Honeywell T8524C User Manual

T8524C,D Multistage
Microelectronic Thermostats
INSTALLATION INSTRUCTIONS
APPLICATION
The T8524C, D Multistage Microelectronic Thermostat provides electronic control of 24 Vac two-stage heating and two­stage cooling systems. Refer to Table 1 for a general description of the thermostat. All T8524 Thermostats require a common wire to supply power.
Table 1. Description of T8524 Thermostats.
T8524 System Changeover
C Heat-Cool Manual Heat-Off-Cool On-Auto System and fan selections are done by
D Heat-Cool Automatic Heat-Off-Cool-Auto On-Auto System and fan selections are done by
System
Selection
Fan
Selection Comments
switches.
keyboard.
RECYCLING NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do control in the trash.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat.
not
place your old
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check out the product operation.
CAUTION
Disconnect power supply to prevent electrical shock or equipment damage.
Location
Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1.
Do not install the thermostat where it can be affected by: — drafts, or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.
Wallplate Installation
The thermostat can be mounted horizontally on the wall or on a 2 in. x 4 in. wiring box. Position wallplate horizontally on the wall or on a 2 in. x 4 in. wiring box.
1. Position and level the wallplate (for appearance
only). The thermostat will function properly even when not level.
®U.S. Registered Trademark Copyright © 1997 Honeywell Inc. • • All Rights Reserved
X-XX UL
69-1055-1
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
WALL ANCHORS (2)
NO
WIRES THROUGH WALL
YES
NO
5 FEET
[1.5 METERS]
Fig. 1. Typical location of thermostat.
WALL
4. Position the wallplate over the holes, pulling wires
through the wiring opening.
5. Loosely insert the mounting screws into the holes.
6. Tighten mounting screws.
WIRING
All wiring must comply with local electrical codes and ordinances. Refer to Fig. 3 for typical hookups. A letter code is located near each terminal for identification.
NO
M10106
MOUNTING HOLES
MOUNTING SCREWS
Fig. 2. Mounting the wallplate.
2. Use a pencil to mark the mounting holes. See Fig. 2.
3. Remove the wallplate from the wall and drill two
3/16 inch holes in the wall (if drywall) as marked. For firmer material such as plaster or wood, drill two 7/32 inch holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
69-1055—1
M6530
CAUTION
Disconnect power before wiring to prevent electrical shock or equipment damage.
1. Loosen the terminal screws on the wallplate and
connect the system wires. See Fig. 4.
IMPORTANT
Use 18 gauge, color-coded thermostat cable for proper wiring.
2. Securely tighten each terminal screw.
3. Push excess wire back into the hole.
4. Plug the hole with nonflammable insulation to
prevent drafts from affecting the thermostat.
2
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
THERMOSTAT
Y1 G C
RC
2
COMPRESSOR CONTACTOR 1
L1 (HOT)
L2
1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
JUMPER RC TERMINAL TO R TERMINAL WHEN INSTALLED ON A ONE TRANSFORMER SYSTEM.
CAN BE USED FOR CHANGEOVER VALVE ON HEAT
3
PUMP SYSTEMS.
Fig. 3. Typical hookup of T8524 in a multistage
O
Y2
FAN
COMPRESSOR
RELAY
CONTACTOR 2
COOL DAMPER
3
COOLING TRANSFORMER
heating and cooling system.
FOR WRAPAROUND INSERTION STRIP 7/16 IN. (11 MM).
W2
HEAT RELAY 2
HEAT DAMPER
3
FOR STRAIGHT INSERTION STRIP 5/16 IN. (8 MM).
HEAT RELAY 1
M4826
Fig. 4. Proper wiring technique.
Mounting Thermostat
1. Engage tabs at the top of the thermostat and
wallplate. See Fig. 5.
2. Press lower edge of case to close and latch.
Using Thermostat Keys
The thermostat keys are used to:
• set temperature,
• display present setting,
• configure Installer Setup,
• check System Test,
• display outdoor temperature (select models).
T8524D has keys to:
• set the system operation,
• set the fan operation.
See Fig. 6 for key information.
OT OTB
RW1
OUTDOOR SENSOR
1
L1 (HOT)
L2
HEATING TRANSFORMER
M11309
A.
ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE.
B.
PRESS LOWER EDGE OF CASE TO LATCH.
M6798A
Fig. 5. Mounting thermostat on wallplate.
NOTE: To remove the thermostat from the wall, first pull out
at the bottom of the thermostat; remove top last.
INCREASE TEMPERATURE SETTING
i
DECREASE TEMPERATURE SETTING
DISPLAY PRESENT SETTINGS AND SCROLL THROUGH INSTALLER SETUP MODES (INFORMATION KEY)
M6801
Fig. 6. Thermostat key locations and descriptions.
SETTINGS
System and Fan Settings
System settings control the thermostat operation as follows:
Heat: The thermostat controls the heating. Off: Both the heating and cooling are off. Cool: The thermostat controls the cooling. Auto (T8524D only): The thermostat automatically
changes between heating and cooling operation, depending on the indoor temperature.
Fan settings control the system fan as follows:
On: Fan operates continuously. Auto: Equipment controls fan.
The system default setting is Heat and the fan default setting is Auto. Use the keyboard or system and fan switches, depending on model, to change to the desired settings. See Figs. 7 and 8.
3
69-1055-1
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
A combination of key presses are required to use the Installer Setup feature.
i
HEAT OFF COOL
ON AUTO
M10146
SYSTEM
Selection for heating or cooling equipment operation.
Heat - Heating equipment Off - No equipment Cool - Cooling equipment
HEAT OFF COOL
ON AUTO
FAN
On - Fan runs continuously Auto - Fan runs when
heating or cooling equipment operates
Fig. 7. T8524C system and fan switches location.
i
Fan
System
Press to select
Press to select
heating or cooling
heating or cooling
equipment.
equipment. Em. Ht.
-Emergency heating
On— Fan runs continuously
Heat—Heating equipment
Auto—Fan runs when Off — No equipment Cool—Cooling equipment Auto—Thermostat
automatically selects heating and cooling equipment.
CHECK LIGHT ON SELECT MODELS
1
heating or cooling equipment operates
System
Fan
1
System
Fan
M10147
Fig. 8. T8524D system and fan keys location.
NOTE: Always press the system and fan keys with your
fingertip or similar blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard.
Temperature Settings
The default setpoint for heat is 70°F (21°C) and for cool is 78°F (25.5°C). Press the increase or decrease key to change the present setting. To change between heat and cool, press the Information i key until the setting to be changed appears.
— To enter the Installer Setup mode, press and hold the
Information i key with the increase and decrease keys until the first number is displayed. All display segments appear for approximately three seconds before the number is displayed. See Fig. 9 and 10.
— To advance to the next Installer Setup number, press
the Information i key.
— To change a setting, use the increase or de-
crease key.
— To exit the Installer Setup, press and hold the
Information i key until the display returns to normal (approximately three seconds). The display scrolls the numbers backwards to get to the normal display. The Installer Setup is automatically exited if no key presses are made for five minutes.
IMPORTANT
Em Ht Temporary Setting Aux Ht
Repl Batt
Em HeatOffCool Auto Only
Fig. 9. Display of all the segments of the LCD.
Only configurable numbers are shown on the device. Example: If the thermostat does not have a system key, Installer Setup Number 12 will not be displayed. Review Table 2 factory-settings and mark any desired changes in the Actual Setting column. When Installer Setup in com­plete, review the settings to confirm that they match the system.
Remote
Room
%Humid
Wait
System Fan
Heat Cool
MODE NUMBER DISPLAY (COLUMN 2 OF TABLE 2)
Outdoor
OnAuto
M4844
FACTORY SETTING OR OTHER CHOICE DISPLAY (COLUMN 3 OR 5 OF TABLE 2)
INSTALLER SETUP
NOTE: For most applications, the thermostat factory-
settings do not need to be changed. Review the factory-settings in Table 2 and if no changes are necessary, go to the Installer System Test section.
The Installer Setup is used to customize the thermostat to specific systems. Installer Setup Numbers are listed in Table 2. The table includes all the configuration options available.
69-1055—1
Fig. 10. Display of Installer Setup mode and setting.
CAUTION
Electric heat systems must be configured to 01 in Installer Setup 02 to prevent equipment damage caused by the system running without the fan.
4
M10105
Loading...
+ 8 hidden pages