SPECIFICAITON DATA

Dimensions

13/16

(21)

3-5/16

(84)

PRODUCT DESCRIPTION

The TR120/TR120-H are color touch screen wall modules compatible with Spyder® Classic, Stryker, and CIPer™ 30 controllers. The wall module communicates and is powered by the Sylk bus, so no additional wiring is needed. All versions include integral temperature and the TR120-H adds a humidity sensor to control comfort. The device enables local controller configuration through an easy to use touch screen interface with menu driven selections.

Features

Home screen can display one to three of any of the following parameters: Temperature Setpoint, Room Temperature, Room Humidity, Outdoor Humidity, Outdoor Temperature, and Time, or one of virtually any parameter in the controller.

Vertical or horizontal orientation

Restricted tenant access to controller parameters or imposed HVAC settings limits via password protection.

Assign labels for enumerated values.

Link setpoint limits to a network variable.

Access and adjust most parameters in the Honeywell controller.

Access and adjust the controller schedule.

Balance the VAV system from the wall module.

Permanent retention of user configuration, including setpoints after a power outage.

4-3/4

(121)

 

 

 

 

 

 

 

 

M36282

 

 

Fig. 1. Dimensions in inches (mm).

 

 

 

 

 

 

 

Table 1. Models

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Module

<![if ! IE]>

<![endif]>Temp

<![if ! IE]>

<![endif]>Humidity

Features

Access

<![if ! IE]>

<![endif]>Customizable Parameters*

 

<![if ! IE]>

<![endif]>ScheduleAccess**

 

Sylk Zio

 

 

 

Password

 

 

 

 

Wall

 

 

 

Protected

 

 

 

 

 

 

 

 

 

 

 

 

 

TR120

X

 

Color Touch Screen

Contractor

X

 

X

 

 

 

 

Temp, Override,

 

 

 

 

 

TR120-H

X

X

 

 

X

 

X

Setpoint

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjustment, Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*For accessing virtually any point in the controller, balancing from wall module, etc.

**Schedule access for simplified commissioning or modification after install.

31-00312-02

TR120 TOUCH SCREEN ZIO® WALL MODULES

Sylk Bus

The wall module communicates with the controller via Sylk, which is a two-wire, polarity-insensitive bus that provides both 18 Vdc power and communications. This enables a faster and less expensive installation all while minimizing errors. The recommended wire for Sylk is 1824 AWG (0.82 to 0.20 sq mm) single twisted pair, solid or stranded wire, unshielded. Standard thermostat wire (nontwisted pair) can be used for runs up to 100ft (30m). See Table 2.

Table 2. Maximum Distance.

Recommended maximum distance from controller to any Sylk device

Single twisted pair, non-

Standard thermostat wire,

shielded, stranded or solid

(non-twisted), shielded or

 

 

non-shielded, stranded or

 

 

solid

 

 

 

18-22 AWG

24 AWG

18-24 AWG

 

 

 

500 ft (150 m)

400 ft (120 m)

100 ft (30 m)

 

 

 

Compatibility

The TR120 wall module has been designed for use with Spyder® Classic, Stryker, and CIPer™ 30. It can directly accept a TR71 or TR75 application download from the controller with no additional modifications needed.

A TR71, TR71-H, TR75, or TR75-H wall module wired to the controller in the field can be directly replaced by the TR120 or TR120-H; simply remove the old wall module and install the new wall module (including new backplate). The backplate sizes and mounting holes are identical. The TR120 will accept the TR71 or TR75 file configuration (proxy file) downloaded from the existing controller and provide exactly the same configuration and functionality in a nicer touch screen user interface.

Honeywell Building Technologies

SPECIFICATIONS

Display:

Resistive LCD Touch Screen 4.3 inch (109 mm) diagonal 480 x 272 pixels

Environmental Ratings:

Operating Temperature: 32°F to 122°F (-0°C to 50°C) Storage Temperature: -4°F to 158°F (-20°C to 70°C) Relative Humidity: 5% to 95% non-condensing

Temperature Setpoint Range:

Default range is 55°F to 85°F (10°C to 35°C) Configurable for other ranges.

Temperature Sensor Accuracy:

±0.36°F at 77°F (±0.2°C at 25°C)

±0.9°F within operating range 41-99°F (±0.5°C within operating range 5-37°C)

Humidity Sensor Accuracy (TR120-H only):

±3% RH from 20% to 80% RH at temperatures 41°F - 122°F (5°C - 50°C)

Power Supply/Consumption:

18 VDC from controller Sylk bus

50 mA maximum

Maximum qty. (1) TR120 per Sylk bus

Mounting/Installation:

Horizonal or vertical orientation 82.5 mm junction box

60 mm J-box UK pattress box

Direct mount with suitable wall anchors

Approvals:

CE

FCC Part 15, Class B for emissions

Canadian ICES-003

Waste Electrical and Electronic Equipment (WEEE):

Correct disposal of this product (applicable in the European Union and other European countries with separate collection systems).