The T8524C, D Multistage Microelectronic Thermostat provides electronic control of 24 Vac two-stage heating and twostage cooling systems. Refer to Table 1 for a general description of the thermostat. All T8524 Thermostats require a
common wire to supply power.
Table 1. Description of T8524 Thermostats.
T8524System Changeover
CHeat-CoolManualHeat-Off-CoolOn-Auto System and fan selections are done by
DHeat-CoolAutomaticHeat-Off-Cool-Auto On-Auto System and fan selections are done by
System
Selection
Fan
SelectionComments
switches.
keyboard.
RECYCLING NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do
control in the trash.
Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of the old thermostat.
not
place your old
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check out the product operation.
CAUTION
Disconnect power supply to prevent electrical
shock or equipment damage.
Location
Install the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.
See Fig. 1.
Do not install the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
Wallplate Installation
The thermostat can be mounted horizontally on the wall or
on a 2 in. x 4 in. wiring box. Position wallplate horizontally
on the wall or on a 2 in. x 4 in. wiring box.
1. Position and level the wallplate (for appearance
only). The thermostat will function properly even
when not level.
4. Position the wallplate over the holes, pulling wires
through the wiring opening.
5. Loosely insert the mounting screws into the holes.
6. Tighten mounting screws.
WIRING
All wiring must comply with local electrical codes and
ordinances. Refer to Fig. 3 for typical hookups. A letter
code is located near each terminal for identification.
NO
M10106
MOUNTING
HOLES
MOUNTING
SCREWS
Fig. 2. Mounting the wallplate.
2. Use a pencil to mark the mounting holes. See Fig. 2.
3. Remove the wallplate from the wall and drill two
3/16 inch holes in the wall (if drywall) as marked. For
firmer material such as plaster or wood, drill two
7/32 inch holes. Gently tap anchors (provided) into
the drilled holes until flush with the wall.
69-1055—1
M6530
CAUTION
Disconnect power before wiring to prevent
electrical shock or equipment damage.
1. Loosen the terminal screws on the wallplate and
connect the system wires. See Fig. 4.
IMPORTANT
Use 18 gauge, color-coded thermostat cable for
proper wiring.
2. Securely tighten each terminal screw.
3. Push excess wire back into the hole.
4. Plug the hole with nonflammable insulation to
prevent drafts from affecting the thermostat.
2
Page 3
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
THERMOSTAT
Y1 GC
RC
2
COMPRESSOR
CONTACTOR 1
L1
(HOT)
L2
1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
JUMPER RC TERMINAL TO R TERMINAL WHEN INSTALLED ON A
ONE TRANSFORMER SYSTEM.
CAN BE USED FOR CHANGEOVER VALVE ON HEAT
3
PUMP SYSTEMS.
Fig. 3. Typical hookup of T8524 in a multistage
O
Y2
FAN
COMPRESSOR
RELAY
CONTACTOR 2
COOL
DAMPER
3
COOLING
TRANSFORMER
heating and cooling system.
FOR WRAPAROUND
INSERTION STRIP
7/16 IN. (11 MM).
W2
HEAT
RELAY
2
HEAT
DAMPER
3
FOR STRAIGHT
INSERTION STRIP
5/16 IN. (8 MM).
HEAT
RELAY
1
M4826
Fig. 4. Proper wiring technique.
Mounting Thermostat
1. Engage tabs at the top of the thermostat and
wallplate. See Fig. 5.
2. Press lower edge of case to close and latch.
Using Thermostat Keys
The thermostat keys are used to:
• set temperature,
• display present setting,
• configure Installer Setup,
• check System Test,
• display outdoor temperature (select models).
T8524D has keys to:
• set the system operation,
• set the fan operation.
See Fig. 6 for key information.
OT OTB
RW1
OUTDOOR
SENSOR
1
L1
(HOT)
L2
HEATING
TRANSFORMER
M11309
A.
ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE.
B.
PRESS LOWER EDGE OF CASE TO LATCH.
M6798A
Fig. 5. Mounting thermostat on wallplate.
NOTE: To remove the thermostat from the wall, first pull out
at the bottom of the thermostat; remove top last.
INCREASE
TEMPERATURE
SETTING
i
DECREASE
TEMPERATURE
SETTING
DISPLAY PRESENT
SETTINGS AND SCROLL
THROUGH INSTALLER
SETUP MODES
(INFORMATION KEY)
M6801
Fig. 6. Thermostat key locations and descriptions.
SETTINGS
System and Fan Settings
System settings control the thermostat operation as
follows:
Heat: The thermostat controls the heating.
Off: Both the heating and cooling are off.
Cool: The thermostat controls the cooling.
Auto (T8524D only): The thermostat automatically
changes between heating and cooling operation,
depending on the indoor temperature.
Fan settings control the system fan as follows:
On: Fan operates continuously.
Auto: Equipment controls fan.
The system default setting is Heat and the fan default
setting is Auto. Use the keyboard or system and fan
switches, depending on model, to change to the desired
settings. See Figs. 7 and 8.
3
69-1055-1
Page 4
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
A combination of key presses are required to use the
Installer Setup feature.
i
HEAT OFF COOL
ON AUTO
M10146
SYSTEM
Selection for heating or cooling
equipment operation.
Heat - Heating equipment
Off - No equipment
Cool - Cooling equipment
HEAT OFF COOL
ON AUTO
FAN
On - Fan runs continuously
Auto - Fan runs when
heating or cooling
equipment operates
Fig. 7. T8524C system and fan switches location.
i
Fan
System
Press to select
Press to select
heating or cooling
heating or cooling
equipment.
equipment.
Em. Ht.
-Emergency heating
On— Fan runs continuously
Heat—Heating equipment
Auto—Fan runs when
Off — No equipment
Cool—Cooling equipment
Auto—Thermostat
automatically selects
heating and cooling
equipment.
CHECK LIGHT ON SELECT MODELS
1
heating or cooling
equipment operates
System
Fan
1
System
Fan
M10147
Fig. 8. T8524D system and fan keys location.
NOTE: Always press the system and fan keys with your
fingertip or similar blunt tool. Sharp instruments
like a pen or pencil point can damage the
keyboard.
Temperature Settings
The default setpoint for heat is 70°F (21°C) and for cool is
78°F (25.5°C). Press the increase ▲ or decrease ▼ key to
change the present setting. To change between heat and
cool, press the Information i key until the setting to be
changed appears.
— To enter the Installer Setup mode, press and hold the
Information i key with the increase ▲ and decrease
▼ keys until the first number is displayed. All display
segments appear for approximately three seconds
before the number is displayed. See Fig. 9 and 10.
— To advance to the next Installer Setup number, press
the Information i key.
— To change a setting, use the increase ▲ or de-
crease ▼ key.
— To exit the Installer Setup, press and hold the
Information i key until the display returns to normal
(approximately three seconds). The display scrolls the
numbers backwards to get to the normal display. The
Installer Setup is automatically exited if no key
presses are made for five minutes.
IMPORTANT
Em Ht Temporary Setting
Aux Ht
Repl
Batt
Em HeatOffCool Auto Only
Fig. 9. Display of all the segments of the LCD.
Only configurable numbers are shown on the
device. Example: If the thermostat does not have
a system key, Installer Setup Number 12 will not
be displayed. Review Table 2 factory-settings
and mark any desired changes in the Actual
Setting column. When Installer Setup in complete, review the settings to confirm that they
match the system.
Remote
Room
%Humid
Wait
SystemFan
Heat Cool
MODE NUMBER DISPLAY
(COLUMN 2 OF TABLE 2)
Outdoor
OnAuto
M4844
FACTORY SETTING OR
OTHER CHOICE DISPLAY
(COLUMN 3 OR 5 OF TABLE 2)
INSTALLER SETUP
NOTE: For most applications, the thermostat factory-
settings do not need to be changed. Review the
factory-settings in Table 2 and if no changes are
necessary, go to the Installer System Test
section.
The Installer Setup is used to customize the thermostat to
specific systems. Installer Setup Numbers are listed in
Table 2. The table includes all the configuration options
available.
69-1055—1
Fig. 10. Display of Installer Setup mode and setting.
CAUTION
Electric heat systems must be configured to 01 in
Installer Setup 02 to prevent equipment damage
caused by the system running without the fan.
4
M10105
Page 5
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
Table 2. Thermostat Installer Setup Options.
Installer Setup
Select
Number
(Press i key
to change)
Factory-Setting
DisplayDescriptionDisplayDescriptionSetting
Not used01—————
Fan operationa0200Conventional applica-
tions where equipment
controls fan operation in
heat mode
01Heat pump and electric heat
Not used03 and 04—————
Stage-two
heating cycle
rate
05066 cph used for
conventional systems
01, 03,
or 09
Not used06 thru 11—————
Changeover
(T8524D only)
12 01Manual changeover00Automatic changeover
Not used13 —————
Degree
temperature
display
1400Temperature is
displayed in °F
01Temperature is displayed in
Not used15 thru 18 —————
Extended fan
operation in
heating
Extended fan
operation in
cooling
19 00No extended fan
a,b
20 00No extended fan
a
operation after the call
for heat ends
operation after the call
for cool ends
01Fan operation is extended
01Fan operation is extended
Not used21 thru 23 —————
Outdoor
temperature
display
2400No outdoor temperature
a
is displayed
01Outdoor temperature is
Not used25 thru 29—————
Deadband3003Heating and cooling
setpoints can be set no
closer than 3°F (1.5°C)
04 thru10Heating and cooling
Not used31 and 32—————
Minimum off
time for the
compressor
a
Available on select models.
b
Installer Setup Number 02 must be set to 01 to extend fan operation.
33055 minute minimum off
time for the compressor
00, 01,
02, 03
or 04
Other Choices
(Press ▲ or ▼ key to change)
applications where
thermostat controls fan
operation in heat mode
01—1 cph used for radiant
floor heat, gravity systems
03—3 cph used for hot water
systems or high efficiency
furnaces
09—9 cph used for electric
heat systems
°C
90 seconds after the call for
heat ends
90 seconds after the call for
cool ends
displayed. Needs a
C7089B1000 Outdoor
Sensor to operate.
setpoints can be set no
closer than the chosen
value:
Review the settings to confirm that they match
the system.
displayed temperature
and actual room
temperature
-3 thru
3
Other Choices
(Press ▲ or ▼ key to change)
anywhere between 40 and
90 in 1°F increments
anywhere between 45
99 in 1°F increments
1—Display adjusts to 1°F
higher than actual room
temperature
2—Display adjusts to 2°F
higher than actual room
temperature
3—Display adjusts to 3°F
higher than actual room
temperature
-1—Display adjusts to 1°F
lower than actual room
temperature
-2—Display adjusts to 2°F
lower than actual room
temperature
-3—Display adjusts to 3°F
lower than actual room
temperature
b
and
Actual
INSTALLER SYSTEM TEST
Use the Installer System Test to check the thermostat
configurations and operation. Refer to Table 3 for a list of
the available system tests.
To start the system test::
NOTE: The minimum off time for compressors is
bypassed during the Installer System Test.
Press and hold the increase ▲ and decrease ▼ keys, at
the same time, until two zeros appear. All segments of the
LCD are displayed before the two zeros appear.
Em Ht Temporary Setting
Aux Ht
Repl
Wait
Batt
SystemFan
Em HeatOffCool Auto Only
69-1055—1
Heat Cool
Remote
Room
%Humid
Outdoor
OnAuto
M4844
TEST MODE
NUMBER
IMPORTANT
T8524C models must set the switches to the
equipment that is being checked for the equipment to operate.
NOTE: Press and hold the increase ▲ and decrease ▼
keys for three seconds to exit the System Test.
The System Test times out after five minutes
without any key presses.
M6792
Table 3. Tests Available In The Installer System Test.
Test
NumberSystem Test Description
10-19Heating equipment can be turned on and off
30-39Cooling equipment can be turned on and off
40-49Fan equipment (T8524D only) can be turned
on and off.
60-69System key or system switch position test
70-79Thermostat information including date code
and software versions are displayed
6
Page 7
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
Table 4. Installer System Test Options.
Key to
Press
Heating Equipment System test
▲ 11Stage-one heat comes on. The system fan is also energized.
▲ 12Stage-two heat comes on. Stage-one heat and system fan remain on.
▼11Stage-two heat turns off.
▼ 10Stage-one heat and system fan turn off.
Cooling Equipment System test
▲ 31Stage-one cool and system fan come on.
▲ 32Stage-two cool comes on. Stage-one cool and system fan remain on.
▼31Stage-two cool turns off.
▼ 30Stage-one cool and system fan turn off.
Fan Equipment System test (T8524D only)
▲ 41Fan comes on.
▼ 40Fan turns off.
Key or Switch Operation System test
IMPORTANT
SYSTEM KEY OR SWITCH SYSTEM TEST (Move switch to see Test Numbers on T8524C.)
System 61Heat Test Number is displayed. (Set system switch to HEAT on T8524C.)
System 62Off Test Number is displayed. (Set system switch to OFF on T8524C.)
System 63Cool Test Number is displayed. (Set system switch to COOL on T8524C.)
System 64Auto Test Number is displayed.
FAN KEY SYSTEM TEST (T8524D only)
Fan68Fan on Test Number is displayed.
Fan69Fan off Test Number is displayed.
a
System fan is energized only if set for electric heat.
Thermostat Information
1. Press the Information i key to access the
Test
NumberDescription
i
i
i
i
thermostat information.
10Enter heating equipment system test. (Set system switch to HEAT on T8524C.)
a
30Enter cooling equipment system test. (Set system switch to COOL on T8524C.)
40Change from cooling to fan equipment system test.
Test Numbers will only be displayed when the system is configured for the selected function.
EXAMPLE: Numbers 60, 61 and 62 are the only numbers that will be displayed when a system
is configured for heat only.
60Change from cooling or fan to key operation system test.
2. Press the increase ▲ key to display the production
date code. The first two large digits are the month
and the third digit is the last digit of the year.
(Example: 026 = February 1996)
M4864
M4865
7
69-1055-1
Page 8
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
3. Press the increase ▲ key again to display the
software identification code.
(Example: 02 = software ID code 2)
M4866
4. Press the increase ▲ key again to display the
software revision number.
(Example: 001 = revision number 1)
5. Press the increase ▲ key again to display the
EEPROM identification code.
(Example: 222 = EEPROM ID 222)
6. Press and hold the increase ▲ and decrease ▼
keys together, until the room temperature is
displayed, to exit the System Test. The System Test
times out after five minutes without any key presses.
CHECKOUT
Outdoor Temperature Sensor
(Where Applicable)
Allow the outdoor temperature sensor to soak in the
M6791
outdoor air for a minimum of five minutes before taking a
reading. With an accurate thermometer (±1°F [±0.5°C]),
measure the temperature at the sensor location, allowing
time for the thermometer to stabilize before reading. Match
the thermometer reading to the outdoor temperature
display at the thermostat.
TROUBLESHOOTING GUIDE
SymptomPossible CauseAction
Display will not
come on.
Temperature
display is incorrect.
Temperature
settings will not
change. (Example:
Cannot set the
heating higher or
the cooling lower.)
a
Available on select models.
Thermostat is not being
powered.
Room temperature display has
been reconfigured.
Thermostat is configured for °F
or °C display.
Bad thermostat location.Relocate the thermostat.
The upper or lower temperature
limits were reached.
The setpoint temperature range
stops were configured.
a
• Check that C terminal is connected to the system
transformer.
• Check for 24 Vac between C and R or RH terminals.
— If missing 24 Vac:
— check if the circuit breaker is tripped—reset the
circuit breaker.
— check if the system fuse is blown—replace the fuse.
— check if the power switch on the HVAC equipment is
in the Off position—set to the On position.
— check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
Enter Installer Setup Number 37 and reconfigure the display.
Enter Installer Setup Number 14 and reconfigure the display.
Check the temperature setpoints:
• Heating limits are 40 to 90°F (7 to 31°C)
• Cooling limits are 45 to 99°F (9 to 37°C) except T8524D
cooling limits are 48 to 99°F
Check Installer Setup mode numbers 34 and 35 and
reconfigure the setpoint stops.
M4867
(Continued)
69-1055—1
8
Page 9
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
TROUBLESHOOTING GUIDE (Continued)
SymptomPossible CauseAction
Heating will not
come on.
Heating will not
come on.
Cooling will not
come on.
Heating or cooling
comes on
momentarily and
shuts off
System On
indicator is lit, but
no heat is being
delivered.
Outdoor
temperature
not displayed
Outdoor
temperature
display is incorrect
a
Available on select models.
No power to the thermostat.• Check that C terminal is connected to the system
Thermostat minimum off time is
activated.
System selection is not set to
Heat.
Heating setpoint is below room
temperature.
No power to the thermostat.• Check that C terminal is connected to the system
Thermostat minimum off time is
activated.
System selection is not set to
Cool.
Cooling setpoint is above room
temperature.
Heat or cool circuit is opening
up or becoming high
impedance.
Fan operation set for 00
(conventional heat) when it
should be set for 01 (electric
heat).
Conventional heating
equipment turns on the fan
when the furnace has
warmed up to a setpoint.
Heating equipment is not
operating.
Option not activated.Enter Installer Setup mode number 24 and set to 01.
a
Outdoor sensor is connected
incorrectly.
a
Wrong sensor.Replace sensor with C7089B1000 sensor.
transformer.
• Check for 24 Vac between C and R or RH terminals.
— If missing 24 Vac:
— check if the circuit breaker is tripped—reset the
circuit breaker.
— check if the system fuse is blown—replace the fuse.
— check if the system switch at the equipment is in the
Off position—set to On position.
— check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
Wait up to five minutes for the system to respond.
Set system selection to Heat.
Check heating setpoint. Set heating setpoint to desired
temperature.
transformer.
• Check for 24 Vac between C and R or RC and Y terminals.
— If missing 24 Vac:
— check if the circuit breaker is tripped—reset the
circuit breaker.
— check if the system fuse is blown—replace the fuse.
— check if the system switch at the equipment is in the
Off position—set to the On position.
— check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
•Wait up to five minutes for the system to respond.
• Enter Installer Setup mode number 33. Reconfigure
minimum off time (if required).
Set system selection to Cool.
Check cooling setpoint. Set cooling setpoint to desired
temperature.
Add resistor in parallel with load or install interface relay.
Enter Installer Setup mode number 02 and reconfigure the fan
operation.
Wait a minute after seeing the On indicator and then check the
registers.
Verify operation of heating equipment in system test.
Thermostat must have OT terminals and a C7089B1000
installed.
Refer to C7089B1000 installation instructions and check wiring
between the thermostat and sensor.
9
69-1055-1
Page 10
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
69-1055—1
10
Page 11
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
11
69-1055-1
Page 12
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis, MN 55408-0524