Honeywell TB3026B Engineering Specification

31-00121-02
TB3026B Configuration Wizard Guide - N4
CONFIGURATION GUIDE
JUNE 2018
BACnet FF Controller
Table of Contents
INTRODUCTION ..................................................................................................................................................................... 5
WEBStation-N4TM ................................................................................................................................................................ 5
Features ..................................................................................................................................................................... 5
TB3026B Configuration Wizard ........................................................................................................................................... 5
TB3026B Configuration Requirement .................................................................................................................................. 6
Organization of the Manual .................................................................................................................................................. 6
CONFIGURATION OF TB3026B AND TB3026B-W CONTROLLERS .................................................................................. 7
Installation ........................................................................................................................................................................... 7
Installation of WEBStation-N4TM Tool ............................................................................................................................. 7
Getting Started..................................................................................................................................................................... 8
Digital Signature ............................................................................................................................................................. 8
TB3026B Configuration Wizard Initial Setup .................................................................................................................12
Connecting to Platform ..............................................................................................................................................12
Adding New Station ...................................................................................................................................................12
Starting New Station .................................................................................................................................................14
Adding BACnet Network to Niagara Network ............................................................................................................16
Adding TB3026B Controller to the BACnet Network .................................................................................................18
TB3026B Configuration Wizard .....................................................................................................................................19
Field Description for TB3026B Configuration Wizard ....................................................................................................20
APPLICATIONS ................................................................................................................................................................... 21
Equipment Type................................................................................................................................................................. 21
AHU ...............................................................................................................................................................................22
General Display .........................................................................................................................................................23
Schedule Options ......................................................................................................................................................25
Zone Setpoints ..........................................................................................................................................................27
Control Settings .........................................................................................................................................................30
Fan / Humidity ...........................................................................................................................................................32
Economizer ...............................................................................................................................................................34
I/O Configurations .....................................................................................................................................................35
Air Source Heat Pump ...................................................................................................................................................37
General Display .........................................................................................................................................................38
Schedule Options ......................................................................................................................................................40
Zone Setpoints ..........................................................................................................................................................42
Control Settings .........................................................................................................................................................45
Fan / Humidity ...........................................................................................................................................................47
Economizer ...............................................................................................................................................................49
I/O Configurations .....................................................................................................................................................50
Water Source Heat Pump..............................................................................................................................................52
General Display .........................................................................................................................................................53
Schedule Options ......................................................................................................................................................55
Zone Setpoints ..........................................................................................................................................................57
Control Settings .........................................................................................................................................................60
Fan / Humidity ...........................................................................................................................................................62
Economizer ...............................................................................................................................................................64
I/O Configurations .....................................................................................................................................................65
Two Pipe Fan Coil Unit ..................................................................................................................................................67
General Display .........................................................................................................................................................69
Schedule Options ......................................................................................................................................................71
BACnet FF Controller
Zone Setpoints .......................................................................................................................................................... 73
Control Settings ........................................................................................................................................................ 76
Fan / Humidity ........................................................................................................................................................... 80
I/O Configurations ..................................................................................................................................................... 82
Four Pipe Fan Coil Unit ................................................................................................................................................. 85
General Display ........................................................................................................................................................ 87
Schedule Options...................................................................................................................................................... 89
Zone Setpoints .......................................................................................................................................................... 91
Control Settings ........................................................................................................................................................ 94
Fan / Humidity ........................................................................................................................................................... 97
Economizer ............................................................................................................................................................. 100
I/O Configurations ................................................................................................................................................... 101
ONLINE OPERATIONS ...................................................................................................................................................... 106
Download ........................................................................................................................................................................ 106
Upload ............................................................................................................................................................................. 106
Write Device Instance...................................................................................................................................................... 106
Sensor Calibration ........................................................................................................................................................... 107
Diagnostics ...................................................................................................................................................................... 108
Modulating Output Diagnostics ................................................................................................................................... 109
Binary Output Diagnostics ........................................................................................................................................... 109
Refresh ....................................................................................................................................................................... 109
Alarms ............................................................................................................................................................................. 110
Error ............................................................................................................................................................................ 110
Error Details ................................................................................................................................................................ 110
Value Limits ................................................................................................................................................................ 110
Current Value .............................................................................................................................................................. 110
Refresh alarm list ........................................................................................................................................................ 110
Auto Refresh / Update auto refresh rate ..................................................................................................................... 110
Time Sync ....................................................................................................................................................................... 111
Batch Operations ............................................................................................................................................................. 112
Download .................................................................................................................................................................... 113
Upload ......................................................................................................................................................................... 113
Set Outputs to Auto ..................................................................................................................................................... 113
HONEYWELL SOFTWARE END USER LICENSE AGREEMENT .................................................................................... 114
2 31-00121—02
BACnet FF Controller
List of Figures
Figure 1: Installing WEBStation-N4
Figure 2: Installing WEBStation-N4TM (selecting installation location) ..................................................................................... 7
Figure 3: Installing Platform Daemon ...................................................................................................................................... 9
Figure 4: WEBStation-N4TM – Getting Started ........................................................................................................................10
Figure 5: Open Platform .........................................................................................................................................................12
Figure 6: Connect Platform ....................................................................................................................................................12
Figure 7: Authentication during connecting Platform ..............................................................................................................12
Figure 8: Identity Verification during Connecting to Platform ..................................................................................................12
Figure 9: Adding New Station .................................................................................................................................................13
Figure 10: New Station Wizard Window .................................................................................................................................13
Figure 11: Entering Admin Password for New Station............................................................................................................13
Figure 12: Location of New Station (BACnetFF) ...................................................................................................................13
Figure 13: Application Director ...............................................................................................................................................14
Figure 14: Selecting the Station to Start .................................................................................................................................14
Figure 15: Starting the Station ................................................................................................................................................14
Figure 16: Started Station ......................................................................................................................................................14
Figure 17: Newly added Station .............................................................................................................................................15
Figure 18: Adding BACnet Network........................................................................................................................................16
Figure 19: Selecting BACnet Network to add .........................................................................................................................16
Figure 20: Adding Specification to add BACnet Network .......................................................................................................17
Figure 21: Newly added BACnet Network ..............................................................................................................................17
Figure 22: Adding Palette .......................................................................................................................................................18
Figure 23: Opening Palette ....................................................................................................................................................18
Figure 24: Adding ‘honeywellTB3026BWizard’ to BACnet Network .......................................................................................18
Figure 25: BACnetFF in Palette TAB......................................................................................................................................18
Figure 26: Drag and drop BACnetFF on BacnetNetwork .......................................................................................................18
Figure 27: Naming Controller .................................................................................................................................................19
Figure 28: Location of Controller ............................................................................................................................................19
Figure 29: Opening TB3026B Configuration Wizard Screen ..................................................................................................20
Figure 30: Field description for TB3026B Configuration Wizard Screen ................................................................................20
Figure 31: Application Screen ................................................................................................................................................21
Figure 32: Equipment Type ....................................................................................................................................................21
Figure 33: AHU window ..........................................................................................................................................................22
Figure 34: General Display Screen (AHU) .............................................................................................................................23
Figure 35: Schedule Options Screen (AHU) ...........................................................................................................................25
Figure 36: Zone Setpoints Screen (Occupancy Mode)...........................................................................................................27
Figure 37: Zone Setpoint Screen (Setpoint Mode) .................................................................................................................29
Figure 38: Control Settings Screen (AHU) .............................................................................................................................30
Figure 39: Fan/Humidity Screen (AHU) ..................................................................................................................................32
Figure 40: Economizer Screen (AHU) ....................................................................................................................................34
Figure 41:I/O Configurations Screen (AHU) ...........................................................................................................................35
Figure 42: Terminal Assignment View (AHU) .........................................................................................................................36
Figure 43: Air Source Heat Pump Window .............................................................................................................................37
Figure 44: General Display Screen (Air Source Heat Pump) .................................................................................................38
Figure 45: Schedule Options Screen (Air Source Heat Pump) ...............................................................................................40
Figure 46: Zone Setpoints Screen (Occupancy Mode)...........................................................................................................42
Figure 47: Zone Setpoint Screen (Setpoint Mode) .................................................................................................................44
Figure 48: Control Settings Screen (Air Source Heat Pump) .................................................................................................45
Figure 49: Fan/Humidity Screen (Air Source Heat Pump) ......................................................................................................47
Figure 50: Economizer Screen (Air Source Heat Pump) ........................................................................................................49
Figure 51: I/O Configurations Screen (Air Source Heat Pump) ..............................................................................................50
TM
..................................................................................................................................... 7
31-00121—02 3
BACnet FF Controller
Figure 52: Terminal Assignment View (Air Source Heat Pump) ............................................................................................. 50
Figure 53: Water Source Heat Pump Window ....................................................................................................................... 52
Figure 54: General Display Screen (Water Source Heat Pump) ............................................................................................ 53
Figure 55: Schedule Options Screen (Water Source Heat Pump) ......................................................................................... 55
Figure 56: Zone Setpoints Screen (Occupancy Mode) .......................................................................................................... 57
Figure 57: Zone Setpoint Screen (Setpoint Mode) ................................................................................................................. 59
Figure 58: Control Settings Screen (Water Source Heat Pump) ............................................................................................ 60
Figure 59: Fan/Humidity Screen (Water Source Heat Pump) ................................................................................................ 62
Figure 60: Economizer Screen (Water Source Heat Pump)................................................................................................... 64
Figure 61: I/O Configurations Screen (Water Source Heat Pump) ......................................................................................... 65
Figure 62: Terminal Assignment View (Water Source Heat Pump) ....................................................................................... 66
Figure 63: Two Pipe Fan Coil Unit Window............................................................................................................................ 67
Figure 64: General Display Screen (Two Pipe Fan Coil Unit) ................................................................................................ 69
Figure 65: Schedule Options Screen (Two Pipe Fan Coil Unit) ............................................................................................. 71
Figure 66: Zone Setpoints Screen (Occupancy Mode) .......................................................................................................... 73
Figure 67: Zone Setpoint Screen (Setpoint Mode) ................................................................................................................. 75
Figure 68: Control Settings Screen (Two Pipe Fan Coil Unit) ................................................................................................ 76
Figure 69: Fan/Humidity Screen (Two Pipe Fan Coil Unit) .................................................................................................... 80
Figure 70: I/O Configurations Screen (Two Pipe Fan Coil Unit) ............................................................................................. 82
Figure 71: Terminal Assignment View (Single Speed Fan) .................................................................................................... 82
Figure 72: Four Pipe Fan Coil Unit window ............................................................................................................................ 85
Figure 73: General Display Screen (Four Pipe Fan Coil Unit)................................................................................................ 87
Figure 74: Schedule Options Screen (Four Pipe Fan Coil Unit) ............................................................................................. 89
Figure 75: Zone Setpoints Screen (Occupancy Mode) .......................................................................................................... 91
Figure 76: Zone Setpoint Wizard Screen (Setpoint Mode) ..................................................................................................... 93
Figure 77: Control Settings Screen (Four Pipe Fan Coil Unit)................................................................................................ 94
Figure 78: Fan/Humidity Screen (Four Pipe Fan Coil Unit) .................................................................................................... 97
Figure 79: Economizer Screen (Four Pipe Fan Coil Unit) .................................................................................................... 100
Figure 80:I/O Configurations Screen (Four Pipe Fan Coil Unit) ........................................................................................... 101
Figure 81: Terminal Assignment View (Three Speed Fan) .................................................................................................. 101
Figure 82: Selecting ‘Download’ ........................................................................................................................................... 106
Figure 83: Selecting ‘Upload’ ............................................................................................................................................... 106
Figure 84: Write Device Instance ......................................................................................................................................... 106
Figure 85: Online Operations View ...................................................................................................................................... 106
Figure 86: Sensor Calibration .............................................................................................................................................. 107
Figure 87: Outputs Overridden Mode/Diagnostics ............................................................................................................... 108
Figure 88: Viewing Alarms ................................................................................................................................................... 110
Figure 89: Selecting ‘Honeywell Time Sync’ ........................................................................................................................ 111
Figure 90: Time Sync View .................................................................................................................................................. 111
Figure 91: Selecting ‘BACnet FF Batch Operations’ ............................................................................................................ 112
Figure 92: BACnet FF Batch Operations’ view ..................................................................................................................... 112
Figure 93: BACnet FF Batch Operations’ view while loading the Mode Status .................................................................... 113
4 31-00121—02
BACnet FF Controller
INTRODUCTION
The BACnet Fixed Function (TB3026B) is a communicating sensor/fixed application controller with a built-in humidity sensor. The TB3026B-W is the wireless version with an onboard wireless receiver for wireless occupancy control.
It supports the following equipment types:
1. AHU
2. Air Source Heat Pump
3. Water Source Heat Pump
4. Two Pipe Fan Coil Unit
5. Four Pipe Fan Coil Unit
Each equipment type has other various configurable settings, which provide multiple options and flexibility to the user. Configuration of the TB3026B and TB3026B-W controllers involves selection of the appropriate settings from available options as per the application requirement.
It can be configured using the ‘TB3026B Configuration Wizard’. This configuration wizard is developed under WEBStation-N4 Framework® software. It utilizes BACnet communication technology (MS/TP).
WEBStation-N4TM
The WEBStation-N4™, powered by the Niagara N4 Framework® is a flexible network server for all connected WEBs-N4 controllers.
WEBStation-N4™ creates a powerful network environment with comprehensive database management, alarm management and messaging services.
WEBStation-N4™ hosts an application called ‘TB3026B Configuration Wizard’, which provides an engineering environment for configuration of TB3026B and TB3026B-W controllers.
TM
software tool which uses the NiagaraN4
®
network
Features
Provisioning of multi-controller systems (tools for updating and installation of software modules).
Central database storage for attached controllers.
Archive destination/repository for log and alarm data.
Central server of graphics and aggregated data (single
point of access to the system – one IP address).
Platform for optional enterprise applications.
WEBStation-N4™ acts as a network server or a ‘Supervisor’ for all connected WEBs-N4™ Controllers. It creates a network environment for the management of these controllers, alarms and messaging services.
TB3026B Configuration Wizard
It is a special application developed in the WEBStation-N4 to configure the TB3026B and TB3026B-W controllers. All configurable network variables of theTB3026B and TB3026B-W controllers are accessible through this application for configuration.
TB3026B Configuration Wizard provides a means to select settings for all equipment types, control strategy and parameters as per the application requirement.
The following operations can be performed using this wizard:
1. Add a TB3026B controller on the BACnet network.
2. Configure and set the parameters as per the application requirements.
3. Download and upload the configuration into the selected TB3026B controller (Online Operation).
4. Set the time and date.
31-00121—02 5
BACnet FF Controller
TB3026B Configuration Requirement
TB3026B controller is configured using following:
1.
With WEBStation- N4 Software Tool
In the WEBStation-N4 Configuration Wizard application is integrated for TB3026B and TB3026B-W controllers’ configuration.

Configuration through PC

TB3026B controllers can be accessed with a personnel computer with WEBStation-N4 Via BACnet converter, which connects a PC, TB3026B controller can be accessed for configuring, uploading, downloading operations.

Configuration through WEBs Controller

If the TB3026B controller is on the BACnet network of WEBs controller, it can be accessed through WEBs controller using a PC with WEBStation-N4
When WEBs controller is already commissioned, then it can be accessed through an IP address via Browser. All required operations on the TB3026B controller can be performed by accessing WEBs controller.
2. Through TB3026B touch screen
Configurable network parameters are also accessible through the TB3026B touch screen. Access to the configurable parameters is password protected with a default password of 0000. For details refer to, ‘BACnet Fixed Function System Engineering Guide, 31-00098.’
TM
software tool, the TB3026B
TM
software tool installed.
TM
tool installed.
Organization of the Manual
This manual is divided into two basic parts: Introduction and Configuration.
The Introduction provides information for the TB3026B configurable controllers, WEBStation-N4TM Software tool, “TB3026B Configuration Wizard”, control application, and abbreviations.
Configuration provides information for the engineering about configurable TB3026B and TB3026B-W controllers’ different application types through “TB3026B Configuration Wizard” using its various settings options.
6 31-00121—02
CONFIGURATION OF TB3026B AND TB3026B-W CONTROLLERS
Installation
Before proceeding to the “TB3026B Configuration Wizard”, WEBStation-N4 configuration wizard.
Installation of WEBStation-N4TM Tool
WEBStation-N4TM software is distributed via the web or a DVD, and has the following minimum hardware requirements:
Processor: Intel Pentium Operating System:
32-bit: Microsoft Windows XP Professional, Windows 2003 or 2008 Server (if Microsoft IIS is disabled), Vista Business or Windows 7
64-bit: Windows XP Professional, Windows 7 Browser: Microsoft IE versions 7, 8, 9, Google Chrome
version 15, and Mozilla Firefox version 8, 10, 12 Memory: 1 GB minimum, 2 GB or more recommended for
large systems, 8 GB or more recommended for the windows 64-bit version
Hard Drive: 1 GB minimum, 5 GB for applications that need more archiving capacity
Display: Video card and monitor capable of displaying 1024 x 768 pixel resolution or greater
Network Support: Ethernet adapter (10/100 Mb with RJ-45 connector)
Modem: 56 KB minimum, full time high speed ISP connection1111 recommended for remote site access (i.e. T1, ADSL, cable modem).
These requirements can vary for the different versions of WEBStation-N4 is added. For the latest product data, visit
http://
After selecting the setup for installation, proceed by clicking ‘Next’ to accept the license agreement.
TM
should be installed as it hosts the
®
IV, 2 GHz or higher
TM
as support for newer operating systems
BACnet FF Controller
Figure 1: Installing WEBStation-N4TM
Select the installation location, (It will create a path in ‘C’ drive under ‘Honeywell’ folder by default)
TM
Figure 2: Installing WEBStation-N4
installation location)
Click ‘Next’ button to proceed after selecting appropriate options. Wait until the installation gets finished.
Note:
(selecting
It is recommended to secure the WEBStation-N4 system in order to make it resistant to the attacks.
Refer to the security documents available within WEBStation-N4 software build to make WEBStation-N4 system secure.
31-00121—02 7
BACnet FF Controller
Getting Started
Digital Signature
IMPORTANT
All the Honeywell WEBs software tools are now signed. Users can verify the signature using any OpenSSL tool. Below are the steps to verify signature using OpenSSL community distribution.
Prerequisites:
Download the Honeywell public key BuildingsCommonSupervisor.crt from location- same location as the software release location
Download the batch file “VerifyWEBsToolsSignature.bat” from location- same location as the software
elease location. This file has the commands to verify the module signature using the public key specified i
r
ep 1
St
Download OPENSSL from this link- https://www.openssl.org/source/openssl-1.0.2o.tar.gz
Extract the file using any ZIP utility to get the folder “openssl-1.0.2o”
In the extracted folder find the file “openssl.cnf”
Set Windows environment variable OPENSSL_CONF=<PATH TO openssl.cnf>, for example
OPENSSL_CONF=C:\openssl-1.0.2o\apps\openssl.cnf
Steps to verify the signature:
1. Place the files BuildingsCommonSupervisor.crt, VerifyWEBsToolsSignature.bat, WEBs tools modules and
signature file in the same location. For example: Following files are in one place a. BuildingsCommonSupervisor.crt b. VerifyWEBsToolsSignature.bat c. honeywellSpyderTool.jar d. honeywellSpyderTool.jar.sig
2. Open the command prompt and navigate to the location of the above files.
3. Execute the batch file VerifyWEBsToolsSignature.bat against a module for verifying its signature, for example
- C:\Spyder_RELEASE\ > VerifyWEBsToolsSignature.bat honeywellSpyderTool.jar
4. OpenSSL will verify this module’s signature and printout the below verification details:
n
5. If the Niagara module is compromised then user will get the below log, where verification has failed:
31-00121—02 8
TB3026B Configuration Wizard is a user interface where a user can set and adjust various types of parameters.
Important
BACnet FF Controller
Note:
Hash Value: Honeywell publishes the Hash Value with
the TB3026B Configuration Wizard module. It is available as “honeywellTB3026BWizard_HashValue.txt” with the released module.
The Hash Value generated at user’s end should match the Hash Value published with the TB3026B Configuration Wizard module. It is recommended to perform this check in order to ensure the authenticity of the TB3026B Configuration Wizard module.
To start working with the configuration wizard, go to ‘Start’ menu, select ‘All Programs’, navigate to ‘WEBStation-N4
4.2.36.34’ folder and click on it. Click ‘Install Platform Daemon’ as shown in Figure 3.
If more than one version of WEBStation-N4 is
installed on the same PC, It is mandatory to install Platform Daemon when switching from one version of WEBStation-N4 to other. It is not required to install Platform Daemon if the same version of WEBStation-N4 needs to open consecutively.
If only single version of WEBStation-N4 is installed,
then it may not be required to install Platform Daemon every time while opening WEBStation-N4.
After installing Platform Daemon completely, go to ‘Start’ menu again and select ‘All Programs, navigate to ‘WEBStation-N4 4.2.36.34’ folder and click on it. Click ‘WEBStation.’ It will open ‘WEBStation-N4’ window. Refer to Figure 4.
Note:
‘WEBStation-N4’ can also be open by clicking an icon named ‘WEBStation-N4 Workbench’ on the desktop
Figure 3: Installing Platform Daemon
31-00121—02 9
BACnet FF Controller
Title Bar
Menu Bar
Standard Toolbar
Path Bar
Controls
View Tab
Right Pane
Left Pane
Figure 4: WEBStation-N4TM – Getting Started
The field description for Figure 4is as follows:
1. Title Bar:
Top of the WEBStation interface is the Title bar. It displays the title of the screen.
2. Controls
An application can be minimized, maximized and closed with these controls.
3. Menu Bar
It displays heading for drop-down menus. According to function, commands are group in to the menu
tabs. These are File, Edit, Search, Bookmarks, Tools, Window, and Help.
I. File: A user can open, close and save the file,
directory, query, new tab, new window using File tab.
II. Edit: Cut, copy, paste, duplicate delete options are
available.
III. Search: A file can be searched and navigate from one
file to other file.
IV. Bookmarks: A user can add or manage bookmarks.
V. Tools: A user can maintain certificates, license,
migration and credential details.
VI. Window: A user can add/ hide Side Bar, Console
window, check Active Plug-in.
VII. Help: A user can get assist by clicking F1 or help tab.
10 31-00121—02
BACnet FF Controller
4. Standard Tool Bar
Various functions can be accessed using this tool bar. It provides a quick shortcut to frequently used functions.
5. Ribbon
It includes menu bar and standard toolbar.
6. Path Bar
A path of a particular function can be tracked using this.
7. View Tab
9. Right Pane
Details about Version, License and Certificate are found over here.
It is used to switch between various views, such as, Html View, Text File Editor, Text File Viewer, and Hex File Editor.
8. Left pane
Nav tree details can be viewed over here.
31-00121—02 11
BACnet FF Controller
TB3026B Configuration Wizard Initial Setup
The TB3026B Configuration Wizard’s user interface window is obtained by following these steps:
1. Connecting to platform
2. Adding new station
3. Starting/Running new station
4. Adding a BACnet network
5. Adding TB3026B device to the BACnet network
Connecting to Platform
To perform various operations, it is necessary to connect to the Platform initially.
To connect Platform, follow the process: Navigate to ‘My Host: …’ in the Left pane, by right clicking
on it, select ‘Open Platform’. Refer to Figure 5.
Enter Username and Password and click ‘OK’
Figure 7: Authentication during connecting Platform
Figure 5: Open Platform
A window will pop up to connect to the Host’s secure platform daemon. Click ‘OK’ to proceed.
Figure 6: Connect Platform
An Identity Verification window may pop up during the first time configuration. Click ‘Accept’ to verify. (Refer to
Figure 8)
12 31-00121—02
Figure 8: Identity Verification during Connecting to
Platform
Adding New Station
The next stage is to add a new station under platform. Different controllers can be added to the respective network assigned to the station.
To add a new station:
Navigate to the Platform by clicking sign of Host in the left pane.
Click ‘Tools’ tab on menu bar.
Navigate to ‘New station’ and click on it.
BACnet FF Controller
Figure 11: Entering Admin Password for New Station
Figure 9: Adding New Station
After clicking ‘New Station’, it opens ‘New Station Wizard, window. (Refer to Figure 10)
Enter name in Station Name field. For example, ‘BACnetFF’ is added here. Station Directory displays a path by default.
Click ‘Next’
It creates a station at ‘My Host > My File System> User Home > Stations > (created station)’. Refer to Figure 12.
Click ‘Finish’ to complete action.
Figure 10: New Station Wizard Window
Enter a password in the ‘Admin Password’ field. Enter the same password in ‘Confirm Admin Password’ field.
Important:
Password must contain:
at least 10 character(s)
at least 1 digit(s)
at least 1 lower case character(s)
at least 1 upper case character(s)
31-00121—02 13
Figure 12: Location of New Station
(BACnetFF)
BACnet FF Controller
Starting New Station
To start configuration of controller, it is necessary to start the station. The following is the process to start a newly added station:
Double click on ‘Platform’, it opens a screen as shown in
Figure 13.
Double click on ‘Application Director’ at the right pane. (Refer to Figure 13).
Figure 13: Application Director
Select the newly created station (‘BACnetFF’ in this case) by just clicking on it. Status for this station will be Idle at this stage.
Click ‘Start’ button as shown in Figure 14. After clicking ‘Start’, the ‘Status’ of this station will change to ‘Starting’ as shown in Figure 15.
Figure 14: Selecting the Station to Start
Figure 15: Starting the Station
Figure 16: Started Station
14 31-00121—02
Once the station is started, its status will change to ‘Running’ (Refer to Figure 16).
Double click on the started station, a ‘verification window will pop up as shown in Figure 8. Click ‘Accept’ to proceed.
It opens an authentication window. Enter username and password. Click ‘OK’ to proceed.
Note:
Check ‘Remember these credentials’ box to remember the username and passwords so that it will not be required to enter it every time during opening the station.
Check newly added station as shown in Figure 17.
BACnet FF Controller
Figure 17: Newly added Station
31-00121—02 15
BACnet FF Controller
Adding BACnet Network to Niagara Network
TB3026B controller works with BACnet network.
To add a BACnet network (Refer to Figure 18):
Navigate to Drivers and double click on it.
Click on ‘New’ tab
Figure 18: Adding BACnet Network
A window will pop out as shown in Figure 19, asking ‘Type to Add’.
Select ‘Bacnet Network’ from the drop down list.
Figure 19: Selecting BACnet Network to add
31-00121—02 16
Required number of networks can be added in ‘Number to Add’ field. (In this guide since only one network is shown, Number is added as ‘1’)
Click ‘OK’ to proceed.
Next, a new window will appear, showing ‘Name’,
‘Type’ and ‘Enabled’(keep its value to ‘True’). Refer to
Figure 20.
Click ‘OK’.
Figure 20: Adding Specification to add BACnet
Network
BACnet FF Controller
A newly added ‘BacnetNetwork’ can be seen under ‘Device manager’ on the right pane highlighted in Amber color as shown in Figure 21
(An amber colored background highlight appears, as BacnetNetwork is offline. Background will turn white when it is online.)
Figure 21: Newly added BACnet Network
31-00121—02 17
BACnet FF Controller
Adding TB3026B Controller to the BACnet Network
After adding a Bacnet Network to the Drivers, the next step is to add a TB3026B controller to the Bacnet Network.
Click on the ‘Window’ option in Menu bar; navigate to ‘Palette’ through sub menu of ‘Side Bars’. (Refer to Figure 22).
Figure 24: Adding ‘honeywellTB3026BWizard’ to
BACnet Network
After adding ‘honeywellTB3026BWizard’, it reflects in the ‘Palette’ tab as ‘BACnetFF’ as seen in Figure 25.
Figure 22: Adding Palette
This will add a ‘Palette’ tab in the left pane. (Refer to
Figure 23). Click ‘Open Palette’ option.
Figure 23: Opening Palette
An ‘Open Palette’ window will open. Find a module named ‘honeywellTB3026BWizard’ as shown in
Figure 24, Select it and click ‘OK’ button to add into
the Palette.
Figure 25: BACnetFF in Palette TAB
Drag ‘BACnetFF’ and Drop it on ‘BacnetNetwork’ added under created station. Refer to Figure 26.
Figure 26: Drag and drop BACnetFF on BacnetNetwork
18 31-00121—02
BACnet FF Controller
A window will pop up as ‘BACnetFF’ is dropped on BacnetNetwork to name the controller. Enter the name accordingly. In this guide, it is named as ‘BACnetFF’ as shown in Figure 27.
Figure 27: Naming Controller
A newly added TB3026B controller can be seen by
clicking sign as shown in Figure 28.
Figure 28: Location of Controller
TB3026B Configuration Wizard
To start working with the TB3026B wizard, navigate to Bacnet Network (Refer to Figure 28). Double click on added controller (here, ‘BACnetFF’). It will open the TB3026B Configuration Wizard window. .
31-00121—02 19
BACnet FF Controller
Figure 29: Opening TB3026B Configuration Wizard Screen
Field Description for TB3026B Configuration Wizard
Figure 30: Field description for TB3026B Configuration Wizard Screen
1. Title Bar
It displays the name ‘TB3026B Configuration View’.
2. Configuration Parameters
It displays the list of setting buttons for various groups of configuration parameters.
3. Configuration Settings
It displays Configuration settings as per the selected group of parameters.
4. Action Buttons
It displays following buttons:
It is used to save the configuration
settings.
It is used to reset actions to its
default value.
It is used to generate proxy
points under TB3026B controller "points" folder for the selected configuration.
20 31-00121—02
APPLICATIONS
Application is the first tab of the Configuration Wizard. The Application screen allows a user to select the required
Equipment Type.
BACnet FF Controller
Figure 31: Application Screen

Equipment Type

A user can select the required equipment type through this option. This is a fundamental setting in a configuration as selection of various other parameters from the different settings depend on the Equipment Type.
A required Equipment Type can be selected from the following:
1. AHU
2. Air Source Heat Pump
3. Water Source Heat Pump
4. Two Pipe Fan Coil Unit
5. Four Pipe Fan Coil Unit
31-00121—02 21
Figure 32: Equipment Type
BACnet FF Controller
AHU
Figure 33: AHU window
Output Stages
Equipment Type ‘AHU’ consists of two types of ‘Output Stages’
1. One Stage Heat/One Stage Cool
2. Two Stage Heat/Two Stage Cool
22 31-00121—02
One Stage Heat/One Stage Cool: Select this option if One stage of cooling and one stage of Heating is required in the application.
Two Stage Heat/Two Stage Cool: Select this option if Two stages of cooling and two stages of Heating are required in the application.
BACnet FF Controller
General Display
Click ‘General Display’ to view the general display settings. The following parameters are used to configure the controller’s display settings.
1. Engineering Units
2. Time Functions
3. Display
4. Contractor Access Codes
Figure 34: General Display Screen (AHU)
Engineering Units
Application Unit: The application units contain two
options to change the controller’s units. By default, the controller’s application units are set to ‘English’. Application Units can be changed to ‘English’ or ‘Metric’.
31-00121—02 23
BACnet FF Controller
Time Function
Clock Format: A user can select a clock format as
12-hour format or 24-hour format.
Display
This feature allows a user to select the Display settings.
Outside Air Temp: A user has an option to hide/show an outside air temperature.
Clock Adjustment: This option allows a user to enable/disable the clock adjustment on the controller display.
Keypad Lockout: This option allows a user to lock/unlock the clock adjustment.
When an option, ‘Temperature Settings Only’ is selected, a user can only set the temperature through keypad.
Backlight: A user can keep the backlight always on or set to delayed off through this option.
Daylight Savings Time: This feature enables to select the Daylight Savings Time settings. By default, Daylight Savings Time is set to ‘Disabled’. Daylight Savings Time can be changed to ‘Pre-2007’ or ‘Post-2007’.
Contractor Access Codes
An access to the controller can be restricted with the help of Access Codes.
Field Service Pin and Installer Service Pin can be set. These codes should be enabled to restrict an access to the controller.
Note:
A user can set only numerical PIN code for ‘Field Service Pin’ and ‘Installer Service Pin’. PIN codes should be set within 0000 – 9999. The following Error Window pops up if this field is left blank after selecting.
Note: When error message pops up, it displays the text field twice in the error window.
24 31-00121—02
Schedule Options
‘Schedule’ tab displays Schedule options. The following parameters are used to configure the
schedule options (i.e. Occupancy Configuration and Bypass and Standby).
BACnet FF Controller
Figure 35: Schedule Options Screen (AHU)
Occupancy Configuration
Schedule Model: A user can set the device’s schedule
model as;
1. Setpoint Mode or
2. Occupancy Mode
Setpoint Mode: In setpoint mode, the controller logically emulates residential thermostats. The space temperature is controlled to "SP Mode Cooling SP" and "SP Mode Heating SP". Each schedule period consists of a start time, a heating setpoint, and a cooling setpoint.
Occupancy Mode: By default, ‘Schedule Model’ is in ‘Occupancy Mode’. The system will be switched to ‘Occupied Mode’ when the occupancy sensor detects occupancy. Occupied Mode allows a user to configure ‘Comm Fails Occupied’, ‘System Block’ & ‘Internal Schedule’ settings.
If a user selects ‘Setpoint Mode’ from the available ‘Schedule Model’, the fields for ‘Comm Fails Occupied’ and ‘System Block’ settings become disabled.
31-00121—02 25
BACnet FF Controller
Comm Fails Occupied: It allows a user to switch the system in Occupied Mode in case of MS/TP communication failure. If the MS/TP communication fails, the system enters into Occupied Mode when this option is selected as ‘Enable’, otherwise the system remains in its current state when this option is selected as ‘Disable’.
System Block: The System Block is hidden when the schedule model is in ‘Setpoint Mode’. When the schedule model is in ‘Occupancy Mode’, it allows a user to switch between the available options. Selecting “Show Unoccupied/Off” places the controller in unoccupied state.
Internal schedule: It can be configured in both Occupancy Mode & Setpoint Mode. By default, ‘Internal Schedule’ is ‘Disable’.
If the internal schedule is ‘Disable’, a user can adjust the setpoint (within setpoint limits).
Display Settings
When a user selects, ‘Two Periods’ or ‘Four Periods’ options an additional ‘Display Settings’ appears as follows:
Bypass and Standby
Bypass Time: In the Unoccupied state, it forces the
controller into the occupied state for up to 4 hours (default value). The override time limit is adjustable from a minimum of 0.2 hours to a maximum of 9.5 hours.
Standby Delay: In Occupied Mode, if any window or door is opened and closed with no motion detected after the time mentioned for the Standby Delay, the room status switches to Standby state. The default value is 180 seconds.
Schedule Access: When a user selects ‘Edit’, it allows a user to view and edit the schedule and when a user selects ‘View’, it allows a user to view the schedule. When a user selects ‘None’, it will not allow a user to view or edit the schedule.
Vacation Hold: It allows/denies a user to override the scheduled setpoint from TB3026B display to “Vacation Hold”.
Permanent Hold: It allows/denies a user to override the scheduled setpoint from TB3026B display to “Permanent Hold”.
26 31-00121—02
BACnet FF Controller
Zone Setpoints
Zone Setpoints , allows a user to set the following parameters as per the requirement:
1. Temperature Setpoints
2. Setpoint Limits
3. Standby Settings
4. Display Options
Figure 36: Zone Setpoints Screen (Occupancy Mode)
Temperature Setpoints
Occupied Setpoint: It is a setpoint in Occupied Mode.
Enter the value within the range of 45 ºF to 99 ºF. The default value is 70ºF.
Cooling Offset: In the Occupied state, the cooling setpoint is calculated as cooling offset plus occupied setpoint. Enter
31-00121—02 27
the value within the range of 0ΔºF to 12.1ΔºF. The default value is 2 ΔºF.
Heating Offset: In the Occupied state, the heating setpoint is calculated as heating offset minus occupied setpoint. Enter the value within the range of 0ΔºF to 12.1ΔºF. The default value is 1 ΔºF.
Unoccupied Heating Setpoint: It is a setpoint for Heating in Unoccupied mode. Enter the value within the range of 45 ºF to 99 ºF. The default value is 55 ºF.
Unoccupied Cooling Setpoint: It is a setpoint for Cooling in Unoccupied mode. Enter the value within the range of 45 ºF to 99 ºF. The default value is 85 ºF.
BACnet FF Controller
Setpoint Limits
Setpoint High Limit: A user can enter a Setpoint High
Limit in Occupied Mode within the range of 45 ºF to 99 ºF. The default value is 78 ºF.
Setpoint Low Limit: A user can enter a Setpoint Low Limit in Occupied Mode within the range of 45 ºF to 99 ºF. The default value is 62 ºF.
Note:
1. Unoccupied Cooling Setpoint should always be set GREATER than Unoccupied Heating Setpoint.
Following Error window appears if Unoccupied Cooling Setpoint is set lower than Unoccupied Heating Setpoint.
2. Setpoint High Limit should always be set GREATER than Setpoint Low Limit.
Following Error window appears if Setpoint High Limit is set lower than Setpoint low Limit.
Standby Settings
Standby state is a power-saving function of Occupancy mode. It occurs when the space is scheduled as Occupied, but sensors detect (When the Standby input is active) there are no humans in the space.
Standby Offset: In this case, the Standby Offset relaxes the occupied setpoints. The value of the Standby Offset [SO] can be set between a minimum of 0ΔºF and a maximum of 12.1ΔºF degrees. The default value is 4 ΔºF.
Reverse Standby Input: It allows a user to configure two types of inputs, ‘Normally Open (NO)’ and ‘Normally Close (NC)’.
28 31-00121—02
BACnet FF Controller
Display Options
Unoccupied Setpoints: It allows a user to either ‘Hide’ or
‘Show’ the unoccupied setpoint.
When a user selects Schedule Mode under the ‘Schedule Options’ tab to ‘Setpoint Mode’, the ‘Zone Setpoints’ configuration window appears as follows:
Figure 37: Zone Setpoint Screen (Setpoint Mode)
31-00121—02 29
Control Settings
‘Control Settings’ allows a user to configure following settings:
1. Cooling PI Control
2. Heating PI Control
3. Compressor Settings
BACnet FF Controller
Figure 38: Control Settings Screen (AHU)
31-00121—02 30
BACnet FF Controller
Cooling PI Control
Proportional Constant K
: A user can enter a value for Kp
p
within the range of 10 to 40. The default value is 20.
Integral Constant K
: A user can enter a value for Ki
i
within the range of 0.50 to 2. The default value is 1.
OAT Lockout Setpoint: Cooling PI control will lockout when outside Temperature decreases below OAT (Cooling) Lockout Setpoint. The default value is 55 ºF.
Heating PI Control
Proportional Constant K
: A user can enter a value for Kp
p
within the range of 10 to 40. The default value is 20.
Integral Constant K
: A user can enter a value for Ki
i
within the range of 0.50 to 2. The default value is 1.
OAT Lockout Setpoint: Heating PI control will lockout when outside Temperature increases above OAT (Heating) Lockout Setpoint. The default value is 62 ºF.
Compressor Settings
Cycle Time: The Compressor Cycle Time is adjustable, it
ranges from minimum of 8 minutes, and a maximum of 30 minutes. The default value is 20 minutes.
Minimum On/Off Time: It is a minimum time for the compressor to stay On/Off. The default value is 3 minutes.
31-00121—02 31
BACnet FF Controller
Fan / Humidity
‘Fan / Humidity’ allows a user to configure the following settings:
1. Fan Operation
2. Humidity Control
3. Filter Alarm
Figure 39: Fan/Humidity Screen (AHU)
Fan Operation
Fan Mode Control: During Setpoint Mode and Occupancy
Mode, the fan can be configured to operate based on the selected Fan Mode Control as describe below:
Auto: When this option is selected, Fan cycles ON when:
1. Cooling or heating is selected or
2. During Unoccupied mode only when called to run by cooling or heating demand.
On: When this option is selected the fan runs continuously for ventilation.
On Cool/Auto Heat: When this option is selected the fan runs continuously in cooling mode. In heating mode the fan cycles on only when the heating signal calls for the fan to run.
32 31-00121—02
BACnet FF Controller
Humidity Control
Fan Circulation Cycle: When a user selects the ‘Enable’
option from Fan Circulation Cycle, it allows a user to edit the Trigger Setpoint, Reset Deadband, and Fan On/Off Cycle Time.
Trigger Setpoint & Reset Deadband: When sensed humidity equals or exceeds humidity trigger setpoint, the fan cycles ON/OFF at low speed until sensed humidity drops below the trigger setpoint minus the reset deadband.
Fan On Cycle Time: This field allows a user to enter a time for fan ON cycle when stratification and humidity control is active. The default value is 300 seconds.
Fan Off Cycle Time: This field allows a user to enter a time for fan OFF cycle when stratification and humidity control is active. The default value is 1800 seconds.
Filter Alarm
Runtime Hours: A filter alarm activates after the Runtime
Hours mentioned in this field. The default value is 3000 hours.
31-00121—02 33
BACnet FF Controller
Economizer
Select Economizer from Configuration parameters. It is used to configure the economizer settings in TB3026B controller.
Figure 40: Economizer Screen (AHU)
Configuration
Minimum Position: When either the occupied command
or the After-hours Timer is ON, the current minimum position is set to the specified Economizer Minimum Position; otherwise, it is zero. The default minimum position is 20%.
Outside Air Lockout: The economizer is forced to Minimum position when Outside Air Temperature goes above the Outside Air Lockout setpoint. The default value is 68º F.
Supply Air Low Limit: The economizer is forced to Minimum position when Supply Temperature goes below the Supply Air Low Limit. The default value is 45º F.
34 31-00121—02
BACnet FF Controller
I/O Configurations
Select I/O Configurations from Configuration parameters. This configuration is mainly used for Terminal Assignment & Output Configuration.
Figure 41:I/O Configurations Screen (AHU)
Terminal Assignment
After completing the AHU configuration, selected inputs and outputs get automatically assigned to the TB3026B controller’s input and output terminals. However, a user can assign the outputs as ‘Economizer Open’ & ‘Economizer Close ’to BO-4 & BO-5 and inputs as ‘BMS Sensor’ or ‘Remote Space Temp’ or ‘Outdoor Air Temp’ to AI/BI0 respectively.
31-00121—02 35
BACnet FF Controller
Figure 42: Terminal Assignment View (AHU)
Output Configuration
When a user assigns the outputs, ‘Economizer Open’ and ‘Economizer Close’ to BO-4 and BO-5 respectively, ‘Economizer Damper Stroke Time’ can be mentioned in the field ‘Output Configuration’. The default value is 3 seconds.
When ‘Output Stage’ is selected as ‘Two Stages Heat/Two Stages Cool’, the ‘Terminal Assignment’ view changes as follows:
36 31-00121—02
Air Source Heat Pump
BACnet FF Controller
Figure 43: Air Source Heat Pump Window
Output Stages
Equipment Type ‘Air Source Heat Pump’ consists of two types of ‘Output Stages’. Required type of output stages can be selected from the following available options:
One Compressor Stage and One Aux Heat Stage:
Select this option if One stage of compressor and one stage of Auxiliary Heating is required in the application
31-00121—02 37
One Compressor Stage and Two Aux Heat Stage:
Select this option if Two stages of Compressors and Two stages of Auxiliary Heating are required in the application
Fan Speeds
A user can select Two types of ‘Fan Speeds’ when the output stage is configured as ‘One Compressor Stage and One Aux Heat Stage’.
1. Single Speed Fan
2. Three Speed Fan
BACnet FF Controller
General Display
Click ‘General Display’ to view the general display settings. The following parameters are used to configure the controller’s display settings.
1. Engineering Units
2. Time Functions
3. Display
4. Contractor Access Codes
Figure 44: General Display Screen (Air Source Heat Pump)
Engineering Units
Application Unit: The application units contain two
options to change the controller’s units. By default, the controller’s application units are set to ‘English’. Application units can be changed to ‘English’ or ‘Metric’.
38 31-00121—02
Time Function
BACnet FF Controller
Clock Format: A user can select a clock format as 12-hour format or 24-hour format.
Display
This feature allows a user to select the Display settings.
Outside Air Temp: A user has an option to hide/show an outside air temperature.
Clock Adjustment: This option allows a user to enable/disable the clock adjustment on the controller display.
Keypad Lockout: This option allows a user to lock/unlock the clock adjustment.
When an option, ‘Temperature Settings Only’ is selected, a user can only set the temperature through keypad.
Backlight: A user can keep the backlight always on or set to delayed off through this option.
Daylight Savings Time: This feature enables to select the Daylight Savings Time settings. By default, Daylight Savings Time is set to ‘Disabled’. Daylight Savings Time can be changed to ‘Pre-2007’ or ‘Post-2007’.
Contractor Access Codes
An access to the controller can be restricted with the help of Access Codes.
Field Service Pin and Installer Service Pin can be set. These codes should be enabled to restrict an access to the controller.
Note:
A user can set only numerical PIN code for ‘Field Service Pin’ and ‘Installer Service Pin’. PIN codes should be set within 0000 – 9999. The following Error Window pops up if this field is left blank after selecting.
31-00121—02 39
BACnet FF Controller
Schedule Options
‘Schedule’ tab displays Schedule options. The following parameters are used to configure the
schedule options (i.e. Occupancy Configuration and Bypass and Standby)
Figure 45: Schedule Options Screen (Air Source Heat Pump)
Occupancy Configuration
Schedule Model: A user can set the device’s schedule
model as;
1. Setpoint Mode or
2. Occupancy Mode
Setpoint Mode: In setpoint mode, the controller logically emulates residential thermostats. The space temperature is controlled to "SP Mode Cooling SP" and "SP Mode Heating SP". Each schedule period consists of a start time, a heating setpoint, and a cooling setpoint.
Occupancy Mode: By default, ‘Schedule Model’ is in ‘Occupancy Mode’. The system will be switched to ‘Occupied Mode’ when the occupancy sensor detects occupancy. Occupied Mode allows a user to configure ‘Comm Fails Occupied’, ‘System Block’ & ‘Internal Schedule’ settings.
If a user selects ‘Setpoint Mode’ from the available ‘Schedule Model’, the fields for ‘Comm Fails Occupied’ and ‘System Block’ settings become disabled.
40 31-00121—02
Comm Fails Occupied: It allows a user to switch the system in Occupied Mode in case of MS/TP communication failure. If the MS/TP communication fails, the system enters into Occupied Mode when this option is selected as ‘Enable’, otherwise the system remains in its current state when this option is selected as ‘Disable’.
‘Enable’, and remains in its current state when this option is selected as ‘Disable’.
System Block: The System Block is hidden when the schedule model is in ‘Setpoint Mode’. When the schedule model is in ‘Occupancy Mode’, it allows a user to switch between the available options. Selecting “Show Unoccupied/Off” places the controller in unoccupied state.
Internal schedule: It can be configured in both Occupancy Mode & Setpoint Mode. By default, ‘Internal Schedule’ is ‘Disable’.
If the internal schedule is ‘Disable’, a user can adjust the setpoint (within setpoint limits).
Display Settings
When a user selects, ‘Two Periods’ or ‘Four Periods’ options an additional ‘Display Settings’ appears as follows:
BACnet FF Controller
Bypass and Standby
Bypass Time: In the Unoccupied state, it forces the
controller into the occupied state for up to 4 hours (default value). The override time limit is adjustable from a minimum of 0.2 hours to a maximum of 9.5 hours.
Standby Delay: In Occupied Mode, if any window or door is opened and closed with no motion detected after the time mentioned for the Standby Delay, the room status switches to Standby state. The default value is 180 seconds.
Schedule Access: When a user selects ‘Edit’, it allows a user to view and edit the schedule and when a user selects ‘View’, it allows a user to view the schedule. When a user selects ‘None’, it will not allow a user to view or edit the schedule.
Vacation Hold: It allows/denies a user to override the scheduled setpoint from TB3026B display to “Vacation Hold”.
Permanent Hold: It allows/denies a user to override the scheduled setpoint from TB3026B display to “Permanent Hold”.
31-00121—02 41
BACnet FF Controller
Zone Setpoints
Zone Setpoints , allows a user to set the following parameters as per the requirement:
1. Temperature Setpoints
2. Setpoint Limits
3. Standby Settings
4. Display Options
Figure 46: Zone Setpoints Screen (Occupancy Mode)
Temperature Setpoints
Occupied Setpoint: It is a setpoint in Occupied Mode.
Enter the value within the range of 45 ºF to 99 ºF. The default value is 70ºF.
Cooling Offset: In the Occupied state, the cooling setpoint is calculated as cooling offset plus occupied setpoint. Enter
42 31-00121—02
the value within the range of 0ΔºF to 12.1ΔºF.The default value is 2 ΔºF.
Heating Offset: In the Occupied state, the heating setpoint is calculated as heating offset minus occupied setpoint. Enter the value within the range of 0ΔºF to 12.1ΔºF. The default value is 1 ΔºF.
Unoccupied Heating Setpoint: It is a setpoint for Heating in Unoccupied mode. Enter the value within the range of 45 ºF to 99 ºF. The default value is 55 ºF.
Unoccupied Cooling Setpoint: It is a setpoint for Cooling in Unoccupied mode. Enter the value within the range of 45ºF to 99ºF.The default value is 85 ºF.
BACnet FF Controller
Setpoint Limits
Setpoint High Limit: A user can enter a Setpoint High
Limit in Occupied Mode within the range of 45 ºF to 99 ºF. The default value is 78ºF.
Setpoint Low Limit: A user can enter a Setpoint Low Limit in Occupied Mode within the range of 45 ºF to 99 ºF. The default value is 62ºF.
Note:
1. Unoccupied Cooling Setpoint should always be set GREATER than Unoccupied Heating Setpoint.
Following Error window appears if Unoccupied Cooling Setpoint is set lower than Unoccupied Heating Setpoint.
2. Setpoint High Limit should always be set GREATER than Setpoint Low Limit.
Following Error window appears if Setpoint High Limit is set lower than Setpoint low Limit.
Standby Settings
Standby state is a power-saving function of Occupancy mode. It occurs when the space is scheduled as Occupied, but sensors detect (When the Standby input is active) there are no humans in the space.
Standby Offset: In this case, the Standby Offset relaxes the occupied setpoints. The value of the Standby Offset [SO] can be set between a minimum of 0ΔºF and a maximum of 12.1ΔºF degrees. The default value is 4 ΔºF.
Reverse Standby Input: It allows a user to configure two types of inputs, ‘Normally Open (NO)’ and ‘Normally Close (NC)’.
31-00121—02 43
BACnet FF Controller
Display Options
When a user selects Schedule Model under the ‘Schedule Options’ tab to ‘Setpoint Mode’, the ‘Zone Setpoints’ configuration window appears as follows:
Figure 47: Zone Setpoint Screen (Setpoint Mode)
Unoccupied Setpoints: It allows a user to either ‘Hide’ or
‘Show’ the unoccupied setpoint.
44 31-00121—02
BACnet FF Controller
Control Settings
‘Control Settings’ allows a user to configure following settings:
1. Cooling PI Control.
2. Heating PI Control.
3. Aux Staged Heating
4. Compressor Settings.
Figure 48: Control Settings Screen (Air Source Heat Pump)
31-00121—02 45
BACnet FF Controller
Cooling PI Control
Proportional Constant K
: A user can enter a value for Kp
p
within the range of 10 to 40. The default value is 20.
Integral Constant K
: A user can enter a value for Ki
i
within the range of 0.50 to 2. The default value is 1.
OAT Lockout Setpoint: Cooling PI control will lockout when outside Temperature increases above OAT (Cooling) Lockout Setpoint. The default value is 55 ºF.
Aux Staged Heating
Heating PI Control
Proportional Constant K
: A user can enter a value for Kp
p
within the range of 10 to 40. The default value is 20.
Integral Constant K
: A user can enter a value for Ki
i
within the range of 0.50 to 2. The default value is 1.
OAT Lockout Setpoint: Heating PI control will lockout when outside Temperature decreases below OAT (Heating) Lockout Setpoint. The default value is 62 ºF.
Compressor Settings
Cycle Time: The Cycle Time ranges from minimum of 8
minutes, and a maximum of 30 minutes. The default value is 15 minutes.
Minimum On/Off Time: It is a minimum On/Off time for the Auxiliary Heating. The default value is 3 minutes.
Cycle Time: The Compressor Cycle Time is adjustable; it ranges from minimum of 8 minutes, and a maximum of 30 minutes. The default value is 20 minutes.
Minimum On/Off Time: It is a minimum time for the compressor to stay On/Off. The default value is 3 minutes.
Reversing Valve: Depending upon heating/cooling demand, a user can energize the Reversing Valve on Heating or Cooling.
46 31-00121—02
BACnet FF Controller
Fan / Humidity
‘Fan / Humidity’ allows a user to configure the following settings:
1. Fan Operation
2. Humidity Control
3. Filter Alarm
Figure 49: Fan/Humidity Screen (Air Source Heat Pump)
Fan Operation
Fan Mode Control: During Setpoint Mode and Occupancy
Mode, the fan can be configured to operate based on the selected Fan Mode Control as describe below:
Auto: When this option is selected, Fan cycles ON when:
1. Cooling or heating is selected or
2. During Unoccupied mode only when called to run by cooling or heating demand.
On: When this option is selected the fan runs continuously for ventilation.
On Cool/Auto Heat: When this option is selected the fan runs continuously in cooling mode. In heating mode the fan cycles on only when the heating signal calls for the fan to run.
31-00121—02 47
BACnet FF Controller
Humidity Control
Fan Circulation Cycle: When a user selects the ‘Enable’
option from Fan Circulation Cycle, it allows a user to edit the Trigger Setpoint, Reset Deadband, and Fan On/Off Cycle Time.
Trigger Setpoint & Reset Deadband: When sensed humidity equals or exceeds humidity trigger setpoint, the fan cycles ON/OFF at low speed until sensed humidity drops below the trigger setpoint minus the reset deadband.
Fan On Cycle Time: This field allows a user to enter a time for fan ON cycle when stratification and humidity control is active. The default value is 300 seconds.
Fan Off Cycle Time: This field allows a user to enter a time for fan OFF cycle when stratification and humidity control is active. The default value is 1800 seconds.
Filter Alarm
Runtime Hours: A filter alarm activates after the Runtime
Hours mentioned in this field. The default value is 3000 hours.
48 31-00121—02
BACnet FF Controller
Economizer
Select Economizer from Configuration parameters. It is used to configure the economizer settings in TB3026B controller
Figure 50: Economizer Screen (Air Source Heat Pump)
Configuration
Minimum Position: When either the occupied command
or the After-hours Timer is ON, the current minimum position is set to the specified Economizer Minimum Position; otherwise, it is zero. The default minimum position is 20%.
Outside Air Lockout: The economizer is forced to Minimum position when Outside Air Temperature goes above the Outside Air Lockout setpoint. The default value is 68º F.
Supply Air Low Limit: The economizer is forced to Minimum position when Supply Temperature goes below the Supply Air Low Limit. The default value is 45º F.
31-00121—02 49
BACnet FF Controller
I/O Configurations
Select I/O Configurations from Configuration parameters. This configuration is used for Terminal Assignment & Output Configuration.
Figure 51: I/O Configurations Screen (Air Source Heat Pump)
Terminal Assignment
After completing the ‘Air Source Heat Pump’ configuration, selected inputs and outputs get automatically assigned to the TB3026B controller’s input and output terminals. However, a user can assign the outputs as ‘Economizer Open’ & ‘Economizer Close’ to BO-4 & BO-5 and inputs as ‘BMS Sensor’ or ‘Remote Space Temp’ or ‘Outdoor Air Temp’ to AI/BI0 respectively.
Figure 52: Terminal Assignment View (Air Source Heat Pump)
50 31-00121—02
BACnet FF Controller
Output Configuration
When a user assigns the outputs, ‘Economizer Open’ and ‘Economizer Close’ to BO-4 and BO-5 respectively, ‘Economizer Damper Stroke Time’ can be mentioned in the field ‘Output Configuration’. The default value is 3 seconds.
When ‘Fan Speed’ is selected as ‘Three Speed Fan’, the ‘Terminal Assignment’ view changes as follows:
When ‘Output Stage’ is selected as ‘One Compressor Stage/Two Aux Stages’, the ‘Terminal Assignment’ view changes as follows:
31-00121—02 51
BACnet FF Controller
Water Source Heat Pump
Figure 53: Water Source Heat Pump Window
Output Stages
Equipment Type ‘Water Source Heat Pump’ consists of two types of ‘Output Stages’
1. One Compressor Stage/One Aux Heat Stage
2. One Compressor Stage/Two Aux Heat Stages
52 31-00121—02
One Compressor Stage and One Aux Heat Stage:
Select this option if One stage of compressor and one stage of Auxiliary Heating is required in the application
One Compressor Stage and Two Aux Heat Stage:
Select this option if Two stages of Compressors and Two stages of Auxiliary Heating are required in the application
BACnet FF Controller
General Display
Click ‘General Display’ to view the general display settings. The following parameters are used to configure the controller’s display settings.
1. Engineering Units
2. Time Functions
3. Display
4. Contractor Access Codes
Figure 54: General Display Screen (Water Source Heat Pump)
Engineering Units
Application Unit: The application units contain two
options to change the controller’s units. By default, the controller’s application units are set to ‘English’. Application Unit can be changed to ‘English’ or ‘Metric’.
31-00121—02 53
BACnet FF Controller
Time Function
Clock Format: A user can select a clock format as
12-hour format or 24-hour format.
Display
This feature allows a user to select the Display settings.
Outside Air Temp: A user has an option to hide/show an outside air temperature.
Clock Adjustment: This option allows a user to enable/disable the clock adjustment on the controller display.
Keypad Lockout: This option allows a user to lock/unlock the clock adjustment.
When an option, ‘Temperature Settings Only’ is selected, a user can only set the temperature through keypad.
Backlight: A user can keep the backlight always on or set to delayed off through this option.
Daylight Savings Time: This feature enables to select the Daylight Savings Time settings. By default, Daylight Savings Time is set to ‘Disabled’. Daylight Savings Time can be changed to ‘Pre-2007’ or ‘Post-2007’.
Contractor Access Codes
An access to the controller can be restricted with the help of Access Codes.
Field Service Pin and Installer Service Pin can be set. These codes should be enabled to restrict an access to the controller.
Note:
A user can set only numerical PIN code for ‘Field Service Pin’ and ‘Installer Service Pin’. PIN codes should be set within 0000 – 9999. The following Error Window pops up if this field is left blank after selecting.
54 31-00121—02
Schedule Options
‘Schedule Options’ tab displays Schedule options. The following parameters are used to configure the
schedule options (i.e. Occupancy Configuration and Bypass and Standby).
BACnet FF Controller
Figure 55: Schedule Options Screen (Water Source Heat Pump)
Occupancy Configuration
Schedule Model: A user can set the device’s schedule
model as;
1. Setpoint Mode or
2. Occupancy Mode
Setpoint Mode: In setpoint mode, the controller logically emulates residential thermostats. The space temperature is controlled to "SP Mode Cooling SP" and "SP Mode Heating SP". Each schedule period consists of a start time, a heating setpoint, and a cooling setpoint.
Occupancy Mode: By default, ‘Schedule Model’ is in ‘Occupancy Mode’. The system will be switched to ‘Occupied Mode’ when the occupancy sensor detects occupancy. Occupied Mode allows a user to configure ‘Comm Fails Occupied’, ‘System Block’ & ‘Internal Schedule’ settings.
If a user selects ‘Setpoint Mode’ from the available ‘Schedule Model’, the fields for ‘Comm Fails Occupied’ and ‘System Block’ settings become disabled.
31-00121—02 55
BACnet FF Controller
Comm Fails Occupied: It allows a user to switch the system in Occupied Mode in case of MS/TP communication failure. If the MS/TP communication fails, the system enters into Occupied Mode when this option is selected as ‘Enable’, otherwise the system remains in its current state when this option is selected as ‘Disable’.
System Block: The System Block is hidden when the schedule model is in ‘Setpoint Mode’. When the schedule model is in ‘Occupancy Mode’, it allows a user to switch between the available options. Selecting “Show Unoccupied/Off” places the controller in unoccupied state.
Internal schedule: It can be configured in both Occupancy Mode & Setpoint Mode. By default, ‘Internal Schedule’ is ‘Disable’.
If the internal schedule is ‘Disable’, a user can adjust the setpoint (within setpoint limits).
Display Settings
When a user selects, ‘Two Periods’ or ‘Four Periods’ options an additional ‘Display Settings’ appears as follows:
Bypass and Standby
Bypass Time: In the Unoccupied state, it forces the
controller into the occupied state for up to 4 hours (default value). The override time limit is adjustable from a minimum of 0.2hours to a maximum of 9.5 hours.
Standby Delay: In Occupied Mode, if any window or door is opened and closed with no motion detected after the time mentioned for the Standby Delay, the room status switches to Standby state. The default value is 180 seconds.
Schedule Access: When a user selects ‘Edit’, it allows a user to view and edit the schedule and when a user selects ‘View’, it allows a user to view the schedule. When a user selects ‘None’, it will not allow a user to view or edit the schedule.
Vacation Hold: It allows/denies a user to override the scheduled setpoint from TB3026B display to “Vacation Hold”.
Permanent Hold: It allows/denies a user to override the scheduled setpoint from TB3026B display to “Permanent Hold”.
56 31-00121—02
BACnet FF Controller
Zone Setpoints
Zone Setpoints , allows a user to set the following parameters as per the requirement:
1. Temperature Setpoints
2. Setpoint Limits
3. Standby Settings
4. Display Options
Figure 56: Zone Setpoints Screen (Occupancy Mode)
Temperature Setpoints
Occupied Setpoint: It is a setpoint in Occupied Mode.
Enter the value within the range of 45 ºF to 99 ºF. The default value is 70 ºF.
Cooling Offset: In the Occupied state, the cooling setpoint is calculated as cooling offset plus occupied setpoint. Enter
31-00121—02 57
the value within the range of 0ΔºF to 12.1ΔºF. The default value is 2 ΔºF.
Heating Offset: In the Occupied state, the heating setpoint is calculated as heating offset minus occupied setpoint. Enter the value within the range of 0ΔºF to 12.1ΔºF. The default value is 1 ΔºF.
Unoccupied Heating Setpoint: It is a setpoint for Heating in Unoccupied mode. Enter the value within the range of 45 ºF to 99 ºF. The default value is 55 ºF.
Unoccupied Cooling Setpoint: It is a setpoint for Cooling in Unoccupied mode. Enter the value within the range of 45 ºF to 99 ºF. The default value is 85 ºF.
BACnet FF Controller
Setpoint Limits
Setpoint High Limit: A user can enter a Setpoint High
Limit in Occupied Mode within the range of 45 ºF to 99 ºF. The default value is 78 ºF.
Setpoint Low Limit: A user can enter a Setpoint Low Limit in Occupied Mode within the range of 45 ºF to 99 ºF. The default value is 62 ºF.
Note:
1. Unoccupied Cooling Setpoint should always be set GREATER than Unoccupied Heating Setpoint.
Following Error window appears if Unoccupied Cooling Setpoint is set lower than Unoccupied Heating Setpoint.
2. Setpoint High Limit should always be set GREATER than Setpoint Low Limit.
Following Error window appears if Setpoint High Limit is set lower than Setpoint low Limit.
Standby Settings
Standby state is a power-saving function of Occupancy mode. It occurs when the space is scheduled as Occupied, but sensors detect (When the Standby input is active) there are no humans in the space.
Standby Offset: In this case, the Standby Offset relaxes the occupied setpoints. The value of the Standby Offset [SO] can be set between a minimum of0ΔºF and a maximum of 12.1ΔºF degrees. The default value is 4 ΔºF.
Reverse Standby Input: It allows a user to configure two types of inputs, ‘Normally Open (NO)’ and ‘Normally Close (NC)’.
58 31-00121—02
BACnet FF Controller
Display Options
Unoccupied Setpoints: It allows a user to either ‘Hide’ or
‘Show’ the unoccupied setpoint.
When a user selects Schedule Model under the ‘Schedule Options’ tab to ‘Setpoint Mode’, the ‘Zone Setpoints’ configuration window appears as follows:
Figure 57: Zone Setpoint Screen (Setpoint Mode)
31-00121—02 59
BACnet FF Controller
Control Settings
‘Control Settings’ allows a user to configure following settings:
1. Cooling PI Control.
2. Heating PI Control.
3. Aux Staged Heating
4. Compressor Settings.
Figure 58: Control Settings Screen (Water Source Heat Pump)
60 31-00121—02
BACnet FF Controller
Cooling PI Control
Proportional Constant K
: A user can enter a value for Kp
p
within the range of 10 to 40. The default value is 20.
Integral Constant K
: A user can enter a value for Ki
i
within the range of 0.50 to 2. The default value is 1.
OAT Lockout Setpoint: Cooling PI control will lockout when outside Temperature increases above OAT (Cooling) Lockout Setpoint. The default value is 55 ºF.
Aux Staged Heating
Heating PI Control
Proportional Constant K
: A user can enter a value for Kp
p
within the range of 10 to 40. The default value is 20.
Integral Constant K
: A user can enter a value for Ki
i
within the range of 0.50 to 2. The default value is 1.
OAT Lockout Setpoint: Heating PI control will lockout when outside Temperature decreases below OAT (Heating) Lockout Setpoint. The default value is 62 ºF.
Compressor Settings
Cycle Time: The Cycle Time ranges from minimum of 8
minutes, and a maximum of 30 minutes. The default value is 15 minutes.
Minimum On/Off Time: It is a minimum On/Off time for the Auxiliary Heating. The default value is 3 minutes.
Cycle Time: The Compressor Cycle Time is adjustable; it ranges from minimum of 8 minutes, and a maximum of 30 minutes. The default value is 20 minutes.
Minimum On/Off Time: It is a minimum time for the compressor to stay On/Off. The default value is 3 minutes.
Reversing Valve: Depending upon heating/cooling demand, a user can Energize the Reversing Valve on Heating or Cooling.
31-00121—02 61
BACnet FF Controller
Fan / Humidity
‘Fan / Humidity’ allows a user to configure the following settings:
1. Fan Operation
2. Humidity Control
3. Filter Alarm
Figure 59: Fan/Humidity Screen (Water Source Heat Pump)
Fan Operation
Fan Mode Control: During Setpoint Mode and Occupancy
Mode, the fan can be configured to operate based on the selected Fan Mode Control as describe below;
Auto: When this option is selected, Fan cycles ON when:
1. Cooling or heating is selected or
2. During Unoccupied mode only when called to run by cooling or heating demand.
On: When this option is selected the fan runs continuously for ventilation.
On Cool/Auto Heat: When this option is selected the fan runs continuously in cooling mode. In heating mode the fan cycles on only when the heating signal calls for the fan to run.
62 31-00121—02
BACnet FF Controller
Humidity Control
Fan Circulation Cycle: When a user selects the ‘Enable’
option from Fan Circulation Cycle, it allows a user to edit the Trigger Setpoint, Reset Deadband, and Fan On/Off Cycle Time.
Trigger Setpoint & Reset Deadband: When sensed humidity equals or exceeds humidity trigger setpoint, the fan cycles ON/OFF at low speed until sensed humidity drops below the trigger setpoint minus the reset deadband.
Fan On Cycle Time: This field allows a user to enter a time for fan ON cycle when stratification and humidity control is active. The default value is 300 seconds.
Fan Off Cycle Time: This field allows a user to enter a time for fan OFF cycle when stratification and humidity control is active. The default value is 1800 seconds.
Filter Alarm
Runtime Hours: A filter alarm activates after the Runtime
Hours mentioned in this field. The default value is 3000 hours.
31-00121—02 63
BACnet FF Controller
Economizer
Select Economizer from Configuration parameters. It is used to configure the economizer settings in TB3026B controller
Figure 60: Economizer Screen (Water Source Heat Pump)
Configuration
Minimum Position: When either the occupied command
or the After-hours Timer is ON, the current minimum position is set to the specified Economizer Minimum Position; otherwise, it is zero. The default minimum position is 20%.
Outside Air Lockout: The economizer is forced to Minimum position when Outside Air Temperature goes above the Outside Air Lockout setpoint. The default value is 68º F.
Supply Air Low Limit: The economizer is forced to Minimum position when Supply Temperature goes below the Supply Air Low Limit. The default value is 45º F.
64 31-00121—02
BACnet FF Controller
I/O Configurations
Select I/O Configurations from Configuration parameters. This configuration is used for Terminal Assignment & Output Configuration.
Figure 61: I/O Configurations Screen (Water Source Heat Pump)
Terminal Assignment
After completing the ‘Water Source Heat Pump’ configuration, selected inputs and outputs get automatically assigned to the TB3026B controller’s input and output terminals. However, a user can assign the outputs as ‘Economizer Open’ & ‘Economizer Close ’to BO-4 & BO-5 and inputs as ‘BMS Sensor’ or ‘Remote Space Temp’ or ‘Outdoor Air Temp’ to AI/BI0 respectively.
31-00121—02 65
BACnet FF Controller
Figure 62: Terminal Assignment View (Water Source Heat Pump)
Output Configuration
When a user assigns the outputs, ‘Economizer Open’ and ‘Economizer Close’ to BO-4 and BO-5 respectively, ‘Economizer Damper Stroke Time’ can be mentioned in the field ‘Output Configuration’. The default value is 3 seconds.
When ‘Output Stage’ is selected as ‘One Compressor Stage/Two Aux Heat Stages’, the ‘Terminal Assignment’ view changes as follows:
66 31-00121—02
Two Pipe Fan Coil Unit
BACnet FF Controller
Figure 63: Two Pipe Fan Coil Unit Window
Fan Speeds
A user can select Two types of ‘Fan Speeds’ when the output stage is configured as ‘One Compressor Stage and One Aux Heat Stage’.
1. Single Speed Fan
2. Three Speed Fan
31-00121—02 67
BACnet FF Controller
Auxiliary Heat
A user can select heating stages from the following options:
No Stage Aux Heat: If auxiliary heating is not required in the system, select this option.
Single Stage Aux Heat: For single auxiliary heating stage, select this option.
Note:
The Auxilliary heat can be selected as ‘No Stage Aux Heat’ or ‘Single Stage Aux Heat’ only when Three Speed Fan is configured.
Valve Actuator
Valve actuator can be configured as ‘Two-Position’ or ‘Floating/Analog’ based on application.
Note:
The valve actuator can be selected as ‘Two-Position’ or ‘Floating/Analog’ only when ‘Three Speed Fan’ is configured.
Input Configuration
Input Configuration can be configured as ‘Remote Space Temp Sensor’ or ‘Door Switch’ or ‘Water Temperature Sensor’ based on application.
68 31-00121—02
BACnet FF Controller
General Display
Click ‘General Display’ to view the general display settings. The following parameters are used to configure the controller’s display settings.
1. Engineering Units
2. Time Functions
3. Display
4. Contractor Access Codes
Figure 64: General Display Screen (Two Pipe Fan Coil Unit)
Engineering Units
Application Unit: The application units contain two
options to change the controller’s units. By default, the controller’s application units are set to ‘English’. Application Unit can be changed to ‘English’ or ‘Metric’.
31-00121—02 69
BACnet FF Controller
Time Function
Clock Format: A user can select a clock format as
12-hour format or 24-hour format.
Display
This feature allows a user to select the Display settings.
Outside Air Temp: A user has an option to hide/show an outside air temperature.
Clock Adjustment: This option allows a user to enable/disable the clock adjustment on the controller display.
Keypad Lockout: This option allows a user to lock/unlock the clock adjustment.
When an option, ‘Temperature Settings Only’ is selected, a user can only set the temperature through keypad.
Backlight: A user can keep the backlight always on or set to delayed off through this option.
Daylight Savings Time: This feature enables to select the Daylight Savings Time settings. By default, Daylight Savings Time is set to ‘Disabled’. Daylight Savings Time can be changed to ‘Pre-2007’ or ‘Post-2007’.
Contractor Access Codes
An access to the controller can be restricted with the help of Access Codes.
Field Service Pin and Installer Service Pin can be set. These codes should be enabled to restrict an access to the controller.
Note:
A user can set only numerical PIN code for ‘Field Service Pin’ and ‘Installer Service Pin’. PIN codes should be set within 0000 – 9999. The following Error Window pops up if this field is left blank after selecting.
70 31-00121—02
Schedule Options
‘Schedule’ tab displays Schedule options. The following parameters are used to configure the
schedule options (i.e. Occupancy Configuration and Bypass and Standby)
BACnet FF Controller
Figure 65: Schedule Options Screen (Two Pipe Fan Coil Unit)
Occupancy Configuration
Schedule Model: A user can set the device’s schedule
model as;
1. Setpoint Mode or
2. Occupancy Mode
Setpoint Mode: In setpoint mode, the controller logically emulates residential thermostats. The space temperature is controlled to "SP Mode Cooling SP" and "SP Mode Heating SP". Each schedule period consists of a start time, a heating setpoint, and a cooling setpoint.
Occupancy Mode: By default, ‘Schedule Model’ is in ‘Occupancy Mode’. The system will be switched to ‘Occupied Mode’ when the occupancy sensor detects occupancy. Occupied Mode allows a user to configure ‘Comm Fails Occupied’, ‘System Block’ & ‘Internal Schedule’ settings.
If a user selects ‘Setpoint Mode’ from the available ‘Schedule Model’, the fields for ‘Comm Fails Occupied’ and ‘System Block’ settings become disabled.
31-00121—02 71
BACnet FF Controller
Comm Fails Occupied: It allows a user to switch the system in Occupied Mode in case of MS/TP communication failure. If the MS/TP communication fails, the system enters into Occupied Mode when this option is selected as ‘Enable’, otherwise the system remains in its current state when this option is selected as ‘Disable’.
System Block: The System Block is hidden when the schedule model is in ‘Setpoint Mode’. When the schedule model is in ‘Occupancy Mode’, it allows a user to switch between the available options. Selecting “Show Unoccupied/Off” places the controller in unoccupied state.
Internal schedule: It can be configured in both Occupancy Mode & Setpoint Mode. By default, ‘Internal Schedule’ is ‘Disable’.
If the internal schedule is ‘Disable’, a user can adjust the setpoint (within setpoint limits).
Display Settings
When a user selects, ‘Two Periods’ or ‘Four Periods’ options an additional ‘Display Settings’ appears as follows:
Bypass and Standby
Bypass Time: In the Unoccupied state, it forces the
controller into the occupied state for up to 4 hours (default value). The override time limit is adjustable from a minimum of 0.2 hours to a maximum of 9.5 hours.
Standby Delay: In Occupied Mode, if any window or door is opened and closed with no motion detected after the time mentioned for the Standby Delay, the room status switches to Standby state. The default value is 180 seconds.
Schedule Access: When a user selects ‘Edit’, it allows a user to view and edit the schedule and when a user selects ‘View’, it allows a user to view the schedule. When a user selects ‘None’, it will not allow a user to view or edit the schedule.
Vacation Hold: It allows/denies a user to override the scheduled setpoint from TB3026B display to “Vacation Hold”.
Permanent Hold: It allows/denies a user to override the scheduled setpoint from TB3026B display to “Permanent Hold”.
72 31-00121—02
BACnet FF Controller
Zone Setpoints
Zone Setpoints , allows a user to set the following parameters as per the requirement:
1. Temperature Setpoints
2. Setpoint Limits
3. Standby Settings
4. Display Options
Figure 66: Zone Setpoints Screen (Occupancy Mode)
Temperature Setpoints
Occupied Setpoint: It is a setpoint in Occupied Mode.
Enter the value within the range of 45 ºF to 99 ºF. The default value is 70ºF.
31-00121—02 73
Cooling Offset: In the Occupied state, the cooling setpoint is calculated as cooling offset plus occupied setpoint. Enter the value within the range of 0ΔºF to 12.1ΔºF. The default value is 2 ΔºF.
Heating Offset: In the Occupied state, the heating setpoint is calculated as heating offset minus occupied setpoint. Enter the value within the range of 0ΔºF to 12.1ΔºF. The default value is 1 ΔºF.
Unoccupied Heating Setpoint: It is a setpoint for Heating in Unoccupied mode. Enter the value within the range of 45 ºF to 99 ºF. The default value is 55 ºF.
Unoccupied Cooling Setpoint: It is a setpoint for Cooling in Unoccupied mode. Enter the value within the range of 45 ºF to 99 ºF. The default value is 85 ºF.
BACnet FF Controller
Setpoint Limits
Setpoint High Limit: A user can enter a Setpoint High
Limit in Occupied Mode within the range of 45 ºF to 99 ºF. The default value is 78ºF.
Setpoint Low Limit: A user can enter a Setpoint Low Limit in Occupied Mode within the range of 45 ºF to 99 ºF. The default value is 62ºF.
Note:
1. Unoccupied Cooling Setpoint should always be set GREATER than Unoccupied Heating Setpoint.
Following Error window appears if Unoccupied Cooling Setpoint is set lower than Unoccupied Heating Setpoint.
2. Setpoint High Limit should always be set GREATER than Setpoint Low Limit.
Following Error window appears if Setpoint High Limit is set lower than Setpoint low Limit.
Standby Settings
Standby state is a power-saving function of Occupancy mode. It occurs when the space is scheduled as Occupied, but sensors detect (When the Standby input is active) there are no humans in the space.
Standby Offset: In this case, the Standby Offset relaxes the occupied setpoints. The value of the Standby Offset [SO] can be set between a minimum of 0 ΔºF and a maximum of 12.1 ΔºF degrees. The default value is 4 ΔºF.
Reverse Standby Input: It allows a user to configure two types of inputs, ‘Normally Open (NO)’ and ‘Normally Close (NC)’.
74 31-00121—02
BACnet FF Controller
Display Options
Unoccupied Setpoints: It allows a user to either ‘Hide’ or
‘Show’ the unoccupied setpoint.
When a user selects Schedule Model under the ‘Schedule Options’ tab to ‘Setpoint Mode’, the ‘Zone Setpoints’ configuration window appears as follows:
Figure 67: Zone Setpoint Screen (Setpoint Mode)
31-00121—02 75
BACnet FF Controller
Control Settings
‘Control Settings’ allows a user to configure following settings:
1. Cooling PI Control
2. Heating PI Control
3. Aux Staged Heating
4. Two-Position Valves
5. FCU Configuration
Figure 68: Control Settings Screen (Two Pipe Fan Coil Unit)
Cooling PI Control
Proportional Constant K
within the range of 10 to 40. The default value is 20.
Integral Constant K
: A user can enter a value for Kp
p
: A user can enter a value for Ki
i
within the range of 0.50 to 2. The default value is 1.
OAT Lockout Setpoint: Cooling PI control will lockout
76 31-00121—02
when outside Temperature decreases below OAT (Cooling) Lockout Setpoint. The default value is 55 ºF.
BACnet FF Controller
Heating PI Control
Proportional Constant K
: A user can enter a value for Kp
p
within the range of 10 to 40. The default value is 20.
Integral Constant K
: A user can enter a value for Ki
i
within the range of 0.50 to 2. The default value is 1.
OAT Lockout Setpoint: Heating PI control will lockout when outside Temperature increases above OAT (Heating) Lockout Setpoint. The default value is 62 ºF.
Aux Staged Heating
A user can configure the Cycle Time & Minimum On/Off Time when a ’Single Stage Auxiliary Heat’ is selected in the application.
Cycle Time: The Cycle Time ranges from minimum of 8 minutes, and a maximum of 30 minutes. The default value is 15 minutes.
Minimum On/Off Time: It is a minimum On/Off time for the Auxiliary Heating. The default value is 3 minutes.
Two-Position Valves
Cycle Time: Two-Position Valve cycle time ranges from
minimum of 3 minutes, and a maximum of 30 minutes. The default value is 15 minutes.
Minimum On Time: It is a minimum time for the compressor to stay On.
Minimum Off Time
: It is a minimum time for the
compressor to stay Off.
Heating/Cooling Valve Control: Physical heating/cooling valve control has three options
On Off: This option selects the opening and closing of heating valve.
Analog To Binary: In this mode the valve is remains open for Cycle Time.
Thermal valve: This option allows a user to select a Thermal valve for Heating/Cooling Valve Control.
FCU Configuration
A user can configure the Water Temperature when ‘Floating/Analog’ valve actuator is selected in the application.
31-00121—02 77
Water Temperature: The water temperature can be monitored either by local or by remote entity (default inactive, ‘Local Mode’).
BACnet FF Controller
When ‘Fan Speeds’ is selected as ‘Three Speed Fan’, the ‘Control Settings’ view changes as follows:
When ‘Auxiliary Heat’ is selected as ‘No Stage Aux heat’, the ‘Control Settings’ view changes as follows:
78 31-00121—02
BACnet FF Controller
When ‘Valve Actuator’ is selected as ‘Two-Position’, the ‘Control Settings’ view changes as follows:
31-00121—02 79
BACnet FF Controller
Fan / Humidity
‘Fan / Humidity’ allows a user to configure the following settings:
1. Fan Operation
2. Humidity Control
3. Filter Alarm
Figure 69: Fan/Humidity Screen (Two Pipe Fan Coil Unit)
Fan Operation
Fan Mode Control: During occupancy & Setpoint mode, the fan operates based on the selected fan control modes.
Auto: When this option is selected, Fan cycles ON when:
1. Cooling or heating is selected or
2. During Unoccupied mode only when called to run by cooling or heating demand.
On: When this option is selected the fan runs continuously for ventilation.
80 31-00121—02
BACnet FF Controller
When a user selects ‘Three Speed Fan’ in the application, the ‘Fan Operation’ parameter appears as follows:
Auto: When this option is selected, Fan cycles ON when:
1. Cooling or heating is selected or
2. During Unoccupied mode only when called to run by cooling or heating demand.
On: When this option is selected the fan runs continuously for ventilation.
On Cool/Auto Heat: When this option is selected the fan runs continuously in cooling mode. In heating mode the fan cycles on only when the heating signal calls for the fan to run.
Local User Fan Control: This selection allows a user to enable/disable the fan Control to local user.
Low Speed Heat/Cool Demand: This field allows a user to set the Heating/Cooling demand limits for the Low Speed Fan.
Medium Speed Heat/Cool Demand: This field allows a user to set the Heating/Cooling demand limits for the Medium Speed Fan.
High Speed Heat/Cool Demand: This field allows a user to set the Heating/Cooling demand limits for the High Speed Fan.
Humidity Control
Fan Circulation Cycle: When a user selects the ‘Enable’
option from Fan Circulation Cycle, it allows a user to edit the Trigger Setpoint, Reset Deadband, and Fan On/Off Cycle Time.
Trigger Setpoint & Reset Deadband: When sensed humidity equals or exceeds humidity trigger setpoint, the fan cycles ON/OFF at low speed until sensed humidity drops below the trigger setpoint minus the reset deadband.
Fan On Cycle Time: This field allows a user to enter a time for fan ON cycle when stratification and humidity control is active. The default value is 300 seconds.
Fan Off Cycle Time: This field allows a user to enter a time for fan OFF cycle when stratification and humidity control is active. The default value is 1800 seconds.
Filter Alarm
31-00121—02 81
Runtime Hours: A filter alarm activates after the Runtime Hours mentioned in this field. The default value is 3000 hours.
BACnet FF Controller
I/O Configurations
Select I/O Configurations from Configuration parameters. This configuration is used for Terminal Assignment & Output Configuration.
Figure 70: I/O Configurations Screen (Two Pipe Fan Coil Unit)
Terminal Assignment
After completing the ‘Two Pipe Fan Coil Unit’ configuration, selected inputs and outputs get automatically assigned to the TB3026B controller’s input and output terminals. A user can assign the outputs as ‘Heating/Cooling Valve Close’ & ‘Heating/Cooling Valve Open’ to BO-4 & BO-3 respectively.
Figure 71: Terminal Assignment View (Single Speed Fan)
82 31-00121—02
BACnet FF Controller
Output Configuration
H/C Valve Stroke Time: This setting is available to
configure, when ‘Floating/ Analog’ ‘Valve Actuator is selected.
When ‘Three Speed Fan’ is configured with ‘Single Stage Aux Heat’, the ‘Terminal Assignment’ view changes as follows:
When ‘No Stage Aux Heat’ is configured with ‘Floating/Analog’ valve actuator, ‘Three Speed Fan’ and ‘Door Switch’, the ‘Terminal Assignment’ view changes as follows:
31-00121—02 83
BACnet FF Controller
When ‘No Stage Aux Heat’ is configured with ‘Two-Position’ valve actuator, ‘Three Speed Fan’ and ‘Water Temperature Sensor’, the ‘Terminal Assignment’ view changes as follows:
When ‘Input Configuration is selected as ‘Remote Space Temp Sensor’ with ‘No Stage Aux Heat’, ‘Floating/Analog’ valve actuator and ‘Three Speed Fan’, the ‘Terminal Assignment’ view changes as follows:
84 31-00121—02
BACnet FF Controller
Four Pipe Fan Coil Unit
Figure 72: Four Pipe Fan Coil Unit window
Fan Speeds
A user can select Two types of ‘Fan Speeds’ when the output stage is configured as ‘One Compressor Stage and One Aux Heat Stage’.
1. Single Speed Fan
2. Three Speed Fan
31-00121—02 85
Auxiliary Heat
A user can select heating stages from the following options:
BACnet FF Controller
Valve Actuator
Valve actuator can be configured as ‘Two-Position’ or ‘Floating’, or ‘Analog’ based on application.
Note:
The valve actuator can be selected as ‘Two-Position’ or ‘Analog’ only when ‘Three Speed Fan’ is configured. Floating valve actuator can be configured only when Single Speed Fan is configured.
Input Configuration
Input Configuration can be configured as ‘Motion Sensor’ or ‘Remote Space Temp Sensor’ based on application.
Economizer Output
Out of the two types of parameters, select ‘Analog Output’ if Floating valve actuator ’is used. Select ‘Floating Output’ when analog valve actuator is used.
Note:
Analog Type Economizer Output can be configured when Single Speed Fan is configured’.
Floating Type Economizer Output can only be configured if Three Speed Fan is configured’.
86 31-00121—02
BACnet FF Controller
General Display
Click ‘General Display’ to view the general display settings. The following parameters are used to configure the controller’s display settings.
1. Engineering Units
2. Time Functions
3. Display
4. Contractor Access Codes
Figure 73: General Display Screen (Four Pipe Fan Coil Unit)
Engineering Units
Application Unit: The application units contain two
options to change the controller’s units. By default, the controller’s application units are set to ‘English’. Application Unit can be changed to ‘English’ or ‘Metric’.
31-00121—02 87
BACnet FF Controller
Time Function
Clock Format: A user can select a clock format as
12-hour format or 24-hour format.
Display
This feature allows a user to select the Display settings.
Outside Air Temp: A user has an option to hide/show an outside air temperature.
Clock Adjustment: This option allows a user to enable/disable the clock adjustment on the controller display.
Keypad Lockout: This option allows a user to lock/unlock the clock adjustment.
When an option, ‘Temperature Settings Only’ is selected, a user can only set the temperature through keypad.
Backlight: A user can keep the backlight always on or set to delayed off through this option.
Daylight Savings Time: This feature enables to select the Daylight Savings Time settings. By default, Daylight Savings Time is set to ‘Disabled’. Daylight Savings Time can be changed to ‘Pre-2007’ or ‘Post-2007’.
Contractor Access Codes
An access to the controller can be restricted with the help of Access Codes.
Field Service Pin and Installer Service Pin can be set. These codes should be enabled to restrict an access to the controller.
Note:
A user can set only numerical PIN code for ‘Field Service Pin’ and ‘Installer Service Pin’. PIN codes should be set within 0000 – 9999. The following Error Window pops up if this field is left blank after selecting.
88 31-00121—02
Schedule Options
‘Schedule’ tab displays Schedule options. The following parameters are used to configure the
schedule options (i.e. Occupancy Configuration and Bypass and Standby)
BACnet FF Controller
Figure 74: Schedule Options Screen (Four Pipe Fan Coil Unit)
Occupancy Configuration
Schedule Model: A user can set the device’s schedule
model as;
1. Setpoint Mode or
2. Occupancy Mode
Setpoint Mode: In setpoint mode, the controller logically emulates residential thermostats. The space temperature is controlled to "SP Mode Cooling SP" and "SP Mode Heating SP". Each schedule period consists of a start time, a heating setpoint, and a cooling setpoint.
Occupancy Mode: By default, ‘Schedule Model’ is in ‘Occupancy Mode’. The system will be switched to ‘Occupied Mode’ when the occupancy sensor detects occupancy. Occupied Mode allows a user to configure ‘Comm Fails Occupied’, ‘System Block’ & ‘Internal Schedule’ settings.
If a user selects ‘Setpoint Mode’ from the available ‘Schedule Model’, the fields for ‘Comm Fails Occupied’ and ‘System Block’ settings become disabled.
31-00121—02 89
BACnet FF Controller
Comm Fails Occupied: It allows a user to switch the system in Occupied Mode in case of MS/TP communication failure. If the MS/TP communication fails, the system enters into Occupied Mode when this option is selected as ‘Enable’, otherwise the system remains in its current state when this option is selected as ‘Disable’.
Note:
When Application 8 or 9 is selected, the ‘Comm Fails Occupied’ will be selected as ‘Enable’ by default and does not allow user to edit this field.
Vacation Hold: It allows/denies a user to override the scheduled setpoint from TB3026B display to “Vacation Hold”.
Permanent Hold: It allows/denies a user to override the scheduled setpoint from TB3026B display to “Permanent Hold”.
Bypass and Standby
System Block: The System Block is hidden when the
schedule model is in ‘Setpoint Mode’. When the schedule model is in ‘Occupancy Mode’, it allows a user to switch between the available options. Selecting “Show Unoccupied/Off” places the controller in unoccupied state.
Internal schedule: It can be configured in both Occupancy Mode & Setpoint Mode. By default, ‘Internal Schedule’ is ‘Disable’.
If the internal schedule is ‘Disable’, a user can adjust the setpoint (within setpoint limits).
Display Settings
When a user selects, ‘Two Periods’ or ‘Four Periods’ options an additional ‘Display Settings’ appears as follows:
Schedule Access: When a user selects ‘Edit’, it allows a user to view and edit the schedule and when a user selects ‘View’, it allows a user to view the schedule. When a user selects ‘None’, it will not allow a user to view or edit the schedule.
Bypass Time: In the Unoccupied state, it forces the controller into the occupied state for up to 4 hours (default value). The override time limit is adjustable from a minimum of 0.2 hours to a maximum of 9.5 hours.
Standby Delay: In Occupied Mode, if any window or door is opened and closed with no motion detected after the time mentioned for the Standby Delay, the room status switches to Standby state. The default value is 180 seconds.
90 31-00121—02
BACnet FF Controller
Zone Setpoints
Zone Setpoints , allows a user to set the following parameters as per the requirement:
1. Temperature Setpoints
2. Setpoint Limits
3. Standby Settings
4. Display Options
Figure 75: Zone Setpoints Screen (Occupancy Mode)
Temperature Setpoints
Occupied Setpoint: It is a setpoint in Occupied Mode.
Enter the value within the range of 45 ºF to 99 ºF. The default value is 70ºF.
Cooling Offset: In the Occupied state, the cooling setpoint is calculated as cooling offset plus occupied setpoint. Enter
31-00121—02 91
the value within the range of 0ΔºF to 12.1ΔºF. The default value is 2 ΔºF.
Heating Offset: In the Occupied state, the heating setpoint is calculated as heating offset minus occupied setpoint. Enter the value within the range of 0ΔºF to 12.1ΔºF. The default value is 1 ΔºF.
Unoccupied Heating Setpoint: It is a setpoint for Heating in Unoccupied mode. Enter the value within the range of 45 ºF to 99 ºF. The default value is 55 ºF.
Unoccupied Cooling Setpoint: It is a setpoint for Cooling in Unoccupied mode. Enter the value within the range of 45 ºF to 99 ºF. The default value is 85 ºF.
BACnet FF Controller
Setpoint Limits
Setpoint High Limit: A user can enter a Setpoint High
Limit in Occupied Mode within the range of 45 ºF to 99 ºF. The default value is 78ºF.
Setpoint Low Limit: A user can enter a Setpoint Low Limit in Occupied Mode within the range of 45 ºF to 99 ºF. The default value is 62ºF.
Note:
1. Unoccupied Cooling Setpoint should always be set GREATER than Unoccupied Heating Setpoint.
Following Error window appears if Unoccupied Cooling Setpoint is set lower than Unoccupied Heating Setpoint.
2. Setpoint High Limit should always be set GREATER than Setpoint Low Limit.
Following Error window appears if Setpoint High Limit is set lower than Setpoint low Limit.
Standby Settings
Standby state is a power-saving function of Occupancy mode. It occurs when the space is scheduled as Occupied, but sensors detect (When the Standby input is active) there are no humans in the space.
Standby Offset: In this case, the Standby Offset relaxes the occupied setpoints. The value of the Standby Offset [SO] can be set between a minimum of 0ΔºF and a maximum of 12.1ΔºF degrees. The default value is 4 ΔºF.
Reverse Standby Input: It allows a user to configure two types of inputs, ‘Normally Open (NO)’ and ‘Normally Close (NC)’.
92 31-00121—02
BACnet FF Controller
Display Options
Unoccupied Setpoints: It allows a user to either ‘Hide’ or
‘Show’ the unoccupied setpoint.
When a user selects Schedule Model under the ‘Schedule Options’ tab to ‘Setpoint Mode’, the ‘Zone Setpoints’ configuration window appears as follows:
Figure 76: Zone Setpoint Wizard Screen (Setpoint Mode)
31-00121—02 93
BACnet FF Controller
Control Settings
‘Control Settings’ allows a user to configure following settings:
1. Cooling PI Control
2. Heating PI Control
3. Two-Position Valves
Figure 77: Control Settings Screen (Four Pipe Fan Coil Unit)
Cooling PI Control
Proportional Constant K
within the range of 10 to 40. The default value is 20.
Integral Constant K
within the range of 0.50 to 2. The default value is 1.
OAT Lockout Setpoint: Cooling PI control will lockout when outside Temperature decreases below OAT (Cooling) Lockout Setpoint. The default value is 55 ºF.
: A user can enter a value for Kp
p
: A user can enter a value for Ki
i
Heating PI Control
Proportional Constant K
: A user can enter a value for Kp
p
within the range of 10 to 40. The default value is 20.
Integral Constant K
: A user can enter a value for Ki
i
within the range of 0.50 to 2. The default value is 1.
OAT Lockout Setpoint: Heating PI control will lockout when outside Temperature increases above OAT (Heating) Lockout Setpoint. The default value is 62 ºF.
94 31-00121—02
BACnet FF Controller
Two-Position Valves
Cycle Time: Two-Position Valve cycle time ranges from
minimum of 3 minutes, and a maximum of 30 minutes. The default value is 15 minutes.
Minimum On Time: It is a minimum time for the compressor to stay On.
Minimum Off Time: It is a minimum time for the compressor to stay Off.
Heating/Cooling Valve Control: Physical heating/cooling valve control has three options
On Off: This option selects the opening and closing of Heating valve.
Analog To Binary: In this mode the valve is remains open for Cycle Time.
Thermal valve: This option allows a user to select a Thermal valve for Heating/Cooling Valve Control.
When ‘Auxiliary heat’ is configured as ‘Single Stage Aux Heat’, the ‘Control Settings’ view changes as follows:
31-00121—02 95
BACnet FF Controller
Aux Staged Heating
A user can configure the Cycle Time & Minimum On/Off Time when a ’Single Stage Auxiliary Heat’ is selected in the application.
Cycle Time: The Cycle Time ranges from minimum of 8 minutes, and a maximum of 30 minutes. The default value is 15 minutes.
Minimum On/Off Time: It is a minimum On/Off time for the Auxiliary Heating. The default value is 3 minutes.
When ‘Analog/Floating’ valve actuator is configured, the ‘Control Settings’ view changes as follows:
96 31-00121—02
BACnet FF Controller
Fan / Humidity
‘Fan / Humidity’ allows a user to configure the following settings:
1. Fan Operation
2. Humidity Control
3. Filter Alarm
Figure 78: Fan/Humidity Screen (Four Pipe Fan Coil Unit)
31-00121—02 97
BACnet FF Controller
Fan Operation
Fan Mode Control: During occupancy & Setpoint mode,
the fan operates based on the selected fan control modes.
Auto: When this option is selected, Fan cycles ON when:
1. Cooling or heating is selected or
2. During Unoccupied mode only when called to run by cooling or heating demand.
On: When this option is selected the fan runs continuously for ventilation.
On Cool/Auto Heat: When this option is selected the fan runs continuously in cooling mode. In heating mode the fan cycles on only when the heating signal calls for the fan to run.
Fan OFF Selection: This selection allows a user to enable/disable the selection to OFF the fan on the LCD of the controller.
Local User Fan Control: This selection allows a user to enable/disable the fan Control to local user.
Low Speed Heat/Cool Demand: This field allows a user to set the Heating/Cooling demand limits for the Low Speed Fan.
Medium Speed Heat/Cool Demand: This field allows a user to set the Heating/Cooling demand limits for the Medium Speed Fan.
High Speed Heat/Cool Demand: This field allows a user to set the Heating/Cooling demand limits for the High Speed Fan.
When a user selects ‘Single Speed Fan’ in the application, the ‘Fan Operation’ parameter appears as follows:
Auto: When this option is selected, Fan cycles ON when:
1. Cooling or heating is selected or
2. During Unoccupied mode only when called to run by cooling or heating demand.
On: When this option is selected the fan runs continuously for ventilation.
On Cool/Auto Heat: When this option is selected the fan runs continuously in cooling mode. In heating mode the fan cycles on only when the heating signal calls for the fan to run.
98 31-00121—02
Loading...