FOR SINGLE- OR MULTI-STAGE CONVENTIONAL/HEAT PUMP
SYSTEMS
INSTALLATION INSTRUCTIONS
APPLICATION
The T7351 Commercial Programmable Thermostat
controls 24 Vac commercial single zone heating,
ventilating and air conditioning (HVAC) equipment. The
T7351 consists of a thermostat and subbase. The
thermostat includes the display and keypad for 7-day
programming. The subbase includes equipment control
connections. The subbase mounts on the wall and the
thermostat mounts to the subbase.
MERCURY NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash. Dispose of properly.
Contact your local waste management authority
for instructions regarding recycling and the
proper disposal of an old control. If you have
questions, call Honeywell Customer Care Center
at 1-800-468-1502.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check ratings given in instructions and on the
product to ensure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage
Hazard. Can shock individuals or short
equipment circuitry.
Disconnect power supply before installation.
Location
Do not install the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
IMPORTANT
To avoid electrical interference, which can
cause erratic performances, keep wiring runs as
short as possible and do not run thermostat
wires adjacent to the line voltage electrical distribution systems. Use shielded cable. The
cable shield must be grounded only at the controlled equipment case.
Subbase
WHEN USED TO SENSE ROOM TEMPERATURE
Install the thermostat about 5 ft. (1.5m) above the floor in
an area with good air circulation at average temperature.
(See Fig. 1.)
WHEN NOT USED TO SENSE ROOM TEMPERATURE
When using the remote-mounted temperature (and
humidity) sensor(s) to sense ambient conditions, install
the thermostat in an area that is accessible for setting
and adjusting the temperature and settings.
Install the remote-mounted sensor(s) about 5 ft. (1.5m)
above the floor in an area with good air circulation at
average temperature (See Fig. 1).
If multiple remote sensors are required, they must be
arranged in a temperature averaging network consisting
of four sensors (See Fig. 2).
NOTE: Only T7770 models with no setpoint adjustment
can be used for temperature averaging.
62-0258
T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
YES
NO
NO
NO
5 FEET
(1.5 METERS)
T4T3
T7770A
TT
SUBBASE
T7770A
T
T
Fig. 1. Typical location of thermostat or
remote-mounted sensor.
Mounting Subbase
The subbase mounts horizontally.
IMPORTANT
• When using the internal temperature or humidity
sensor, the device must be mounted horizontally
(with the LCD facing upwards). Precise leveling
is not needed.
• When using remote room temperature and
humidity sensors, thermostat mounting
orientation does not matter.
Wall mounting (using standard drywall screws) is
standard. Mounting to a 2 in. by 4 in. (50.8 mm by 101.6
mm) wiring box can be accomplished:
— for a horizontal box, no extra hardware is required.
— for a vertical box, part 209651A is required.
— Mount to European standard wall box (having 2.4 in.
(60.3 mm) between mounting screws in a horizontal
line) with or without adaptive hardware.
1. Position and level the subbase.
NOTE: A level wallplate is only for appearance.
The thermostat functions properly when
not level.
2. Use a pencil to mark the mounting holes. (See
Fig. 3).
3. Remove the subbase from the wall and drill two 3/
16 in. (4.8 mm) holes in the wall (if drywall) as
marked. For firmer material such as plaster or
wood, drill two 7/32 in. (5.6 mm) holes.
4. Gently tap anchors (provided) into the drilled holes
until flush with the wall.
5. Position the subbase over the holes, pulling wires
through the wiring opening.
6. Loosely insert the mounting screws into the holes.
7. Tighten mounting screws.
T
MOUNTING
HOLES
T7770A
T
T
M19606A
T7770A
M4823A
Fig. 2. Four T7770A Sensors providing temperature
averaging network for T7351 Thermostat.
WALL
ANCHORS
(2)
T
WIRES THROUGH WALL
Fig. 3. Mounting the subbase.
Mounting Thermostat on Subbase (Fig. 4)
With the subbase installed, mount the thermostat:
1. Engage top subbase tabs into the thermostat top.
2. Swing the thermostat down.
3. Press the lower edge of the case to latch.
NOTE: To remove the thermostat from the wall, first pull
out at the bottom of the thermostat; then remove
the top.
MOUNTING
SCREWS
M19608
62-02582
T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
A.
ENGAGE TABS AT TOP OF THERMOSTAT AND SUBBASE OR WALLPLATE.
B.
PRESS LOWER EDGE OF CASE TO LATCH.
M19609
Fig. 4. Mounting thermostat on subbase.
Wiring
Follow equipment manufacturer wiring instructions when
available. Refer to the Wiring Diagram section for typical
hookups. A letter code is located near each terminal for
identification.
IMPORTANT
All wiring must comply with local electrical codes
and ordinances.
NOTE: Maximum (and recommended) wire size is 18-
gauge. Do not use wire smaller than 22-gauge.
1. Loosen subbase terminal screws and connect system wires.
2. Securely tighten each terminal screw.
3. Push excess wire back into the hole in the wall.
4. Plug the hole with nonflammable insulation to pre-
vent drafts from affecting the thermostat.
SETTINGS
Using Thermostat Keys
The thermostat keys are used to:
• set current time and day,
• program times and setpoints for heating and cooling,
• override the program temperatures,
• display present setting,
• set system and fan operation.
NOTE: See Fig. 5 for keypad information.
Setting Temperature
Refer to Table 2 for the default temperature setpoints. To
set the Occupied and Not Occupied Heat and Cool
setpoints, simply press the Heat and Cool button under
the Occupied or Not Occupied area of the keypad. To set
the Standby Heat setpoint, press both the Occupied and
Not Occupied Heat buttons simultaneous. To set the
Standby Cool setpoint, press the Occupied Cool and Not
Occupied Heat buttons simultaneously.
Setting System and Fan
System default setting is Auto. Fan default setting is On.
NOTE: Use System and Fan keys to change settings.
System Settings
— Auto: Thermostat automatically changes between
heating and cooling based on indoor temperature.
— Cool: Thermostat controls cooling.
— Off: Heating, cooling, and fan are all off.
— Heat: Thermostat controls heating.
— Em Heat: Auxiliary heat serves as first stage.
Compressor stages are locked off.
Fan Settings
— On: See Table 1.
— Auto: Fan always cycles with call for heat or cool.
— Conventional: The equipment (i.e. plenum switch)
controls fan operation in heat mode. Thermostat
controls fan operation in cool mode.
— Electric Heat: Thermostat controls fan operation in
both heat and cool modes.
NOTES: Fan operation can extend (delay Off) after the
heating/cooling turns off:
—Heating choices are 0 or 90 seconds.
—Cooling choices are 0 or 40 seconds.
Table 1. Fan On Control Logic.
OccupancyCall for Heat/Cool
ScheduledSensor SignalYesNo
OccupiedOccupiedOnOn
OccupiedStandbyOn
Standby—OnOn
Not Occupied —On
a
In heat mode, when set for conventional heat, the equipment (i.e. plenum switch) could power the fan despite
the T7351.
Off
Off
a
a
362-0258
T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
Temperature
Occupied
HEATHEATCOOLCOOL
Not Occupied
Schedule
Clear
Start Time
Fig. 5. Thermostat key locations.
INSTALLER SETUP
For most applications, the thermostat factory settings do
not need to be changed. Review the factory settings in
Table 2.
NOTE: When power is first applied to the thermostat, the
display will show all segments (see Fig. 6).
Table 2. Default Setpoints.
ControlOccupiedNot Occupied Standby
Heating 70° F (21° C) 55° F (13° C)67° F (19° C)
Cooling 75° F (24° C) 85° F (29° C)78° F (26° C)
Temporary Standby
Not Occupied12
System
EmHeatOff CoolAuto
StartTime
MonTue WedTh uFri
Set ScheduleSet
SatSunHol
DehumidOnAuto
AM
PM
Room
MinsDays
Fan
%
M19611
Fig. 6. LCD display of all segments.
CAUTION
Possible Equipment Damage.
Fan must be running when system is
operating.
Heat pump and electric heat systems must be
configured correctly to prevent equipment damage
caused by the system running without the fan.
Set Day/Time
DayTime
HEAT COOL
CopyNot OccupiedOccupiedDay
SystemFan
Override
Temporary
Occupied
ON AUTO
Temp or ar y
Not Occupied
Run
Schedule
M19610
Setup Using Keypad
The installer uses the Installer Setup to customize the
thermostat to specific systems
A combination of key presses are required to use the
Installer Setup feature:
1. To enter the Installer Setup, press and hold both the
Run Schedule and the Copy keys until DEGREES
00 (or DEGREES 01) displays.
NOTE: Installer Setup will display WAIT and is
unavailable for 30 seconds after power up.
2. To advance to the next Installer Setup number,
press .
NOTE: Pressing Run/Copy again while in this
mode displays the T7351 firmware version
number.
3. To return to a Setup item, cycle through the options.
4. To change a setting, use the up ! or down " key.
5. To exit the Installer Setup, press Run Schedule.
6. Display prompts SAV CFG (save configuration).
a. If you want to save the new configuration, use
the up ! or down " key to change NO to YES
before pressing Run Schedule.
b. If you want the configuration to remain as it was
before starting this change, ensure the
display indicates SAV CFG NO and press Run Schedule.
NOTE: Installer Setup is automatically exited after five
minutes with no key pressed. Upon this automatic exit, all changes are lost.
62-02584
Configuration
Configuration can be done with the keypad using the
Installer Setup (ISU).
T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 3. Installer Setup.
TextDefaultChoicesNotes
DEGREES 00 -1 Degree Temperature Format
CLOCK00 - 1Clock Display Format
KEYLOCK 00 - 3Keypad Lockout Level
HEATPMP 00 - 2Application Type Selection
COOLSTG 10 - 4Number of Cooling Stages
HEATSTG 10 - 3Number of Heating Stages
AUX STG 00 - 2Only shown when Heat Pump is selected
AUX CON 00 - 3Aux Contact Functionality
WALLMOD 00 - 3Remote Room Sensor Selection
OATSENS 00 - 1Outdoor Air Sensor Selection
DATSENS 00 - 1Discharge Air Sensor Selection
HUMSENS 00 - 2Room Humidity Sensor selection
OCCSENS 00 - 1Occupancy Sensor Selection
FAN HT00 - 1Fan Operation on Heat
0: Degrees F
1: Degrees C
0: 12 hour
1: 24 hour
0: None
1: Lockout all keys except Set Day, Set Time, Set Date, Set Holidays,
Temporary Occupied, Temporary Not Occupied, System, Fan, Up, Down and
Information
2: Lockout all keys except Set Day, Set Time. Set Date, Set Holidays,
Temporary Occupied, Temporary Not Occupied, Up, Down and Information
3: Lockout all keys except Information
0: Conventional
1: Heat Pump - Cooling (Energize O/B on call for cool)
2: Heat Pump - Heating (Energize O/B on call for heat)
0: 0 Stages of Cooling
1: 1 Stages of Cooling
2: 2 Stages of Cooling
3: 3 Stages of Cooling
4: 4 Stages of Cooling (W3 will be used as 4th stage relay)
0: 0 Stages of Heating
1: 1 Stages of Heating
2: 2 Stages of Heating (This is the max if 4 cooling stages is selected)
3: 3 Stages of Heating
0: 0 Aux Stages
1: 1 Aux Stages
2: 2 Aux Stages
0: Time of Day
1: Economizer
2: Dehumid - Hot Gas Bypass
3: Simple Dehumid
0: Local sensor only
1: T7770A/D (Remote Sensor, No Remote Setpoint, Bypass 0)
2: T7770B/C (Remote Sensor, Remote Setpoint, Bypass 0)
3: T7771 (Remote sensor, Remote Setpoint, Bypass 1)
(Display only if sub-base 2, 3, 4+)
(This item is not displayed when
0: None
1: Remote Outdoor Air Sensor
0: None
1: Remote Discharge Air Sensor
0: None
1: On Board Sensor
2: Remote Sensor
0: None
1: Remote Occ Sensor
0: Conventional (Equipment controls Fan)
1: Electric (Thermostat turns on Fan with call for Heat)
562-0258
T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 3. Installer Setup. (Continued)
TextDefaultChoicesNotes
XFAN HT YESYES or NOExtended Fan on Heat
XFAN CL NOYES or NOExtended Fan on Cool
STRTDEL 00 - 15Sequential Start Delay
ADVANCE NOYES or NOAdvanced Settings
TMP LIM30 - 5Temporary Setpoint Adjustment
TMP OCC 31 - 8Temporary Occupied Duration
TMP CAL 0-4 - 3Temporary Display Adjustment
MINCOOL 45° F
MAXHEAT 90° F
(7° C)
(32° C)
45° - 99° F
(7° - 37° C)
40° - 90° F
(4° - 32°)
HEATLCK NOYES or NOHeating Lockout (Only displayed if Outdoor Air Sensor is selected)
HTLCKSP 70° F
(21° C)
-40° - 120 ° F
(-40° - 49° F)
COOLLCK NOYES or NOCooling Lockout (Only displayed if Outdoor Air Sensor is Selected)
CLLCKSP 35° F
(2° C)
-40° - 120° F
(-40° - 49° C)
DAT LLNOYES or NODischarge Low Limit (Only displayed if Discharge Air Sensor is Selected)
DATLLSP 45° F
(7° C)
35° - 60° F
(2° - 16° C)
DAT HLNOYES or NODischarge High Limit (Only displayed if Discharge Air Sensor is Selected)
DATHLSP 110° F
(43° C)
65° - 140° F
(18° - 60° C)
DEHUMID 00 - 5Dehumidification
NO: None
YES: 90 seconds
NO: None
YES: 40 seconds
0 to 150 seconds in 10 second increments
NO: Hide
YES: Show
0: 0 Deg. F
1: 1 Deg. F
2: 2 Deg. F
3: 3 Deg. F
4: 4 Deg. F
5: 5 Deg. F
1 to 8 hours
0 - 3 = 0 to 3 DDF
4 - 7 = -4 to -1 DDF
Min Cool Setpoint
Max Heat Setpoint
NO: None
YES: Enabled
Heating Lockout Temperature
(Display only if Remote Outdoor Air Sensor is configured)
NO: None
YES: Enabled
Cooling Lockout Temperature
(Display only if Remote Outdoor Air Sensor is configured)
NO: None
YES: Enabled
Discharge Low Temp Limit
(Display only if Discharge Sensor is configured)
NO: None
YES: Enabled
Discharge High Temperature Limit
(Display only if Discharge Sensor is configured)
0: None
1: MinOn Time
2: Reset Temp Setpoint
3: Reset w/ MinOn
4: Reheat
5: Reheat w/ Min On
MAXCLRT 60 - 20 DDF/HR Maximum Cool Recovery Ramp Rate (Only Displayed if Outdoor Sensor is
MINCLOA 90° F
MAXCLOA 70° F
DSTMON1 30 - 12DLS Spring Month
DSTDAY1 400 - 31, 32 - 74 DLS Spring Day
DSTMON2 110 - 12DLS Fall Month
DSTDAY2 330 - 31, 32 - 74 DLS Fall Day
HT RESP 10 - 30: Standard - 3 cph
CL RESP 00 - 10: Standard - 3 cph
(4° C)
(32° C)
(21° C)
-20° - 120° F
(-29° - 49° C)
-20° - 120° F
(-29° - 49° C)
-20° - 120° F
(-29° - 49° C)
Maximum Heat Outdoor Air Temperature (Only Displayed if Outdoor Sensor is
Selected)
Selected)
Minimum Cool Outdoor Air Temperature (Only Displayed if Outdoor Sensor is
Selected)
Maximum Cool Outdoor Air Temperature (Only Displayed if Outdoor Sensor is
Selected)
(DayLight Savings options only display when Date is valid)
0 - 31 = Day of Month
32 = Last Day of Month
33 = First Sunday
etc…
0 - 31 = Day of Month
32 = Last Day of Month
33 = First Sunday
etc…
1: Medium - 6 cph
2: Fast - 9 cph
3: Super Fast - 20 cph
1: Fast - 4 cph
Holidays and 365 - Day Clock
The T7351can be configured to schedule up to 10
separate holidays, each with a duration of up to 99 days.
To enable this function, the user must set the date:
1. Press Set Day and Set Time keys simultaneously.
2. Use the Up/Down keys to set the date to YES, then
press the key.
3. Use the Up/Down keys to set the month, then press
the key.
4. Use the Up/Down keys to set the day, then press
the key (See Table 4 for valid day choices).
5. Use the Up/Down keys to set the year, then press
the key.
1. Press the “Temporary Occupied” and Temporary
Not Occupied” keys simultaneously.
2. The month (MON) of the first holiday is then displayed (00 means the holiday is ignored).
3. Use the Up/Down keys to set the month, then press
the key.
4. Use the Up/Down keys to set the day, then press
the key (see Table 4 for valid day choices).
5. Use the Up/Down keys to set the duration.
The first holiday is now set and pressing the key will
take you to programming the second holiday (denoted by
the number 2 on the screen).
762-0258
T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 5. T7351 Key Function Summary.
GroupingButtonDefinition
InformationDown ArrowLowers setpoint, day, or time. When setting times or temperatures, hold key
InformationObtains information (where humidity “high-limit” can be set), cycles through
Up ArrowRaises setpoint, day, or time. When setting times or temperatures, hold key
Temperature Occupied
SetDaySets day of week. Tapping key with 'Set Value' segment on increases current
OverrideTemporary
ScheduleDaySelects day schedule to modify. (Used also with copy key.)
Heat
Occupied
Cool
Not
Occupied
Heat
Not
Occupied
Cool
TimeSets time. Tapping key with “Set Value” segment on increases time in one
Occupied
Temporary Not
Occupied
OccupiedSelects occupied event start times for specified day. Repeatedly press this
Not OccupiedSelects not occupied event start times for specified day. Repeatedly press
Clear Start TimeClears start time for specified period and day.
"
down to continuously decrease value. Also can make temporary change in
temperature setpoint.
setup options.
!
down to continuously increase value. Also can make temporary change in
temperature setpoint.
Sets Occupied Heat setpoint.
Sets Occupied Cool setpoint.
Sets Not Occupied Heat setpoint.
Sets Not Occupied Cool setpoint.
day (same effect as Up Arrow key).
hour increments.
Temporary occupied setting for length of time defined by installer. User can
modify setpoints.
Sets holiday length. User selects number of days (“0”-”99”), or “---” for
continuous override.
key to toggle between two occupied events.
this key to toggle between two not occupied events.
CopyCopies schedule from one day to another.
SystemSelects System Mode. Toggles through Em Heat, Heat, Off, Cool, and Auto.
Fan
Run ScheduleResumes running schedule (cancels Temporary Occupied action, Holiday,
a
On: Continuous fan operation (occupied and standby). During not occupied periods, fan cycles with call for heat or cool.
Auto: Fan cycles with call for heat or cool during all periods. (See Product Data Sheet, form 63-2605, for more details).
NOTES: The display returns to default screen after pressing Run Schedule (or after a period of time without keypress):
—ten seconds: when returning from temporary setpoint changes, info screen, temp occ, and temp not occ.
—one minute: when returning from setting clock/day.
—ten minutes: when returning from System Checkout.
—five minutes: when returning from all other modes.
Selects fan operation mode. Toggles between On and Auto.
and/or Temporary setpoint changes.)
a
Special Functions
Restore Factory Configuration (Run/Clear)
IMPORTANT
This operation erases current configuration and
restores factory defaults for all configuration,
parameters, setpoints and schedules. To regain
the old requires device reconfiguration.
62-02588
1. Press both Run Schedule and Clear StartTime.
2. The display gives the option to revert to FAC CFG.
a. To restore the factory defaults, press up ! or
down " until the display indicates YES.
b. To cancel this option, ensure the display
indicates NO.
3. Press Run Schedule.
T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
Get Factory Schedule (Info/Clear)
Performing this operation reverts the schedules to the
factory defaults:
1. Press both Info and Clear Start Time.
2. The display gives the option to revert to FAC SCH.
a. To restore the factory schedule, press up ! or
down " until the display indicates YES.
b. To cancel this option, ensure display indicates
NO.
3. Press Run Schedule.
Test Mode (Occupied/Not Occupied/Schedule
Day)
CAUTION
Possible Equipment Damage.
Equipment damage can result if compressor is
cycled too quickly.
The minimum off time for compressors is
bypassed during Test Mode. Equipment damage
can occur if the compressor is cycled too quickly.
Use the Test Mode to check the thermostat configurations
and operation. To start the system test:
1. Press Schedule Day, Occupied and Not Occupied
simultaneously.
2. The display gives the option to TEST.
a. To enter test mode, press up ! or down " until
the display indicates IN TEST.
b. To cancel this option, ensure display indicates
NO TEST.
3. Press Run Schedule.
NOTES:
—To verify whether or not the system test is still
active, repeat the above process.
—The system test times out after ten minutes
with no key pressed.
Save User Schedule (Info/Copy)
Performing this operation saves the current schedule
(including holidays) to memory, overwriting the old saved
schedule:
1. Press both Info and Copy.
2. The display gives the option to revert to SAV SHD.
a. To save the current schedule, press up ! or
down " until the display indicates YES.
b. To cancel this option, ensure display indicates
NO.
3. Press Run Schedule.
Get User Schedule (Info/Run)
Getting the user schedule restores the schedule
(including holidays) from saved memory, overwriting the
schedule currently in use:
1. Press both Run Schedule and Info.
2. The display gives the option to GET SHD.
a. To retrieve the saved schedule, press up ! or
down " until the display indicates YES.
b. To cancel this option, ensure display indicates
NO.
3. Press Run Schedule
DEHUMIDIFICATION
There are five methods through which the T7351 can
control for dehumidification. Three of them modify the
control algorithm, thus providing limited dehumidification
through cooling. The other two use the auxiliary output to
control another device.
NOTE: The dehumidification high limit can be set within
the range of 10 to 90 percent relative humidity.
Control Through Cooling
Configure using some combination of the following:
— Minimum On.
— Reheat.
— Reset.
NOTES:
—These methods operate only during cooling.
—Selecting both Reheat and Reset options can
cause frequent setpoint adjustments. This
selection is not recommended.
Min. ON Time
Dehumidifies by increasing the compressor minimum on
time (normally 3 minutes) by a programmable amount.
This is useful with oversized systems in that it forces the
coils to cool to a point where dehumidification can occur.
NOTES:
—Can force wider temperature swings by cool-
ing when setpoint control does not require it.
—The minimum on time can be set within the
range of 5 to 15 minutes.
—Hysteresis and a minimum timer are used to
ensure this behavior does not change with
every equipment cycle.
Reheat
Dehumidifies by operating cooling during typical off time.
The T7351 maintains the proper setpoint by running the
heat at the same time.
IMPORTANT
At times during Reheat dehumidification, the
T7351 operates heating and the cooling simultaneously. This is normal.
NOTES:
—The heat stage never energizes during
Reheat if more than one cool stage is on.
—Reheat mode cannot occur during heating.
Reset Temp SetPt
The room temperature set point resets to a specified
number of degrees below the actual set point when room
relative humidity (RH) rises above humidity high limit set
point.
Though this may not technically reduce relative humidity
in the room, it reduces the dew point to provide the
customer with a sense of comfort due to a lower
temperature setting in the room.
As long as RH stays above humidity high limit set point,
this set point is maintained.
NOTE: Hysteresis and a minimum timer prevent the set
point from short interval alternation (between
standard and reset set points).
962-0258
T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
Options Utilizing Auxiliary Output
There are two dehumidification options that utilize the
auxiliary output. They are:
— Simple Dehumidification.
— Hot Gas Bypass Dehumidification.
Simple Dehumid(ification)
The auxiliary output:
— Energizes when RH rises above humidity high limit.
— De-energizes when RH drops below humidity high
limit.
NOTES:
—Hysteresis and a minimum timer prevent
short cycling of this output.
—Unlike Dehumid Hot Gas BP the relay
remains energized during calls for multiple
cooling stages.
Dehumid Hot Gas BP
The auxiliary output operates as shown in Table 6.
Table 6. Hot Gas Bypass Dehumidification Logic.
Humidity Cooling Stages Active Auxiliary Output
Highmore than oneDe-energized
Highone or lessEnergized
Lowmore than oneDe-energized
Lowone or lessDe-energized
Auxiliary output during call for multiple cooling stages for
two reasons:
1. This method assumes that the cooling provides
dehumidification.
2. Multiple cooling stages probably provide necessary
dehumidification.
3. Hysteresis and a minimum timer prevent short
cycling of this output.
WIRING DIAGRAMS
OUTDOOR
HUMIDITY
SENSOR
AIR
SENSOR
123456789
MMHC HPHS
MOTION
SENSOR
DISCHARGE
AIR
SENSOR
OSOSASAS
RCX
RH
2
transformers.
AUX
W1G
HEAT
RELAY 1
3
ECONOMIZER
COMPRESSOR
CONTACTOR 2
HEAT
RELAY 2
W2 Y2
Y1
FAN
RELAY
COMPRESSOR
CONTACTOR 1
COOLING
TRANSFORMER
L2
L1
(HOT)
M25324
1
T7770 REMOTE SENSOR
SUBBASE
T5 T6 T7 T4 T3
L2
1
L1
(HOT)
HEATING
TRANSFORMER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
2
WHEN INSTALLED ON A SYSTEM WITH TWO TRANSFORMERS, REMOVE THE FACTORY-INSTALLED JUMPER.
3
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
Fig. 7. Typical hookup of T7351F2010 in two-stage heat and two-stage cool heat pump system with two
OUTDOOR
HUMIDITY
SENSOR
AIR
SENSOR
M
MOTION
SENSOR
OSOSASAS
MHC HP
DISCHARGE
AIR
SENSOR
3
123456789
T3
T7770 REMOTE SENSOR
SUBBASE
T5 T6 T7 T4
HS
L2
2
1
L1
(HOT)
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
ENSURE TRANSFORMER IS SIZED TO HANDLE THE LOAD.
2
3
HEAT/COOL SYSTEMS WITH ONE TRANSFORMER REQUIRE THE FACTORY-INSTALLED JUMPER.
4
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
COMPRESSOR
CONTACTOR 4
W3/Y4 Y3 W2
RCX
AUXRH
4
ECONOMIZER
HEAT
RELAY 2
W1G
HEAT
RELAY 1
COMPRESSOR
CONTACTOR 1
COMPRESSOR
CONTACTOR 2
Y1
FAN
RELAY
Y2
COMPRESSOR
CONTACTOR 3
M19768A
Fig. 8. Typical hookup of T7351F201U in two-stage heat and four-stage cool conventional system.
62-025810
T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
M
MOTION
SENSOR
OSOSASAS
MHC HPHS
4
ECONOMIZER
DISCHARGE
AIR
SENSOR
X
HEAT
RELAY 3
AUX
W3/Y4 Y3 W2 Y2
AUXRH
3
HEAT
RELAY 2
RC
HEAT
RELAY 1
COMPRESSOR
CONTACTOR 1
COMPRESSOR
CONTACTOR 2
Y1
FAN
RELAY
COMPRESSOR
CONTACTOR 3
M25319
OUTDOOR
T7770 REMOTE SENSOR
SUBBASE
T5 T6 T7 T4 T3
W1G
L2
2
1
L1
(HOT)
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
ENSURE TRANSFORMER IS SIZED TO HANDLE THE LOAD.
2
3
HEAT/COOL SYSTEMS WITH ONE TRANSFORMER REQUIRE THE FACTORY-INSTALLED JUMPER.
4
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
Fig. 9. Typical hookup of T7350F2010 in three-stage heat and three-stage cool conventional system
AIR
SENSOR
123456789
HUMIDITY
SENSOR
with one transformer.
TROUBLESHOOTING GUIDE (TABLE 7)
Table 7. Troubleshooting Information.
SymptomPossible CauseAction
Display will not
come on.
Temperature
display is
incorrect.
Temperature
settings will not
change.
(Example:
Cannot set
heating higher or
cooling lower.)
Room
temperature is
out of control.
Thermostat is not being powered. Check that X terminal is connected to the system transformer.
Thermostat is configured for °F or
°C display.
Check for 24 Vac between X and RH terminals.
If missing 24 Vac:
• Check if circuit breaker is tripped; if so, reset circuit breaker.
• Check if system fuse is blown; if so, replace fuse.
• Check if the HVAC equipment power switch is in the Off
position; if so, set to the On position.
• Check wiring between thermostat and HVAC equipment.
Replace broken wires and tighten loose connections.
If 24 Vac is present, proceed with troubleshooting.
Press both Run Schedule and Copy, then reconfigure the
display.
Bad thermostat location.Relocate the thermostat.
Display shows three dashes and a
degree sign (all systems shut
down).
Upper or lower temperature limits
were reached.
Occupied setpoint temperature
range stops were configured.
Keypad is locked. When a locked
key is pressed, LOCKED appears
momentarily on the LCD.
Remote temperature sensing is not
working.
T7351 is set for remote sensing and sensor is missing or circuit
is either open or shorted.
Check the temperature setpoints:
• Heating limits are 40 to 90°F (7 to 31°C)
• Cooling limits are 45 to 99°F (9 to 37°C)
Check setpoint stops. If necessary, reconfigure the stop(s).
Press both Run Schedule and Copy, then change keypad lock
level.
Check all remote sensors.
1162-0258
T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 7. Troubleshooting Information. (Continued)
SymptomPossible CauseAction
Heat will not
come on.
Cooling will not
come on.
System indicator
(flame: heat,
snowflake: cool)
is displayed, but
no warm or cool
air is coming
from the
registers.
No power to the thermostat.Check that X terminal is connected to the system transformer.
Thermostat minimum off time is
activated.
System selection is set to Off or
Cool.
No power to the thermostat.Check that X terminal is connected to the system transformer.
Thermostat minimum off time is
activated.
System selection is set to Off or
Heat.
The call for heat or cool is not yet
given.
Conventional heating equipment
turns the fan on only after the
furnace has warmed to a setpoint.
Heating or cooling equipment is
not operating.
Check for 24 Vac between X and RH terminals.
If missing 24 Vac:
• Check if circuit breaker is tripped; if so, reset circuit breaker.
• Check if system fuse is blown; if so, replace fuse.
• Check if the HVAC equipment power switch is in the Off
position; if so, set to the On position.
• Check wiring between thermostat and HVAC equipment.
Replace broken wires and tighten loose connections.
If 24 Vac is present, proceed with troubleshooting.
• Wait up to five minutes for the system to respond.
• Configure heating response.
Set system selection to Heat or Auto.
Check for 24 Vac between X and RH terminals.
If missing 24 Vac:
• Check if circuit breaker is tripped; if so, reset circuit breaker.
• Check if system fuse is blown; if so, replace fuse.
• Check if the HVAC equipment power switch is in the Off
position; if so, set to the On position.
• Check wiring between thermostat and HVAC equipment.
Replace broken wires and tighten loose connections.
If 24 Vac is present, proceed with troubleshooting.
• Wait up to five minutes for the system to respond.
• Configure cooling response.
Set system selection to Cool or Auto.
Check if any stage indicators (dots next to the system
indicator) are displayed. With no display of stage indicators, no
call for cool/heat is yet given.
Wait one minute after seeing the on indicator and then check
the registers.
Verify operation of heating or cooling equipment in self-test.
Automation and Control Solutions
Honeywell International Inc.Honeywell Limited-Honeywell Limitée