Honeywell TM300SOLAR, TM200, TM50 Product specification sheet

Page 1
TM50/TM200/TM300SOLAR
Thermostatic mixing valve with scald protection
for solar installations
Product specification sheet
Application
Thermostatic mixing valves of this type are used for central regu­lation of the water temperature in solar-powered, bivalent water heaters.
A cold water break can be fitted in the circulation line in water heater systems, which prevents cold water from mixing at the extraction point via the circulation line.
Special Features
• Highly sensitive thermal element with good all-round water­temperature sensing, even at low flow rates
• Simple setting of the required water temperature
• Scald protection - the hot water inlet is automatically cut off if
TM200SOLAR
the cold supply fails provided that the hot water inlet tempe­rature is at least 10 K higher than that of mixed water setting
• The cold water inlet is automatically cut off if the hot supply fails
• Meets KTW recommendations for potable water
• Inner components are of scale-resistant materials
TM300SOLAR
Construction
The thermostatic mixing valve comprises:
•Housing
• Connection fittings (not in TM50SOLAR)
• Adjustment knob
•Thermostat
• Protective cap to fix the set mix water temperature (not in TM50SOLAR)
Materials
• Dezincification resistant brass housing, nickel plated
• Dezincification resistant brass connection fittings, nickel plated (not in TM50SOLAR)
• Moving parts of high-quality, scale-resistant synthetic material
• High quality-synthetic material adjustment knob
• Stainless-steel spring
• Protective cap made of transparent plastic (not in
EN0H-1358GE23 R0908 • Subject to change
TM50SOLAR)
Range of Application
Medium Water
Operating pressure Max. 10 bar
Maximum pressure diffe­rence between hot and cold inlet supplies
Technical Data
Installation position Arbitrary
Hot water inlet temperature
Connection size
Setting range 30 °C - 60 °C
Set at the factory to 40 °C 40 °C 40 °C
Flow rate at 1.0 bar pressure differential across valve approx.
Control accuracy < ± 4 K < ± 4 K < ± 4 K
2,5 bar
TM50SOLAR
1
/2"
25 l/min 27 l/min 40 l/min
TM200SOLAR TM300SOLAR
Max. 110 °C
3
/4"
3
/4"
www.honeywell.com 1
Page 2
TM50/TM200/TM300SOLAR Thermostatic mixing valve with scald protection
Method of Operation
Thermostatic mixing valves of this type are used for central regu­lation of the water temperature in solar-powered, bivalent water
H
h
H
h
A
A
l
L
TM50SOLAR
A
l
TM300SOLAR
A
A
A
H
h
A
l
L
TM200SOLAR
A
L
heaters.
A
The highly sensitive thermal element located in the outlet of the valve controls a plug which regulates the flow proportions of cold and hot water in relation to the mixed hot water setting selected. Soft seatings are fitted to both hot and cold water inlets.
They provide:
• A positive hot inlet shutoff if the cold water supply is inter­rupted, provided that the hot water inlet temperature is at least 10 K higher than that of the mixed water setting.
• The cold water supply is cut off if the hot water supply is inter­rupted.
Options
TM50SOLAR-1/2E = without connection fittings R
TM200SOLAR-3/4A = with threaded union connectors R
TM200SOLAR-3/4E = without connection fittings R
TM300SOLAR-3/4A = with threaded union connectors R
1
/2"
3
/4"
3
/4"
3
/4"
TM50SOLAR-1/2E TM200SOLAR-3/4A TM200SOLAR-3/4E TM300SOLAR-3/4A Connection size A G Dimensions (mm)
L
l
h
H
1
/2" R 3/4" G 3/4" R
57 29 37 93
134
67 65
128
66 33 40 93
3
180
90 78
132
/4"
2 www.honeywell.com
EN0H-1358GE23 R0908 • Subject to change
Page 3
Installation Example
TM50/TM200/TM300SOLAR Thermostatic mixing valve with scald protection
1/2" max. 17 m 3/4" max. 10 m
RV284
10
5
bar
15
0
16
Installation Guidelines
• Fit a return flow-retarder unit where the hot water supply system includes a circulation circuit
• Observe the flow direction arrow when fitting a KB191 return flow-retarder unit
• To prevent the growth of legionella, DVGW-W551 specify that the water volume in the pipework between the mixer valve and the furthest take-off point should not exceed 3 litres. This corresponds to a maximum length of 10 metres for
3
/4" (20 mm) pipework and 17 metres for 1/2" (15 mm)
Typical Applications
Thermostatic mixing valves are installed in water heating systems according to your specification.
The following are some typical applications:
o Single and multiple-occupancy households o Retirement homes o Children's nurseries o Schools oHotels o Commercial kitchens o For industrial applications with control either from a central
location or adjacent to point-of-use outlets
Maintenance
It is recommended that the mixing valves are inspected on a regular basis, at least annually, or more frequently if performance is impaired, to ensure they are working correctly and that dirt ingress into the system does not cause a loss in performance of the mixing valve.
The temperature setting is to be inspected at regular intervals and adjusted as necessary.
EN0H-1358GE23 R0908 • Subject to change
www.honeywell.com 3
Page 4
TM50/TM200/TM300SOLAR Thermostatic mixing valve with scald protection
Spare Parts
TM200SOLAR (exemplary)
1
Thermostatic mixing valve TM50/200/300SOLAR, from 2008 onwards
1 Control valve, complete
for TM50SOLAR TM50A-30/60 for TM200SOLAR TM200A-30/60 for TM300SOLAR TM300A-30/60
Automation and Control Solutions
Honeywell GmbH Hardhofweg D-74821 Mosbach Phone: (49) 6261 810 Fax: (49) 6261 81309 http://europe.hbc.honeywell.com www.honeywell.com
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorised Repre­sentative Honeywell GmbH
EN0H-1358GE23 R0908 Subject to change without notice © 2008 Honeywell GmbH