59311-3
HONEYWELL UDC1200 & UDC1700 MICRO-PRO
UNIVERSAL DIGITAL CONTROLLER PRODUCT MANUAL (51-52-25-123-EN)
CAUTION: Installation should be only performed by
technically competent personnel. Local Regulations
regarding electrical installation & safety must be observed.
1. INSTALLATION
Models UDC1200 and UDC1700 have different case sizes (refer to section 10).
Installation differences between these models the have been clearly shown.
Note: The functions described in sections 2 thru 9 are common to all models.
Installing Option Modules
CPU PCB
Option Module 1
Option Module 2
CPU PCB
Option Module B
Option Module 2
Option Module 1
To access modules 1, A or B, first detach the PSU and CPU boards from the front b
lifting first the upper, and then lower mounting struts. Gently separate the boards.
a. Plug the required option modules into the correct connectors, as shown below.
b. Locate the module tongues in the corresponding slot on the opposite board.
c. Hold the main boards together while relocating back on the mounting struts.
d. Replace the instrument by aligning the CPU and PSU boards with their guides
in the housing, then slowly push the instrument back into position.
Note: Option modules are automatically detected at power up.
Option Module Connectors
Option Slot 1
Connectors
PL7 & PL8
Option Slot 2
Connecto
Option Slot B
Connectors
PL2A, PL2B &
Option Slot 2
Connecto
Option Slot 1
Connectors
PL7 & PL8
PL4A
PL2C
PL4A
UDC1200 Module Positions
UDC1700 Module Positions
UDC1200 Module Connectors
UDC1700 Module Connectors
Mounting Struts
Option Module A
Option Module 3
PSU PCB
Mounting Struts
Option Module A
Option Module 3
PSU PCB
Option Slot A
Connectors
PL5 & PL6
Option Slot 3
Connector
PL4B
Option Slot A
Connectors
PL5 & PL6
Option Slot 3
Connector
PL4B
Panel-Mounting
The mounting panel must be rigid, and may be up to
6.0mm (0.25inch) thick. Cut-out sizes are:
UDC1200 UDC1700
Dim A = 45mm Dim A = 45mm
Dim B = 45mm Dim B = 92mm
For n multiple instruments mounted side-by-side, cut-out
dimension A is 48n-4mm
Mounting Panel
Instrument
Housing
Ratchets
Gasket
B
A
Tolerance +0.5, -0.0mm
Slide mounting clamp
over the instrument
housing towards rear face
of mounting panel until
the tongues engage in
ratchets and instrument is
clamped in position.
Hold instrument firmly in
position (apply pressure
to bezel only)
CAUTION: Do not remove the panel gasket; it is a seal against dust and
moisture.
Rear Terminal Wiring
USE COPPER CONDUCTORS (EXCEPT FOR T/C INPUT)
Single Strand wire gauge: Max 1.2mm (18SWG)
UDC1200 Wiring Diagram
UDC1700 Wiring Diagram
These diagrams show all possible option combinations. The actual
connections required depends on the exact model and options fitted.
CAUTION: Check information label on housing for correct operating
voltage before connecting supply to Power Input
Fuse: 100 – 240V ac – 1amp anti-surge
24/48V ac/dc – 315mA anti-surge
Note: At first power-up the message !"#" $"%& is displayed, as described in
section 7 of this manual. Access to other menus is denied until configuration
mode is completed
2. SELECT MODE
Select mode is used to access the configuration and operation menu functions.
It can be accessed at any time by holding down and pressing .
In select mode, press or to choose the required mode, press to enter.
An unlock code is required to prevent unauthorised entry to Configuration, & Setup
modes. Press or to enter the unlock code, then press to proceed.
Mode Upper
Display
Operator
Set Up
Configuration
Product Info
Auto-Tuning
'(#)* +,$#*
+-#(* +,$#*
$"%&* +,$#*
1%&"* +,$#*
2#3%* +,$#*
Lower
Display
Description Default
Unlock
Codes
Normal operation None
Tailor settings to the application
Configure the instrument for use
./*
0/*
Check manufacturing information None
Invoke Pre-Tune or Self-Tune
/*
Note: The instrument will always return automatically to Operator mode if
there is no key activity for 2 minutes.
3. CONFIGURATION MODE
First select Configuration mode from Select mode (refer to section 2).
Press to scroll through the parameters, then press or to set the
required value. Press to accept the change, otherwise parameter will revert to
previous value. To exit from Configuration mode, hold down and press , to
return to Select mode.
Note: Parameters displayed depends on how instrument has been configured.
Refer to user guide (available from your supplier) for further details.
Parameters marked * are repeated in Setup Mode.
Parameter Lower
Input
Range/Type
Code Input Type &
Range
B: 100 - 1824 ºC
bC
B: 211 - 3315 ºF
bF
C: 0 - 2320 ºC
CC
C: 32 - 4208 ºF
CF
J: –200 - 1200 ºC
JC
J: –328 - 2192 ºF
JF
J: –128.8 - 537.7 ºC
j.C
J: –199.9 - 999.9 ºF
j.F
K: –240 - 1373 ºC
KC
K: –400 - 2503 ºF
KF
K: –128.8 - 537.7 ºC
k.C
K: –199.9 - 999.9 ºF
K.F
L: 0 - 762 ºC
LC
L: 32 - 1403 ºF
LF
Note: Decimal point shown in table indicates temperature resolution of 0.1°
Parameter Lower
Scale Range
Upper Limit
Scale Range
Lower Limit
Decimal point
position
Control Type
Primary Output
Control Action
Alarm 1Type
High Alarm 1
value*
Low Alarm 1
value*
Band Alarm 1
value*
Dev. Alarm 1
value*
Alarm 1
Hysteresis*
Alarm 2 Type*
High Alarm 2
value*
Low Alarm 2
value*
Band Alarm 2
value*
Upper
Display
1%4#
Display
)3,
),,*
94"+
$:;4
$:<,
2,2.
4@2.
4,2.
?2,.
92,.
2=;.
Adjustment range & Description Default
Display
See following table for possible codes
Code Input Type &
Range
L: 0.0 - 537.7 ºC
L.C
L: 32.0 - 999.9 ºF
L.F
N: 0 - 1399 ºC
NC
N: 32 - 2551 ºF
NF
R: 0 - 1759 ºC
rC
R: 32 - 3198 ºF
rF
S: 0 - 1762 ºC
SC
S: 32 - 3204 ºF
SF
T: –240 - 400 ºC
tC
T: –400 - 752 ºF
tF
T: –128.8 - 400.0 ºC
t.C
T: –199.9 - 752.0 ºF
t.F
PtRh20% vs. 40%:
P24C
0 - 1850 ºC
Upper
Adjustment range & Description Default
Code Input Type &
Range
PtRh20% vs 40%:
P24F
32 - 3362 ºF
Pt100: -199 - 800 ºC
PTC
Pt100: -328 - 1472 ºF
PtF
Pt100: -128.8 - 537.7 ºC
Pt.C
Pt100: -199.9 - 999.9 ºF
Pt.F
0 - 20 mA DC
/60/
4 - 20 mA DC
760/
0 - 50 mV DC
/68/
10 - 50 mV DC
./.8/
0 - 5 V DC
/68
1 - 5 V DC
.68
0 - 10 V DC
/6./
2 - 10 V DC
06./
Display
Scale Range Lower Limit +100
to Range Maximum
Range Minimum to
Scale Range Upper Limit -100
0=XXXX, 1=XXX.X, 2=XX.XX, 3=X.XXX
(non-temperature ranges only)
+%!,
932,
)-3*
91)*
46=1
46,"
9>*
?2%9
%"%>
Primary only
Primary & Secondary
(e.g. heat & cool)
Reverse Acting
Direct Acting
Process High Alarm
Process Low Alarm
Deviation Alarm
Band Alarm
No alarm
Range Minimum to Range Maximum in
display units
1 LSD to span from setpoint in display units
+/- Span from setpoint in display units
1 LSD to full span in display units
5$*
Range max
(Lin=1000)
Range min
(Linear=0)
+%!,*
)-3*
46=1*
Range Max
Range Min
2,20 46,"*
4@20
4,20
Options as for alarm 1
Range Max
Range Min
?2,0
1
8*
8*
.*
8*
Parameter Lower
Display
Dev. Alarm 2
Value*
Alarm 2
Hysteresis*
Loop Alarm
Loop Alarm
Time*
Alarm Inhibit
Output 1 Usage
Linear Output 1
Range
Retransmit
Output 1 Scale
maximum
Retransmit
Output 1 Scale
minimum
Output 2 Usage
Linear Output 2
Range
Retransmit
Output 2 Scale
maximum
Retransmit
Output 2 Scale
minimum
Output 3 Usage
Linear Output 3
Range
Retransmit
Output 3 Scale
maximum
Retransmit
Output 3 Scale
minimum
Display Strategy
Serial
Communications
Protocol
Serial
Communications
Bit Rate
Comms Address
Comms Write
Digital Input 1
Usage
Digital Input 2
Usage
Note: 91!0 has priority over 91!1 if both are configured for the same usage.
91!1 or 91!0 = 91+. the remote setpoint input is disabled.
If
Upper
Adjustment range & Description Default
Display
92,0* 8
Options as for alarm 1
2=;0*
,2>%*
,2:1*
C%@1*
F+>.*
#;4.*
91+2 (disabled) or >%2? (enabled)
1 sec to 99 mins. 59secs
%"%2,2.
2,20
?"#@
4)1
+-D*
2E69
2.6)
2069
206)
,469
,46)
')69
')6)
2969
296)
)-#+
)-#4
/68*
/6./
06./
/60/
760/
No alarms Inhibited
Alarm 1 inhibited
Alarm 2 inhibited
Alarm 1 and alarm 2 inhibited
Primary Power
Secondary Power
Alarm 1, Direct
Alarm 1, Reverse
Alarm 2, Direct
Alarm 2, Reverse
Loop Alarm, Direct
Loop Alarm, Reverse
Logical Alarm 1 OR 2, Direct
Logical Alarm 1 OR 2, Reverse
Logical Alarm 1 AND 2, Direct
Logical Alarm 1 AND 2, Reverse
Retransmit SP Output
Retransmit PV Output
0 to 5 V DC output 1
0 to 10 V DC output
2 to 10 V DC output
0 to 20 mA DC output
4 to 20 mA DC output
91A2
BB.8B
%"%-
4)1
/6./
-1999 to 9999
)".=*
(display value at which output
will be maximum)
Range max
-1999 to 9999
)".,*
F+>0*
#;40*
(display value at which output
will be minimum)
As for output 1 Sec or Al2
As for output 1
Range min
/6./
-1999 to 9999
)"0=*
(display value at which output
will be maximum)
Range max
-1999 to 9999
)"0,*
F+>G*
#;4G*
(display value at which output
will be minimum)
As for output 1
As for output 1
Range min
2E69
/6./
-1999 to 9999
)"G=*
(display value at which output
will be maximum)
Range max
-1999 to 9999
)"G,*
91A(*
., 0, G, 7, 8 or H
2+$C
Mm?%
4)"#*
Mm?>
Mm?"
..0*
0.7*
?239*
7.I*
B.H*
.B.0*
299)* *.*
)6Ww
$">%*
91!1*
)6/*
91+.
912A
91+.
91!0*
912A
91)A
(display value at which output
will be minimum)
(refer to section 8)
ASCII
Modbus with no parity
Modbus with Even Parity
Modbus with Odd Parity
1.2 kbps
2.4 kbps
4.8 kbps
9.6 kbps
19.2 kbps
1 to 255 (Modbus), 1 to 99 (ASCII)
Read/Write
Read only
Setpoint 1 / Setpoint 2 select*
Automatic / Manual select
Setpoint 1 / Setpoint 2 select*
Automatic / Manual select
Remote / Local setpoint select
Range min
Mm?%
7.I
)6Ww
91+.
91)+
Continued on next page…
.
.
.
Parameter Lower
Display
Remote Setpoint
Input Range
RSP Upper Limit
RSP Lower Limit
RSP Offset
Configuration
Lock Code
Upper
Adjustment range & Description Default
Display
/60/*
760/*
/6./*
06./*
)1%4*
/68*
.68*
.//*
4"#*
)+43*
)+4,*
Constrained within Scale Range Upper &
)+4"*
$,"D*
0 to 20 mA DC input*
4 to 20 mA DC input
0 to 10 V DC input
2 to 10 V DC input
0 to 5 V DC input
1 to 5 V DC input
0 to 100mV DC input
Potentiometer
(2KΩ minimum)
-1999 to 9999 Range max
-1999 to 9999 Range min
Scale Range Lower limits
0 to 9999
/6./*
vailable on
full RSP
(Slot B) only
0/*
4. SETUP MODE
Note: Configuration must be completed before adjusting Setup parameters.
First select Setup mode from Select mode (refer to section 2). The MAN LED
will light while in Setup mode. Press to scroll through the parameters,
then press or to set the required value.
To exit from Setup mode, hold down and press to return to Select mode.
Note: Parameters displayed depends on how instrument has been configured.
Parameter Lower
Display
Input Filter Time Constant
Process Variable Offset
Primary Power
Secondary Power
Primary Proportional
Band
Secondary Proportional
Band
Automatic Reset
(Integral Time)
Rate (Derivative Time)
Overlap/Deadband
Manual Reset (Bias)
Primary ON/OFF
Differential
Secondary ON/OFF Diff.
Prim. & Sec. ON/OFF
Differential
Setpoint Upper Limit
Setpoint Lower limit
Primary Output Power
Limit
Output 1 Cycle Time
Output 2 Cycle Time
Output 3 Cycle Time
High Alarm 1 value
Low Alarm 1 value
Deviation Alarm 1 Value
Band Alarm 1 value
Alarm 1 Hysteresis
High Alarm 2 value
Low Alarm 2 value
Deviation Alarm 2 Value
Band Alarm 2 value
Alarm 2 Hysteresis
Loop Alarm Time
Auto Pre-tune
Auto/manual Control
selection
Setpoint Select shown in
Operator Mode
Setpoint ramp adjustment
shown in Operator Mode
SP Ramp Rate Value
Setpoint Value
Local Setpoint Value
Setpoint 1 Value
Setpoint 2 Value
Setup Lock Code
&1,#*
'&&+*
44Ww
+4Ww
4?64*
4?6+*
2)A#*
)2:>*
',*
?12+*
91&4*
91&+*
91&&*
+43,*
+4,,*
'43,*
$:.*
$:0*
$:G*
4@2.*
4,2.*
92,.*
?2,.*
2=;.*
4@20*
4,20*
92,0*
?2,0*
2=;0*
,2:1*
24:*
4">%*
++>%*
+()*
)4*
+4*
6,+4
6+4.
6+40
+,"D*
Upper Display Adjustment
Default
Range & Description
OFF or 0.5 to 100.0 secs
0./*
±Span of controller
Current power levels (read only)
0.0% (ON/OFF) and 0.5% to
999.9% of input span
1 sec to 99 mins 59 secs and OFF
00 secs to 99 mins 59 secs
N/A
././*
8.//*
...8*
-20 to +20% of Primary and
Secondary Proportional Band
0%(-100% if dual control) to 100%
08*
0.1% to 10.0% of input span
centered about the setpoint.
(Entered as a percentage
/.8*
of span)
Current Setpoint to Range max R/max
Range min to Current Setpoint R/min
0% to 100% of full power
0.5, 1, 2, 4, 8, 16, 32, 64, 128,
256 or 512 secs.
Range Minimum to Range
Maximum
.//*
G0*
R/max
R/min
±Span from SP in display units
1 LSD to span from setpoint
1 LSD to full span in display units
Range Minimum to Range
Maximum
R/max
R/min
±Span from SP in display units
1 LSD to span from setpoint
1 LSD to full span in display units
1 LSD to full span in display units
91+2 (disabled) or
>%2? (enabled)
BB.8B*
91+2*
1 to 9999 units/hour or Off (blank) Off
Scale range upper to lower limits.
(when dual or remote setpoint
options are used,
+4 is replaced by
+4. & +40 or ,+4
* before the legend
6 or
indicates the currently active SP)
0 to 9999
Scale
Range
Minimum
./*
/
/*
/*
8*
8*
.*
8*
8*
.*
5. AUTOMATIC TUNING MODE
First select Automatic tuning mode from Select mode (refer to section 2).
Press to scroll through the modes, then press or to set the required
value.
To exit from Automatic tuning mode, hold down and press , to return to
Select mode.
Pre-tune is a single-shot routine and is thus self-disengaging when complete.
If 24: in Setup mode = >%2?, Pre-tune will attempt to run at every power up*.
Refer to the full user guide (available from your supplier) for details on controller
tuning.
Parameter Lower
Upper Display Default
Display
Pre-Tune
Self-Tune
Tune Lock
4#3%*
'% or '&&. Indication remains '&& if automatic
+#3%*
#,"D*
tuning cannot be used at this time*
0 to 9999
Off
* Note: Automatic tuning will not engage if either proportional band = 0.
Also, Pre-tune will not engage if setpoint is ramping, or the PV is less than 5%
of input span from the setpoint.
6. PRODUCT INFORMATION MODE
First select Product information mode from Select mode (refer to section 2).
Press to view each parameter. To exit from Product Information mode,
hold down and press to return to Select mode.
Note: These parameters are all read only.
Parameter Lower
Display
Input type
Option 1 module type
fitted
Option 2 module type
fitted
Option 3 module type
fitted
Auxiliary Option A
module type fitted
Auxiliary Option B
module type fitted
C%6.* F%1*
'4%.*
'4%0*
'4%G*
'4%2*
'4%?*
Firmware type
Firmware issue
Product Revision Level
Date of manufacture
9'Mm*
Serial number 1
Serial number 2
Serial number 3
&KL*
CAA*
4<,*
+%.*
+%0*
+%G*
Upper
Description
Display
Universal input
%"%>*
),J*
++)*
#)1*
,1%*
%"%>*
),J*
++)*
,1%*
9D07*
%"%-*
)7I8*
91!1*
)+41*
%"%-*
)+41*
Linear DC voltage / current output
Linear DC voltage / current output
Transmitter power supply
Remote Setpoint Input (basic)*
Remote Setpoint Input (full)
No option fitted
Relay output
SSR drive output
Triac output
No option fitted
Relay output
SSR drive output
No option fitted
RS485 communications
Digital Input*
No option fitted
and Digital Input 2*
Value displayed is firmware type number
Value displayed is firmware issue number
Value displayed is Product Revision level
Manufacturing date code (mmyy)
First four digits of serial number
Middle four digits of serial number
Last four digits of serial number
As Option 1
7. MESSAGES & ERROR INDICATIONS
These messages indicate that an error has occurred or there is a problem with the
process variable signal or its wiring.
Caution: Do not continue with the process until the issue is resolved.
Parameter Upper
Display
Instrument
parameters are in
default conditions
Input Over Range
Input Under
Range
Input Sensor
Break
RSP Over Range
RSP Under
Range
RSP Break Normal
Option 1 Error
Option 2 Error
Option 3 Error
Option A Error
Option B Error
Lower
Display
!"#"* $"%&
Normal
M==N*
Normal
M,,N*
Normal
'4>O*
Normal
M==N **
Normal
M,,N ***
'4>O ***
'(%.*
'(%0*
><<*
'(%G*
'(%2
'(%?*
Description
Configuration & Setup required. This screen is
seen at first turn on, or if hardware
configuration has been changed. Press to
enter the Configuration Mode, next press
or to enter the unlock code number,
then press to proceed
Process variable input > 5% over-range
Process variable input > 5% under-range
Break detected in process variable input
sensor or wiring
RSP input over-range
RSP input under-range
Break detected in RSP
input signal
** also seen
wherever RSP
value would be
displayed
Option 1 module fault
Option 2 module fault
Option 3 module fault
Option A module fault or RSP in both A & B
Option B module fault
8. OPERATOR MODE
This mode is entered at power on, or accessed from Select mode (see section 2).
Note: All Configuration mode and Setup mode parameters must be set as
required before starting normal operations.
Press to scroll through the parameters, then press or to set the
required value.
Note: All Operator Mode parameters in Display strategy 6 are read only (see
91+4 in configuration mode), they can only be adjusted via Setup mode.
Upper
Display
PV Value
PV Value
/
PV Value
Active SP
Value
SP Value
SP1 Value
SP2 Value
Local SP
Value
Remote SP
Value
Lower
Display
Active
SP
Value
Actual
SP
Value
(Blank)
(Blank)
+4*
6+4.
6+40
6,+4
6)+4
Display Strategy and
When Visible
1 & 2 (initial screen)
3 & 6 (initial screen)
4 (initial screen)
5 (initial screen)
1, 3, 4, 5 & 6 if digital
input is not 91+. and
RSP not fitted
Digital input = 91+..
_6 lit if active SP = SP1
Digital input = 91+..
6 lit if active SP = SP2
RSP fitted.
6 or
* lit if the
active SP = ,+4
RSP fitted.
* lit if the
6 or
active SP = )+4
Description
PV and target value of selected SP
Local Setpoints are adjustable in
Strategy 2
PV and actual value of selected SP
(e.g. ramping SP value). Read only
Process variable only
Read only
Target value of selected setpoint
only. Read only
Target value of SP
Adjustable except in Strategy 6
Target value of SP1
Adjustable except in Strategy 6
Target value of SP2
Adjustable except in Strategy 6
Target value of local setpoint
Adjustable except in Strategy 6
Target value of remote setpoint
Read only
Selects local/remote active setpoint
,+4 = local SP, )+4 = remote SP
91!1 = selection via digital input
(if configured). Note: selecting ,+4
or )+4 will override digital input,
active SP indication changes to
*
91!1,
,+4 or )+4
RSP is fitted, digital
input is not 91+. and
+4A*
++>% is enabled in
Setup mode
Adjustable except in Strategy 6
Actual SP
Value
Ramp Rate
Active Alarm
Status
+4)4
)4*
When one or more
alarms are active.
2,+#
)4 is not blank
+() enabled in
Setup mode
ALM indicator
will also flash*
Actual (ramping) value of
selected SP. Read only
SP ramping rate, in units per hour
Adjustable except in Strategy 6
L Alarm 2 active
,0. Alarm 1 active
L Loop Alarm active
Manual Control
If 4">% is set to >%2? in Setup mode, manual control can be selected/de-selected
by pressing the key in Operator mode, or by changing the status of a digital
input if 91!1 or 91!0 have been configured for 912A in Configuration mode.
While in Manual Control mode, the indicator will flash and the lower display will
show 4xxx (where xxx is the current manual power level). Switching to/from manual
mode is via Bumpless Transfer. Press or to set the required output power.
Caution: Manual power level is not restricted by the '43, power limit.
9. SERIAL COMMUNICATIONS
Refer to the full user guide (available from your supplier) for details.
10. SPECIFICATIONS
UNIVERSAL INPUT
Thermocouple
Calibration:
PT100 Calibration:
DC Calibration:
Sampling Rate: 4 per second.
Impedance:
Sensor Break
Detection:
Isolation: Isolated from all outputs (except SSR driver). If relay outputs
REMOTE SETPOINT INPUT
Accuracy:
Sampling Rate: 4 per second.
Sensor Break
Detection:
Isolation: Slot A - Basic isolation, Slot B - Reinforced safety isolation
DIGITAL INPUTS
Volt-free(or TTL): Open(2 to 24VDC) = SP1, Local SP or Auto Mode,
Isolation: Reinforced safety isolation from inputs and other outputs.
OUTPUTS
Relay
Contact Type &
Rating:
Lifetime: >500,000 operations at rated voltage/current.
Isolation: Basic Isolation from universal input and SSR outputs.
SSR Driver
Drive Capability:
Isolation: Not isolated from universal input or other SSR driver outputs.
Triac
Operating Voltage: 20 to 280Vrms (47 to 63Hz).
Current Rating: 0.01 to 1A (full cycle rms on-state @ 25°C);
Isolation: Reinforced safety isolation from inputs and other outputs.
DC
Resolution: 8 bits in 250mS (10 bits in 1s typical, >10 bits in >1s typical).
Isolation: Reinforced safety isolation from inputs and other outputs.
Transmitter PSU
Power Rating:
Isolation: Reinforced safety isolation from inputs and other outputs.
SERIAL COMMUNICATIONS
Physical: RS485, at 1200, 2400, 4800, 9600 or 19200 bps.
Protocols: Selectable between Modbus and West ASCII.
Isolation: Reinforced safety isolation from all inputs and outputs.
OPERATING CONDITIONS (FOR INDOOR USE)
Ambient
Temperature:
Relative Humidity: 20% to 95% non-condensing.
Supply Voltage and
Power:
ENVIRONMENTAL
Standards: CE, UL, ULC.
EMI: Complies with EN61326 (Susceptibility & Emissions).
Safety
Considerations:
Front Panel Sealing: To IP66 (IP20 behind the panel).
PHYSICAL
Front Bezel Size: UDC1200 = 48 x 48mm, UDC1700 = 96 x 48mm,
Depth Behind Panel: UDC1200 = 110mm, UDC1700 = 100mm.
Weight: 0.21kg maximum.
±0.1% of full range, ±1LSD (±1°C for Thermocouple CJC).
BS4937, NBS125 & IEC584.
±0.1% of full range, ±1LSD.
BS1904 & DIN43760 (0.00385
Ω/Ω
/°C).
±0.1% of full range, ±1LSD.
>10MΩ resistive, except DC mA (5Ω) and V (47kΩ ).
Thermocouple, RTD, 4 to 20 mA, 2 to 10V and 1 to 5V ranges
only. Control outputs turn off.
are connected to a hazardous voltage source, and the
universal input is connected to operator accessible circuits,
supplementary insulation or input grounding is required.
±0.25% of input range ±1 LSD.
4 to 20 mA, 2 to 10V and 1 to 5V ranges only. Control outputs
turn off if RSP is the active SP.
from other inputs and outputs.
Closed(<0.8VDC) = SP2, Remote SP or Manual Mode.
Single pole double throw (SPDT); 2A resistive at 120/240VAC.
SSR drive voltage >10V into 500Ω min.
derates linearly above 40°C to 0.5A @ 80°C.
20 to 28V DC (24V nominal) into 910Ω minimum resistance.
0°C to 55°C (Operating), –20°C to 80°C (Storage).
100 to 240VAC ±10%, 50/60Hz, 7.5VA
(for mains powered versions), or
20 to 48VAC 50/60Hz 7.5VA or 22 to 65VDC 5W
(for low voltage versions).
Complies with EN61010-1 & UL3121.
Pollution Degree 2, Installation Category II.