Honeywell TO485 Product specification sheet

TO485
A
Temperature regulator with balanced single-seat piston valve
(Cooling water regulator)
Product specification sheet
pplication
TO485 temperature regulators are used in commercial and industrial installations where the operating temperature in the system is to be limited to a preset value. The TO485 temperature regulator is therefore especially suitable for use in cooling systems.
The integral strainer protects the regulator against individual loose dirt particles which may be circulating through the system. Where dirt is constantly present, a separate upstream strainer must also be fitted where dirt is constantly present (see "Accessories").
Special Features
Actuator with pressure-balanced valve - fluctuating inlet pressures have no influence on the control temperature
Soft-seat valve
Thermostat with standard setting range 30 °C to 100 °C
Over-temperature safety protection at 50 K above the set
value
Sensor phial with 3m long capillary
Separate immersion pocket
Construction
The temperature regulator comprises:
V25 actuator with union connectors
T445 thermostat
Materials
Brass housing
Brass union connectors
Corrosion resistant synthetic material valve seat
NBR seals
Stainless-steel strainer
Nickel-plated brass thermostat immers ion phi al
Heat conducting sheath between sensor phial and
immersion pocket
Thermostat can be replaced without draining the system
Range of Application
Medium
Technical Data
Setting range 30 °C to 100 °C (Standard) Nominal pressure PN 16 Operating pressure
Differential pressure max. 4.0 bar Operating temperature max. 70 °C Connection sizes R
Water, oil-free compressed air and nitrogen up to 70 °C
max. 16.0 bar For pressures above 13.0 bar a T 447 thermostat relief valve is required
1
/2" to 2"
Subject to change 103 EN0H-1319GE23 R0304
TO485 temperature regulator
A
Method of Operation
The TO485 temperature regulator operates on the expansion principle. As the temperature at the sensor increases or decreases, the fill medium expands or contracts and this causes the piston to move, which then closes or opens the valve. The valve then permits only the amount of flow of heating medium to pass through which is required to maintain the set temperature.
Options
TO485- ... A = Setting range 30 °C to 100 °C TO485- ... B = Setting range 0 °C to 70 °C
Connection size
Connection size R
1
/2"
3
/4"1"1 1/4"1 1/2"2" Weight (kg) 4.9 5.1 5.3 6 .2 6.2 8.9 Dimension (mm) L 140 160 180 200 225 255 Max. differential
pressure (bar) 4 4 4 4 4 4 kvs-value 2.4 3.1 7.6 9.1 12.6 12.6
All pressure values given are the excess above atmospheric pressure
ccessories
T447 Thermostat relief valve
A thermostat relief valve must be fitted where the operating pressure is above 13.0 bar.
FY30
Strainer
with double mesh, brass housing A = Mesh size approx. 0.35 mm B = Mesh size approx. 0.18 mm
T447
F76S
Reverse rinsable and cleanable fine filter
AA= With threaded union connectors
upper/lower mesh size 105/135 µm (DIN/DVGW-tested)
AAM =With threaded union connectors,
F76S
FY30
EN0H-1319GE23 R0304 104 Subject to change
upper/lower mesh size 105/135 µm (DIN/DVGW-tested), with red-bronze filter bowl
Loading...