Honeywell T8524C User Manual

Page 1
T8524C,D Multistage
Microelectronic Thermostats
INSTALLATION INSTRUCTIONS
APPLICATION
The T8524C, D Multistage Microelectronic Thermostat provides electronic control of 24 Vac two-stage heating and two­stage cooling systems. Refer to Table 1 for a general description of the thermostat. All T8524 Thermostats require a common wire to supply power.
Table 1. Description of T8524 Thermostats.
T8524 System Changeover
C Heat-Cool Manual Heat-Off-Cool On-Auto System and fan selections are done by
D Heat-Cool Automatic Heat-Off-Cool-Auto On-Auto System and fan selections are done by
System
Selection
Fan
Selection Comments
switches.
keyboard.
RECYCLING NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do control in the trash.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat.
not
place your old
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check out the product operation.
CAUTION
Disconnect power supply to prevent electrical shock or equipment damage.
Location
Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1.
Do not install the thermostat where it can be affected by: — drafts, or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.
Wallplate Installation
The thermostat can be mounted horizontally on the wall or on a 2 in. x 4 in. wiring box. Position wallplate horizontally on the wall or on a 2 in. x 4 in. wiring box.
1. Position and level the wallplate (for appearance
only). The thermostat will function properly even when not level.
®U.S. Registered Trademark Copyright © 1997 Honeywell Inc. • • All Rights Reserved
X-XX UL
69-1055-1
Page 2
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
WALL ANCHORS (2)
NO
WIRES THROUGH WALL
YES
NO
5 FEET
[1.5 METERS]
Fig. 1. Typical location of thermostat.
WALL
4. Position the wallplate over the holes, pulling wires
through the wiring opening.
5. Loosely insert the mounting screws into the holes.
6. Tighten mounting screws.
WIRING
All wiring must comply with local electrical codes and ordinances. Refer to Fig. 3 for typical hookups. A letter code is located near each terminal for identification.
NO
M10106
MOUNTING HOLES
MOUNTING SCREWS
Fig. 2. Mounting the wallplate.
2. Use a pencil to mark the mounting holes. See Fig. 2.
3. Remove the wallplate from the wall and drill two
3/16 inch holes in the wall (if drywall) as marked. For firmer material such as plaster or wood, drill two 7/32 inch holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
69-1055—1
M6530
CAUTION
Disconnect power before wiring to prevent electrical shock or equipment damage.
1. Loosen the terminal screws on the wallplate and
connect the system wires. See Fig. 4.
IMPORTANT
Use 18 gauge, color-coded thermostat cable for proper wiring.
2. Securely tighten each terminal screw.
3. Push excess wire back into the hole.
4. Plug the hole with nonflammable insulation to
prevent drafts from affecting the thermostat.
2
Page 3
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
THERMOSTAT
Y1 G C
RC
2
COMPRESSOR CONTACTOR 1
L1 (HOT)
L2
1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
JUMPER RC TERMINAL TO R TERMINAL WHEN INSTALLED ON A ONE TRANSFORMER SYSTEM.
CAN BE USED FOR CHANGEOVER VALVE ON HEAT
3
PUMP SYSTEMS.
Fig. 3. Typical hookup of T8524 in a multistage
O
Y2
FAN
COMPRESSOR
RELAY
CONTACTOR 2
COOL DAMPER
3
COOLING TRANSFORMER
heating and cooling system.
FOR WRAPAROUND INSERTION STRIP 7/16 IN. (11 MM).
W2
HEAT RELAY 2
HEAT DAMPER
3
FOR STRAIGHT INSERTION STRIP 5/16 IN. (8 MM).
HEAT RELAY 1
M4826
Fig. 4. Proper wiring technique.
Mounting Thermostat
1. Engage tabs at the top of the thermostat and
wallplate. See Fig. 5.
2. Press lower edge of case to close and latch.
Using Thermostat Keys
The thermostat keys are used to:
• set temperature,
• display present setting,
• configure Installer Setup,
• check System Test,
• display outdoor temperature (select models).
T8524D has keys to:
• set the system operation,
• set the fan operation.
See Fig. 6 for key information.
OT OTB
RW1
OUTDOOR SENSOR
1
L1 (HOT)
L2
HEATING TRANSFORMER
M11309
A.
ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE.
B.
PRESS LOWER EDGE OF CASE TO LATCH.
M6798A
Fig. 5. Mounting thermostat on wallplate.
NOTE: To remove the thermostat from the wall, first pull out
at the bottom of the thermostat; remove top last.
INCREASE TEMPERATURE SETTING
i
DECREASE TEMPERATURE SETTING
DISPLAY PRESENT SETTINGS AND SCROLL THROUGH INSTALLER SETUP MODES (INFORMATION KEY)
M6801
Fig. 6. Thermostat key locations and descriptions.
SETTINGS
System and Fan Settings
System settings control the thermostat operation as follows:
Heat: The thermostat controls the heating. Off: Both the heating and cooling are off. Cool: The thermostat controls the cooling. Auto (T8524D only): The thermostat automatically
changes between heating and cooling operation, depending on the indoor temperature.
Fan settings control the system fan as follows:
On: Fan operates continuously. Auto: Equipment controls fan.
The system default setting is Heat and the fan default setting is Auto. Use the keyboard or system and fan switches, depending on model, to change to the desired settings. See Figs. 7 and 8.
3
69-1055-1
Page 4
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
A combination of key presses are required to use the Installer Setup feature.
i
HEAT OFF COOL
ON AUTO
M10146
SYSTEM
Selection for heating or cooling equipment operation.
Heat - Heating equipment Off - No equipment Cool - Cooling equipment
HEAT OFF COOL
ON AUTO
FAN
On - Fan runs continuously Auto - Fan runs when
heating or cooling equipment operates
Fig. 7. T8524C system and fan switches location.
i
Fan
System
Press to select
Press to select
heating or cooling
heating or cooling
equipment.
equipment. Em. Ht.
-Emergency heating
On— Fan runs continuously
Heat—Heating equipment
Auto—Fan runs when Off — No equipment Cool—Cooling equipment Auto—Thermostat
automatically selects heating and cooling equipment.
CHECK LIGHT ON SELECT MODELS
1
heating or cooling equipment operates
System
Fan
1
System
Fan
M10147
Fig. 8. T8524D system and fan keys location.
NOTE: Always press the system and fan keys with your
fingertip or similar blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard.
Temperature Settings
The default setpoint for heat is 70°F (21°C) and for cool is 78°F (25.5°C). Press the increase or decrease key to change the present setting. To change between heat and cool, press the Information i key until the setting to be changed appears.
— To enter the Installer Setup mode, press and hold the
Information i key with the increase and decrease keys until the first number is displayed. All display segments appear for approximately three seconds before the number is displayed. See Fig. 9 and 10.
— To advance to the next Installer Setup number, press
the Information i key.
— To change a setting, use the increase or de-
crease key.
— To exit the Installer Setup, press and hold the
Information i key until the display returns to normal (approximately three seconds). The display scrolls the numbers backwards to get to the normal display. The Installer Setup is automatically exited if no key presses are made for five minutes.
IMPORTANT
Em Ht Temporary Setting Aux Ht
Repl Batt
Em HeatOffCool Auto Only
Fig. 9. Display of all the segments of the LCD.
Only configurable numbers are shown on the device. Example: If the thermostat does not have a system key, Installer Setup Number 12 will not be displayed. Review Table 2 factory-settings and mark any desired changes in the Actual Setting column. When Installer Setup in com­plete, review the settings to confirm that they match the system.
Remote
Room
%Humid
Wait
System Fan
Heat Cool
MODE NUMBER DISPLAY (COLUMN 2 OF TABLE 2)
Outdoor
OnAuto
M4844
FACTORY SETTING OR OTHER CHOICE DISPLAY (COLUMN 3 OR 5 OF TABLE 2)
INSTALLER SETUP
NOTE: For most applications, the thermostat factory-
settings do not need to be changed. Review the factory-settings in Table 2 and if no changes are necessary, go to the Installer System Test section.
The Installer Setup is used to customize the thermostat to specific systems. Installer Setup Numbers are listed in Table 2. The table includes all the configuration options available.
69-1055—1
Fig. 10. Display of Installer Setup mode and setting.
CAUTION
Electric heat systems must be configured to 01 in Installer Setup 02 to prevent equipment damage caused by the system running without the fan.
4
M10105
Page 5
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
Table 2. Thermostat Installer Setup Options.
Installer Setup
Select
Number
(Press i key
to change)
Factory-Setting
Display Description Display Description Setting
Not used 01 — Fan operationa02 00 Conventional applica-
tions where equipment controls fan operation in heat mode
01 Heat pump and electric heat
Not used 03 and 04 — Stage-two
heating cycle rate
05 06 6 cph used for
conventional systems
01, 03, or 09
Not used 06 thru 11 — Changeover
(T8524D only)
12 01 Manual changeover 00 Automatic changeover
Not used 13 — Degree
temperature display
14 00 Temperature is
displayed in °F
01 Temperature is displayed in
Not used 15 thru 18 — Extended fan
operation in heating
Extended fan operation in cooling
19 00 No extended fan
a,b
20 00 No extended fan
a
operation after the call for heat ends
operation after the call for cool ends
01 Fan operation is extended
01 Fan operation is extended
Not used 21 thru 23 — Outdoor
temperature display
24 00 No outdoor temperature
a
is displayed
01 Outdoor temperature is
Not used 25 thru 29 — Deadband 30 03 Heating and cooling
setpoints can be set no closer than 3°F (1.5°C)
04 thru10Heating and cooling
Not used 31 and 32 — Minimum off
time for the compressor
a
Available on select models.
b
Installer Setup Number 02 must be set to 01 to extend fan operation.
33 05 5 minute minimum off
time for the compressor
00, 01, 02, 03 or 04
Other Choices
(Press ▲ or ▼ key to change)
applications where thermostat controls fan operation in heat mode
01—1 cph used for radiant
floor heat, gravity systems
03—3 cph used for hot water
systems or high efficiency furnaces
09—9 cph used for electric
heat systems
°C
90 seconds after the call for heat ends
90 seconds after the call for cool ends
displayed. Needs a C7089B1000 Outdoor Sensor to operate.
setpoints can be set no closer than the chosen value:
04—4°F (2°C) 05—5°F (2.5°C) 06—6°F (3°C) 07—7°F (3.5°C) 08—8°F (4°C) 09—9°F (4.5°C) 10—10°F (5°C)
Minimum number of minutes (0 thru 5) the compressor will be off between calls for the compressor
Actual
(Continued)
5
69-1055-1
Page 6
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
Table 2. Thermostat Installer Setup Options (continued).
Installer Setup
Select
Heating setpoint range
a
stop Cooling
setpoint range
a
stop
Number
(Press i key
to change)
34 90 Heating setpoint can be
35 45
Factory-Setting
Display Description Display Description Setting
set no higher than 90°F
b
Cooling setpoint can be set no lower than 45°F
40 thru90Number can be set
45b thru99Number can be set
b
Not used 36 — Temperature
display adjustment
a
Available on select models.
b
T8524D is 48°F (9°C).
IMPORTANT
37 00 No difference in
Review the settings to confirm that they match the system.
displayed temperature and actual room temperature
-3 thru 3
Other Choices
(Press ▲ or ▼ key to change)
anywhere between 40 and 90 in 1°F increments
anywhere between 45 99 in 1°F increments
1—Display adjusts to 1°F
higher than actual room temperature
2—Display adjusts to 2°F
higher than actual room temperature
3—Display adjusts to 3°F
higher than actual room temperature
-1—Display adjusts to 1°F lower than actual room temperature
-2—Display adjusts to 2°F lower than actual room temperature
-3—Display adjusts to 3°F lower than actual room temperature
b
and
Actual
INSTALLER SYSTEM TEST
Use the Installer System Test to check the thermostat configurations and operation. Refer to Table 3 for a list of the available system tests.
To start the system test::
NOTE: The minimum off time for compressors is
bypassed during the Installer System Test.
Press and hold the increase and decrease keys, at the same time, until two zeros appear. All segments of the LCD are displayed before the two zeros appear.
Em Ht Temporary Setting Aux Ht
Repl
Wait
Batt
System Fan
Em HeatOffCool Auto Only
69-1055—1
Heat Cool
Remote
Room
%Humid
Outdoor
OnAuto
M4844
TEST MODE NUMBER
IMPORTANT
T8524C models must set the switches to the equipment that is being checked for the equip­ment to operate.
NOTE: Press and hold the increase and decrease
keys for three seconds to exit the System Test. The System Test times out after five minutes without any key presses.
M6792
Table 3. Tests Available In The Installer System Test.
Test
Number System Test Description
10-19 Heating equipment can be turned on and off 30-39 Cooling equipment can be turned on and off 40-49 Fan equipment (T8524D only) can be turned
on and off. 60-69 System key or system switch position test 70-79 Thermostat information including date code
and software versions are displayed
6
Page 7
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
Table 4. Installer System Test Options.
Key to
Press
Heating Equipment System test
11 Stage-one heat comes on. The system fan is also energized. ▲ 12 Stage-two heat comes on. Stage-one heat and system fan remain on. ▼ 11 Stage-two heat turns off. ▼ 10 Stage-one heat and system fan turn off.
Cooling Equipment System test
31 Stage-one cool and system fan come on. ▲ 32 Stage-two cool comes on. Stage-one cool and system fan remain on. ▼ 31 Stage-two cool turns off. ▼ 30 Stage-one cool and system fan turn off.
Fan Equipment System test (T8524D only)
41 Fan comes on. ▼ 40 Fan turns off.
Key or Switch Operation System test IMPORTANT
SYSTEM KEY OR SWITCH SYSTEM TEST (Move switch to see Test Numbers on T8524C.)
System 61 Heat Test Number is displayed. (Set system switch to HEAT on T8524C.) System 62 Off Test Number is displayed. (Set system switch to OFF on T8524C.) System 63 Cool Test Number is displayed. (Set system switch to COOL on T8524C.) System 64 Auto Test Number is displayed.
FAN KEY SYSTEM TEST (T8524D only)
Fan 68 Fan on Test Number is displayed. Fan 69 Fan off Test Number is displayed.
a
System fan is energized only if set for electric heat.
Thermostat Information
1. Press the Information i key to access the
Test
Number Description
i
i
i
i
thermostat information.
10 Enter heating equipment system test. (Set system switch to HEAT on T8524C.)
a
30 Enter cooling equipment system test. (Set system switch to COOL on T8524C.)
40 Change from cooling to fan equipment system test.
Test Numbers will only be displayed when the system is configured for the selected function. EXAMPLE: Numbers 60, 61 and 62 are the only numbers that will be displayed when a system is configured for heat only.
60 Change from cooling or fan to key operation system test.
2. Press the increase ▲ key to display the production
date code. The first two large digits are the month and the third digit is the last digit of the year. (Example: 026 = February 1996)
M4864
M4865
7
69-1055-1
Page 8
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
3. Press the increase ▲ key again to display the
software identification code. (Example: 02 = software ID code 2)
M4866
4. Press the increase ▲ key again to display the
software revision number. (Example: 001 = revision number 1)
5. Press the increase ▲ key again to display the
EEPROM identification code. (Example: 222 = EEPROM ID 222)
6. Press and hold the increase ▲ and decrease
keys together, until the room temperature is displayed, to exit the System Test. The System Test times out after five minutes without any key presses.
CHECKOUT
Outdoor Temperature Sensor (Where Applicable)
Allow the outdoor temperature sensor to soak in the
M6791
outdoor air for a minimum of five minutes before taking a reading. With an accurate thermometer (±1°F [±0.5°C]), measure the temperature at the sensor location, allowing time for the thermometer to stabilize before reading. Match the thermometer reading to the outdoor temperature display at the thermostat.
TROUBLESHOOTING GUIDE
Symptom Possible Cause Action
Display will not come on.
Temperature display is incorrect.
Temperature settings will not change. (Example: Cannot set the
heating higher or the cooling lower.)
a
Available on select models.
Thermostat is not being powered.
Room temperature display has been reconfigured.
Thermostat is configured for °F or °C display.
Bad thermostat location. Relocate the thermostat. The upper or lower temperature
limits were reached.
The setpoint temperature range stops were configured.
a
• Check that C terminal is connected to the system transformer.
• Check for 24 Vac between C and R or RH terminals. — If missing 24 Vac:
— check if the circuit breaker is tripped—reset the
circuit breaker. — check if the system fuse is blown—replace the fuse. — check if the power switch on the HVAC equipment is
in the Off position—set to the On position. — check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
Enter Installer Setup Number 37 and reconfigure the display.
Enter Installer Setup Number 14 and reconfigure the display.
Check the temperature setpoints:
• Heating limits are 40 to 90°F (7 to 31°C)
• Cooling limits are 45 to 99°F (9 to 37°C) except T8524D cooling limits are 48 to 99°F
Check Installer Setup mode numbers 34 and 35 and reconfigure the setpoint stops.
M4867
(Continued)
69-1055—1
8
Page 9
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
TROUBLESHOOTING GUIDE (Continued)
Symptom Possible Cause Action
Heating will not come on.
Heating will not come on.
Cooling will not come on.
Heating or cooling comes on momentarily and shuts off
System On indicator is lit, but no heat is being delivered.
Outdoor temperature not displayed
Outdoor temperature display is incorrect
a
Available on select models.
No power to the thermostat. • Check that C terminal is connected to the system
Thermostat minimum off time is activated.
System selection is not set to Heat.
Heating setpoint is below room temperature.
No power to the thermostat. • Check that C terminal is connected to the system
Thermostat minimum off time is activated.
System selection is not set to Cool.
Cooling setpoint is above room temperature.
Heat or cool circuit is opening up or becoming high impedance.
Fan operation set for 00 (conventional heat) when it should be set for 01 (electric heat).
Conventional heating equipment turns on the fan when the furnace has warmed up to a setpoint.
Heating equipment is not operating.
Option not activated. Enter Installer Setup mode number 24 and set to 01.
a
Outdoor sensor is connected incorrectly.
a
Wrong sensor. Replace sensor with C7089B1000 sensor.
transformer.
• Check for 24 Vac between C and R or RH terminals. — If missing 24 Vac:
— check if the circuit breaker is tripped—reset the
circuit breaker. — check if the system fuse is blown—replace the fuse. — check if the system switch at the equipment is in the
Off position—set to On position. — check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
Wait up to five minutes for the system to respond.
Set system selection to Heat.
Check heating setpoint. Set heating setpoint to desired temperature.
transformer.
• Check for 24 Vac between C and R or RC and Y terminals. — If missing 24 Vac:
— check if the circuit breaker is tripped—reset the
circuit breaker. — check if the system fuse is blown—replace the fuse. — check if the system switch at the equipment is in the
Off position—set to the On position. — check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
•Wait up to five minutes for the system to respond.
• Enter Installer Setup mode number 33. Reconfigure minimum off time (if required).
Set system selection to Cool.
Check cooling setpoint. Set cooling setpoint to desired temperature.
Add resistor in parallel with load or install interface relay.
Enter Installer Setup mode number 02 and reconfigure the fan operation.
Wait a minute after seeing the On indicator and then check the registers.
Verify operation of heating equipment in system test.
Thermostat must have OT terminals and a C7089B1000 installed.
Refer to C7089B1000 installation instructions and check wiring between the thermostat and sensor.
9
69-1055-1
Page 10
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
69-1055—1
10
Page 11
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
11
69-1055-1
Page 12
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
Home and Building Control
Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis, MN 55408-0524
69-1055—1
69-1055—1 J.H. Rev. 6-97 www.honeywell.com/yourhome
Home and Building Control
Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 3N7
12
Loading...