Honeywell t8501A, t8501B, t8501C, t8501D Installation Instructions Manual

T8501A,B,C,D
Microelectronic Thermostats
INSTALLATION INSTRUCTIONS
APPLICATION
The T8501 Microelectronic Thermostat provides electronic control of 24 Vac single-stage heating and cooling systems. Refer to Table 1 for a general description of the thermostat. All T8501 Thermostats require a common wire to supply power.
Table 1. Description of T8501 Thermostats.
T8501 System Changeover
A Heat only None None None — B Heat only None Heat-Off On-Auto Select models have only a system switch or fan
C Heat-Cool Manual Heat-Off-Cool On-Auto System and fan selections are done by
D Heat-Cool Automatic Heat-Off-Cool-Auto On-Auto System and fan selections are done by
System
Selection
Fan
Selection Comments
switch and some models have both.
switches.
keyboard.
RECYCLING NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do control in the trash.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat.
not
place your old
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After completing installation, use these instructions to check out the product operation.
Copyright © 1996 Honeywell Inc. • • All Rights Reserved
CAUTION
Disconnect power supply to prevent electrical shock or equipment damage.
Location
Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1.
Do not install the thermostat where it can be affected by: —drafts, or dead spots behind doors and in corners. — hot or cold air from ducts. —radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.
Wallplate Installation
The thermostat can be mounted horizontally on the wall or on a 2 in. x 4 in. wiring box. Position wallplate horizontally on the wall or on a 2 in. x 4 in. wiring box.
Position and level the wallplate (for appearance
only). The thermostat will function properly even when not level.
X-XX UL
69-0959
T8501A,B,C,D MICROELECTRONIC THERMOSTATS
WALL ANCHORS (2)
NO
WIRES THROUGH WALL
YES
NO
5 FEET
[1.5 METERS]
Fig. 1. Typical location of thermostat.
WALL
Position the wallplate over the holes, pulling wires
through the wiring opening.
Loosely insert the mounting screws into the holes.
Tighten mounting screws.
WIRING
All wiring must comply with local electrical codes and ordinances. Refer to Fig. 3 through 5 for typical hookups. A letter code is located near each terminal for identifica­tion.
NO
M10106
MOUNTING HOLES
MOUNTING SCREWS
Fig. 2. Mounting the wallplate.
Use a pencil to mark the mounting holes. See Fig. 2.
Remove the wallplate from the wall and drill two
3/16 inch holes in the wall (if drywall) as marked. For firmer material such as plaster or wood, drill two 7/32 inch holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
69-0959
M6530
CAUTION
Disconnect power before wiring to prevent electrical shock or equipment damage.
Loosen the terminal screws on the wallplate and
connect the system wires. See Fig. 6.
IMPORTANT
Use 18 gauge, color-coded thermostat cable for proper wiring.
Securely tighten each terminal screw.
Push excess wire back into the hole.
Plug the hole with nonflammable insulation to
prevent drafts from affecting the thermostat.
2
T8501A,B,C,D MICROELECTRONIC THERMOSTATS
M4826
FOR WRAPAROUND INSERTION STRIP 7/16 IN. (11 MM).
FOR STRAIGHT INSERTION STRIP 5/16 IN. (8 MM).
THERMOSTAT
T
2
OUTDOOR TEMPERATURE SENSOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
AVAILABLE ON SELECT MODELS.
2
CW
HEATING RELAY OR VALVE COIL
1
M4822
L1 (HOT)
L2
Fig. 3. Typical hookup in heat only application.
THERMOSTAT
2
COMPRESSOR CONTACTOR
HEATING RELAY OR VALVE COIL
1
M4821
OUTDOOR TEMPERATURE SENSOR
COOL CHANGEOVER VALVE OR DAMPER
HEAT CHANGEOVER VALVE OR DAMPER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
AVAILABLE ON SELECT MODELS.
2
FAN RELAY
ROTO
ROTOTCBOGYW
L1 (HOT)
L2
THERMOSTAT
T
OGYC BW
Rc
2
OUTDOOR TEMPERATURE SENSOR
COMPRESSOR CONTACTOR
FAN RELAY
COOL CHANGEOVER VALVE OR DAMPER
1
L1 (HOT)
L2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
AVAILABLE ON SELECT MODELS.
2
3
JUMPER Rh TO Rc IN A SINGLE TRANSFORMER SYSTEM.
Fig. 5. Typical hookup in heat and cool
system with two transformers.
HEAT CHANGEOVER VALVE OR DAMPER
HEATING RELAY OR VALVE COIL
1
M4820
3
RhOTO
L1 (HOT)
L2
Fig. 4. Typical hookup in heat and cool
system with one transformer.
Mounting Thermostat
Engage tabs at the top of the thermostat and
wallplate. See Fig. 7.
Press lower edge of case to close and latch.
Fig. 6. Proper wiring technique.
3
69-0959
T8501A,B,C,D MICROELECTRONIC THERMOSTATS
A.
ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE.
B.
PRESS LOWER EDGE OF CASE TO LATCH.
Fan settings control the system fan as follows:
On: Fan operates continuously. Auto: Equipment controls fan.
The system default setting is Heat and the fan default setting is Auto. Use the keyboard or system and fan switches, depending on model, to change to the desired settings. See Figs. 9 and 10.
i
HEAT OFF COOL
ON AUTO
SYSTEM
Selection for heating or cooling equipment operation.
Heat - Heating equipment Off - No equipment Cool - Cooling equipment
HEAT OFF COOL
ON AUTO
FAN
On - Fan runs continuously Auto - Fan runs when
heating or cooling equipment operates
M6798A
Fig. 7. Mounting thermostat on wallplate.
NOTE: To remove the thermostat from the wall, first pull out
at the bottom of the thermostat; remove top last.
Using Thermostat Keys
The thermostat keys are used to:
• set temperature,
•display present setting,
• configure Installer Setup,
• check Self-Test,
•display outdoor temperature (select models).
Select models have keys to:
• set the system operation,
• set the fan operation.
See Fig. 8 for key information.
INCREASE TEMPERATURE SETTING
i
DECREASE TEMPERATURE SETTING
DISPLAY PRESENT SETTINGS AND SCROLL THROUGH INSTALLER SETUP MODES (INFORMATION KEY)
M6801
Fig. 8. Thermostat key locations and descriptions.
SETTINGS
System and Fan Settings
System settings control the thermostat operation as follows:
Heat: The thermostat controls the heating. Off: Both the heating and cooling are off. Cool: The thermostat controls the cooling. Auto: The thermostat automatically changes between
heating and cooling operation, depending on the indoor temperature.
M10146
Fig. 9. T8501C system and fan switches location.
i
Fan
System
Press to select
Press to select
heating or cooling
heating or cooling
equipment.
equipment. Em. Ht.
-Emergency heating
On— Fan runs continuously
Heat—Heating equipment
Auto—Fan runs when Off — No equipment Cool—Cooling equipment Auto—Thermostat
automatically selects heating and cooling equipment.
CHECK LIGHT ON SELECT MODELS
1
heating or cooling equipment operates
System
Fan
1
System
Fan
M10147
Fig. 10. T8501D system and fan keys location.
NOTE: Always press the system and fan keys with your
fingertip or similar blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard.
Temperature Settings
The default setpoint for heat is 70°F (21°C) and for cool is 78°F (25.5°C). Press the increase or decrease key to change the present setting. To change between heat and cool, press the Information i key until the setting to be changed appears.
INSTALLER SETUP
NOTE: For most applications, the thermostat factory-
settings do not need to be changed. Review the factory settings in Table 2 and if no changes are necessary, go to the Installer Self-Test section.
69-0959
4
Loading...
+ 8 hidden pages