Honeywell T7400 User Manual

‘.
,
Con~raiulations! You are the owner of on&of the finest thermostats t?“w produced by Honeywell.
The unique features of the T7400 Programmable Commercial Thermostat,satisfy the special requirements of commercial single zone aif
conditioning systems, and provide convenience and temperature control accuracy that is un~oralleled in the industrv n7is thermostat also includes enerav saving feaiures which allow it to minimize the &rgy
needed to maintain comfort conditions by using
outdoor air for ‘We” cooling whenever possible. A thorough review of this Owner’s Guide will help you
identify those features which will maximize comfoit, convenience and savings in your application.
Terms and words that may not be familiar to you are explained in the glossary at the end of this guide.
STARTUP
When power is first applied, an internal startup
prcgrom begins. This reauires 1 minute to complete. and takes place after any total loss of power (supply
voltage and backup battery). During this titie, default temperature set point values
exe used for temperature control. These CIIC: heating 68 F (20 C]. economizer 72 F (22 C), and cooling 78 F (26 C]. Following the statiup period. you can enter new set points which will @e ,used in place of these
default values. Should a power failure occur after your time and
temperature schedule entries are made, the backup
battery will maintain your schedule. As long as either system or battery backup power is present, your program is available and will be used for’ temperature control.
OPERATION
IMPORTANT: Note that the T7400 svstem will not read instonton~usly to s&t point changes. Except os
mentioned below, the minimum stage on- and otf-
times will oIwoys be followed. Although the temperature control monitoring occurs constantly, the temperature display updates approximately every 2 minutes unless the ROOM TEMPERATURE key is depressed.
The temperature control program takes effect after the startup period. If space temperature is far below set point, CI stage of heat could turn on within 1 minute of startup. This is the only exception to the heating minimum off-time of 2 minutes.
If mechanical cooling is called for. the minimum off­time of 4 minutes will elapse after the 1 minute startup period (5 minutes total).
MINUTES
1 COOLING 1 HEATING 1
>
Fig. 1 -Thermostat cycle timing illustrations
OPERATIONAL
xe temizerature = 70 F; heat 1
,
i
MINUTES
I
POWER-UP
I I
0 . Power on (1 st applied or after ioss of
supply voltage and backup
/I/
battery.
7
PROGRAM SCHEdJCE
Each day of the week ccl” be individually programmed with an Occupied and an Unoccupied period to make maximum use of schedule variations. In addition to the Occupied and Unoccupied mode
of thermostat operation. there is CI third mode called
Intelligent Recovery”. Occupied operation is based on 3 set points: heat.
economizer. and cool. Unoccupied operation is based on 2 set points: heating and cooling. l%he
economizer is operational during the Unoccupied
period, but at a s&point fixed at 3 F (2 C) helow the Unoccupied cool set point.
Fig. 2-17400 program schedule and temperature control.
Intelligent Recovery’“, based on CI set point ramping
feature, is used when switching from Unoccupied operation to Occupied operation. This selves energy
by varying switchover time depending on prevailing weather conditions. The time used to achieve the occupied set point is the shortest possible time that will still ensure comfort conditions are reached by the occupied stat time.
I
10
Convenient keyboard layout provides effortless
program entry. .youi avenue to maximum energy
and cost savings. The following pages provide function-by-function
instructions to progrcrr the T7400 Programmable Commercial Thermostat.
The following general steps are required to enter your weekly time and temperature schedule into the T7400. See the pages indicated for detailed
programming instructions.
l
Enter the correct time and day. (3ee pages 14 through 17.)
l
Enter the temperature set points you want for programming step. ~For example. to review the heating. economizer, and cooling system
l
To review program entries. simply press the same function keys used to begin each
ECONOMIZER temperature set point, press the
operation. ECONOMIZER key.
l
(See pages 18 through 27.)
l
For each day of the week. enter starting time for
For sample schedules and their programs. see pages 32 through 37.
the periods when your building will be occupied and unoccupied. (See pages 28 through 31.)
11
I
SELECTING~HE DESIRED OPERATING
DISPLAY
. PRESENT TIME and ROQM TEMPERATURE keys
•~ If neither key is pressed, T7400 will automatically
(Optional)
allow you to select c@tinuous display of time or temperature. respectively.
revert to a display of,,present time within 2 minutes of the last keypress.
l
T7400 will default to Occupied mode and control to respective Heat, Economizer. and Cool set points of 68 F. 72 F, and 78 F until thermostat is reprogrammed.
LOSS Of External Power
l
Blinking display of time or temperature
indicates loss of external power. The backup botteiy maintains your time and temperature schedule during the power loss.
l
Keyboard and red indicator lights exe
inoperative while the 77400 is on batteN power
12
PROBLEM INDICATORS
Loss of Stored Program
l
Blinking display of 3 dashes (- -) indicates 10% of stored program. (Three steady dashes
represent an occupied or unoccupied time slot that is not programmed.)
TEMPORARILY OVERRIDING THE 17400’s PROGRAM
l
3 HOUR OCCUPIED key allows you to <activate the temperature set points programmed for your building’s occupied period for 3 hours.
l
‘Once pressed. the 3 HOUR OCCUPIED key can
be pressed again to cancel this command,
and return the T7400 to program control.
l
CONTINUOUS UNOCCUPIED key allows you to activate the temperature set points programmed for your building’s unoccupied period for an indefinite time.
(optional)
Failure of Temperature Sensor
. While in the ROOM TEMP display mode. 0
display of (- “) indicates failure of wiring or the temperature sensor.
. System will safely deenergize all heating and
cooling stages if cI sensor failure occurs.
l Once
l
l
pressed. the CONTINUOUS UNOCCUPIED
key must be pressed again to cancel this command, and return the 17400 to piogiam control.
The 3.HOUROCCUPIED and
CONTINUOUS UNOCCUPIED keys cannot be used at the same tir&The last key pressed will be in control.
Red indicators near the display window show when 3 HOUR OCCUPIED and CONTINUOUS UNOCCUPIED ovenide functions are activated.
13
Loading...
+ 16 hidden pages