Honeywell SK-Beam-T Installation And Maintenance Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
SK-Beam, SK-Beam-T
I56-3433-004
Single-ended Reected Type Projected Beam Smoke Detector
SPECIFICATIONS GENERAL
Range: 16 to 230 Feet (5 to 70 m); 230 to 328 Feet (70 to 100 m) using optional accessory BEAMLRK Sensitivity: 25% to 50% Total Obscuration in 6 levels Level 1 = 25% Level 2 = 30% Level 3 = 40% Level 4 = 50% Level 5 = 30% to 50% (Acclimate) Level 6 = 40% to 50% (Acclimate) Spacing: 30 to 60 Feet (9.1 to 18.3 m) Response Time: ALARM - 20 seconds typical TROUBLE - 30 seconds typical Trouble Conditions: Beam Blockage (96% or More Obscuration) Improper Initial Alignment Self-compensation limit reached (service needed) In Alignment mode Test/Reset Features: Integral Sensitivity Test Filter (SK-Beam-T only, requires additional external power supply) Sensitivity Filter (Incremental scale on reflector) Local Alarm Test Switch Local Alarm Reset Switch Remote Test and Reset Switch Capability (compatible with RTS451/RTS451KEY/RTS151/RTS151KEY) Indicators: ALARM - Remote Output, Local LED (red) TROUBLE - Remote Output, Local LED (yellow) Blink Pattern Indicates Trouble Diagnostics NORMAL OPERATION - Local LED (flashing green with communication) ALIGNMENT AIDS - Optical Gunsight (coarse adjustment) 00 to 99 Digital Display (fine adjustment) SENSITIVITY - Digital Display Readout in Percent Obscuration Style 7 Operation: On-board isolators provide style 7 operation. (may be disabled via shunts on circuit board)
12 Clintonville Road, Northford, CT 06472-1610
Phone: 203-484-7161 Fax: 203-484-7118
www.silentknight.com
ENVIRONMENTAL
Temperature: –22°F to 131°F (–30°C to 55°C); NOTE: for applications below 32°F (0°C) see Special Applications section of this manual. Humidity: 10% to 93% RH Noncondensing Mechanical Shipping Weight: 3.9 lbs. (1.77 kg) Shipping Size: 15˝ × 10.5˝ × 6.5˝ (381 mm × 267 mm × 165 mm) Mounting: Wall only without optional accessories Wiring: Plug-in Terminal Blocks (12 to 22 AWG) Adjustment Angle: ±10° Horizontal and Vertical Paintable Trim Ring: May be painted using enamel or acrylic type paints Electrical Voltage: 15 to 32 VDC Standby Current: Avg. Standby: 2 mA Max. (1 communication every 5 sec., LED flashing, SLC @ 24 V) Max. Alarm (LED on): 8.5 mA Max. Max. Trouble (LED on): 4.5 mA Max. Max. Alignment: 20 mA Max. External Supply (SK-Beam-T only): VO LTAG E - 15 to 32 VDC CURRENT - 0.5 A Max. Remote Output: (alarm) VOLTAGE - 15 to 32 VDC; NOTE: Output voltage same as device input voltage. CURRENT - 15 mA maximum; 6 mA minimum; NOTE: Output current is limited by 2.2 k resistor.
GENERAL DESCRIPTION
Model SK-Beam/SK-Beam-T is a long range projected beam smoke detector designed to provide open area protection. It is to be used with UL-listed com­patible control panels only. The detector consists of a transmitter/receiver unit and a reflector. Smoke entering the area between the transmitter/receiver and reflector causes a reduction in signal. When the obscuration reaches alarm thresholds (chosen at the transmitter/receiver unit), the detector generates an alarm signal. Complete blockage of the beam causes a trouble signal. Slow changes in obscuration due to a build up of dirt or dust on the lens of the detector are compensated for by a microcontroller that continuously monitors
the signal strength and periodically updates the alarm and trouble thresh­olds. When the self-compensation circuit reaches its limit, the detector gen­erates a trouble signal, indicating the need for service.
Three LEDs on the detector indicate the current status: a red LED for alarm, a yellow LED for trouble, and a blinking green LED for standby operation. Note: The panel controls the status of the red and green LEDs. The local reset button is accessible by removing the outer paintable trim ring. The yellow LED will blink in specific patterns to provide a diagnostic aid when diagnosing the cause of a trouble signal. It will also blink the amount of drift compensation that has been used at the conclusion of the test. Trouble sig-
1 I56-3433-004 04-12
nals automatically reset upon removing the cause of trouble. Red and yellow
TERMINAL BLOCK
ISOLATOR
SHUNT
PAINTABLE TRIM RING
LEDs can be remotely connected to the remote Alarm and Trouble outputs. These outputs mimic the functions of the detector’s red and yellow LEDs. In addition to these indicators, there is a dual digital display that reads 00 to
99. This display is used to indicate the signal strength of the beam in align­ment mode and to indicate the sensitivity setting of the detector in percent obscuration when setting the sensitivity of the detector. No additional equip­ment is needed for alignment of the beam.
SPECIAL APPLICATIONS
Due to the inherent capabilities of projected type beam detectors they are often installed in locations where spot-type detection is impractical. Projected type beam smoke detectors are ideally suited for environmental conditions that might include high ceilings, dusty and dirty environments, or environ­ments that experience temperature extremes. Often these conditions present special problems for the installation of spot-type detectors and even greater problems for their proper maintenance. Due to the inherent flexibility of mounting locations and large coverage area of projected type beam detectors often the conditions above can be addressed or minimized.
Some examples of applications for beam detectors might include freezers, air­craft hangars, cold storage warehouses, shipping warehouses, enclosed park­ing facilities, sporting arenas and stadiums, concert halls, barns, or stables. Some of these environments might be considered too hostile for spot-type smoke detectors. If the environment is considered to be hostile then the colder alarm threshold settings should be used.
Before installing the transmitter/receiver unit or reflector in these types of applications special consideration should be given to insure proper operation of the beam detector. The beam detector should not be installed in environ­ments where heavy condensation or icing is likely. Condensation or icing of the reflector surface or the outer surface of the transmitter/receiver unit will obscure the light beam resulting in a false alarm. If elevated humidity levels and rapidly changing temperatures can be expected then condensation will likely form and the application should not be considered acceptable for the beam detector.
APPROVED ACCESSORIES
The following accessories can be purchased separately for use with this beam detector.
BEAMLRK
The BEAMLRK allows reflected beam detectors to be installed at separations between 230 and 328 feet (70 to 100 meters). At these distances, four 8˝ × 8˝ reflectors must be used to provide enough reflected infrared light. This kit includes 3 additional reflectors with new test scale legends. The reflector included with the transmitter/receiver unit is the fourth reflector to be used. This kit is not compatible with the multi-mount kit (BEAMMMK).
BEAMMMK
The BEAMMMK allows reflected beam detectors and reflectors to be mounted to either a vertical wall or the ceiling. The kit allows for additional alignment range in cases where the detector and reflector cannot be mounted within 10° of each other. The kit includes the hardware necessary to mount either a single transmitter/receiver unit or a single reflector. (To mount the trans­mitter/receiver the surface mount kit, BEAMSMK, must also be used). If the transmitter/receiver and the reflector require additional alignment range two kits are required. The kit is not compatible with the long-range reflector kit (BEAMLRK).
BEAMSMK
The BEAMSMK allows reflected beam detectors to be mounted when surface wiring is used. This kit must be used when mounting the transmitter/receiver unit with the multi-mount kit (BEAMMMK).
6500-MMK
The 6500-MMK provides a heavy-duty multi-mount bracket for installations prone to building movement or vibration. It offers similar tilt and swivel flex­ibility found on the BEAMMMK. (To mount the transmitter/receiver to the 6500-MMK, the surface mount kit, 6500-SMK, must be used).
6500-SMK
The 6500-SMK allows the transmitter/receiver to be mounted to the 6500­MMK heavy duty multi-mount kit.
2 I56-3433-004 04-12
BEAMHK
The BEAMHK allows the transmitter/receiver unit to operate in environments prone to the formation of condensation. Condensation forming on the beam detector unit may result in trouble or false alarm conditions. BEAMHK will lessen the likelihood of condensation by maintaining the unit at a temperature that is slightly higher than the surrounding air. Please refer to the BEAMHK installation manual for operation instructions.
BEAMHKR
The BEAMHKR allows the reflector to operate in environments prone to the formation of condensation. Condensation forming on the reflector may re­sult in trouble or false alarm conditions. BEAMHKR will lessen the likelihood of condensation by maintaining the reflector at a temperature that is slightly higher than surrounding air. The kit requires a 24V power supply. When used with the long-range reflector kit (BEAMLRK), it is necessary to purchase and install four BEAMHKR kits. Please refer to the BEAMHKR installation manual for operation instructions.
RTS451/RTS451KEY/RTS151/RTS151KEY
The remote test accessory, RTS451/RTS451KEY or RTS151/RTS151KEY, allows for the beam detector to be tested remotely. The test accessory provides test and reset functions and green and red LED’s that mimic the LEDs on the detector.
PARTS LIST
Description Quantity
Transmitter/Receiver Unit .....................................1
Paintable Trim Ring .........................................1
Reflector ..............................................1
Plug-in Terminal Blocks ......................................3
Isolator Shunts ............................................2
Instruction Manual .........................................1
Orange Paper Sheet .........................................1
PARTS DIAGRAM (NOT TO SCALE)
C0306-00
DETECTOR PLACEMENT
This section of the manual discusses the placement of projected beam detec­tors. Though this information is based upon industry expertise, it is intended to be used only as a technical guide. Always comply with the requirements of applicable codes and standards such as, NFPA 72, National Fire Alarm Code, as well as directives of the Authority Having Jurisdiction (AHJ).
Projected beam detectors are usually located with their beams parallel to the ceiling. However, they can be mounted vertically or at any angle to protect the area involved. Since beam detectors sense the smoke buildup over a distance, they are ideal for locations with high ceilings. They can also be mounted on a wall or ceiling below the level of a spot type detector, reducing the effects of air stratification. Some typical locations would include large areas with high ceilings such as atriums, warehouses, and factories.
NOTE: Projected beam smoke detectors should always be mounted to sta­ble mounting surfaces. See the MOUNTING LOCATION section for details. Some fire codes specify spacing on a given center-to-center distance between detectors under ideal conditions. This spacing is based on rooms with smooth ceilings and no physical obstructions between the contents being protected and the detectors. Moreover, they are also based on a maximum ceiling height, and on the assumption that the value and the combustible nature of the con­tents of the room being protected do not warrant greater protection or closer spacing.
In a room with a smooth ceiling, detectors should be spaced between 30 and
MAX.
MOUNT SPOT DETECTOR
60 feet (9.1 to 18.3 m). One-half that spacing between the beam and the side­wall may be used as a guide. See Figure 1. The beam detector can be mounted with the transmitter/receiver on one wall and the reflector on the opposite wall, or both suspended from the ceiling, or any wall/ceiling combination. In the case of the ceiling mount, the distance from the end walls should not exceed one-quarter of the selected spacing (7.5 ft. [2.3 m] maximum if the spacing is 30 ft. [9.1 m] ). See Figure 2.
FIGURE 1. SPACING FOR SMOOTH CEILING (SIDE VIEW):
1
/2 S S
FIGURE 3. SLOPED CEILING (SHED TYPE):
3 FT.
(0.9M)MAX.
S
REFLECTOR
Tx/Rx
S
1
2
/
S MAX.
12 - 18 IN.
(0.3 - 0.46M)
WALL
FIGURE 2. SPACING FOR SMOOTH CEILING (TOP VIEW):
1
/2 S MAXIMUM
Tx/Rx REFLECTOR
1
/4 S
S
Tx/Rx REFLECTOR
16 FT. (5M) MINIMUM
328 FT. (100M) MAXIMUM
In the case of peaked or sloped ceilings, codes may specify spacing of detec­tors by using horizontal spacing from the peak of the roof or ceiling. Figures 3 and 4 show the spacing for both the shed type and peaked type sloped ceilings.
On smooth ceilings, beam smoke detectors should generally be mounted be­tween 12 and 18 inches (0.3 to 0.46 m) from the ceiling. In many cases, how­ever, the location and sensitivity of the detectors shall be the result of an engineering evaluation that includes the following: structural features, size and shape of the room and bays, occupancy and uses of the area, ceiling height, ceiling shape, surface and obstructions, ventilation, ambient environ­ment, burning characteristics of the combustible materials present, and the configuration of the contents in the area to be protected. As a general rule, reflective objects such as ductwork or windows should be a minimum of 15 inches (38.1 cm) from the path of the beam.
C0254-00
C0255-00
C0256-00
FIGURE 4. SLOPED CEILING (PEAKED TYPE):
ANYWHERE IN THIS
AREA AT LEAST 4 IN. (100 mm)
VERTICALLY FROM PEAK
REFLECTOR
Tx/Rx
1
2
/
S S
3 FT. (0.9M)
MAX.
S
3 FT. (0.9M)
MAX.
1
2
/
S
C0257-04
MOUNTING LOCATIONS
Beam detectors require a stable mounting surface for proper operation. A sur­face that moves, shifts, vibrates, or warps over time will cause false alarm or trouble conditions. Initial selection of a proper mounting surface will elimi­nate false alarms and nuisance trouble signals.
Mount the detector on a stable mounting surface, such as brick, concrete, a sturdy load-bearing wall, support column, structural beam, or other sur­face that is not expected to experience vibration or movement over time. DO NOT MOUNT the beam detector on corrugated metal walls, sheet metal walls, external building sheathing, external siding, suspended ceilings, steel web trusses, rafters, nonstructural beam, joists, or other such surfaces.
In cases where only one stable mounting surface as defined above can be used, the transmitter/receiver unit should be mounted to the stable surface and the reflector should be mounted to the less stable surface. The reflec­tor has a much greater tolerance for the unstable mounting locations defined above.
MOUNTING INSTRUCTIONS
The transmitter/receiver unit may be mounted over a recessed junction box. The cavity behind the detector is then used for routing of the wiring from the junction box to the terminal blocks on the detector. The transmitter/receiver unit should be mounted to the wall such that unit covers the recessed junc­tion box in the wall completely. If the junction box is not recessed then you may use the surface mount kit (BEAMSMK). See the BEAMSMK installation instructions for surface mounting instructions. The transmitter/receiver unit can be mounted to the wall using the supplied drilling template (see Appendix II). The detector base has 4 primary mounting keyholes, one in each corner of the base. All four hole locations should be used to provide a secure mounting. The outer housing of the beam detector is held to the base using four screws. In order to mount the detector you must remove the outer housing first.
The reflector can be mounted to the wall using the supplied drilling template (see Appendix III). The reflector has 4 mounting holes, one in each corner. All four hole locations should be used to provide a secure mounting. The reflector must be mounted such that it is within 10° in both the X and Y planes of the transmitter/receiver unit. See Figure 5a. The reflector must also be mounted such that the plane of the reflector is perpendicular to the optical
3 I56-3433-004 04-12
line of sight to the transmitter/receiver unit. The maximum tolerance for non­perpendicular mounting locations is 10°. See Figure 5b. If the reflector cannot be mounted within 10° of the transmitter/receiver unit then the multi-mount kit (BEAMMMK) or the heavy-duty multi-mount kit (6500-MMK) may be used to provide greater angular adjustment of the transmitter/receiver unit. If the perpendicular plane of the reflector cannot be mounted within 10° of the op­tical line of sight then the multi-mount kit can be used for the reflector. See BEAMMMK or 6500-MMK instructions.
To aid in locating the reflector in the alignment mirror at long distances an orange, adhesive-backed sheet of paper is provided. Remove the protective backing from the orange paper. Temporarily affix the orange paper next to the reflector. The location of the paper is not critical. It may be placed anywhere near the reflector as long as it not covering the reflective surface of the reflec­tor. This paper should be removed once the installation is completed.
FIGURE 5A. REFLECTOR MOUNTING GUIDELINES
X
WALL
Y
10°
10°
REFLECTOR
ACCEPTABLE MOUNTING LOCATIONS FOR REFLECTOR
C0258-01
FIGURE 5B. REFLECTOR MOUNTING GUIDELINES
10° MAXIMUM
OPTICAL LINE OF SIGHT
REFLECTOR
C0259-00
MOUNTING CONSIDERATIONS FOR SINGLE ENDED BEAM DETECTORS
There must be a permanent clear line of vision between the detector and the reflector. Reflective objects must not be near the line of vision between the detector and reflector. Reflective objects too near to the line of sight can reflect the light beam from the transmitter to the receiver. If this occurs, the detector will not be able to distinguish these reflections from those of the reflector and the protected space will be compromised. Reflective objects such as ductwork or windows should be a minimum of 15 inches (38.1 cm) from the path of the beam. In cases where reflective objects cannot be avoided, the complete re­flector blockage test can be used to determine if the installation is acceptable. See Testing and Maintenance Section of this manual.
Light sources of extreme intensity such as sunlight and halogen lamps, if di­rected at the receiver, can cause a dramatic signal change resulting in fault and alarm signals. To prevent this problem direct sunlight into the trans­mitter/receiver unit should be avoided. There should be a minimum of 10° between the pathway of the light source and detector and the line of sight between detector and reflector.
Operation of the detector through panes of glass should be avoided. Since single ended beam detectors operate on a reflection principle, a pane of glass perpendicular to the line of sight between the detector and the reflector can reflect the light beam from the transmitter to the receiver. If this occurs, the
detector will not be able to distinguish these reflections from those of the re­flector and the protected space will be compromised.
Panes of glass will also absorb some of the light as it passes through it. This absorption of light will reduce the acceptable installed distance between the detector and the reflector.
In cases where operation through panes of glass cannot be avoided some spe­cific installation practices can help to minimize the effects of the glass. These practices include: avoid penetration of multiple panes of glass, position the glass so that it is not perpendicular to the line of sight between the detector and the reflector, (A minimum of 10° off perpendicular should be considered), and make certain that the glass is smooth, clear and mounted securely. The complete reflector blockage test can be used to determine if the installation is acceptable. See Testing and Maintenance Section of this manual.
Where high ceilings (in excess of 30 feet or 9.1 meters) are present additional beams may be required to detect smoke at lower levels.
WIRING INSTALLATION GUIDELINES
Always install all wiring in compliance with the National Electrical Code, and/ or the applicable local codes, and any special requirements of the local au­thority having jurisdiction. Proper wire gauges and suitable means for strain relief should be used. The conductors used to connect beam smoke detectors to control panels and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a fire.
Installation wire used for the beam detector shall be no smaller than 22 AWG (1.0 mm2). For best system performance, all wiring should be twisted pair and installed in separate grounded conduit. Do NOT mix fire system wiring in the same conduit as any other electrical wiring. Shielded cable may be used to provide additional protection against electrical interference.
When installing the beam smoke detector in applications where the head unit will be mounted to either a wall or the ceiling using the multi-mount kit (BEAMMMK) or 6500-SMK flexible conduit will be used. The surface mount kit (BEAMSMK) or 6500-SMK and multi-mount kit (BEAMMMK) or 6500-SMK must be installed with the cable before wiring the unit, according to the in­structions supplied with the kit.
When the detector has been mounted over a recessed junction box, all wiring should be routed out of the box and behind the detector to the bottom of the detector where the terminal blocks are located. When installing the wiring in the junction box be sure to leave enough wire in the box to connect to the terminal blocks. (Approximately 9˝ (23 cm) of wire outside of the junction box will be required for proper installation). All wiring to the detector is done via pluggable terminal blocks. In order to properly make electrical connections strip approximately 1/4˝ (6 mm) of insulation from the end of the wire, sliding the bare end of the wire under the clamping plate screw.
Figure 6 shows all the wiring connections to the transmitter/receiver unit. Figure 7 shows the proper wiring diagram for either Class A or Class B opera­tion. Figure 8 shows the connections that are necessary when using one of the optional remote test stations (RTS451/RTS151 or RTS451KEY/RTS151KEY). Figure 9 shows the remote output for alarm indication.
WARNING: Disable the zone or system before applying power to the beam
detector to prevent unwanted alarms. When applying power to the beam detector before the alignment procedure has been com­pleted the detector may enter alarm or fault.
4 I56-3433-004 04-12
FIGURE 6. WIRING CONNECTIONS AT DETECTOR
TROUBLE OUT
T
DETECTOR
manual for cir cuit output ratings.
FIGURE 8. WIRING DIAGRAM (RTS451/RTS151)
T3 T2 T1
RESET I NPUT
TEST INPUT
AUX (–)
REMOTE ALARM OUT
NOT USED
REMOTE
TEST OPTION (–)
TEST OPTION (+)
SLC (–)
SLC (+)
SLC (–)
SLC (+)
C0260-01
PIN 1
PIN 2
PIN 4
PIN 3
PIN 5
RTS451/RTS451KEY
or RTS151/RTS151KEY
SLC IN +T1-1
T1-2
T2-1
REMOTE ALARM OUT
T2-2
AUX (–)
T2-4
RESET INPUT
T2-3
TEST INPUT
T3-3
REMOTE TROUBLE OUTPUT
OPTIONAL YELLOW LED
FIGURE 9. WIRING DIAGRAM (RTS451/RTS151)
BDT-SS
SLC (+)
Alarm Signal
Circuit
(Note 1)
SLC ( –)
Note 1: See electrical ratings section of this
T2-1
T2-2
SLC OUT +
SLC OUT –
Red
T1-3
T1-4SLC IN –
C0328-06
C0369-00
FIGURE 7. WIRING DIAGRAM
T3 T2 T1
LISTED
REMOTE
POWER
SOURCE
* Only used for SK-BEAM-T. See electrical ratings.
+
ñ
FROM PANEL OR
PREVIOUS DEVICE
COMMUNICATION LINE
+ñ+ñ+
ñ
32 VDC MAX. TWISTED PAIR IS RECOMMENDED.
TO NEX
DEVICE
C0335-03
INSTALLATION / ALIGNMENT
Reference Figures 10 through 14 for installation, alignment, and maintenance.
Please make sure to complete all steps in order to ensure a successful installa­tion. Proper application, mounting, alignment, and set-up will minimize false alarms and nuisance trouble signals.
PRE-ALIGNMENT CHECKLIST
• Insure that both the detector and reflector are mounted securely to stable surfaces.
• Insure that all wiring is correct.
• Insure that terminal blocks are fully seated into their receptacles on the detector.
• Complete any wiring dressing to minimize movement to the detector once the alignment procedure is completed.
• Insure that the appropriate number of reflectors are used for the installed distance. Distances between 230 and 328 Feet (70 – 100 m) require ad­ditional reflectors (4 total). The BEAMLRK accessory should be used in these cases.
• Insure that the line of sight between the detector and reflector is clear and that reflective objects are not too near. See Mounting Instructions for more details.
• Insure that both the detector and reflector are mounted within their
ñ
+
operational parameters for off axis angles. See Mounting Instructions for more details.
• Disable the zone or system to prevent unwanted alarms before applying power.
• Insure power to the detector is “ON”.
• Insure that the appropriate address is set on the code wheels.
You are now ready to begin the alignment procedure.
5 I56-3433-004 04-12
Loading...
+ 9 hidden pages