Honeywell ST 800, ST 700 Installation Guide

ST 800/ST 700 SmartLine Pressure Transmitter
Quick Start Installation Guide
34-ST-25-36, Revision 10, June 2020
Table of Contents
Figure 12: Jumper Location HART/DE ....................................................................... 5
Figure 1:Mounting Brackets
This document provides descriptions and procedures for the Quick Installation of Honeywell’s family of SmartLine Pressure Transmitters.
The SmartLine Pressure Transmitter is available in a variety of models for measuring Differential Pressure (DP), Gauge Pressure (GP), and Absolute Pressure (AP). For full details refer to the manuals listed below for protocols, human interface (HMI), Operation, Installation, Configuration, Calibration, Maintenance, Parts, Safety and Approvals etc. including options.
Documentation
To access complete documentation, including language variants, scan the QR code below using your smart phone/device or QR code scanner.
Go to the APP store for your free Smartphone QR scanner
Or you can follow the URL to access the online SmartLine HUB page. The HUB page will contain direct links to open SmartLine product
documentation.
URL QR Code
https://hwll.co/SmartLineHUB
Copyrights, Notices and Trademarks
Copyright 2020 by Honeywell Revision 10 – June 2020
Trademarks
SFC, SmartLine, ST 800 and ST 700 are U.S. registered trademarks of Honeywell Inc.
HART® and FOUNDATION™ are trademarks of the FieldComm Group™
Installation ................................................................................................................... 1
Mounting the Transmitter ............................................................................................ 1
Bracket Mounting ........................................................................................................ 1
Optional Mounting Bracket ......................................................................................... 1
Existing Mounting Bracket.......................................................................................... 2
Rotating Transmitter Housing .................................................................................... 2
Leveling Transmitters with Small Absolute or Differential Pressure Spans .......... 2
Flange Mounting ......................................................................................................... 2
Flush Mounting ............................................................................................................ 3
Remote Seal Mounting ............................................................................................... 3
Conduit Entry Plugs and Adapters .............................................................................. 3
Wiring Connections and Power Up ............................................................................. 4
Wiring Variations ......................................................................................................... 4
Explosion-Proof Conduit Seal ..................................................................................... 4
Tri m the Transmitter .................................................................................................... 4
Procedure to Trim the Transmitter ............................................................................ 4
Set the Jumpers For HART/DE ................................................................................... 5
Setting Failsafe Direction and Write Protect Jumpers ............................................. 5
Write Protect Jumper on Foundation Fieldbus (FF) .................................................... 5
Configuration Guide .................................................................................................... 5
PRODUCT CERTIFICATIONS ................................................................................... 6
Hazardous Locations Certifications............................................................................. 7
Control Drawing .......................................................................................................... 9
Table 1 - Conduit Entry Plugs ..................................................................................... 3
Table 2 - Conduit Adapters ......................................................................................... 3
Table 3 - Jumper Settings ........................................................................................... 5
Table 4 - Fieldbus Write Protect.................................................................................. 5
Figure 1:Mounting Brackets ........................................................................................ 1
Figure 2: Angle Mounting Bracket ............................................................................... 1
Figure 3: LGP and LAP models .................................................................................. 2
Figure 4: Rotating Transmitter Housing ...................................................................... 2
Figure 5: Using level to mount transmitter .................................................................. 2
Figure 6: Flange mounting .......................................................................................... 2
Figure 7: Flush Mounting ............................................................................................ 3
Figure 8: Remote Seal mounting ................................................................................ 3
Figure 9: Electronic Housing Conduit Entries ............................................................. 3
Figure 10: Two-wire power/current loop ...................................................................... 4
Figure 11: Terminal Block and Grounding Screw location .......................................... 4
Tables
Figures

Installation

Evaluate the site selected for the Transmitter installation with respect to the process system design specifications and Honeywell’s published performance characteristics for your particular model. Temperature extremes can affect display quality. The display can become unreadable at temperature extremes; however, this is only a temporary condition. The display will again be readable when temperatures return to within operable limits.

Mounting the Transmitter

Transmitter models, except flush mounts and those with integral flanges, can be attached to a two-inch (50 millimeter) vertical or horizontal pipe using Honeywell’s optional angle or flat mounting bracket; alternately you can use your own bracket. Flush-mount models are attached directly to a process pipe or tank by a one-inch weld nipple. Models with integral flanges are supported by the flange connection.
Typical Bracket mounted and Flange Mounted Installations

Bracket Mounting

Optional mounting bracket, see Figure 2
Existing mounting bracket, see Figure 3
Rotate the transmitter housing, see Figure 4
Level a transmitter with small absolute or differential pressure spans, see Figure 5

Optional Mounting Bracket

Position the bracket on a 2-inch (50.8mm) and install “U” bolt around pipe and through holes in bracket. Secure with nuts and lock washers provided.
Figure 2 Example - Angle mounting bracket secured to horizontal or vertical pipe.
Figure 2: Angle Mounting Bracket
Quick Start Installation Guide 1

Existing Mounting Bracket

Align appropriate mounting holes in transmitter with holes in bracket and secure with bolts and washers provided.
Note: If the meter body is hexagonal, you must use the additional bracket supplied. If meter body is round, discard the bracket.
Example – LGP model transmitter mounted to optional angle mounting bracket.
If Transmitter is….
DP, Dual Head GP, Dual Head AP and DP Remote Seals.
In-line GP and AP (LGP model) or GP/AP Remote Seal
Then….
Use smaller “U” bolt provided to attach meter body to bracket. See Figure 3.

Rotating Transmitter Housing

Loosen set screw on outside neck of transmitter one full turn. Rotate Transmitter housing in maximum of 180 degree increment in left or right direction from center to position you require and tighten set screw (1.46 to 1.68Nm/13 to 15lb-in).
Figure 4 Example – Rotating Transmitter Housing.
Figure 4: Rotating Transmitter Housing
Figure 3: LGP and LAP models

Leveling Transmitters with Small Absolute or Differential Pressure Spans

Mounting position of these transmitters is critical due to the smaller transmitter spans. To minimize these positional effects on calibration (zero shift), take the appropriate
mounting precautions that follow for the given transmitter model. See Figure 5 for suggestions on how to level the transmitter using a spirit balance. To perform a Zero Trim after leveling, refer to Trim the Transmitter on page 4.
Figure 5: Using level to mount transmitter
For model STA840, STA822, STA740 or STA722 transmitters, you must ensure that the transmitter is vertical when mounting it. You do this by leveling the transmitter side-to-side and front-to-back.
Mount transmitter vertically to assure best accuracy. Position the spirit balance on the pressure connection surface of AP body.

Flange Mounting

To mount a flange mounted transmitter model, bolt the transmitter’s flange to the flange pipe on the wall of the tank.
On insulated tanks, remove enough insulation to accommodate the flange extension. It is the End User’s responsibility to provide a flange gasket and mounting hardware that are suitable for the transmitter’s service condition.
To prevent degradation of performance in Flush-Mounted Flanged Transm itters, exercis e care to ensure that the internal diameter of the flange gasket does not obstruct the sensing diaphragm.
To prevent degradation of performance in Extended Mount Flanged Transmitters, ensure that there is sufficient clearance in front of the sensing diaphragm body.
Figure 6: Flange mounting
Quick Start Installation Guide 2
Step
Action
1
Remove the protective plastic cap from the threaded conduit entry.
2
To ensure the environmental ingress protection rating on tapered
Thread the appropriate size conduit plug (M20 or ½” NPT) into the
4
Tighten adapters according to the following table.
½” NPT Conduit
Entry
Step
Action
1
Remove the protective plastic cap from the threaded conduit entry.
2
To ensure the environmental ingress rating on tapered threads (NPT),
Thread the appropriate size adapter (M20 or ½ NPT) into the conduit entry opening
4
Tighten adapters according to the following table.

Flush Mounting

To mount a flush mounted transmitter model, cut a hole for a 1-inch standard pipe in the tank or pipe where the transmitter is to be mounted. See Figure 7.
Weld the 1-inch mounting sleeve to the wall of the tank or to the hole cut on the pipe. Insert the meter body of the transmitter into the mounting sleeve and secure with the locking bolt. Tighten the bolt to a torque of 6.4Nm ±0.30Nm [4.7ft.-lbs. ±0.2ft.-lbs.]
Once the transmitter is mounted, the transmitter housing can be rotated to the desired position. See Figure 7.
Figure 7: Flush Mounting

Remote Seal Mounting

Mount the transmitter at a remote distance determined by length of capillary tubing. Note: The combination of tank vacuum and high pressure capillary head effect should
not exceed 9psi (300mm Hg) absolute. On insulated tanks, remove enough insulation to accommodate the mounting sleeve.
Figure 8 Example – Typical Remote Seal Transmitter installation.
Note: For Sanitary 3-A installations, only mount the transmitter outside of the Non­Product Contact area where incidental contact with the process material is unlikely, use a minimum capillary length of 1.5m (5ft.)
Figure 8: Remote Seal mounting

Conduit Entry Plugs and Adapters

Procedures
It is the User/Installer’s responsibility to install the Transmitters in accordance with national and local code requirements. Conduit entry plugs and adapters shall be suitable for the environment, shall be certified for the hazardous location when required and acceptable to the authority having jurisdiction for the plant.
CONDUIT ENTRY PRECAUTIONARY NOTICE
THE CONDUIT/CABLE GLAND ENTRIES OF THIS PRODUCT ARE SUPPLIED WITH PLASTIC DUST CAPS WHICH ARE NOT TO BE USED IN SERVICE. IT IS THE USER’S RESPONSIBILITY TO REPLACE THE DUST CAPS WITH CABLE GLANDS, ADAPTORS AND/OR BLANKING PLUGS WHICH ARE SUITABLE FOR THE ENVIRONMENT INTO WHICH THIS PRODUCT WILL BE INSTALLED. THIS INCLUDES ENSURING COMPLIANCE WITH HAZARDOUS LOCATION REQUIREMENTS AND REQUIREMENTS OF OTHER GOVERNING AUTHORITIES AS APPLICABLE.
Use the following procedures for installation:
Table 1 - Conduit Entry Plugs
a non-hardening thread sealant may be used.
3
Table 2 - Conduit Adapters
Description Tool Torque
½ to ¾ NPT Adapter 1 ¼” Wrench 32Nm 24Lb-ft
threads (NPT), a non-hardening thread sealant may be used.
3
conduit entry opening. Do not install conduit entry plugs in conduit entry openings if adapters or reducers will be used.
Description Tool Torque
M20 Conduit Entry 10mm Hex Wrench 32Nm 24Lb-ft
10mm Hex Wrench 32Nm 24Lb-ft
Note. No plugs come installed in the housings. All housings come with temporary plastic dust protectors (red) installed and are not certified for use in any installation
Figure 9: Electronic Housing Conduit Entries
Quick Start Installation Guide 3

Wiring Connections and Power Up

The above procedures are used to connect power to a Transmitter. For loop wiring and
Step
Action
2
Remove the end cap cover from the terminal block end of the Electronics
3 4
5 6
Step
Action
1
Attach the transmitter to the mounting bracket but do not completely tighten the mounting bolts
2
Connect a tube between the input connections in the high
3
Connect 24Vdc power to the transmitter. For HART/DE connect
5
or near zero, and then completely tighten the mounting bolts.
6
The Local Display or applicable communicator can be used to
tightened.
7
Summary
The transmitter is designed to operate in a two-wire power/current loop with loop resistance and power supply voltage within the operating range shown in Figure 10.
Loop wiring is connected to the transmitter by simply attaching the positive (+) and negative (–) loop wires to the positive (+) and negative (–) SIGNAL screw terminals on the terminal block in the transmitter’s electronics housing shown in Figure 11. Each transmitter includes an internal terminal to connect it to earth ground. Also, a ground terminal can be optionally added to the outside of the electronics housing. While it is not necessary to ground the transmitter for proper operation, doing so tends to minimize the possible effects of noise on the output signal and affords protect ion aga inst lightn ing and static discharge.
An optional lightning terminal block can be installed in place of the non-lightning terminal block for Transmitters that will be installed in an area that is highly susceptible to lightning strikes.
Figure 10: Two-wire power/current loop

Explosion-Proof Conduit Seal

When installed as explosion proof in a Division 1 Hazardous Location, keep covers tight while the Transmitter is energized. Disconnect power to the Transmitter in the non-hazardous area prior to removing end caps for service.
When installed as non-incendive equipment in a Division 2 hazardous location, disconnect power to the Transmitter in the non-hazardous area, or determine that the location is non-hazardous before disconnecting or connecting the Transmitter wires.
Transmitters installed in f o r p r ot ect ion explosion proof in Class I, Division 1 do not need an explosion proof seal in ac c o r dance with ANSI/ NF PA 70, the US National Elect rical Code. A LISTED explosion proof seal t o be installed in the conduit, wit h in 18 in ch es (457.2mm) of the Transmitt er w h en 3/4" co n d u it is u sed .
Crouse-Hinds type EYS/EYD or EYSX/EYDX are examples of LISTED explosion proof seals that meet this requirement. Transmitters installed as explosion proof in Class I, Division 1, Group B, C or D hazardous (classified) locations do not require that explosion proof seal be installed in the conduit.
1
See Figure 11, above, for parts locations.
Housing Feed loop power leads through one end of the conduit entrances on
either side of the Electronics Housing. The Transmitter accepts up to 16 AWG wire.
Plug the unused conduit entrance as specified in Table 1. Connect the positive loop power lead to the positive (+) terminal and the
negative loop power lead to the negative (-) terminal. Note that the Transmitter is not polarity-sensitive.
Replace the end cap, and secure it in place using a 1.5mm hex wrench.
Figure 11: Terminal Block and Grounding Screw location
Note: The right hand terminal is for loop test and is not applicable for the Fieldbus
option.

Wiring Variations

external wiring, detailed drawings are provided for Transmitter installation in
non-intrinsically safe areas and for intrinsically safe loops in hazardous area locations.
This procedure shows the steps for connecting power to the transmitter.
Wiring must comply with local codes, regulations and ordinances. Grounding may be required to meet various approval body certification, for example CE conformity. Refer to the SmartLine Transmitter User’s Manual, Documents # 34- ST-25-35 (ST 800) or 34-ST-25-44 (ST 700) for details.

Trim the Transmitter

Procedure to Trim the Transmitter

For a transmitter with a small differential pressure span, you must ensure that the
transmitter is vertical when mounting it. You do this by leveling the transmitter side-to-
side and front-to-back. See Figure 5 for suggestions on how to level the transmitter
using a spirit balance. You must also zero the transmitter by following the steps in
this table.
pressure (HP) and low pressure (LP) heads to eliminate the effects of any surrounding air currents.
a digital voltmeter to monitor the PV output.
4 Use applicable communicator to establish communications with
the transmitter. For DE transmitter use SFC, SCT, or MCT. For Hart, use MCT or other Hart Communicator with applicable Honeywell DD's. For Fieldbus, use NI FBUS tools with applicable Honeywell DD's.
While reading the transmitter’s output on a communication tool or a voltmeter, position the transmitter so the output reading is at
perform the Zero Corrects. This corrects the transmitter for any minor error that may occur after the mounting bolts are
Remove the tube from between the input connections, the power, and the digital voltmeter or communication tool.
Quick Start Installation Guide 4
Jumper
Settings
Description
Write Protect = ON (Protected)
The SmartLine Pressure Transmitter (DE or
ATTENTION: Electrostatic
devices
Step
Action
1
2
3
4
5 6
ATTENTION:
WARNING! PERSONAL INJURY: Risk of electrical shock.
Failure to comply with these instructions could result in death or
Step
Action
Turn OFF Transmitter power.
Electronics side of the Transmitter housing.
Module and pull it off.
positioning.
Turn ON Transmitter power.

Set the Jumpers For HART/DE

Setting Failsafe Direction and Write Protect Jumpers

HART) provides two jumpers to set the desired failsafe action and Write Protect option. See
The top jumper on the electronics module sets the Failsafe direction. The default setting is up-scale failsafe.
Up Scale drives the loop to a value greater than 21mA while Down Scale drives the loop to a value less than 3.8mA.
You can change the failsafe direction by moving the Failsafe Jumper (top jumper) to the desired position (UP or DOWN).
If your transmitter is operating in DE mode, the upscale failsafe action will cause the transmitter to generate a “+ infinity” digital signal, while a downscale failsafe will cause the transmitter to generate a “– infinity” digital sign al.
The bottom jumper sets the Write Protect. The default setting is OFF (Unprotected).
When set to the ON (Protected) position, Changed configuration parameters cannot be written to the transmitter.
When set to the OFF (Unprotected) position, Changed configuration parameters can be written to the transmitter.
Discharge (ESD) hazards. Observe precautions for handling electrostatic sensitive
Turn OFF Transmitter power.
Loosen the end-cap lock, and unscrew the end cap from the Electronics side of the Transmitter housing.
If applicable, carefully depress the tabs on the sides of the Display Module and pull it off.
If necessary, move the interface connector from the Communication Module to the display module to provide the preferred orientation of the display module in the window.
Set the Failsafe Jumper (top jumper) to the desired action (UP or DOWN). And the Write Protect jumper (Bottom jumper) to the desired behavior (Protected or Unprotected) See Table for jumper positioning.
Screw on the end cap and tighten the end-cap lock.
Turn ON Transmitter power.
Figure 12: Jumper Location HART/DE
Table 3 - Jumper Settings
Failsafe = UP (High) Write Protect = OFF (Not Protected)
Failsafe = DOWN (Low) Write Protect = OFF (Not Protected )
Failsafe = UP (High) Write Protect = ON (Protected)
Failsafe = DOWN (Low)

Write Protect Jumper on Foundation Fieldbus (FF)

On Foundation Fieldbus transmitters there is no Failsafe jumper selection but there is a Write Protect jumper.
The bottom jumper sets the Write Protect. The default setting is OFF (Unprotected). When set to the ON (Protected) position, changes to configuration parameters cannot be
written to the transmitter. When set to the OFF (Unprotected) pos ition, changes to configuration parameters can be
written to the transmitter.
precautions for handling electrostatic sensitive devices.
Disconnect power before proceeding. HAZARDOUS LIVE voltages greater than 30Vrms, 42.4 V peak, or 60VDC may be accessible.
Electrostatic Discharge (ESD) hazards. Observe

Configuration Guide

This transmitter comes with a standard factory configuration. Consult the nameplate for basic information. Reconfiguration for your particular application can be accomplished by following instructions in the Transmitter User’s manual. This can be found by following the website URL or QR code on page 1 of this document.
1 2
3
Loosen the end-cap lock, and unscrew the end cap from the
If applicable, carefully depress the tabs on the sides of the Display
4
5 6
Quick Start Installation Guide 5
Set the Write Protect jumper (Bottom jumper) to the desired behavior (Protected or Unprotected). See Table 4 for jumper
Screw on the end cap and tighten the end-cap lock.
Table 4 - Fieldbus Write Protect
Image Description
Fieldbus SIM Mode = OFF Write Protect = OFF (Not Protected)
Fieldbus SIM Mode = OFF Write Protect = ON (Protected)
Fieldbus SIM Mode = ON Write Protect = OFF (Not Protected)

PRODUCT CERTIFICATIONS

A1. Safety Instrumented Systems (S IS ) Install a tions
For Safety, Certified Installations, please refer to ST 800 & ST 700 Safety Manual 34­ST-25-37 for installation procedure and system requirements.
A2. European Di rec tiv e Inf orm ation (CE Mark)
Quick Start Installation Guide 6
FIELD
METERS
Explosionproof:
Class ll, Zone 21, AEx tb IIIC T95o Db
Foundation
Fieldbus
-50 ºC to 70ºC
Nonincendive:
Class l, Zone 2 , AEx nA IIC T4 Gc
4-20 mA /
Fieldbus
Enclosure: Type 4X/ IP66/ IP67
All
All
-
Canadian
Standards
Explosion Proof:
Ex tb IIIC T95o Db
Foundation
Fieldbus
-50 ºC to 70ºC
Enclosure: Type 4X/ IP66/ IP67
All
All
-
TEX
Flameproof:
II 2 D Ex tb IIIC T95o Db
Intrinsically Safe:
Ex ia IIC T4 Ga; Ex ic IIC T4 Gc
4-20 mA / DE/ HART
4-20 mA /
Fieldbus
Enclosure: IP66/ IP67
All
All
-
Flameproof :
Ex tb IIIC Db T 95oC Db
Intrinsically Safe:
Ex ia IIC T4 Ga; Ex ic IIC T4 Gc
4-20 mA /
DE/ HART
Nonincendive:
4-20 mA /
Fieldbus
Enclosure: IP66/ IP67
All
All
-
Flameproof :
Ex tb IIIC Db T 95oC
Intrinsically Safe:
Ex ia IIC T4 Ga; Ex ic IIC T4 Gc
4-20 mA /
DE/ HART
Nonincendive:
4-20 mA /
Fieldbus
Enclosure: IP66/ IP67
All
All
-

Hazardous Locations Certifications

AGENCY TYPE OF PROTECTION
Class I, Divis ion 1, Groups A, B, C, D; Dust Ignition Pro of: Class II, I II, Division 1, Groups E, F, G ; T6..T5 Class l, Zone 0 /1, AEx db IIC T6..T5 Ga/Gb
FM
Intrinsically Safe:
T
Approvals
Associati
on (CSA)
Class I, II , III, Division 1, Groups A, B, C,
M
D, E, F, G: T4
USA
Class l, Zone 0 , AEx ia IIC T4 Ga FISCO Field Dev ice (Only for FF Option) Ex ia IIC T4 Ga; Ex ic IIC T4 Gc
Class I, Divis ion 2, Groups A, B, C, D locations, T4
Class I, Divis ion 1, Groups A, B, C, D; Dust Ignition Pro of: Class II, I II, Division 1, Groups E, F, G ; T6..T5 Class I Zone 1 AEx db IIC T6..T5 Ga/Gb Ex db IIC T6..T5 Ga /Gb Zone 22 AEx tb II IC T95o Db
Intrinsically Safe: Class I, II , III, Division 1, Groups A, B, C, D, E, F, G; T4 Class I Zone 0 AEx ia IIC T4 Ga
USA and
Ex ia IIC T4 Ga
Canada
FISCO Field Dev ice (Only for FF Option) Ex ia IIC T4 Ga; Ex ic IIC T4 Gc
Nonincendive:
Class I, Divis ion 2, Groups A, B, C, D; T4 Class I Zone 0 AEx nA IIC T4 Gc Ex nA IIC T4 Gc
COMM.
OPTION
All Note 1
4-20 mA / DE/ HART
DE/ HART/
Foundation
All Note 1
4-20 mA / DE/ HART
4-20 mA /
DE/ HART/
Foundation
Fieldbus
PARA-
Note 2a -50 ºC to 70ºC
Note 2b
Note 1 -50 ºC to 85ºC
Note 2a -50 ºC to 70ºC
Note 2b
Note 1 -50 ºC to 85ºC
AMBIENT
TEMP (Ta)
T5: -50 ºC to
85ºC
T6: -50 ºC to
65ºC
T5: -50 ºC to
85ºC
T6: -50 ºC to
65ºC
II 1/2 G Ex db II C T6..T5 Ga/Gb
II 1 G Ex ia IIC T4 Ga FISCO Field Dev ice (Only for
A
FF Option)
Nonincendive:
II 3 G Ex nA IIC T4 Gc
Ex db IIC T6..T5 Ga/ Gb
Ex ia IIC T4 Ga
FISCO Field Dev ice (Only for
IECEx
FF Option)
World
Ex nA IIC T4 Gc
Ex d IIC Ga/Gb T4
Ex ia IIC Ga T4
SAEx
FISCO Field Dev ice (Only for
South
FF Option)
Africa
Ex nA IIC Gc T4
All Note 1
Foundation
Fieldbus
DE/ HART/
Foundation
All
Note 1
Foundation
Fieldbus
DE/ HART/
Foundation
All Note 1 -50 ºC to 85ºC
Foundation
Fieldbus
DE/ HART/
Foundation
T5: -50 ºC to 85ºC T6: -50 ºC to 65ºC
Note 2a -50 ºC to 70ºC
Note 2b
Note 1 -50 ºC to 85ºC
Note 2a -50 ºC to 70ºC
Note 2b
Note 1 -50 ºC to 85ºC
Note 2a -50 ºC to 70ºC
Note 2b
Note 1 -50 ºC to 85ºC
-50 ºC to 70ºC
T5: -50 ºC to 85ºC T6: -50 ºC to 65ºC
-50 ºC to 70ºC
-50 ºC to 70ºC
Quick Start Installation Guide 7
Flameproof: Ex Ex tb IIIC T 95oC Db
Intrinsically Safe: Ex ia IIC T4 Ga
FISCO Field Dev ice (Only for FF Option) Ex ia IIC T4 Ga; Ex ic I IC T4 Gc
4-20 mA / DE/
HART
Note
2a
Nonincendive:
Ex nA IIC T4 Gc
4-20 mA / DE/
Fieldbus
Enclosure : IP 66/67
All
All
-
Flameproof: Ex d IIC Ga/Gb T4 Ex tb IIIC Db T 85oC
Intrinsically Safe:
FISCO Field Dev ice (Only for FF Option) Ex ia IIC T4
4-20 mA / DE/
HART
Note
2a
Nonincendive:
Ex nA IIC Gc T4
4-20 mA / DE/
Fieldbus
Enclosure : IP 66/67
All
All
-
Belarus and
Flameproof:
1 Ex d IIC Ga/G b T4 Ex tb IIIC Db T 85oC
Intrinsically Safe:
FISCO Field Dev ice (Only for FF Option) Ex ia IIC T4
4-20 mA / DE/ HART
Note
2a
Enclosure : IP 66/67
All
All
T6: Ta= -50 ºC to
85ºC
4-20 mA / DE/ HART
Note
2a
Note
2c
Ta= -50 ºC to
Enclosure: IP66/ IP67
All
All
-
Voltage= 11 to 42 V
Current= 4-20 mA Normal (3.8 – 23 mA Faults)
that the product was manufactured in 2002, in the 23rd week
Maximum Process Temperat ure
Temperature C lass
T6
T5
T4
Ambient Temperature
-50oC TO +65 oC
80 oC
----
120 oC
-50oC TO +70 oC
-----
----
120 oC
-50oC TO +85 oC
-----
95 oC
110 oC
INMETRO
Brazil
NEPSI China
db IIC T6..T5 Ga/G b
Ex ia IIC Ga T4
All Note 1 50 ºC to 85ºC
50 ºC to 70ºC
Foundation
Fieldbus
HART/
Foundation
Foundation
Fieldbus
HART/
Foundation
Note
50 ºC to 70ºC
2b
Note
-50 ºC to 85ºC
1
All Note 1 -50 ºC to 85ºC
-50 ºC to 70ºC
Note
-50 ºC to 70ºC
2b
Note
1
-50 ºC to 85ºC
EAC
Russia,
0 Ex ia IIC Ga T4
Kazakhstan
Flameproof :
Ex d IIC T6..T5 Ex tD T 95oC
KOSHA
Korea
Intrinsically Safe:
Ex ia IIC T4
Notes
1. Operating Parameters:
2. Intrinsically Safe Entity Parameters
For details see Control Drawing below.
3. Marking ATEX Directive General:
The following information is provided as part of the labeling of the transmitter:
Name and Address of the manufacturer
Notified Body identification: DEKRA Quality B.V., Arnhem, the
For complete model number, see the Model Selection Guide
The serial number of the transmitter is located on the Meter
Netherlands for the particular model of pressure transmitter. Body data-plate. The first two digits of the serial number
identify the year (02) and the second two digits identify the week of the year (23); for example, 0223xxxxxxxx indicates
All Note 1 -50 ºC to 85ºC
-50 ºC to 70ºC
Foundation
Fieldbus
Foundation
Fieldbus
Note
2b
All Note 1
2b &
-50 ºC to 70ºC
T5: Ta= -50 ºC to
Ta= -50 ºC to 70ºC
65ºC
70ºC
Notes
3., continued Apparatus Marked with Multiple Types of Protection
The user must determine the type of protection required for installation the equipment. The user shall then check the box [ ] adjacent to the type of protection used on the equipment certification nameplate. Once a type of protection has been checked on the nameplate, the equipment shall not then be reinstalled using any of the other certification types.
4. WARNINGS and Cautions:
Intrinsically Safe and Non-Incendive Equipment: WARNING: SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR USE IN HAZARDOUS LOCATIONS. Explosion-Proof/ Flameproof: WARNING: DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE MAY BE PRESENT Non-Incendive Equipment: WARNING: DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE MAYBE PRESENT WARNING: FOR CONNECTION IN AMBIENTS ABOVE 60oC USE WIRE RATED 105oC
5. Conditions of Use for Ex Equipment, “Hazardous Location Equipment” or “Schedule of Limitations”:
Painted surface of the ST700/ST800 may store electrostatic charge and become a source of ignition in applications with a low relative humidity less than approximately30% relative humidity where the painted surface is relatively free of surface contamination such as dirt, dust or oil. Cleaning of the painted surface should only be done with a damp cloth.
Flame-proof Installations: The transmitter can installed in the boundary wall between an area of EPL Ga/ Class I Zone 0/ Category 1 and the less hazardous area, EPL Gb/ Class I Zone 1/ Category 2. In this configuration, the process connection is installed in EPL Ga/ Class I Zone 0/ Category 1, while the transmitter housing is located in EPL Gb/ Class I Zone 1/ Category 2.
The applicable temperature class, ambient temperature range and maximum process temperature of the equipment is as follows;
5. Continued
PROCESS TEMPERA TURE VS AMBIENT TEMPERATURE
Consult the manufacturer for dimensional information on the flameproof joints for repair. The transmitter can be installed in the boundary wall between an area of Category 1 and the less hazardous area, Category 2. In this configuration, the process connection is installed in Category 1 while the transmitter housing is installed in Category 2.
Intrinsically Safe: Must be installed per drawing 50049892 Division 2: This equipment is suitable for use in a Class I, Division 2,
Groups A, B, C, D; T4 or Non-Hazardous Locations Only. The enclosure is manufactured from low copper aluminum alloy. In rare
cases, ignition sources due to impact and friction sparks could occur. This shall be considered during Installation, particularly if equipment is installed a Zone 0 location. If a charge-generating mechanism is present, the exposed metallic part on the enclosure is capable of storing a level of electrostatic that could become incendive for IIC gases. Therefore, the user/ installer shall implement precautions to prevent the buildup of electrostatic charge, e.g. earthing the metallic part. This is particularly important if equipment is installed a Zone 0 location.
Quick Start Installation Guide 8
This certificate defines the certifications covered for the
these products into marine applications.
American Bureau of Shipping (ABS) - 2009 Steel
PDA
Bureau Veritas (BV) - Product Code: 389:1H. Certificate number: 12660/B0 BV
Det Norske Veritas (DNV) - Location Classes:
applied. Certificate number: A-11476
Korean Register of Shipping (KR) - Certificate number: LOX17743-AE001
Lloyd's Register (LR) - Certificate number: 02/60001(E1) & (E2)
SIL 2/3
IEC 61508 SIL 2 for non-redundant use and SIL 3 for
2010; IEC 61508-2: 2010; IEC61508-3: 2010.
MEASUREMENT
Certificate Issued by NMI Certin B.V.
Unit
Custom Calibration
STA84L
0 to 35 Bar A
STG84L
0 to 35 Bar
STA87L
0 to 100 Bar A
STG87L
0 to 100 Bar
Marine
Certificates
ST 800 Pressure Transmitter family of products, it represents the compilation of the five certificates Honeywell currently has covering the certification of
Vessel Rules 1-1-4/3.7, 4-6-2/5.15, 4-8-3/13 & 13.5, 4-8­4/27.5.1, 4-9-7/13. Certificate number: 04-HS417416-
Temperature D, Humidity B, Vibration A, EMC B, Enclosure C. For salt spray exposure; enclosure of 316 SST or 2-part epoxy protection with 316 SST bolts to be

Control Drawing

Certification
INTRUMENTS DIRECTIVE (MID) 2004/ 22/ EC
ST800 only
redundant use according to EXIDA and TÜV Nord Sys Tec GmbH & Co. KG under the following standards: IEC61508-1:
Mechanical Class: M3 Electromagnetic Environment: E3 Ambient Temperature Range: -25 oC to + 55 oC
Quick Start Installation Guide 9
34-ST-25-36, Rev .10 2020 Honeywell International Inc.
ASIA PACIFIC (TAC) hfs-tac-support@honeywell.com
EMEA, Phone: + 80012026455 or +44 (0)1202645583. FAX: +44 (0) 1344 655554
AMERICAS, Honeywell Process Solutions,
WARRANTY/REMEDY
Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship. Contact your local sales office for warranty information. If warranted goods are returned to Honeywell during the period of coverage, Honeywell will repair or replace without charge those items it finds defective. The foregoing is Buyer's sole remedy and is in lieu of all other warranties, expressed or implied, including those of merchantability and fitness for a particular purpose. Specifications may change without notice. The information we supply is believed to be accurate and reliable as of this printing. However, we assume no responsibility for its use.
Sales and Service
For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one of the offices below.
Australia Honeywell Limited, Phone: +(61) 7-3846 1255, FAX: +(61) 7-3840 6481 Toll Free 1300-36-39-36, Toll Free Fax: 1300-36-04-70 China – PRC – Shanghai, Honeywell China Inc. Phone: (86-21) 5257-4568, Fax: (86-21) 6237-2826
Singapore, Honeywell Pte Ltd. Phone: +(65) 6580 3278. Fax: +(65) 6445-3033 South Korea, Honeywell Korea Co Ltd. Phone:+(822)799 6114. Fax:+(822) 792 9015
Email: (Sales) sc-cp-apps-salespa62@honeywell.com or (TAC) hfs-tac-support@honeywell.com
Phone: (TAC) 1-800-423-9883 or 215/641-3610. (Sales) 1-800-343-0228. Email: (Sales) FP-Sales-Apps@Honeywell.com or (TAC) hfs-tac-support@honeywell.com
While we provide application assistance personally, through our literature and the Honeywell web site, it is up to the customer to determine the suitability of the product in the application.
For more information To learn more about SmartLine Transmitters, visit www.honeywellprocess.com Or contact your Honeywell Account Manager
Process Solutions Honeywell
1250 W Sam Houston Pkwy S Houston, TX 77042
Honeywell Control Systems Ltd Honeywell House, Skimped Hill Lane Bracknell, England, RG12 1EB
Shanghai City Centre, 100 Jungi Road Shanghai, China 20061
www.honeywellprocess.com
June 2020
Loading...