Honeywell TAZ-4 Installation Guide

TotalZone® Add-A-Zone™(TAZ-4)
Zone Control Panel
INSTALLATION INSTRUCTIONS

APPLICATION

The TAZ-4 is a zone panel used to add zones to the TZ-4. See Fig. 1. The TZ-4 provides up to four zones. Each TAZ-4 can add up to four additional zones for a total of 32 zones. The TAZ-4 is also compatible with the TZ-3, Rev 4.2.2, zone control panel and with the TAZ-1, TAZ-2 and TAZ-3, Rev 4, Add-A-Zone panels.
AZ1 AZ2
TotalZone Panel
DIP-SWITCHES
O N
54321
TotalZone
Add-A-Zone Panel
AZ1 AZ2
AZ1 AZ2
TO NEXT ADD-A-ZONE PANEL
3. Installer must be a trained, experienced service techni­cian.
4. After installation is complete, check out product opera­tion as provided in these instructions.
5. Follow local codes for installation and application.
CAUTION
Voltage Hazard. Can cause electrical shock or equipment damage.
Disconnect power before beginning installation.

Location

Select a location for the TAZ-4 as close as possible to the Total Zone panel.

Mounting

Mount the TotalZone Add-A-Zone Panel as close as possible to the TotalZone Panel. See Fig. 1.

WIRING

CAUTION
Electrical Interference Hazard. Running cable near line voltage can interfere with panel operation.
Run cable connecting AZ terminals at least 12 in. from line voltage wiring.
M20362
Fig. 1. TAZ-4 Zone Control Panel.

INSTALLATION

When Installing this Product . . .

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condi­tion.
2. Check the rating given in the instructions and on the product to make sure the product is suitable for your application.
® U.S. Registered Trademark Copyright © 2002 Honeywell • All Rights Reserved
IMPORTANT
Be sure AZ1 and AZ2 wires do not cross and are a minimum of 12 in. from any line voltage wiring. If not possible, use shielded cable for AZ1 and AZ2 wires.
NOTE: Only two wires are required to connect the TAZ-4
panels to the main TZ-4 panel. Each TAZ-4 is wired in a daisy chain or parallel to each other, connecting the AZ1 and AZ2 terminals between panels.
Connect the AZ1 and AZ2 terminals on both panels using standard 18-gauge thermostat wire:
1. Connect AZ1 on the TotalZone panel to AZ1 on the Add-A-Zone panel.
2. Connect AZ2 on the TotalZone panel to AZ2 on the Add­A-Zone panel.
69-1366-2
TOTALZONE® ADD-A-ZONE™(TAZ-4) ZONE CONTROL PANEL
3. Connect a 24V, 40 VA transformer to terminals R and C. R is Hot and C is 24 Vac (Common). See Fig. 2.
4. If there are five to ten ARD or ZD dampers connected to the TAZ-4, wire an additional 40 VA transformer to T1 and T2. See Fig. 2.
5. Connect damper and thermostat wiring as shown in Fig. 2.
Table 1. DIP Switch Settings.
Zones
5-8 001 01
6-9 001 10
7-10 0 0 1 1 1
8-11 0 1 0 0 0
9-12 0 1 0 0 1
Switch 1 Switch 2 Switch 3 Switch 4 Switch 5

SETUP

Each TAZ-4 panel has a set of five DIP switches. When using a TZ-4 and one TAZ-4, set DIP switches 1, 2, and 4 to off and switches 3 and 5 to on. Refer to Table 1 for other panel configurations. Identify the zones that are controlled by the TAZ-4 panel and set the DIP switches accordingly.
If the TAZ-4 is connected to a TZ-3 zone control panel, set DIP switches 1, 2, and 4 to off, and switches 3 and 5 to on. Set the switches on additional TAZ-1, TAZ-2, and TAZ-3, or TAZ-4 panels to control the zones they are wired to; but be careful that there is no duplication of zone numbers. See Table 1.
Switch Positions
10-13 010 10
11-14 01011
12-15 011 00
13-16 011 01
14-17 011 10
15-18 011 11
16-19 100 00
17-20 100 01
18-21 100 10
19-22 100 11
20-23 101 00
21-24 101 01
22-25 101 10
23-26 101 11
24-27 110 00
25-28 110 01
26-29 110 10
27-30 110 11
28-31 111 00
29-32 111 01
69-1366-2 2
Loading...
+ 2 hidden pages