Honeywell T8501D User Manual

Page 1
/
T8501D
Deluxe Zone Thermostat
INSTALLATION INSTRUCTIONS
APPLICATION
The T8501 Deluxe Zone Thermostat provides electronic control of 24 Vac single-stage zoned heating and cooling systems. Refer to Table 1 for a general description of the thermostat.
Table 1. Description of T8501 Thermostat.
Model Application Powering Method Changeover System Selection Fan Selection
T8501D Zone 1 on MABS II or
TotalZone® system
RECYCLING NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do control in the trash.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat.
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After completing installation, use these instructions to check out the product operation.
Location
Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1.
Requires common wire to power supply
not
place your old
Automatic or
Manual
Do not install the thermostat where it can be affected by: —drafts, or dead spots behind doors and in corners. — hot or cold air from ducts. —radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.
Wallplate Installation
The thermostat can be mounted horizontally on the wall or on a 2 in. x 4 in. wiring box. Position wallplate horizontally on the wall or on a 2 in. x 4 in. wiring box.
1. Position and level the wallplate (for appearance
only). The thermostat will function properly even when not level.
2. Use a pencil to mark the mounting holes. See Fig. 2.
3. Remove the wallplate from the wall and drill two
3/16 inch holes in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32 inch holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
4. Position the wallplate over the holes, pulling wires
through the wiring opening.
5. Loosely insert the mounting screws into the holes.
6. Tighten mounting screws.
Heat-Off-Cool-Auto On-Auto
®U.S. Registered Trademark Copyright © 1997 Honeywell Inc. • • All Rights Reserved
X-XX UL
69-1049-1
Page 2
T8501D DELUXE ZONE THERMOSTAT
NO
WIRES THROUGH WALL
WALL ANCHORS (2)
Fig. 2. Mounting the wallplate.
YES
NO
5 FEET
[1.5 METERS]
Fig. 1. Typical location of thermostat.
WALL
Wiring
All wiring must comply with local electrical codes and ordinances. Refer to Fig. 3 and 4 for typical hookups. A letter code is located near each terminal for identification.
1. Loosen the terminal screws on the wallplate and
connect the system wires. See Fig. 5.
IMPORTANT
MOUNTING HOLES
MOUNTING SCREWS
M6530
2. Securely tighten each terminal screw.
3. Push excess wire back into the hole.
4. Plug the hole with nonflammable insulation to
prevent drafts from affecting the thermostat.
NO
M10106
CAUTION
Disconnect power before wiring to prevent electrical shock or equipment damage.
Use 18 gauge, color-coded thermostat cable for proper wiring.
69-1049—1
2
Page 3
T8501D DELUXE ZONE THERMOSTAT
OUTDOOR
TEMPERATURE
SENSOR
OGB CWRYOTOT
O1
G1
B1
E1
CHANGEOVER CONTROL
Fig. 3. Typical wiring diagram for T8501D with zone 1
OBGYRWCOTOT
W2 L G Y R W M6 M4 M1
TotalZone® PANEL THERMOSTAT CONNECTIONS
Fig. 4. Typical wiring diagram for T8501D with zone 1
THERMOSTAT
MABS II control panel.
THERMOSTAT
TotalZone® control panel.
FOR WRAPAROUND INSERTION STRIP 7/16 IN. (11 MM).
(OPTIONAL)
ZONE 1
T8
T7
T6
T5
T4
M1
OUTDOOR
THERMOSTAT
SENSOR
(OPTIONAL)
FOR STRAIGHT INSERTION STRIP 5/16 IN. (8 MM).
M4826
M12187
M12186
Fig. 5. Proper wiring technique.
Mounting Thermostat
1. Engage tabs at the top of the thermostat and
wallplate. See Fig. 6.
2. Press lower edge of case to close and latch.
NOTE: To remove the thermostat from the wall, first pull out
at the bottom of the thermostat; remove top last.
A.
ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE.
B.
PRESS LOWER EDGE OF CASE TO LATCH.
M6798A
Fig. 6. Mounting thermostat on wallplate.
Using Thermostat Keys
The thermostat keys are used to:
• set temperature,
•display present setting,
• configure Installer Setup,
• check System-Test,
•display outdoor temperature (select models),
• set the system operation,
• set the fan operation.
See Fig. 7 for the location of the keys.
INCREASE TEMPERATURE SETTING
i
DECREASE TEMPERATURE SETTING
DISPLAY PRESENT SETTINGS AND SCROLL THROUGH INSTALLER SETUP MODES (INFORMATION KEY)
M6801
Fig. 7. Key locations and descriptions.
3
69-1049—1
Page 4
T8501D DELUXE ZONE THERMOSTAT
SETTINGS
System and Fan Settings
System settings control the thermostat operation as follows:
Heat: The thermostat controls the heating. Off: Both the heating and cooling are off. Cool: The thermostat controls the cooling. Auto: The thermostat automatically changes between
heating and cooling operation, depending on the indoor temperature.
Fan settings control the system fan as follows:
On: Fan operates continuously. Auto: Fan operates with equipment.
The system default setting is Heat and the fan default setting is Auto. Use the keyboard to change to the desired settings. See Fig. 8.
i
Fan
System
Press to select
Press to select
heating or cooling
heating or cooling
equipment.
equipment. Em. Ht.
-Emergency heating
On— Fan runs continuously
Heat—Heating equipment
Auto—Fan runs when Off — No equipment Cool—Cooling equipment Auto—Thermostat
automatically selects heating and cooling equipment.
CHECK LIGHT ON SELECT MODELS
1
heating or cooling equipment operates
System
Fan
1
Fig. 8. Thermostat System and Fan key location.
NOTE: Always press the keys with your fingertip or
similar blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard.
Temperature Settings
The default setpoint for heat is 70°F (21°C) and for cool is 78°F (25.5°C). Press the increase or decrease key to change the present setting to change between heat and cool, press the Information i key until the setting to be changed appears. Press the increase or decrease key to adjust the setting.
System
Fan
M10147
The Installer Setup is used to customize the thermostat to specific systems. Some of the options include temperature display, changeover and outdoor temperature display. Installer Setup numbers are listed in Table 2. The table includes all the configuration options and the factory settings for the T8501.
A combination of key presses are required to use the Installer Setup feature. — To enter the Installer Setup, press and hold the
Information i key with the increase and decrease keys until the first number is displayed. All display segments appear for approximately three seconds before the number is displayed. See Fig. 9 and 10.
— To advance to the next Installer Setup, press the
Information i key.
— To change a setting, use the increase and de-
crease keys.
— To exit the Installer Setup, press and hold the
Information i key until the display returns to normal (approximately three seconds). The display will scroll the numbers backwards to get to the normal display. The Installer Setup is automatically exited if no key presses are made for ten minutes.
Em Ht Temporary Setting Aux Ht
Remote
Room
%Humid
Repl
Wait
Batt
System Fan
Heat Cool
Em HeatOffCool Auto Only
Fig. 9. Display of all the segments of the LCD.
INSTALLER SETUP MODE NUMBER DISPLAY (COLUMN 2 OF TABLE 2)
Outdoor
OnAuto
M4844
FACTORY SETTING OR OTHER CHOICE DISPLAY (COLUMN 3 OR 5 OF TABLE 2)
INSTALLER SETUP
NOTE: For most applications, the thermostat factory-
settings will not need to be changed. Review the factory settings in Table 2 and if no changes are necessary, go to the Installer System-Test section.
69-1049—1
M10105A
Fig. 10. Display of Installer Setup number and setting.
IMPORTANT
Only configurable numbers are shown on the device. Example: If thermostat does not have outdoor temperature capability, Installer Setup Number 24 will not be displayed. Review Table 2 factory-settings and mark any desired changes in the Actual Settings column. When Installer Setup is complete, review the settings to confirm that they match the system.
4
Page 5
T8501D DELUXE ZONE THERMOSTAT
Table 2. Thermostat Installer Setup Options.
Installer Setup
Number
(Press i key Factory Setting
Select
Not used 01 — Fan operation
to change)
a
Display Description Display Description
02 00 Conventional applica-
tions where equipment controls fan operation in heat mode
01 Heat pump and electric heat
Not used 03 — Heating cycle
rate
04 06 6 cph used for
conventional systems
01, 03,
or 09
Not used 05 thru 11 — Changeover 12 01 Manual changeover 00 or0200—Manual changeover
Not used 13 — Degree
temperature display
14 00 Temperature is
displayed in °F
01 Temperature is displayed in °C
Not used 15 thru 18 — Extended fan
operation in
a,b
heating Extended fan
operation in
a,b
cooling
19 00 No extended fan
20 00 No extended fan
operation after the call for heat ends
operation after the call for cool ends
01 Fan operation is extended
01 Fan operation is extended
Not used 21 thru 23 — Outdoor
temperature
b
display
24 00 No outdoor
temperature is displayed
01 Outdoor temperature is
Not used 25 thru 32 — Minimum off
time for the compressor
Heating setpoint range stop
Cooling setpoint range stop
System on indicator (flame=heat, snowflake=cool) is displayed
Temperature display adjustment
a b
b
b
b
Number 02 must be set to 01 to extend fan operation. Available on select models.
33 05 5 minute minimum off
34 90 Heating setpoint can
35 48 Cooling setpoint can
36 00 LCD On symbol is
37 00 No difference in
time for the compressor
be set no higher than 90°F
be set no lower than 48°F
displayed when system is energized
displayed temperature and actual room temperature
5
00, 01, 02, 03
or 04
40 thru90Number can be set anywhere
48 thru99Number can be set anywhere
01 Display is disabled
-3 thru0301—Display adjusts to 1°F higher
Other Choices
(Press ▲ or ▼ key to change) Actual
Setting
applications where thermostat controls fan operation in heat mode
01—1 cph used for radiant floor heat, gravity systems 03—3 cph used for hot water systems or high efficiency furnaces 09—9 cph used for electric heat systems
02—Auto only
90 seconds after the call for heat ends
90 seconds after the call for cool ends
displayed. Needs a C7089B1000 Outdoor Sensor to operate.
Minimum number of minutes (0 thru 5) the compressor will be off between calls for the compressor
between 40 and 90 in 1°F increments
between 48 and 99 in 1°F increments
than actual room temperature 02—Display adjusts to 2°F higher than actual room temperature 03—Display adjusts to 3°F higher than actual room temperature
-1—Display adjusts to 1°F lower than actual room temperature
-2—Display adjusts to 2°F lower than actual room temperature
-3—Display adjusts to 3°F lower than actual room temperature
69-1049—1
Page 6
T8501D DELUXE ZONE THERMOSTAT
IMPORTANT
Review the settings to confirm that they match the system. To exit the Installer Setup, press and hold the Information returns to normal (approximately three seconds).
i
key until the display
INSTALLER SYSTEM-TEST
Use the Installer System-Test to check the thermostat operation. Refer to Table 3 for a list of the available system-tests.
To start the system-test:
CAUTION
The minimum off time for compressors is bypassed during the Installer System-Test. Equipment damage can occur if the compressor is cycled too quickly.
Press and hold the increase and decrease keys at the same time, until two zeros appear. All segments of the LCD will be displayed before the two zeros appear. See Fig. 11 and 12.
Table 3. Tests Available In The Installer System-Test.
Test
Number Self-Test Description
10-19 Heating equipment can be turned on
and off
30-39 Cooling equipment can be turned on
and off 40-49 Fan equipment can be turned on and off 60-69 Keyboard keys test 70-79 Thermostat information including date
code and software versions are displayed
Em Ht Temporary Setting
Aux Ht
Remote
Room
%Humid
Repl
Wait
Batt
System Fan
Heat Cool
Em HeatOffCool Auto Only
Fig. 11. Display of all the segments of the LCD.
TEST MODE NUMBER
Fig. 12. Display of test number.
Refer to Table 4 for the directions and results of the specific tests.
NOTE: Press and hold the increase and decrease
keys together for three seconds to exit the system-test. The system-test will time out after ten minutes without any key presses.
Outdoor
OnAuto
M4844
M6792
Table 4. Installer System-Test Options.
Key to
Press
Heating Equipment System-Test
i 10 Enter heating equipment system-test.
11 Heat comes on. When Installer Setup number 02 is 01, the system fan is also energized. ▼ 10 Heat and system fan turn off.
Cooling Equipment System-Test
i 30 Change from heating to cooling equipment system-test.
31 Cool and system fan come on. ▼ 30 Cool and system fan turn off.
Fan Equipment System-Test
i 40 Change from cooling to fan equipment system-test.
41 Fan comes on. ▼ 40 Fan turns off.
69-1049—1
Test
Number Description
6
(Continued)
Page 7
T8501D DELUXE ZONE THERMOSTAT
Key to
Press
Table 4. Installer Self-Test Options
Test
Number Description
(Continued)
.
Key Operation System-Test
IMPORTANT
Test numbers will only be displayed when the system is configured for the selected function. EXAMPLE: Numbers 60, 61 and 62 are the only numbers that will be displayed when a system is configured for heat only.
System Key System-Test
i 60 Change from cooling or fan to key operation system-test.
System 61 Heat Test Number is displayed. System 62 Off Test Number is displayed. System 63 Cool Test Number is displayed. System 64 Auto Test Number is displayed.
Fan Key System-Test
Fan 68 Fan on Test Number is displayed. Fan 69 Fan off Test Number is displayed.
NOTE: Press and hold the increase and decrease keys together for three seconds to exit the system-test. The
system-test will time out after ten minutes without any key presses.
THERMOSTAT INFORMATION
1. Press the Information i key to access the thermo-
stat information.
3. Press the increase ▲ key again to display the
software identification code.
M4864
2. Press the increase ▲ key to display the production
date code. The first two large digits are the month and the third digit is the last digit of the year (Example: 027=February 1997).
M10444
4. Press the increase ▲ key again to display the
software revision number (Example: 001=Revision number 1).
7
M4866
M6791
69-1049—1
Page 8
T8501D DELUXE ZONE THERMOSTAT
5. Press the increase ▲ key again to display the
EEPROM identification code.
CHECKOUT
Outdoor Temperature Sensor (Where Applicable)
Allow the outdoor temperature sensor to soak in the outdoor air for a minimum of five minutes before taking a reading. With an accurate thermometer (±1°F [±0.5°C]), measure the temperature at the sensor location, allowing time for the thermometer to stabilize before reading. Match the thermometer reading to the outdoor temperature display at the thermostat.
6. Press and hold the increase ▲ and decrease
keys together, until the room temperature is displayed, to exit the system-test. The system-test times out after ten minutes without any key presses.
M4867
TROUBLESHOOTING GUIDE
Symptom Possible Cause Action
Display will not come on.
Temperature display is incorrect.
Temperature settings will not change. (Example: Cannot set the heating higher or the cooling lower.)
a
Available on select models.
Thermostat is not being powered.
Thermostat microprocessor is locked up.
Room temperature display has been reconfigured.
Thermostat is configured for °F or °C display.
Bad thermostat location. Relocate the thermostat. The upper or lower
temperature limits were reached.
The setpoint temperature range stops were configured.
a
• Check that C terminal is connected to the system transformer.
• Check for 24 Vac between C and R terminals. — If missing 24 Vac:
— check if the circuit breaker is tripped—reset the
circuit breaker. — check if the system fuse is blown—replace the fuse. — check if the power switch on the HVAC equipment is
in the Off position—set to the On position. — check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
Remove the thermostat from the wallplate for 2 minutes. After 2 minutes, replace the thermostat on the wallplate.
Enter Installer Setup number 37 and reconfigure the display.
Enter Installer Setup number 14 and reconfigure the display.
Check the temperature setpoints:
• Heating limits are 40 to 90°F (4.5 to 32°C)
• Cooling limits are 48 to 99°F (7 to 35°C).
Check Installer Setup numbers 34 and 35 and reconfigure the setpoint stops.
(Continued)
69-1049—1
8
Page 9
T8501D DELUXE ZONE THERMOSTAT
Troubleshooting Guide
(Continued).
Symptom Possible Cause Action
Heating will not come on.
Cooling will not come on.
System on indicator (flame=heat, snowflake=cool) is displayed, but no warm or cool air is coming from the registers.
System on indicator is not displayed, but heating or cooling system is operating
Outdoor temperature not displayed
Outdoor temperature display is incorrect
a
Available on select models.
No power to the thermostat. • Check that C terminal is connected to the system transformer.
Thermostat minimum off time is activated.
System selection is not set to Heat.
No power to the thermostat. • Check that C terminal is connected to the system transformer.
Thermostat minimum off time is activated.
System selection is not set to Cool.
Fan operation set for 00 (conventional heat) when it should be set for 01 (electric heat).
Conventional heating equipment turns on the fan when the furnace has warmed up to a setpoint.
Heating equipment is not operating.
•Check for 24 Vac between C and R and between R and W terminals. — If missing 24 Vac:
— check if the circuit breaker is tripped—reset the
circuit breaker. — check if the system fuse is blown—replace the fuse. — check if the system switch at the equipment is in the
Off position—set to On position. — check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
Wait up to five minutes for the system to respond.
Set system selection to Heat.
•Check for 24 Vac between C and R and between R and Y terminals. — If missing 24 Vac:
— check if the circuit breaker is tripped—reset the
circuit breaker. — check if the system fuse is blown—replace the fuse. — check if the system switch at the equipment is in the
Off position—set to the On position. — check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
•Wait up to five minutes for the system to respond.
•Enter Installer Setup number 33. Reconfigure minimum off time (if required).
Set system selection to Cool.
Enter Installer Setup number 02 and reconfigure the fan operation.
Wait a minute after seeing the On indicator and then check the registers.
Verify operation of heating equipment in self-test.
Option not activated. Enter Installer Setup number 36 and reconfigure to 00.
Option not activated. Enter Installer Setup number 24 and set to 01. Thermostat must
a
Outdoor sensor is connected incorrectly.
a
Wrong sensor. Replace sensor with C7089B1000 sensor.
have OT terminals and a C7089B1000 installed.
Refer to C7089B1000 installation instructions and check wiring between the thermostat and sensor.
9
69-1049—1
Page 10
T8501D DELUXE ZONE THERMOSTAT
69-1049—1
10
Page 11
T8501D DELUXE ZONE THERMOSTAT
11
69-1049—1
Page 12
T8501D DELUXE ZONE THERMOSTAT
Honeywell Trol-A-Temp
Helping You Control Your World