Wire cutter/stripper
1-3/4-in. diameter hole saw
1/8-in. drill bit
Standard screwdriver
18-gauge wire (up to 5 conductor)
Torx driver T-20 and T-30
Other Requirements
Steam Humidifier flushes water at or above 140°F (60°C).
Refer to local codes for proper draining practices
for hot water.
Condensate pump rating of 212°F (100°C) if used.
Drip pan with water sensor shut-off required underneath
Steam Humidifier if installed in or above finished space.
G
KL
E
F
G
H
I
J3
K
L
M
H
Steam Humidifier
Mounting bracket and hardware
Backflow preventer
Saddle valve
Water supply hose
Drain hose (10 feet)
Duct nozzle and gasket
Owner’s manual
Service label
HumidiPRO Digital Control
Hose clamp
Water Hardness Test Kit
RO Filter System
*RO Tank not needed with installation
I
M*
AND SERVICE
OPERATION
Remote installation requires separate purchase of the
Honeywell Remote Mounting Kit (#50024917)
Steam Humidier
Critical Installation Information ................................2
Water Quality and Hardness ...............................................2
Testing Water Quality and Interperting Results ....................2
Choosing the Filter ...............................................................2
Set the Automatic Flush Cycle Timing .................................3
Proper Sizing of a Steam Humidier Humidier ..................5
Steam Humidier Pre-Install Information .............................7
Safety Denitions and Precautions ..........................8
Complete this information sheet and leave on all jobsites
In the event that a service technician needs to call in to the steam humidier support techline, the following
information is typically required for the Honeywell tech support specialist to accurately evaluate each situation.
Failure to have this information ready may result in resolution delays or a potentially incomplete diagnosis.
Honeywell recommends completing the below questionnaire and leaving a copy
behind at the home along with the Steam Humidier installation guide with every steam
humidier installation.
Honeywell steam humidier techline: 800-814-9452
Steam Humidier Pre-Install Information
Model Number of Steam Humidier Unit
Date Code (xxxx)
Water Quality Test 1 2 3 (circle one)
Water Pressure Test (psi)
Flush Cycle Setting
DIP 1 OFF ON OFF ON (circle one)
DIP 2 OFF ON ON OFF (circle one)
STARTED
GETTING
Duct Static Pressure Test (in.wc.)
(Maximum static pressure is 0.5 in.wc.)
Condensate Pump or Drain Pump Drain (circle one)
If Drain - PVC or Standard PVC Standard N/A (circle one)
Supply Voltage to Unit (V)
Monitoring Air Flow/System Power/
None
Control - Wireless or Wired Wireless Wired (circle one)
Fan Control - Steam Humidier or
Controller
Other (any additional relevant
information)
DIP 4 ON OFF (circle one)
DIP 5 ON OFF (circle one)
Steam Humidier Controller (circle one)
Steam Humidier System 69-2285—097
GETTING
STARTED
Safety Denitions and Precautions
Safety Denitions
These safety terms identify information you must read.
CAUTION: Indicates a hazardous situation which, if not avoided, could cause bodily injury
or property damage.
WARNING: Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Safety Precautions
Make sure you read and understand the following safety hazards before installing, using, or working
with the steam humidier:
• Do not direct the steam nozzle at people.
• Water inside tank can be very hot. Explain this to homeowner and emphasize the warning label
on steam humidier.
• Scalding danger from draining water. When the water tank drains, the water can be hot enough to cause
injury. Make sure the homeowner understands the danger of hot water and steam.
CAUTION: Voltage Hazard.
Can cause electrical shock or equipment damage.
Disconnect HVAC equipment before beginning installation.
WARNING: Electrocution, Heavy Equipment, and Water Hazard.
Can cause death, blindness, and water damage to home, and heating element failure.
CAUTION: Steam Condensation, Fire, and Freezing Water Hazard.
Can cause failure of fan or limit control or result in water damage to home.
8
Steam Humidier System 69-2285—09
Setting Homeowner Expectations
Make sure the homeowners know what to expect from their steam humidier. Discuss the following points with the
homeowners and answer any questions they have.
• Achieving Humidity Setpoint. It may take up to a week of continuous operation to achieve the humidity
setpoint. This depends on such factors as weather, size of home, furnishings in the home, and insulation.
• Plastic or Rubber Odor. At startup, it is normal to smell a slight plastic odor in the home. If the remote hose is
used, there may be a slight rubber odor. These odors will go away within a few days.
• Ideal Humidity. 35% – 45% relative humidity in typical winter weather is considered ideal by industry experts.
Homeowners can adjust to their own comfort or until there is condensation on the windows. Lower the setpoint
if condensation appears.
• Unit Not Humidifying. If steam humidier is not running but the humidity is below the setpoint, the humidity
control may have a frost protection setting. Steam humidier will not humidify while in a drain cycle mode.
STARTED
GETTING
• Setpoint Not Reached. If humidity doesn’t reach the setpoint, steam humidier may be undersized for the
home. This can be due to factors such as insulation, windows, and arid climate. Also, the outdoor temperature
may be too low to maintain the humidity level. Wait for the outdoor temperature to warm closer to 20°F (-6°C). If
the desired humidity is still not reached, then a larger capacity steam humidier may be needed.
• Home Ventilation. Excessive ventilation sends moist air outside and replaces it with dry air. This can make it
hard to maintain the humidity setpoint. If installing a ventilator, use a solution that retains moisture. An Energy
Recovery Ventilator (ERV) is recommended.
• Cleaning Required Light. If the Cleaning Required light is on, clean steam humidier using the steps found in
the “Routine Maintenance” section on page 44, or in the Homeowner’s Operating Manual. Steam Humidier
will continue to run normally while this light is on.
• Hard Water. The home’s water hardness determines how often steam humidier must be cleaned. A water
hardness test kit is provided with your steam humidier. It will help you determine the cleaning interval and
lter requirements for your steam humidier.
• Energy Consumption. There may be a slight increase in overall energy consumption when operating
any humidier. However, steam humidier will make the home feel warmer. This allows the homeowner to lower
the temperature setting on the thermostat. Every degree lower on the thermostat can save up to 3% on
heating costs.
Steam Humidier System 69-2285—099
GETTING
STARTED
Important Installation Requirements
Failure to comply with these requirements will result in voided warranty, improper installation, and
service callbacks.
Personal Safety
• Wear safety glasses while installing steam humidier.
• Do not cut into any air conditioning or electrical line.
• Follow professional safety standards and all local regulations.
Mounting Location
• Mount steam humidier in a level position to avoid water damage or heating element failure.
• Install steam humidier on the supply duct. Use the Remote Mounting Kit if duct mounting is not possible.
• Do not install steam humidier where the ambient temperature is lower than 34°F (1.1°C) or higher
than 104°F (40°C).
• Mounting area must be strong enough to support steam humidier’s weight when full of water (up to 15 lbs.).
• Choose a location that is well ventilated. Do not install steam humidier in completely enclosed spaces, such
as a cabinet or unventilated closet.
• Allow at least 1 foot clearance to ventilation holes in the steam humidier cover. Do not cover the holes.
Covering them can increase the temperature inside steam humidier and shorten its life.
• Do not mount directly to duct board. The remote mount nozzle attachment is allowed only with a Honeywell
duct board adapter kit. See “Appendix C: Parts List” on page 55.
• If used near a pool or spa, make sure steam humidier can not fall into the water or be splashed. Also, ensure
steam humidier is plugged into a ground fault interrupted (GFI) outlet.
10
Duct Nozzle
• Do not install the duct nozzle into a supply duct with static pressure exceeding 0.5 in. w.c.
• Do not install the duct nozzle through wooden sidewalls (e.g., oor joist).
• If the duct has exposed insulation on the interior, be sure the nozzle extends beyond the insulation. Clear away
excess insulation at the insertion point, or replace a section of insulated duct (approximately 6 in. x
6 in.) with rigid, non-insulated sheet metal.
• Allow at least 4 in. clearance between nozzle outlet and any interior duct to avoid water condensation.
• Mount steam humidier where the nozzle outlet has a minimum 24 in. of downstream open air space.
Water Drainage
• Consult local plumbing codes for drain size, material, and maximum temperature allowed.
Steam Humidier System 69-2285—09
Choosing a Mounting Method
Return
Supply
MCR29596
Supply
MCR35264
Before installing steam humidier in a home, you must decide which mounting method you want to use:
Which is right for you?
DUCT MOUNTING – if you can mount steam
humidier onto the supply duct of
the HVAC system:
The generated steam goes directly into the
supply duct.
This is the simplest type of installation, but
it requires that a suitable mounting location
can be found on the supply duct.
REMOTE MOUNTING – if a suitable
mounting location can not be found
on the supply duct:
The steam humidier can be mounted up to
20 feet away from the supply duct for
select models.
A remote hose must be installed to carry
steam from steam humidier to the supply
duct.
You will need to use a remote mounting kit
(see “Appendix C: Parts List” on page 66).
MOUNTING
This manual covers duct mounting of steam humidier. For Remote Mounting Instructions, see “Remote
Installation” on page 19 or “Document 69-2317” (included with Remote Mounting Kit).
Before proceeding:
I have decided to use: Duct Mounting Remote Mounting
Steam Humidier System 69-2285—0911
Duct Mounting
M29598
M29599
Before beginning Duct Mounting:
I have conrmed local codes for proper draining practices for hot water
I have chosen an installation location that meets the requirements on page 10
Follow these steps to mount steam humidier directly to the supply duct of the homeowner’s HVAC equipment.
STEP ONE: Select a Mounting Location
Choose a location that has access to a cold
1
water supply pipe.
MOUNTING
STEP TWO: Connect the Duct Nozzle
Select a vertical or horizontal surface on the HVAC
supply duct, with adequate clearances, where steam
humidier can be mounted.
2
3
Make sure there is a 120 VAC electrical outlet
rated for the steam humidier being installed.
Steam Humidier Required Minimum
Circuit Capacity:
HM609 10 Amps
HM612 12 Amps
4
Ensure the location is near a drain with a high-
temperature water rating. Consult local plumbing
codes for proper drainage. If no main oor drain
is available, see “Other Plumbing Options” on page
16.
1
2
12
Slide the foam gasket over the nozzle.
Make sure the o-ring gasket is properly seated
in the groove.
3
Insert the duct nozzle into steam humidier. Twist
clockwise to ensure a tight seal.
Steam Humidier System 69-2285—09
STEP THREE: Install Mounting Bracket to the Duct
M29600
Position the template on the supply duct:
• Make sure the template is level and in the desired
position on the duct.
• Ensure proper clearances from A-coil.
• Make sure the duct nozzle will have proper
clearances from duct walls.
• Minimum 4-inch clearance from nozzle outlet to any
duct wall.
• Minimum 24 inches of downstream open duct air
space. (Needed to prevent water condensation.)
Drill the 1-3/4 inch hole.
Secure the mounting bracket to the duct, using four
self-drilling sheet metal screws provided.
2
12”
(min)
4”
Flow
1
4”4”
3
MOUNTING
STEP FOUR: Install Steam Humidier onto the Mounting Bracket
Make sure the foam gasket is positioned correctly over
1
2
3
4
M29601A
Before proceeding to Plumbing:
I selected a duct mounting location
I connected the duct nozzle
I installed the mounting bracket to the duct
I installed the steam humidier onto the mounting bracket
the nozzle.
Lift steam humidier into place against the mounting
bracket. Insert the nozzle directly into the duct hole.
Check the foam gasket – it must form a tight seal in
the duct hole.
Push down to secure steam humidier to the bracket
arms.
Steam Humidier System 69-2285—0913
MCR35266
BEST
PRACTICE
Use a manual shutoff valve when tapping into a water line.
Water Supply and Drain Connections
STEP ONE: Connect the Cold Water Supply
2
Do not use hot water supply. Cold water is required
to cool boiling water to safe draining temperatures.
PLUMBING
1
Insert one end of the water line into the water lter
or reverse osmosis kit. Use the 1/4-inch plastic
water line provided or a 1/4-inch copper water line.
Apply a modest pull to ensure a tight t.
Use clamps or ties to secure the water lter in a
location that allows for removing and replacing it in
the future. Honeywell recommends changing the
water lter or RO canisters 1 & 2 annually, or as
needed based on water conditions.
Install the provided backow preventer, as required
by code. See “Reverse Osmosis Filter” if using the
Reverse Osmosis Filter.
4
3
Cut the water line so it is long enough to reach
from the water lter to the supply tting on the
bottom of the steam humidier.
Insert the water line into the steam humidier
5
supply tting.
STEP TWO: Tap into a Water Line
Water Supply
Line
Manual Shutoff
Valve
T-fitting
14
Note: Failure to check for a tight t with plastic water line
could result in the line coming loose in the future. Apply
modest pull to ensure water line is properly seated and
secure.
• Consult local codes for proper plumbing.
• Use the saddle valve provided or a T-tting and
manual shutoff valve to tap into a cold water
line.
• Refer to the literature included with the valve
you chose and the local plumbing codes. Use
proper technique for the valve.
Saddle Valve
M29605
Steam Humidier System 69-2285—09
STEP THREE: Connect Steam Humidier to the Cold Water Pipe
MCR32901
1
Connect one end of the remaining length of water
line to the backow preventer. Apply a modest pull
2
to ensure a tight t. See “Reverse Osmosis Filter” on
page 24 if using the Reverse Osmosis Filter.
Connect the other end of this line to the saddle valve
or T-tting and manual shutoff valve.
STEP FOUR: Connect to the Water Drain
• Consult and follow local plumbing codes for drain
pipe size and maximum temperature requirement.
• The ideal installation is directly to the main oor
drain using the rubber hose provided.
• If direct oor drain access is not available, see
“Other Plumbing Options” on page 16.
Connect the 1/2-inch drain hose provided to the drain
tting on the bottom of the steam humidier.
PLUMBING
1
2
3
MCR29607
4
CAUTION: Scalding Hazard.
During operation, hot water may exit drain and can cause burns from scalding.
Make sure the hose is securely connected to the drain.
Before proceeding to Wiring:
I have conrmed minimum required circuit capacity
I have connected the water supply using cold water
I have installed the drain connection
Use the hose clamp provided to secure the drain hose
to the barbed tting.
Route the drain hose to the oor drain. The hose must
have a continuous downward slope.
Direct the hose outlet into the oor drain. Secure
the hose to reduce the risk of hot water pooling
or splashing.
Note: Some building codes require an air gap between
discharge hose and oor drain.
Steam Humidier System 69-2285—0915
Other Plumbing Options
1/2 IN. BARB X 3/4 IN. MNPT
3/8-IN. TUBING
M28713A
The following diagrams are for applications where standard draining to a oor drain is not available.Choose the
plumbing option that suits your installation. Use A, B, C, or D based on type of pipe or condensate pump. Consult
and follow local plumbing codes in addition to these instructions.
For All Options Shown:
PLUMBING
• Support rubber hose every 6 in.
• PVC must be schedule 40 or higher rating.
Connect to Steam Humidifier
Common to all plumbing options.
SEAL ALL CONNECTIONS FROM
SOLENOID VALVE TO DRAIN STACK
FLEXIBLE
HOSE
HOSE
CLAMPS
212°F RATED PUMP
HOSE FROM
STEAM
HUMIDIFIER
• All plastic pipe joints are welded.
• Drain into a P-trap that will remain wetted at all
times.
3/4 IN. FNPT X SWEAT
3/4 IN. COPPER PIPE
3/4 IN. FNPT X
1-1/2 IN. PVC
1-1/2 IN. (MINIMUM) PVC PIPE
3/4 IN. FNPT X 3/4 IN. CPVC
3/4 IN. CPVC PIPE
3/8-IN. TUBING
RATED AT 212°F
MCR28678
Option 1: Plumbing
to drain with
condensate pump.
16
RATED AT 212°F
ALTERNATIVE
3/4 IN. FNPT X 3/4 IN. CPVC
3/4 IN. CPVC PIPE
TO PUMP
HOSE CLAMPS AT
ALL CONNECTIONS
HOSE FROM
STEAM HUMIDIFIER
• Use Hartell A3X-115 condensate pump or equivalent
(212°F temperature rating, > 1 GPM pump flow rate).
• Pump must be powered when Steam Humidifier is operating.
• Use a pump with a built-in overflow sensor or install the pump
in a drip pan with wet switch wired to turn off Steam Humidifier.
Steam Humidier System 69-2285—09
M28679
3/4 IN. FNPT X 1-1/2 IN. PVC
3/8 IN. BARB X 3/4 IN. MNPT
SIZE TO FIT PUMP OUTPUT
Option 2: Plumbing to a dedicated trap.
1-1/2 IN. (MINIMUM)
PVC PIPE
STAINLESS STEEL
SLOTTED BAND
COUPLING SIZED TO
FIT PIPE (COPPER,
PVC, CPVC
SIZE TO FIT PUMP OUTPUT
3/4 IN. MNPT X SWEAT
3/4 IN. FNPT X 1-1/2 IN. PVC
1-1/2 IN. (MINIMUM) PVC PIPE
1-1/2 IN. PVC
3/4 IN. MNPT X 3/4 IN. CPVC
3/4 IN. FNPT X 1-1/2 IN. PVC
HOSE CLAMP
1-1/2 IN. MINIMUM TRAP
(OR SIZE PER LOCAL CODE)
VENTED PER
LOCAL CODE
ALL PLASTIC PIPE
JOINTS ARE WELDED
Option 3: Plumbing to sink with a dedicated trap.
PLUMBING
3/4 IN. MNPT X SWEAT
3/4 IN. FNPT X 1-1/2 IN. PVC
1-1/2 IN. PVC
3/4 IN. MNPT X 3/4 IN. CPVC
3/4 IN. FNPT X 1-1/2 IN. PVC
HOSE CLAMP
3/8 IN. BARB X 3/4 IN. MNPT
3/4 IN. FNPT X 1-1/2 IN. PVC
)
WELD
ALTERNATIVE
THIS CONFIGURATION ALLOWS FOR
REMOVAL OF THE TRAP
1-1/2 IN. PVC
ALL CONNECTIONS FROM
SOLENOID VALVE TO
DRAIN TRAP ARE SEALED
SINK
WELD
WELD
THREADS
ALL PLASTIC PIPE UNDER
SINK 1-1/2 IN. MINIMUM PVC
COUPLING
WELD
WYE
THREADS
M28681
Steam Humidier System 69-2285—0917
3/4 IN. MNPT X SWEAT
.
STAINLESS STEEL
SLOTTED BAND
COUPLING SIZED TO
FIT PIPE (COPPER,
PVC, CPVC)
Option 4: Plumbing to sink trap.
PLUMBING
3/4 IN. FNPT X 1-1/2 IN. PVC
1-1/2 IN. (MINIMUM)
PVC PIPE
1-1/2 IN. PVC
3/4 IN. MNPT X 3/4 IN. CPVC
3/4 IN. FNPT X 1-1/2 IN. PVC
HOSE CLAMP
3/8 IN. BARB X 3/4 IN. MNPT
3/4 IN. FNPT X 1-1/2 IN. PVC
SIZE TO FIT PUMP OUTPUT
1-1/2 IN. PVC
ALL CONNECTIONS FROM
SOLENOID VALVE TO
DRAIN TRAP ARE SEALED
SINK
WELD
WELD
ALTERNATIVE
THIS CONFIGURATION ALLOWS FOR
REMOVAL OF THE TRAP
COUPLING
1-1/2 IN.
PVC TEE
WELD
THREADS
1-1/2 IN
PVC
M28680
18
Steam Humidier System 69-2285—09
If humidier is in nished space, always install a drip pan
MCR28708
BEST
PRACTICE
with wet switch. Honeywell recommends Diversitech WS-1
(wiring shown here).
Remote Installation
Use remote installation when no suitable duct mounting location can be found on the homeowner’s
HVAC system. For detailed instructions on remote installation, see the steam humidier Remote Mount Kit
Installation Instructions (69-2317).
Always pitch the remote Adapter Nozzle upwards
Use provided anchors if mounting
to drywall or plaster
If humidifier is in finished space, always
install a drip pan with wet switch.
Honeywell recommends Diversitech WS-1
(wiring shown here.)
RED
BLACK
GREEN
ORANGE
STEAM
HUMIDIFIER
TERMINAL
24V
24V
HUM
HUM
C
GT
R
RT
GF
EXT
On
Off
1
65432
APPENDICES
Steam Humidier System 69-2285—09
19
BEST
Cut a slit in the insulation half way
around the hose
Minimum
pitch
per
Nozzle
PRACTICE
.
Always inspect the hose installation after at least 1 hour of
steam production to conrm that there are no sags in the
hose or leaks at the connection points.
at upward pitch.
upward
of 2 inches
foot.
Avoid sharp kinks and
prevent bends.
Minimum of
6 inches
of straight
vertical rise.
12 inches
Do not cut into the
rubber steam hose.
3 inches minimum clearance from nozzle
outlet to duct.
1-3/4 inch hole
Clamp
On straight runs, use perforated angle
iron. Otherwise, secure hose every 12 inches
using provided hooks.
Clearance hole for hose and insulation.
Seal off unconditioned space with
Clamp
grommet (not provided) or caulk.
Always install nozzle so the
outlet is pointed up.
Do not route the steam
hose through the hole
in the mounting plate.
On straight runs, use
perforated angle iron.
Otherwise, support
hose every 12 inches
using provided hooks.
24 inches open air downstream.
If hose slopes downhill…
Downward slope can not be more than
3 feet below humidifier steam outlet.
Provide a 212°F rated Te e at the
lowest point. Do not use plastic Te e.
Minimum 6 inches
Minimum 2 inches
Insert the hose clamp into
the slit and hook it onto the
rubber hose.
Hose clamps at
every connection.
Minimum upward
pitch of 2 inches
per foot.
Nozzle at
Clamps
upward pitch.
APPENDICES
20
Always consult and follow local
plumbing codes for drain pipe
size and maximum temperature
requirement.
Water in elbow.
Note: Some building codes require
an air gap between discharge hose
and floor drain.
M29636
Steam Humidier System 69-2285—09
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.