TP975A and B
Diffuser
Thermostat
Installation Instructions
Before Installation
1.Install TP975A and B Diffuser Thermostat in accordance with job drawings.
2.Mount units with fixed minimum outdoor air dampers such that the thermostat does not see any outdoor air.
Installation
General |
Mounting |
The TP975 Diffuser Thermostat is designed to provide proportional control for pneumatic valves and mixing boxes in heating or air conditioning systems. It is a one-pipe thermostat which mounts in one end of a slot or light troffer diffuser; or in a return air grille. Air connection is a sharp barb fitting for 5/32 plastic tubing. The TP975 is factory calibrated, however, field calibration is possible. The proportional band (TR) is adjustable from 2 to 1OF.
The TP975A is direct acting while the TP975B is reverse acting. Normal main line pressure is 18 psig .
PROPORTIONAL
BAND ADJ. (TR)
SETPOINT
ADJ. LEVER
R974
Fig. 1. TP975 with Setpoint Lever in Vertical Position.
The thermostat can be mounted in a variety of positions in fan coil units, return air grilles (wall or ceiling) or in a plenum return The setpoint lever of the TP975 can be rotated 90 degrees to line up in two different mounting planes,
NOTE: On fan coil units it is not recommended to apply a return air thermostat to a unit with a 100 percent outdoor air damper interference and the probability of reducing air flow across the thermostat.
R973
Fig. 2, TP975 with Setpoint Lever in Horizontal Position.
95-7152
Copyright © 1973 Honeywell Inc. All Rights Reserved |
MLF TAB: ll.C.2.a. |
TOP GRILLE
MOTOR CONTROL
AND JCT BOX
|
|
PIPING |
- O P E N I N G F R O N T |
PIPING |
|
|
|
|
OPENING |
|
|
OPENING |
LOCATE PER |
|
|
\ |
|
||
|
|
|
|
|
|
|
|
HOLES |
8-32 x3/8 (MAX) |
MIN |
|
|
|
4070
Fig. 3. Mounting in a Typical Fan Coil Unit.
2