Honeywell T7411B PRODUCT DATA

T7411B

FLEXIBLE DUCT TEMPERATURE SENSORS

PRODUCT DATA

FEATURES

PT1000 or NTC20ktemperature sensing element

Wide sensing range

High accuracy

GENERAL

The T7411B Flexible Duct Temperature Sensors are used in ventilating and air conditioning systems to measure discharge, return, or outside air temperature. They are designed for duct mounting.

These sensors are used in the following control systems:

Excel 5000

MicroniK 200

MicroniK 100

Excel Classic

Excel Plus

High Performance Excel Plus

Excel EMC

SPECIFICATION

Nominal value

 

PT1000

1000 Ω at 0 °C

NTC20kΩ

20 kΩ at 25 °C

Accuracy

 

PT1000

IEC751 Class B

 

0.3 K +0.5% • |t| (t in °C)

NTC20kΩ

0.3 K at 25 °C

Sensitivity

 

PT1000

≈ 3.85 Ω / K

NTC20kΩ

≈ -934.5 Ω / K at 25 °C (non-linear)

Response time (at air velocity of 5 m/s [16.4 ft/s])

T7411B

τ0.5 ≈ 45 s

Electrical connection

 

T7411B

terminals for 2 x 1.5 mm² cable

Ambient Limits (wiring box)

Storage temperature

-35...+70 °C (-31…+158 °F)

Humidity

5…95% rh, non-condensing

Safety (terminal box)

 

Protection standard

 

T7411B

IP54

Flame retardant

V1 as per UL94

 

Plastic (PC)

Dimensions

See Fig. 1 on page 2

or other systems using PT1000 or NTC 20kΩ temperature sensing elements.

® U.S. Registered Trademark

 

EN0B-0444GE51 R0907

Copyright © 2007 Honeywell Inc. • All rights reserved

 

 

 

 

Honeywell T7411B PRODUCT DATA

T7411B FLEXIBLE DUCT TEMPERATURE SENSORS

Models

OS number

Sensor type

Sensing range

 

 

 

T7411B1009

NTC20kΩ

-40...+80 °C

 

 

 

T7411B1017

PT1000

-40...+80 °C

 

 

 

DIMENSIONS OF T7411B

50 (1.97)

33 (1.3)

4 (0.16)

65

(2.55)

 

 

 

 

 

 

 

 

 

 

 

22 (7/8”)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

450 (17 3/4”)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

case hole diameter

 

 

 

 

 

 

 

 

7 (0.28)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

allows Pg9 cable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 1. Dimensions of T7411B in mm (inches)

INSTALLATION

wiring run

max. length

Sensor to controller

200 m (660 ft)

NOTE: Use shielded wiring in areas with high EMI. Maintain a minimum distance of 15 cm (5.9’’) between sensor lines and 230 Vac power lines.

Honeywell

Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative:

Automation and Control Solutions

Honeywell GmbH

Böblinger Straße 17

D-71101 Schönaich

Phone: (49) 7031 63701

Fax: (49) 7031 637493

http://ecc.emea.honeywell.com