Honeywell Touchpoint Plus Specifications

Gas Detection
Touchpoint Plus
A whole new control experience
Unique User Experience
Taking the user experience to a whole new level
Touchpoint Plus
Touchpoint Plus brings a whole new control experience to your small system of gas
detectors. Touchpoint Plus is an easily configurable, wall-mounted control system
that supports up to 16 gas detection channels. Its modular approach enables you to
take control and configure what you need for a wide range of applications.
Delivering Reliable Control
• Honeywell reliability from the most trusted experts in gas detection
• Built-in bat tery backup for constant uptime
• Robust, shockproof housing for a wide range of industrial environments
Flexible Capabilities
• Compatible with the full range of Honey well gas detectors
• Powered audiovisual alarms simplify field installation
• Configuration includes easy grouping and voting alarm logic without specialist knowledge
• Next-generation compatibility
• Optional Modbus output for integration with a higher level system
Providing Ease and Efficiency
• Quick and easy installation, configuration, setup, and maintenance
• Easy diagnostics, data, and reporting
• Minimum training time
• Large color touchscreen LCD
• Multilingual functionality
• Green-yellow-red status at a glance
The signature feature of the Touchpoint line is a user-friendly touchscreen inter face,
which the Touchpoint Plus takes to a new level. With this unique interface, it’s easier
than ever to see the status of your system at a glance - maximizing the time you have
to make the right decisions. The intuitive, multilingual interface simplifies operation
and reduces training requirements. The full-color stoplight-style status indication
provides clarity from a distance too.
Touchpoint Plus features a comprehensive set of outputs as standard, including
common alarms and dedicated drives for remote audiovisual indicators. Its
modularity enables you to customize your system to meet your specific application
requirements. Selecting the right detector for use with your controller can deliver
significant savings in star tup costs and ongoing operations. Our global partner
network and dedicated application specialists are able to help you make the right
choices for your industr y.
With everything at your fingertips, you can take ownership of your system and operate it with confidence, helping to ensure the safety
of your people and the productivity of your site.
Want a simple
end-to-end
solution?
Easy ordering, installation,
and servicing from the
gas detection experts
Want to make
fast, informed
decisions?
System status at a glance
when time is critical
Large color touchscreen LCD with multilingual options
Built-in sounder
fully utilize
Want peace
of mind?
your controller?
Built for ease –
so you can operate it
with confidence
Engineered to the highest
standards of quality and
reliability
know what’s
going on?
View real-time and
historical data, analyze
readings, and
much more
Individual channel status indicators (green, yellow, red)
simplify system
setup?
With the intuitive,
ergonomic touchscreen,
setup couldn’t
be easier
Clear common status indicators (green, yellow, red)
Mute/Reset
One System Solution
Honeywell Analytics’ one system solution to meet your safety requirements
Touchpoint Plus provides a reliable
safety solution for small-scale gas
detection systems across a wide range of
applications and industries. If you need to
integrate your gas detection with a higher-
level management system, the Modbus
output option makes this straightfor ward.
As the heart of your gas detection system,
Touchpoint Plus is designed to work with
Honeywell’s industry-leading gas detectors
and drive actuators, and audible and visual
alarms to provide a complete end-to-end
solution that you can configure as your own.
TYPICAL EXAMPLE OF A SMALL
GAS DETECTION SYSTEM USING
TOUCHPOINT PLUS
Key
Relays, actuators, and audio/visual alarms
SD card
mA oop sensors
XNX universal transmitter
End user
Cloud
Sensepoint
mV bridge sensors
Designed for Speed and Reliability
Made of high-impact polymer plastic,
Touchpoint Plus is versatile
and durable. It is dustproof
and waterproof, and has been
tested to withstand the toughest
operating environments, both
indoors and out. So you can count
on the Touchpoint Plus to stand
up to the challenges of industrial
environments, from mechanical
rooms to chemical plants.
Touchpoint Plus is supplied with
pre-drilled and sealed cable
entries and a unique tiered
internal arrangement providing
ease of access to save installers time
and money.
7
6
10
9
3
1. Main module
5
4
8
1
2
2. Input module
3. Relay output module
4. mA output module
5. Power supply
6. Display module
7. Touchscreen
8. Backup battery
9. Modbus TCP/Web
10. Modbus RTU
Touchpoint Plus Control System
Touchpoint Plus Expansion Unit
Gas Detector
Audible & Visual Alarm
System Configuration Options
Alarm 2 Configurable
Provided As Standard
• Dedicated powered audiovisual alarm drives
• Common alarm outputs, one for fault and two configurable
• Datalogging to SD card
• Remote reset and inhibit inputs
Options
• Choice of AC or DC supply voltage
• Optional backup battery
• Choice of inputs: 2, 4 , or 8 mA; 2, 4 , or 8 mV; 2 mA and 2 mV; 4 mA and 4 mV
• Optional expansion unit for up to
16 inputs
• Choice of 12 or 24 relay outputs
• Choice of 4 or 8 mA outputs
• Optional RS485 Modbus RTU
• Optional TCP/IP Modbus/HTTP
SD Card
Remote Inhibit
Remote Reset
Alarm 1 Failure
Dedicated Audible/Visual Alarm Outputs
Buzzer Mute/Reset
Power Supply
110/220 VAC 18-32 VDC
Not included in Expansion Unit
Fault Visible
Alarm 1
Alarm 2
1 0 0
WarningFault Inhibit
01 02 03 04 05 06 07 08
09 10 11 12 13 14 15 16
System State Relays
Alarm 3
000
Backup Battery
12
Outputs
12
Outputs
Input/Output
2, 4, or 8 Inputs 2-Wire 4-20 mA 3-Wire 4-20 mA
3-Wire mV Bridge
4-20mA
4-20mA
4
Outputs4 Outputs
Installation
Quick and easy installation - designed to save you time and money
Touchpoint Plus can be directly wall-mounted, or, for an easier
1-man installation, simply use the optional mounting plate.
Open the hinged front cover to find plenty of space for wiring
and a unique tiered terminal arrangement for easy access.
Cable entries are pre-drilled and sealed ready to use reducing
installation time and cost further.
156mm
300mm
426mm
Optional Mounting Plate
Sensor Connection - Compatible with a wide range of field devices
Sensor
4-20mA
2-Wire L oop Powe red
Sensepoint
Signalpoint
705
Searchpoint Optima Plus
Sensepoint XCD
Series 3000 MkII/MKIII
RAEGuard II PID
IAQPoint2
XNX Universal Transmitter
Searchline Excel
E3Point, EC F9, IR F9
+24 vdc
+VE
-VE
SIG
66 Ω
0 Vdc
4-20mA
Sensor
Touchpoint Plus mA Input Module
Simple devices, intrusive configuration, power up to 8 devices directly from Touchpoint Plus
Enhanced devices, non­intrusive local operation, in-field adjustment, power up to 8 devices directly from Touchpoint Plus
High-integrity devices, specialized configuration, in-field adjustment, monitor up to 8 devices with external power as required
3-Wire Current Source 3-Wire mV Bridge
+24 vdc
+VE
SIG
66 Ω
-VE
0 Vdc
AVAILABLE GAS DETECTORS
Touchpoint Plus is supp lied with 13 pre-drilled and se aled cable entrie s for PG16/M20 glands .
+24 Vdc
GND
4-20mA
Sensor
Touchpoint Plus mA Input Module
3-Wire Externally Powered
Direct Surface Mounting
External 24 VDC
Supply
+24 Vdc
+VE
SIG
66 Ω
-VE
0 Vdc
Touchpoint Plus mA Input Module
Sensitive
Bead
Sensor
Non-
Sensitive
Bead
+
Signal Signal
_
GENERAL SPECIFICATION
Capacity
Up to 8 channels with base unit, up to 16 channels with expansion unit
2 or 3-wire, mA, mV, max. 15 W per
Input Type
channel, max. 40 W total (with dedicated A/V drive)/68 W total (without dedicated A/V drive)
Size (WallMounted Version)
426 mm × 300 mm × 156 mm (16.8” x 11.8” x 6.1”)
Housing Material Polycarbonate ABS
Weight
User Interface (UI) - Controller Only
Max. 8.5 kg (18.7 lb), max. 17 kg (37.4 lb) with expansion unit
Available I/O Modules (continued)
mV Input
Dual Input
Relay Output
420mA Output
Common Inputs Remote reset, remote inhibit
Display 7’’ color LCD touchscreen. Graphic User Interface
Visual Indicators
channel. Green: Normal; Yellow: Fault: Inhibit; Red: Alarm
Audible Alarm ≥ 70dB @ 1 m (3.28 ft)
Button Common for reset/mute operation
3 LEDs for master indicators. LED for each
Language
Power Supply*
English, French, German, Italian, Dutch, Spanish, Portuguese, Russian, Chinese
Common Outputs
Approvals
Electromagnetic Compatibility and Electrical Safety
Performance**
AC Power 110/220 VAC, 5060 Hz Manual switching
DC Power 18 to 32 VDC (+/10%) Typical 24 VDC
Power Consumption
Environmental
Max. 105 W (including detector and external devices), max. 210 W with expansion unit
10 °C to +55 °C (14 °F to +131 °F)
Operating
continuous, up to 95% RH (non­condensing), IP65, and NEMA 4X
Storage
Available I/O Modules
420mA Input
+V
-V
Touchpoint Plus mV Input Module
Instrument 25 °C to +60 °C (13 °F to + 140 °F), up to 95% RH (non-condensing)
2 or 3-wire, 2/4/8 channel modules, 10/12/16 with expansion unit
ORDERING INFORMATION
Safety Integrity**
Hazardous Location
Others
Backup Battery
Datalogging Configuration, logged events, and data
Communication
* Basic an d expansion uni ts each require a power suppl y ** Contact Honeywell A nalytic s for availabilit y ** * Not available in expansion unit
Output Option
GENERAL SPECIFICATION
Catalytic-type flammable gas detectors (Honeywell models). 2/4/8-channel modules, 10/12/16 with expansion unit
2-channel mA + 2-channel mV module or 4-channel mA + 4-channel mV module
12 or 24 relay outputs, NO/C/NC changeover, 1.7 A @ 30 VDC/250 VAC, user-configurable - energized/de-energized, latching/non-latching, time delay
4 or 8 isolated repeated mA outputs, 022 mA, 0100% FSD = 420 mA
4 powered A/V outputs for alarms and fault, 3 common alarm outputs
EMC/RFI (EN 50270:2015) LVD (EN 610101:2010) CSAC22.2 No. 61010104 UL 610101 (3rd Edition) and 508
Designed to meet: EN 50271:2010; EN 60079291:2007; EN 455441 /2/3:2015; EN 50104:2010 C22.2 No. 152M1984, ISA 12.13.01
Designed to meet IEC/EN 61508:2010 and EN 50402:2005+A1:2008 SIL2 certification
Class I, Division 2, Group A, B, C, and D, or non-hazardous only
22.2 V Lithium Ion Battery, 2600 mAh capacity (>30 minutes for typical system)
MODBUS TCP, WEB monitoring, and MODBUS RTU
4: 4ch mA Output
Product Name
8: 8ch mA Output
Power
A: AC D: DC
Mounting Type
W: Wall Mount
N: No mA Output
TPPLBAWA8S 8 BNNN
Battery
B: Backup Battey N: None
Future Use
Communication***
Unit Type
B: Base Unit E: Expansion Unit
Input Option
A2: 2ch mA Input A4: 4ch mA Input A8: 8ch mA Input V2: 2ch mV Input
Communication***
R: MODBUS RTU N: None
N: None R: MODBUS TCP+WEB(read) T: MODBUS TCP W: MODBUS TCP+WEB(read/write)**
V4: 4ch mV Input V8: 8ch mV Input D4: 2ch mA + 2ch mV input D8: 4ch mA + 4ch mV input
Relay Option
S: 12 Relays D: 24 Relays N: No Relays
Note: O ther field devices available on request. Some dev ices are not availabl e in all re gions.
Honeywell Gas Detection
Honeywell is able to provide gas detection solutions to meet the requirements of a wide range of applications and industries. Contact us in the following ways:
HEADQUARTERS
Europe, Middle East, Africa
Life Safety Distribution GmbH Javastrasse 2 8604 Hegnau Switzerland Tel: +41 (0)44 943 4300 Fax: +41 (0)44 943 4398 gasdetection@honeywell.com
Customer Service:
Tel: 00800 333 222 44 (Freephone number) Tel: +41 44 943 4380 (Alternative number) Fax: 00800 333 222 55 Middle East Tel: +971 4 450 5800 (Fixed Gas Detection) Middle East Tel: +971 4 450 5852 (Portable Gas Detection)
TECHNICAL SUPPORT
EMEA: HAexpert@honeywell.com US: ha.us.service@honeywell.com AP: ha.ap.service@honeywell.com
Americas
Honeywell Analytics Distribution Inc. 405 Barclay Blvd. Lincolnshire, IL 60069 USA Tel: +1 847 955 8200 Toll free: +1 800 538 0363 Fax: +1 847 955 8210 detectgas@honeywell.com
Asia Pacific
Honeywell Industrial Safety 7F SangAm IT Tower, 434 Worldcup Buk-ro, Mapo-gu, Seoul 03922 Korea Tel: +82 (0) 2 6909 0300 Fax: +82 (0) 2 2025 0328 India Tel: +91 124 4752700 analytics.ap@honeywell.com
www.honeywellanalytics.com www.raesystems.com
13496_H_Touchpoint Plus_DS01157_V2_EMEA
03/16
© 2016 Honeywell Analytics
Please Note:
While e very ef fort has be en made to ensur e accuracy i n this pub lication , no responsib ility can b e accepted f or errors or omissi ons. Data may c hange, as wel l as legislation, a nd you are str ongly a dvis ed to obt ain copies of t he most rece ntly issue d regul ations, st andards, an d guidelines . This publi cation is not in tended to for m the basis of a co ntract .
Loading...