)* +,$#*
Normal operation None
Set Up
+-#(* +,$#*
Tailor settings to the application
./
Configuration
$"%&* +,$#*
Configure the instrument for use
0/
Product Info
1%&"* +,$#*
Check manufacturing information None
Note: The instrument will always return automatically to Operator mode if there is no key activity for 2 minutes.
3. CONFIGURATION MODE
First select Configuration mode from Select mode (refer to section 2). Press to scroll through the parameters, then press or to set the required value. Press to accept the change, otherwise parameter will revert to previous value. To exit from Configuration mode, hold down and press , to return to Select mode.
Note: Parameters displayed depends on how instrument has been configured. Refer to user guide (available from your supplier) for further details. Parameters marked * are repeated in Setup Mode.
Parameter Lower
Display
Upper
Display
Adjustment range & Description Default
Value
Input Range/Type
1%2#*
See following table for possible codes
3$
Code Input Type &
Range
Code Input Type &
Range
Code Input Type &
Range
bC
B: 100 - 1824 ºC
L.C
L: 0.0 - 537.7 ºC
bF
B: 211 - 3315 ºF
L.F
L: 32.0 - 999.9 ºF
P24F
PtRh20% vs 40%: 32 - 3362 ºF
CC
C: 0 - 2320 ºC
NC
N: 0 - 1399 ºC
PTC
Pt100: –199 - 800 ºC
CF
C: 32 - 4208 ºF
NF
N: 32 - 2551 ºF
PtF
Pt100: –328 - 1472 ºF
JC
J: –200 - 1200 ºC
rC
R: 0 - 1759 ºC
Pt.C
Pt100: –128.8 - 537.7 ºC
JF
J: –328 - 2192 ºF
rF
R: 32 - 3198 ºF
Pt.F
Pt100: –199.9 - 999.9 ºF
j.C
J: –128.8 - 537.7 ºC
SC
S: 0 - 1762 ºC
/40/
0 - 20 mA DC
j.F
J: –199.9 - 999.9 ºF
SF
S: 32 - 3204 ºF
540/
4 - 20 mA DC
KC
K: –240 - 1373 ºC
tC
T: –240 - 400 ºC
/46/
0 - 50 mV DC
KF
K: –400 - 2503 ºF
tF
T: –400 - 752 ºF
./.6/
10 - 50 mV DC
k.C
K: –128.8 - 537.7 ºC
t.C
T: –128.8 - 400.0 ºC
/46*
0 - 5 V DC
K.F
K: –199.9 - 999.9 ºF
t.F
T: –199.9 - 752.0 ºF
.46*
1 - 5 V DC
LC
L: 0 - 762 ºC
/4./
0 - 10 V DC
LF
L: 32 - 1403 ºF
P24C
PtRh20% vs. 40%: 0 - 1850 ºC
04./
2 - 10 V DC
Note: Decimal point shown in table indicates temperature resolution of 0.1° Parameter Lower
Display
Upper
Display
Adjustment range & Description Default
Value
Scale Range Upper Limit
)7,*
Scale Range Lower Limit +100
to Range Maximum
Range max
(Lin=1000) Scale Range Lower Limit
),,*
Range Minimum to
Scale Range Upper Limit -100
Range min
(Linear=0)
Decimal point position
82"+*
/=XXXX, .=XXX.X, 0=XX.XX, 9=X.XXX
(non-temperature ranges only)
.
Process Variable Offset
'&&+*
±Span of controller
(see CAUTION note at end of section)
/
:1*
High Limit.
Limit relay is energised when
process “safe” (PV < Limit Setpoint)
Limit Action
$;<,*
,"*
Low Limit.
Limit relay is energised when
process “safe” (PV > Limit Setpoint)
:1
Setpoint Upper Limit
+27,*
Current Setpoint to Scale Range maximum R/max
Setpoint Lower Limit
+2,,*
Scale Range minimum to Current Setpoint R/min
24:1*
Process High Alarm
24,"*
Process Low Alarm
8=*
Deviation Alarm
>?%8*
Band Alarm
Alarm 1Type
?,?.*
%"%=*
No alarm
24:1
High Alarm 1 value*
2@?.*
Range Max
Low Alarm 1 value*
2,?.*
Scaled Range Minimum to
scaled Range Maximum in display units
Range Min
Band Alarm 1 value*
>?,.*
1 LSD to span from setpoint in display units
6
Dev. Alarm 1 value*
8?,.*
+/- Span from setpoint in display units
6
Alarm 1 Hysteresis*
?:A.*
1 LSD to full span in display units
.
Alarm 2 Type*
?,?0 24,"*
High Alarm 2 value*
2@?0
Range Max
Low Alarm 2 value*
2,?0
Range Min
Band Alarm 2 value*
>?,0 6*
Dev. Alarm 2 Value*
8?,0 6*
Alarm 2 Hysteresis*
?:A0
Options as for alarm 1
.*
,Mm#
Limit Output Relay
?B48
Alarm 1, Direct
?.4)
Alarm 1, Reverse
?048
Alarm 2, Direct
?04)
Alarm 2, Reverse
')48
Logical Alarm 1 OR 2, Direct
')4)
Logical Alarm 1 OR 2, Reverse
?848
Logical Alarm 1 AND 2, Direct
?84)
Logical Alarm 1 AND 2, Reverse
?%48
Limit Annunciator, Direct
?%4)
Limit Annunciator, Reverse
?B48*
)-#+
Retransmit Limit SP Output
Output 2 Usage
C+=0
)-#2
Retransmit PV Output
)-#2
/46*
0 to 5 V DC output 1
/4./
0 to 10 V DC output
04./
2 to 10 V DC output
/40/
0 to 20 mA DC output
Linear Output 2 Range
#A20
540/
4 to 20 mA DC output
/4./*
Retransmit Output 2 Scale maximum
)"0:
-1999 to 9999
(display value at which output
will be maximum)
Range max
Retransmit Output 3 Scale minimum
)"0,
-1999 to 9999
(display value at which output
will be minimum)
Range min
Output 3 Usage
C+=9
As for output 2
?B48*
Linear Output 3 Range
#A29
As for output 2
/4./*
Retransmit Output 3 Scale maximum
)"9:
-1999 to 9999
(display value at which output
will be maximum)
Range max
Retransmit Output 3 Scale minimum
)"9,
-1999 to 9999
(display value at which output
will be minimum)
Range min
=%?>
PV is visible in Operator mode
Display Strategy
81D(
81+?
PV not visible in Operator mode
=%?>
?+$E
ASCII
Mm>%
Modbus with no parity
Mm>=
Modbus with Even Parity
Serial Communications Protocol
2)"#
Mm>"
Modbus with Odd Parity
Mm>%*
..0*
1.2 kbps
0.5*
2.4 kbps
5.F*
4.8 kbps
G.H*
9.6 kbps
Serial Communications Bit Rate
>?78
.G.0*
19.2 kbps
5.F*
Comms Address
?88)
*1 to 255 (Modbus), 1 to 99 (ASCII)
.*
)4Ww
Read/Write
Comms Write
$"=%
)4/*
Read only
)4Ww*
Configuration Lock Code
$,"I
0 to 9999
0/*
Notes: Output 1 is always a Latching Limit Relay output. If Option Slot A has the Digital Input module fitted, this always functions as a Remote Reset, duplicating the function of the Reset) key .
As these functions cannot be changed, no Configuration menus are required.
CAUTION: Process Variable Offset can be use to modify the measured
value to compensate for probe errors. Positive values increase the reading, negative values are subtracted. This parameter is effectively, a calibration adjustment and MUST be used with care.
There is no front panel indication of when this parameter is in use.
4. SETUP MODE
Note: Configuration must be completed before adjusting Setup parameters.
First select Setup mode from Select mode (refer to section 2). The Setup LED will light while in Setup mode. Press to scroll through the parameters, then press or to set the required value. To exit from Setup mode, hold down and press to return to Select mode.
Note: Parameters displayed depends on how instrument has been configured.
Parameter Lower
Display
Upper Display Adjustment
Range & Description
Default
Value
Limit Setpoint value
+2*
Scaled Range Minimum to
scaled Range Maximum
R/max if
$#),=:1
R/min if
$#),=,"
Limit Hysteresis
:J+#*
1 LSD to full span in display units,
on the safe side of the limit SP
.
Input Filter Time Constant
&1,#*
OFF or 0.5 to 100.0 secs
(see CAUTION note below)
0./
High Alarm 1 value
2@?.
R/max
Low Alarm 1 value
2,?.*
Scaled Range Minimum to
scaled Range Maximum
R/min
Deviation Alarm 1 Value
8?,.*
±Span from SP in display units
6
Band Alarm 1 value
>?,.*
1 LSD to span from setpoint
6
Alarm 1 Hysteresis
?:A.
1 LSD to full span in display units
.
High Alarm 2 value
2@?0
R/max
Low Alarm 2 value
2,?0*
Scaled Range Minimum to
scaled Range Maximum
R/min
Deviation Alarm 2 Value
8?,0*
±Span from SP in display units
6
Band Alarm 2 value
>?,0*
1 LSD to span from setpoint
6
Alarm 2 Hysteresis
?:A0
1 LSD to full span in display units
.
Setup Lock Code
+,"I*
0 to 9999
./
Note: Operator mode screens follow, without exiting from Setup mode.
CAUTION: An excessively large filter time could significantly delay
detection of a limit condition. Set this value to the minimum required to remove noise from the process variable
5. PRODUCT INFORMATION MODE
First select Product information mode from Select mode (refer to section 2). Press to view each parameter. To exit from Product Information mode, hold down and press to return to Select mode. Note: These parameters are all read only.
Parameter Lower
Display
Upper
Display
Description
Input type
E%4. C%1*
Universal input
Option 1 type (fixed)
'2%. ),J*
Latching Limit Relay
%"%=
No option fitted
),J*
Relay output
++)*
SSR drive output
#)1*
Triac output
Option 2 module type fitted
'2%0
,1%*
Linear DC voltage / current output
%"%=
No option fitted
),J*
Relay output
++)*
SSR drive output
,1%*
Linear DC voltage / current output
Option 3 module type fitted
'2%9
8I05
24VDC Transmitter power supply
%"%-
No option fitted
)5F6
RS485 communications
Auxiliary Option A module type fitted
'2%?
81!1
Digital Input for remote reset
Firmware type
&KL*
Value displayed is firmware type number
Firmware issue
EDD*
Value displayed is firmware issue number
Product Revision Level
2<,*
Value displayed is Product Revision level
Date of manufacture
8'Mm
Manufacturing date code (mmyy)
Serial number 1
+%.*
First four digits of serial number
Serial number 2
+%0*
Middle four digits of serial number
Serial number 3
+%9*
Last four digits of serial number
45 x 45mm
(+0.5 /
-
6. MESSAGES & ERROR INDICATIONS
Parameter Upper
Display
Lower
Display
Description
Instrument parameters are in default conditions
!"#"* $"%&
Configuration & Setup required. This screen is
seen at first turn on, or if hardware
configuration has been changed. Press to
enter the Configuration Mode, next press or to enter the unlock code number,
then press to proceed
Input Over Range
M::N*
Normal
Process variable input > 5% over-range
Input Under Range
M,,N*
Normal
Process variable input > 5% under-range
Input Sensor Break
'2=O*
Normal
Break detected in process variable input
sensor or wiring
Option 1 Error
'(%.*
Option 1 module fault
Option 2 Error
'(%0*
Option 2 module fault
Option 3 Error
'(%9*
Option 3 module fault
Option A Error
=<<*
'(%?
Option A module fault
7. OPERATOR MODE
This mode is entered at power on, or accessed from Select mode (see section 2).
Note: All Configuration mode and Setup mode parameters must be set as required before starting normal operations. Press to scroll through the parameters.
Upper Display
Lower
Display
Display Strategy and
When Visible
Description
PV Value
Limit SP
Value
81+2 = =%?>* (initial screen)
PV and Limit Setpoint values
Read only
Limit SP Value
(Blank)
81+2 = 81+?* (initial screen)
Limit Setpoint value
Read only
High Limit Hold
:1:8
$#), = :1
Highest PV value since this
parameter was last reset.
To reset, press for 5 seconds,
display =
PPPP
when reset
Low Limit Hold
,":8
$#), = ,"
Lowest PV value since this
parameter was last reset.
To reset, press for 5 seconds,
display =
PPPP
when reset
Exceed Time Value
#1
Always available
Format mm.ss to 99.59
then mmm.s
(10 sec increments)
Shows
M::N if 999.9
Accumulated time of Limit SP
exceed conditions since this
parameter was last reset.
To reset, press for 5 seconds,
display =
PPPP
when reset
Active Alarm Status
?,+#*
When one or more alarms are active.
ALM indicator will also flash*
L Alarm 2 active
?%0. Alarm 1 active
L Annunciator active
Exceed Condition
An Exceed Condition is when the Process Variable exceeds the Limit Setpoint value (i.e. PV > SP when set for high limit action, PV < SP for low limit action). The LED is on during this condition, and is extinguished once it has passed.
Limit Output Function
Limit Output relay(s) de-energise whenever an Exceed condition occurs, causing the process to shut down. The LED is on when the relay is de-energised. The relay remains latched off even if the Exceed condition is no longer present. Only giving a reset instruction (after
the exceed condition has passed) will re-
energise the relay, allowing the process to continue. The LED then turns off.
Limit Annunciator Outputs
An Annunciator output will activate when an Exceed condition occurs, and will remain active until a reset instruction is received, or the Exceed condition has passed. Unlike the Limit Output, an Annunciator can be reset even if the Exceed condition is present. When an Annunciator is active, the LED will flash and the Alarm Status screen is available.
Resetting Limit Outputs & Annunciators
A reset instruction can be given by pressing the key, via the Digital Input (if fitted) or via a Comms command if an RS485 Communications module is fitted. Annunciators will deactivate. Limit Outputs will only re-energise if the Exceed condition has passed.
CAUTION: Ensure that the cause of the Exceed condition has been
rectified before resetting the Limit Output.
8. SERIAL COMMUNICATIONS
Refer to the full user guide (available from your supplier) for details.
9. SPECIFICATIONS
UNIVERSAL INPUT
Thermocouple Calibration:
±0.1% of full range, ±1LSD (±1°C for Thermocouple CJC). BS4937, NBS125 & IEC584.
PT100 Calibration:
±0.1% of full range, ±1LSD. BS1904 & DIN43760 (0.00385
Ω/Ω
/°C).
DC Calibration:
±0.1% of full range, ±1LSD. Sampling Rate: 4 per second.
Impedance:
>10M resistive, except DC mA (5) and V (47k ). Sensor Break
Detection:
Thermocouple, RTD, 4 to 20 mA, 2 to 10V and 1 to 5V ranges
only. Limit outputs turn off (goes into Exceed condition), high
alarms activate for thermocouple/RTD sensor break, low
alarms activate for mA/V DC sensor break.
Isolation: Isolated from all outputs (except SSR driver).
Universal input must not be connected to operator accessible
circuits if relay outputs are connected to a hazardous voltage
source. Supplementary insulation or input grounding would
then be required.
DIGITAL INPUT
Volt-free(or TTL): Open(2 to 24VDC) = No Reset.
Closed(<0.8VDC) = Reset (edge triggered). Isolation: Reinforced safety isolation from inputs and other outputs.
OUTPUTS
Limit Relay
Contact Type & Rating:
Latching limit control relay. Single pole double throw (SPDT);
5A resistive at 120/240VAC. Slot 1 position fixed for this
function, optional function for Slot 2 & 3 relay modules, Lifetime: >100,000 operations at rated voltage/current.
Isolation: Basic Isolation from universal input and SSR outputs.
Alarm Rela ys
Contact Type & Rating:
Slot 2 or 3 position non-latching alarm relay.
Single pole double throw (SPDT); 2A resistive at 120/240VAC. Lifetime: >500,000 operations at rated voltage/current.
Isolation: Basic Isolation from universal input and SSR outputs.
SSR Driver
Drive Capability:
SSR drive voltage >10V into 500 min. Isolation: Not isolated from universal input or other SSR driver outputs.
Triac
Operating Voltage: 20 to 280Vrms (47 to 63Hz).
Current Rating: 0.01 to 1A (full cycle rms on-state @ 25°C);
derates linearly above 40°C to 0.5A @ 80°C. Isolation: Reinforced safety isolation from inputs and other outputs.
DC
Resolution: 8 bits in 250mS (10 bits in 1s typical, >10 bits in >1s typical).
Isolation: Reinforced safety isolation from inputs and other outputs.
Transmitter PSU
Power Rating:
20 to 28V DC (24V nominal) into 910 minimum resistance. Isolation: Reinforced safety isolation from inputs and other outputs.
SERIAL COMMUNICATIONS
Physical: RS485, at 1200, 2400, 4800, 9600 or 19200 bps.
Protocols: Selectable between Modbus and ASCII.
Isolation: Reinforced safety isolation from all inputs and outputs.
OPERATING CONDITIONS (FOR INDOOR USE)
Ambient Temperature:
0°C to 55°C (Operating), –20°C to 80°C (Storage).
Relative Humidity: 20% to 95% non-condensing.
Supply Voltage and Power:
100 to 240VAC ±10%, 50/60Hz, 7.5VA
(for mains powered versions), or
20 to 48VAC 50/60Hz 7.5VA or 22 to 65VDC 5W
(for low voltage versions).
ENVIRONMENTAL
Standards: CE, UL, ULC & FM 3545, 1998
EMI: Complies with EN61326 (Susceptibility & Emissions).
Safety Considerations:
Complies with EN61010-1 & UL3121.
Pollution Degree 2, Installation Category II. Front Panel Sealing: To IP66 (IP20 behind the panel).
PHYSICAL
Front Bezel Size: 48 x 48mm
Depth Behind Panel: 110mm.
Weight: 0.21kg maximum.
Loading...