Honeywell TZ-3 User Manual

PRODUCT DATA
3-2
pyrig
TZ-3 TotalZone® Zone Control Panel

APPLICATION

p
p

FEATURES

• Up to three stages heat and two stages cooling can be
p
y
pp
g
Contents
p
p
p
g
controlled by thermostat or built-in timer, based on the number of zones calling.
• Controls up to three zones and can be expanded with TotalZone Add-A-Zone zone Control Panel for up to 30 zones.
• Uses virtually any Honeywell four-wire, single-stage, multi-stage, or Trol-A-Temp heat pump thermostat.
• Zone-A-Lone central setback feature.
• Purge timer protects equipment between calls for heat or cool with choice of continually on or equipment controlled fan.
• System and zone damper LEDs indicate system and damper status.
• Individual zone fan control.
• Optional Discharge Air Temperature Sensor for capacity control with adjustable high and low limits.
• Thermal circuit breaker protects panel and transformer from damage if miswired.
The TZ-3 TotalZone Zone Control Panel controls single-stage, multi-stage, conventional or heat pump heat/cool equipment. It controls 2 or 3 zones, and is ex
tional TotalZone® Add-A-Zone™ Zone Control Panel.
o
® U.S. Registered Trademark
ht © 2001 Honeywell • All Rights Reserved
Co
andable up to 30 zones with
For Internet access: www.trolatem
www.hone
For technical su
To download Zonin
Application.........................................................................1
Features ............................................................................1
ecifications ....................................................................2
S
Installation .........................................................................4
Startu
eration...........................................................................10
O Troubleshootin
well.com/yourhome/zoning/zoning_home.htm
and Checkout........................................................9
.................................................................13
.com or
ort, call 1-800-TAT-Temp (1-800-828-8367).
literature: http://hbctechlit.honeywell.com
68- 022
TZ-3 TOTALZONE® ZONE CONTROL PANEL

SPECIFICATIONS

g
(p
gaug
p
(
(
g
g
y
p
y
(
ps)
q
p
Electrical:
Dimensions:
Mounting:
24 Vac, 60 Hz.
See Fi
. 1.
Mounts with three screws
rovided) through
7-5/8 (195)
COOL
HEAT
PURGE
FAN
EM. HT. ZONE 1 ZONE 2 ZONE 3
holes in cabinet back
Wiring:
18-
e wire for all equipment and system
connections
Wiring Connections:
Thermostat: W2, L, G, Y, R, W
ers: M6 (Closed); M4 (Open); M1 (Common)
Dam
ZoneMax TL, TL Zone-A-Lone: OC,OC. Transformer: TR1
hot), TR2 (common).
®
Equipment: Y2, Y1, O, R, G, B, W1, E, W2, W3.
Thermostats (See Table 1):
Conventional 4-wire Manual or automatic chan
each zone thermostat. Multi-sta
e or select heat pump thermostats can be used.
R,W,Y,G) thermostats.
eover switching subbase for
Fig. 1. TZ-3 dimensions in in. (mm).
Table 1. Recommended Thermostats.
System Trol-A-Temp Logo Honeywell Logo
Single Stage
Non-Programmable Programmable Non-Programmable Programmable
7-13/16
(198)
1-5/8
(41)
M19062
T87F3715/Q539A1436 T87F3707Q539A1428
T8601D2027 T8131C1020
T87F1859/Q539A1014 Q87F4010/Q539A4026 T8400C1016 T8400C1040
T8600D2069 T8600D2028 T8601D2019 T8602D2018 T8602D2000 T8000C1002 T8000C1010
Heat Pum
a
T8611G2051
a
Y594R1243 Y594G1252
a a
T8011R1006 T8011R1014
T8411R1002 T8411R1028
b
Multi-Stage
a
Heat pump thermostat with single Y first-stage terminals. See Heat Pump Thermostats with Single Y Output section and Fig. 3.
b
Multi-stage and heat pump thermostats are not required to control multi-stage and heat pump systems with TotalZone. They are
used onl
when second stage or emergency heat control from the zone thermostat is needed.
Y594D1347
b
T8624D2004 T8624D2012
a b
Dampers (See Table 2):
Five dam Use SDCR for additional dampers required on one zone. Use isolation rela
Dampers are connected to M1, M4, and M6 (see Fig. 6-10
ers maximum connected to each panel.
when CDO-32 Damper or ML6161
Motor Actuator is used
for hooku
.
see Fig. 10).
M1 Common
M4 Power Open
M6 Power Close
Accessories:
For re
uired accessories, see Table 3.
68-0223-2 2
TZ-3 TOTALZONE® ZONE CONTROL PANEL
)
)
p
Table 2. Recommended Dampers.
Honeywell Damper Type Round Rectangular
Power-open/power-closed MARD IOBD
AOBD AOBD-BM CDO-51
Spring-open/power-closed ARD ZDB
ZDS
Table 3. Required Accessories (Not Supplied With Panel).
Accessory Description
40 VA transformer AT140D1046 (PMT-40
Capacity protector ZMS, DATS (C7735A1000
Round static pressure regulator damper
7 SPRD 8 SPRD 9 SPRD 10 SPRD 12 SPRD 14 SPRD 16 SPRD 18 SPRD
Rectangular static pressure regulator
er
dam
12 x 8 SPRD 12 x 10 SPRD 12 x 12 SPRD 20 x 8 SPRD 20 x 10 SPRD 20 x 12 SPRD
300 400 600 750 1200 1800 2400 3200
1000 1200 1400 1600 2000 3000
Bypass Rating
(cfm)
3 68-0223-2
TZ-3 TOTALZONE® ZONE CONTROL PANEL

INSTALLATION

Mounting

y
g sp
p
p
g

Wiring

p
g
g
g
p
g
g
p
p
g
quip
p
(
y
g

Wiring Diagrams (Fig. 3-17)

Conventional Thermostats
q
p
p
Heat Pump Thermostats
g
CAUTION
Equipment Damage Hazard. Do not mount TZ-3 inside HVAC equipment
Mount onl
1.
Mount the thermostats in each zone of the livin
on wall or on cold air return
using the installation instructions provided with each
thermostat.
2.
Mount the dam
ers in the ductwork using the installa-
tion instructions provided with each damper.
3.
Mount the TZ-3 zone
anel near the HVAC equipment;
locate it on a wall or on the cold-air return. See Fi
4.
Level the TZ-3 for appearance only.
CAUTION
Voltage Hazard. Can cause electrical shock or equipment damage.
Disconnect
must comply with applicable codes, ordinances, and
Wirin
ulations.
re
1.
Connect thermostats as shown in Fi
2.
Connect dam
3.
Connect the Dischar
supplied) to the TL terminals.The wires are not polar-
ized. See Fi
4.
Connect Add-A-Zone
AZ2 terminals. The AZ1 terminal on the TZ-3 must be
wired to the AZ1 terminal on the TAZ
the AZ2 terminal must be wired on the TZ-3 to the AZ2
on the TAZ. See Fi
5.
Connect the HVAC e
on the
6.
Connect a 40 VA, 24 volt transformer to TR1 (hot) and
common). This must be a dedicated transformer
TR2
and an
transformer. See Fi
ower before continuing installation.
. 3-5.
ers as shown in Fig. 6-10.
e Air Temperature Sensor (not
.12.
anels (if used) to the AZ1 and
anel. Similarly,
. 13.
ment to the EQUIP terminals
anel. See Fig. 14-17.
additional TAZ boards also each require a
. 11.
ace
. 2.
RETURN
AIR
T2-3 OPTIONAL LOCATION
EFFICIENCY
AIR CLEANER
HIGH
E L E
C T R
O N I C A I
R C L
E A N
E R
FURNACE OR BOILER
WATER
HEATER
T2-3
M19063
Fig. 2. TZ-3 mounting location.
The C (common) terminal is used only on thermostats that
uire a common (for example:T8601). See Fig. 3. Wire the
re W2 terminal on a multi-stage thermostat (for example: T8624) to the W2 on the
anel for second stage control from the thermostat. If the thermostat has a Y2 terminal, do not connect it to the
anel.
ZONE CONNECTIONS ON PANEL
THERMOSTAT
LW2 G Y R W M6
GYR WC
ZONE THERMOSTAT
MOTOR
M4 M1
M19064
68-0223-2 4
Fig. 3. Typical single-stage thermostat wiring.
Select a heat pump thermostat from Table 1. If the thermostat selected has a separate Y1 and W1, see Fig. 4. When using the thermostat to control the second sta
e of heat (W2), set DIP switch 5 to On, and DIP switch 1 to Off. Set both DIP switches 6 and 7 to Off.
TZ-3 TOTALZONE® ZONE CONTROL PANEL
g
(
p
g
(W2)
AOBD Dampers
g
p
ARD or ZD Dampers
p
p
g
MARD or CDO-51 Dampers
g
p
ZONE CONNECTIONS ON PANEL
THERMOSTAT
LW2 G Y R W M6
GLW2E Y1 R W1 C/X
ZONE THERMOSTAT
MOTOR
M4 M1
M19065
Fig. 4. Heat pump thermostat with separate Y1 and W1
terminals and multi-stage thermostat wiring.
If the thermostat selected has a sin
le Y terminal, see Fig. 5.
Select a single Y thermostat for each zone. See Table 1.
Set DIP switch 6 or 7
not both) to the On position. Set switch 6 to On when B on the thermostat is wired to W on the panel. Set switch 7 to On when 0 on the thermostat is wired to W on
anel.
the
When usin of heat
the zone thermostat to control the second stage
, set DIP switch 5 to On, and DIP switch 1 to Off.
MOTOR TERMINALS
M6 M4 M1
4
5 6
123ZX
FIELD JUMPER
DAMPER MOTOR
Fig. 6. AOBD single damper wiring.
MOTOR TERMINALS
FIELD JUMPER
4 5 6 123ZX
M6 M4 M1
4
5 6
123
Z X
M19067
ZONE CONNECTIONS ON PANEL
THERMOSTAT
LGYR W M6
E W2 L G Y R O C/X
HEAT PUMP ZONE THERMOSTAT
MOTOR
M4 M1W2
M19066
Fig. 5. Heat pump thermostat with single Y thermostat
wiring.
Wire the AOBD, AOBD-BM and IOBD Dampers to the panel as shown in Fi
. 6. See Fig. 7 when using two dampers on one zone. When three or more dampers are controlled on one zone, a slave dam
er control relay (SDCR) is required.
DAMPER MOTORS
M19068
Fig. 7. AOBD multiple damper wiring.
Wire the ARD or ZD Damper to the panel as shown in Fig. 8.
le dampers can be wired in parallel. When ARD or ZD
Multi
er is used, the zone LEDs switch directly from red to
dam
reen (never amber).
DAMPER TERMINALS
ON PANEL
M6 M4 M1
POWER CLOSE SPRING OPEN MODEL ARD, ZDS, ZDB
M19037A
Fig. 8. ARD or ZD Damper wiring.
Wire the MARD or CDO-51 Damper to the panel as shown in
. 9. These are floating control modulating dampers, but are
Fi controlled as two-
osition dampers on the TZ-3 panel.Two
dampers can be wired in parallel.
5 68-0223-2
TZ-3 TOTALZONE® ZONE CONTROL PANEL
ML6161 Motor Actuator
g
Transformer
p
Discharge Air Temperature Sensor
Add-A-Zone Panel
p
gaug
p
g
Conventional Equipment
g
g
y
quip
g
y
p
TO ADDITIONAL
TAZ PANELS
M19073
AZ2
AZ1
TAZ
AZ2
AZ1
TAZ
AZ2
AZ1
TZ-3
ZONE CONTROL PANEL
DAMPER TERMINALS
M6 M4 M1
MARD OR CDO-51
COM / M1
CL / M6
OP / M4
M19069
ZMS
SENSOR
TL TL
M19072
Fig. 12. Discharge Air Temperature Sensor (C7735A or
ZMS) wiring.
Fig. 9. MARD and CDO-51 Damper wiring.
When the ML6161 Motor Actuator is used, wire as shown in
. 10. Wire the R8222 relay to prevent the damper LED from
Fi constantly lighting amber.
ZONE CONTROL PANEL
DAMPER TERMINALS
M6 M4 M1
R8222 RELAY
THERMOSTAT
R
ZONE
TERMINAL
ML6161
COM / M1
CL / M6
OP / M4
M19070
Fig. 10. ML6161 Damper Motor Actuator wiring.
Wire the transformer to the panel as shown in Fig. 11.
Wire the Add-A-Zone (TAZ) Panel to the TotalZone (TZ-3) Panel as shown in Fig. 13. Up to nine TAZ Panels can be wired to one TZ-3
Use 18­500 feet. Kee
and equipment; otherwise, use shielded cable wiring.
wirin
anel. See Fig. 13.
e thermostat wire for runs up to a maximum of
these wires at least 12 in. from line voltage
IMPORTANT:
When multiple panels are used, it is important that the transformers be in-phase. Check the phasing by measuring for 24V across the TR2 transformer termi­nals on each panel. There should be 0 Vac. If not, reverse the TR1and TR2 transformer wires on one of the panels and recheck.
NOTE: If the installation includes an Add-A-Zone
the TotalZone Add-A-Zone Panels section.
24 VOLT TRANSFORMER
TR2 TR1
24V, 40 VA
TRANSFORMER
MODEL AT140D1046
Fig. 11. Transformer wiring.
Wire the C7735A or the ZMS to the panel as shown in Fig. 12.
68-0223-2 6
anel, see
Fig. 13. TotalZone Add-A-Zone wiring.
Wire the heating and cooling equipment to the equipment terminals on the TZ-3 Panel as shown in Fi
Electric Furnaces: Set DIP switch 8 to On to ener
C
R
M19071
with a call for heat.
dro-Air: Wire the zone valve or circulator relay to the W1
H
ment terminal. (If the circulator relay has powered
e
. 14.
ize the fan
terminals, use an isolation relay.) Set DIP switch 8 to On to
ize the fan with a call for heat.
ener
Oil Heat: Wire an isolation rela isolate the oil
rimary from the panel.
on the W equipment wire to
TZ-3 TOTALZONE® ZONE CONTROL PANEL
g
Heat Pump Equipment
g
quip
y
g
p
g
Multi-Stage: Wire the equipment as shown in Fig. 14 using the W2 terminal for second sta
e of heat and the W3 terminal for
third stage of heat. Wire the Y2 for second stage of cooling.
HEAT
TM
ZoneMAX
TEMPERATURE
SENSOR
TO TERMINAL AZ2 ON TAZ (IF USED) TO TERMINAL AZ1 ON TAZ (IF USED)
OUTDOOR CONDENSING UNIT
Y2
C
24V TRANSFORMER
FAN RELAY
HEAT RELAY
HVAC CONTROLS
Y
R
G
W
W2
ZoneMAX
Add-A-Zone
2 STAGE EM HEAT
MODEL TZ-3
TM
TL TL
AZ2 AZ1
Y2 Y1 O R G B W1 E W2 W3
COOL PURGE FAN EM.HT ZONE 1 ZONE 2 ZONE 3
130 F
140 F
120 F 110 F
MAXIMUM
TEMPERATURE
THERMOSTAT MOTOR
LW2 G Y R W M6 M4
15 MINUTES
150 F
10 MINUTES
160 F
5 MINUTES
ON
2 3 4 5 6 7 8
1
ZONE 1
STAGE TIMER
M1
20 MINUTES
25 MINUTES
30 MINUTES
THERMOSTAT MOTOR
LW2 G Y R W M6 M4
OVERRIDE
PURGE
ZONE 2
THERMOSTAT MOTOR
M1
LW2 G Y R W M6 M4
REMOTE OCCUPIED/
UNOCCUPIED CONTROL
(CLOSE IN UNOCCUPIED)
ON
BOOT
OFF
Emergency Heat
OCCUP
REMOTE
Zone-A-Lone
UNOCCUP
OC OC TR2 TR1
ZONE 3
M1
CGYRW
ZONE 1
THERMOSTAT
456Z
123X
Fig. 14. Heating and cooling equipment.
Wire the heat pump to the equipment terminals on the panel as shown in Fig. 15. Refer to manufacturer’s instructions for additional wirin
ment terminals for the thermostat terminals shown.
e
instructions and substitute the TZ-3
IMPORTANT
Some heat pump manufacturers (such as York and Trane) use the B terminal as the transformer com­mon. Do not connect the common from the equip­ment to the zone control panel.
C
CGYRW
ZONE 2
THERMOSTAT
456Z
123X
OPPOSED BLADE DAMPER MOTORS
GYRW
ZONE 3
THERMOSTAT
MODEL ARD OR ZD DAMPERS
24V, 40 VA TRANSFORMER
Two-speed Compressor: Wire the second stage compressor to both Y2 and W2. Wire the auxiliar two-sta
e emergency heat jumper and install a jumper from
heat to W3. Remove the
W3 to E.
Fossil Fuel Kits with Heat Pum
s: Wire these systems like Fig.15 but use the manufacturer’s fossil fuel kit. Wire the Trane XL 1800 and the TAYPLUS 103 as shown in Fi The recommended thermostat is theT8611G2051.
CR
M19074
. 16.
7 68-0223-2
TZ-3 TOTALZONE® ZONE CONTROL PANEL
Water Source Heat Pumps
OUTDOOR CONDENSING UNIT
TZ-3 COMPRESSOR RELAY
REVERSING VALVE (COOL)
C
24V TRANSFORMER
FAN RELAY
EMERGENCY HEATING RELAY
2 STAGE HEATING RELAY
HEAT PUMP CONTROLS
Y
O
R
G
E
W2
PAN EL
EQUIP
Fig. 15. Heat pump with auxiliary heat wiring.
.
TAYPLUS 103
Y3 X3 G3
W3
Y2 G1
X2 Y1 B W1
G
W2
W1
B
O
Y
YLO
BK
R
VARIABLE
SPEED
GAS
FURNACE
T
F
Y2
R
B
Y1
O
X2
TRANE XL1800
CONDENSING
UNIT
ODT
2
3
1
K2
4
M19075
1
Y2 Y1 O R G B W1 E W2 W3
HEAT
COOL PURGE FAN EM.HT ZONE 1
TM
ZoneMAX
TL TL
AZ2 AZ1
Add-A-Zone
Y2
130 F
120 F 110 F
MAXIMUM
TEMPERATURE
140 F
15 MINUTES
150 F
10 MINUTES
160 F
5 MINUTES
ON
1
2 3 4 5 6 7 8
STAGE TIMER
20 MINUTES
25 MINUTES
30 MINUTES
OVERRIDE
PURGE
Y1 O R G B W1 E W2
2 STAGE EM HEAT
MODEL TZ-3
W3
ZONE 1
THERMOSTAT MOTOR
LW2 G Y R W M6 M4
YERW2
L
G O/B C
M1
THERMOSTAT MOTOR
LW2 G Y R W M6 M4
ZONE 2
M1
T8611G2051
3
5
NOTES:
1. DIP SWITCHES 6 OFF AND 7 ON.
2. DIP SWITCHES 1 OFF AND 5 ON.
3. T8011R OR T8411R MAY ALSO BE USED.
4. REMOVE THE 2 STAGE EM HEAT JUMPER.
M19076
Fig. 16. Trane XL 1800 with TAYPLUS 103 in restricted mode wiring.
Wire the equipment, as applicable, to the TZ-3 as shown in
68-0223-2 8
Fig. 17. Turn DIP switch number 8 to On for fan on in heat. Remove the two-stage emergency heat jumper.
TZ-3 TOTALZONE® ZONE CONTROL PANEL
p

STARTUP AND CHECKOUT

(
p
(up) p
q
p
g
(
g
p
g
p
y
p
p
(
g
y
g
Waterfurnace: Wire this system to the panel as shown in Fig. 17 exce
t use two isolation relays on compressor wires W1,
Y1 and W2, Y2.
1ST STAGE COMPRESSOR
2ND STAGE COMPRESSOR
AUXILIARY HEAT
O
G
Fig. 17. Water source heat pump wiring.
After the installation is complete, verify correct operation as follows:
1.
Place the Em Heat switch in the Off
2.
Place the Zone-A-Lone switch in the Occu
down) position.
/Remote
osition.
3.
Verify that the DIP switches are set correctly. See
uence of Operation section and Table 6 for correct
Se configuration.
4.
Power u are callin
the TZ-3 and set the thermostats so no zones
. The board then enters the Purge mode where all dampers open and the fan operates for two or three and one-half minutes no Dischar
e Air Temperature Sensor connected to the
configurable). (If there is
R
C
Y1
Y2
W
2 STAGE EM. HT.
Y2 Y1 O R G B W1 E W2 W3
M19077
anel, the Idle LED flashes seven times before entering the Pur dam
5.
Set zone one thermostat to heat and raise the setpoint to call for heat. Verif one dam
e mode.) Then the Idle LED turns red and each
er LED turns green.
that the heat LED is red and zone
er remains green while the other damper LED
turns red.
6.
Raise zone two set
oint to call for heat. Lower zone one setpoint to stop the call for heat to that zone. Verify that zone one LED turns red and zone two LED turns
7.
Repeat for zone three.
8.
Alternatel that the
, lower the setpoint to call for cooling.Verify
reen cool LED illuminates.
it may be amber while moving)
reen.
9 68-0223-2
TZ-3 TOTALZONE® ZONE CONTROL PANEL

OPERATION

Sequence of Operation

g
g
y
g
purg
y
p
g
g
g
Purge Mode
g
g
y
quip
g
g
Individual Zone Fan Control
p
p
p
g

Single and Multi-Stage Operation

g
g
g
g
g
g
quip
1st Stage by Thermostat, 2nd and 3rd Stages by
Timer (Fig. 18)
p
y
1st Stage by Thermostat, 2nd Stage Heat by
Thermostat
g
y
p
purg
On a call for heating or cooling, the zone damper stays open to the callin are not calling. The TZ-3 panel brings on the heating or coolin until that zone is satisfied. When the call is satisfied, the
stem enters the Purge mode. This holds open the damper
s of the last zone callin time can be set to three and one-half or two minutes. After
e, all dampers return to the Open position.
An
zone thermostat can call for heating or cooling. If there are co-existing calls for heat and cool, the panel first accepts the first call. Once that call is satisfied, or a maximum of 20 minutes has ela call.
On a call for heatin or the cool LED illuminates green. The zone damper LED turns not callin LEDs turn amber.
At the end of every call for heat or cool, the panel enters a
e mode that holds open the calling zone damper for three
Pur and one-half or two minutes. Durin HVAC equipment can operate the fan. Purge also serves as a time dela e system is in the Purge mode. Pressing the purge override button for two seconds overrides the Pur there is a new call for heat or cool durin dampers are moved to the Open position at the end of purge.
zone, and the dampers close to the zones that
and conditioned air is delivered to the calling zone
and purges into that zone. The purge
sed, the panel switches to allow the opposite
or cooling, the heat LED illuminates red
reen for the zone calling, and the dampers in the zones
close and turn red. As AOBD dampers move, the
this time, the panel or the
to prevent short cycling of the heating and cooling
ment after each call. Purge LED lights to signal that the
e mode. Unless
the Purge mode, all
The panel can control up to three stages of heating and two
es of cooling. The first stage is energized by the
sta thermostat. The second stage of heating is brought on by the thermostat, timer, or number of zones callin of heatin calling. The second stage of cooling is brought on by the timer or number of zones callin
The followin sta
If the e follows:
The thermostat controls the first stage of heat or cool. If the call is not satisfied by the first stage within the time set on the timer, the is not satisfied b timer, the panel brings on the third stage.
Set the DIP switches as follows:
is brought on by the timer or number of zones
.
instructions show how to configure the panel for
e control.
ment is single stage, set the DIP switches as
DIP Switch Number Status
1 Off
5 Off
anel energizes the second stage. If the call for heat
the second stage within the time set on the
DIP Switch Number Status
. The third stage
DIP Switch
Number Status Purge Time
3 Off 3.5 minutes
3 On 2 minutes
DIP Switch
Number
4 Off Panel control of fan
4 On HVAC control of fan
When all zones are satisfied, the Fan switch of each thermostat controls the fan o Fan switch is in the On position, the fan is energized, and the
ers close to zones where the Fan switch is in the Auto
dam
osition. If there is a call for heat or cool during this time, the circulation mode ceases, and the heat or cool call is honored. When the zone callin resumes.
68-0223-2 10
Status Fan Control
e
in
in purge
eration for that zone. When the
is satisfied, the circulation call
1 Off
5 Off
15 MINUTES
10 MINUTES
5 MINUTES
STAGE TIMER
Fig. 18. Stage timer.
The thermostat controls the first stage of heat or cool and the second sta cool and third stage of heat. If the first and second stages combined do not satisf on the timer, the
Set the DIP switches as follows:
e of heat. The timer controls the second stage of
the heat call within the time specified
anel brings on the third stage of heat.
20 MINUTES
25 MINUTES
30 MINUTES
M19078
TZ-3 TOTALZONE® ZONE CONTROL PANEL
Stages Based On Number of Zones Calling
g
g
y
pp

Thermostat Operation

Conventional Thermostats
g
g
g
y
pump
Heat Pump Thermostats
HEAT PUMP THERMOSTATS WITH SINGLE Y OUTPUT
g
g
g
y
y
HEAT PUMP THERMOSTATS WITH SEPARATE Y1 AND W1
TERMINALS
g
p
Emergency Heat Control
g
p
pump
y
g
g
p
g
jump
p
quip
p
Multi-Stage Thermostats
g
g
Manual and Automatic Changeover Thermostats
g
.
DIP Switch Number Status
1 Off
5 On
The thermostat controls the first stage of heat or cool. The second sta energized by the percentage of zones calling. See Table 4. Set the DIP switches as follows:
DIP Switch Number Status
See Table 4 to determine the number of zones required to activate sta the s system, not the number of zones used for the particular
lication. As zones satisfy, stages 2 and 3 drop out.
a
e of heat and cool and the third stage of heat are
1On
5Off
es of equipment based on the number of zones in
stem. Staging is based on the zones available in the
Table 4. Staging by Percentage of Zones Calling.
e heat using a 5-30 minute panel, or staging can be
sta controlled b equipment terminals are energized for changeover use with heat
Heat pump thermostats can be used if thermostat control of
nd
stage is desired. Thermostats that have a single Y
2 terminal for first sta selected, all thermostats must be similar.
If the thermostat ener must be set to On and the O thermostat wire connected to W on the thermostat connections for that zone. If the thermostat ener and the B wire connected to W on the panel. In either case, the O is alwa B is alwa
the percentage of zones calling. The O and B
s.
e heat and cool can be used. When
izes O on a call for cool, DIP switch 7
izes B on a call for heat, DIP switch 6 must be set to On
s energized to the equipment in cooling, and the
s energized to the equipment in heating.
IMPORTANT
Be sure DIP switches 6 and 7 are never both in the On position.
Use heat pump thermostats with separate Y1 and W1 terminals for first sta and 7 in the Off used.
e heat and cool. Keep DIP switches 6
osition when thermostat O or B wire is not
Number of
Zones in
System
32 32
42 33
52 43
63 54
73 54
83 65
94 75
10 4 7 6
11 4 8 6
12 5 9 7
Conventional (R,W,Y,G) heat/cool thermostats can be used with the TZ-3 to control sin systems and heat pumps with auxiliary heat. The panel can be confi
ured to control second stage heat and cool and third
Number of Zones Required
2nd Stage
Heat
3rd Stage
Heat
le or multi-stage gas, electric or oil
2nd Stage
Cool
Emergency heat is defined as using an auxiliary heat source without usin thermostat heat pump is locked out and calls for heat are sent to the E terminal.
A heat from the thermostat s durin recommended heat pump thermostats all have hot L terminals. See Table 1.
The two sta both emer W2, remove the with electric heat stri below the e
anel.
Use multi-stage thermostats to control two stages of heat via W1 and W2 thermostat terminals. Control the third sta heat throu second stage of cooling with the timer.
Automatic changeover thermostats provide automatic chan cool based on the mode of each zone thermostat.
the heat pump. When the Em Heat switch or a
uts the panel in the emergency heat mode, the
thermostat can also control emergency heat
stem switch. An L terminal energized
the emergency heat mode is required. The
e Em heat jumper connects W2 and E. Jumper ins to energize the W2 equipment on a call for ency heat. When E is a different source of heat than
er (for example, two-stage heat pump
auxiliary heat ). The jumper is located
ment terminals on the lower-left corner of the
e of
h the stage timer built into the panel. Control the
eover by zone. Manual changeover thermostats heat or
11 68-0223-2
TZ-3 TOTALZONE® ZONE CONTROL PANEL

Rebooting Microprocessor

g

Discharge Air Temperature Sensor

p
p
g
p
g
y
g
y
g
p
pp
g
p
quip

Zone-A-Lone Switch

y
p
g
y
g
p
q

Circuit Breaker Protection

p
p
pp
p
y

Fan On In Heat

g

TotalZone Add-A-Zone Panels

p
q
Certain conditions can hang up the microprocessor. To reset it, press and release the Boot button. The system reboots and enters the Pur
The Discharge Air Temperature Sensor (not included) is a supply-duct-mounted temperature probe used to control
acity and prevent over-heating or coil-icing. The sensor
ca attaches to the TL terminals on the
Set the hi dial on the Set the temperature from 110 °F to 160°F in ten-degree increments. The recommended settin
stems is 160°F (default factory setting). For heat pump
s systems, the recommended setting is 120F.
The coolin
e mode.
anel.
h limit temperature on the maximum temperature
anel, located left of the stage timer. See. Fig. 19.
for fossil fuel/ electric
temperature limit can be set at 40°F or 48°F.
130 F
120 F
110 F
MAXIMUM
TEMPERATURE
Fig. 19. Maximum temperature dial.
140 F
150 F 160 F
M19079
IMPORTANT
Be sure the Discharge Air Temperature Sensor wir­ing does not run parallel with line voltage wiring unless more than 12 in. of separation exists or shielded cable is used.
Use DIP switch 2 to change cooling limit settings.
When the Zone-A-Lone switch is in the occupied position and the OC/OC terminals are not used, the system functions as a normal zone control s unoccu for heat, cool, or fan, except from zone one, are not honored. The zone one thermostat becomes the controllin for the entire s thermostat can be set back instead of adjusting each zone thermostat in the buildin
The T8601D2027 and T8611G2051 include two OC terminals. When wired to the TZ-3 OC terminals, and with the Zone-A­Lone switch in the occu unoccupied mode during the Leave and Sleep programs. This feature re
A built-in thermal circuit breaker protects the TotalZone panel. This circuit breaker protects the panel against shorts in the thermostat and dam unoccu wiring of the HVAC equipment into the panel.
When the circuit breaker is tri illuminate and the yellow rectangular component located to the left of the TR1 and TR2 terminals is hot to the touch. Remove the circuit breaker to cool off and reset. To eliminate the short, verif
The system blower can be set to come on with a call for heat as required for hydro-air, heat pump, or electric heat systems. Set the blower usin
ied position, all dampers are opened and all requests
uires two extra wires to the Zone 1 thermostat.
ied switch. It does not protect against shorts in the
ower to the panel for at least ten seconds to allow
the dampers and thermostat wiring.
stem. When switched to the
thermostat
stem. During long unoccupied periods, one
.
ied position, the board enters the
er wiring and the remote occupied/
ed, none of the LEDs
DIP switch 8.
Cooling
Dip Switch Status
2 Off 40°F
2 On 48°F
If the s limit, the heatin continues running to purge the conditioned air from the
When the low limit is tri resets. When the hi until it resets.
Once the tem e
68-0223-2 12
stem trips due to exceeding a high or low temperature
or cooling system shuts down and the fan
lenum.
ed, the Cool LED flashes until it
h limit is tripped, the Heat LED flashes
erature recovers by ten degrees, the
ment run resumes.
Temperature
Limit
DIP Switch 8 Fan Control
Off HVAC system
On Fan on in heat
Using TotalZone Add-A-Zone Panels, the system can be ex
anded to up to 30 zones. There are three models: TAZ-1,
one zone; TAZ-2, two zone; and TAZ-3, three zone. Two wires
uired to connect the TAZ to the TZ-3.
are re
IMPORTANT:
When multiple panels are used, it is important that the transformers be in-phase. Check the phasing by measuring for 24V across the TR2 transformer termi­nals on each panel. There should be 0 Vac. If not, reverse the TR1and TR2 transformer wires on one of the panels and recheck.
See Fig. 13 and the TAZ installation instructions for more information.
TZ-3 TOTALZONE® ZONE CONTROL PANEL

TROUBLESHOOTING

g
g
y
p
y
y
p
Table 5. Troubleshooting.
Symptom Possible Cause Action
No LEDs are Illuminated No power to the board. Check for 24 Vac (±10%) across TR1 and TR2
Shorted wire. Check fuse. If hot, a short exists in thermostat, damper,
Damper LEDs on, but no other LEDs illuminated.
Erratic Operation Emergency Heat switch on. Turn off (down) Emergency Heat switch.
Heat pump operates incorrectl
Heat LED flashing. High limit reached. LED stops flashing with ten-degree fall.
Cool LED flashing. Low limit reached. LED stops flashing with ten-degree rise.
Idle LED flashes five times on bootu
Idle LED flashes continuousl
Add-A-Zone not operating. Incorrectly configured. Verify DIP switch settings on the TAZ panels.
or not at all.
.
Insufficient voltage. Check for 24 Vac (±10%) across TR1 and TR2.
Incorrect configuration. Check jumpers and DIP switches for correct
Zone-A-Lone Feature on. Turn off (up) Zone-A-Lone.
Incorrectly wired. Verify that W1 and Y1 equipment terminals are jumped.
Incorrectly configured. Verify DIP switches 6 and 7 are correctly set for the type
ZMS problem or not connected.
ZMS failure. Check for dc voltage across TL terminals:
or Zone-A-Lone wirin
uration.
confi
of thermostat used.
Verify that ZMS (if any) is connected, and wired correctl
If 0 volt = short. If 1 volt = o If .2 to .8 volt = normal.
.
en.
.
Incorrectly wired. Check AZ1and AZ2 for correct wiring.
Be sure that AZ1 and AZ2 are at least 12 in. from line voltage wiring.
Be sure the transformers are in-phase.
13 68-0223-2
TZ-3 TOTALZONE® ZONE CONTROL PANEL
g
g
g
g
quip
g (
p
)
Table 6. DIP Switch Settings and Functions.
DIP Switch Function Off (default) On
1 Staging by number of zones
.
callin
Stages timer or thermostat controlled.
Stages controlled by number of zones
.
callin
2 ZMS low limit. 40°F 48°F
3 Purge mode timing. Three and one-half minutes. Two minutes.
4 Fan control during purge. Controlled by panel. HVAC equipment controlled
5 Control of W2 outpu.t Timer controlled. Controlled by W2 from thermostat,
6 Cool changeover from
thermostat.
Not using B on single Y thermostats; or usin
Using B on single Y thermostat.
conventional thermostats.
7 Heat changeover from
thermostat.
Not using O on single Y thermostats; or usin
Using O on single Y thermostat.
conventional thermostats.
8 Fan control in heat. Fan controlled by panel in cool
and HVAC e
ment in heat.
Panel in heat and cool controlling fan.
Table 7. LED Indicators.
LED Color Illuminated Not Illuminated Flashing
Heat Red Heat call No heat calls. High limit reached
Cool Green Cool call No cool calls. Low limit reached
Purge Amber Purge mode Not in Purge mode. ZMS failure
Idle Red No calls Call for heat, cool, or fan. Initial powerup without ZMS
wired
Fan Green Fan only call No fan only call.
EM Heat Red Emergency Heat mode Not in emergency Heat mode.
Zone 1,2,3 Zone
1,2,3
Green—open Red—closed Amber—movin
ers
dam
some
68-0223-2 14
See Fig. 20 for TZ-TotalZone Zone Control Panel.
TZ-3 TOTALZONE® ZONE CONTROL PANEL
ZoneMAX™
TERMINALS
ZoneMAX™
TEMP
SETTING
ADD-A-
ZONE™
TERMINALS
STAGE
TIMER
HVAC
EQUIPMENT
TERMINALS
2 STAGE
EM HEAT
JUMPER
TEST JUMPERS
(NOT USED)
SYSTEM STATUS LED INDICATIORS
ZONE DAMPER LED INDICATORS
BOOT BUTTON
EMERGENCY HEAT SWITCH
ZONE-A- LONE™
SWITCH
REMOTE
ZONE-A-LONE™
CONTROL TERMINALS
TRANSFORMER TERMINALS
DIP SWITCHES FOR
SYSTEM CONFIGURATION
ZONE, THERMOSTAT & DAMPER
MOTOR TERMINALS
Fig. 20. TZ-3 TotalZone Zone Control Panel.
15 68-0223-2
RESETTABLE
FUSE
M13421
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.