Honeywell S9361A, S9360A, S9371A, S9370A User Manual

S9360A, S9361A, S9370A, S9371A Integrated Boiler Controllers
INSTALLATION INSTRUCTIONS
SPECIFICATIONS
IMPORTANT:
The specifications given in this publication do not include normal manufacturing tolerances. Therefore, an individual unit may not match the listed specifications exactly. Also, this product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those conditions are changed.
Model Numbers
APPLICATION
These integrated boiler control modules provide ignition sequence, flame monitoring and safety shutoff for either intermittent pilot spark ignition or direct hot surface ignition heating systems. They also provide limit rated water temperature control and display interface capability for either “on-board” or remote user interface applications.
• S9360A—Spark Ignition, Intermittent Pilot, Remote Display.
• S9361A—Spark Ignition, Intermittent Pilot, “On board” Display.
• S9370A—Hot Surface Ignition, Remote Display.
• S9371A—Hot Surface Ignition, “On board” Display.
• Enabled with EnviraCOM™ communication capability to support remote monitoring and diagnostics.
• Limit-rated Temperature Sensing Probe.
• One or Two Sensor Models.
S—Switching Control
93—Integrated Hydronic Control Platform
6—Spark Ignition 7—Hot Surface Ignition
0—Remote Display Required 1—Integrated On-Board Display
A—Boiler Control B—Water Heater Control C—Pool Heater Control
1—No Circulator 2—On/Off Circulator
S9360A1000
Dimensions:
See Fig. 1.
69-2076-01
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS
111
I
2 x 84.5
2 x 15
Fig. 1. S936X Integrated Boiler Controller, dimensions in in. (mm).
Electrical Ratings:
Line Voltage: 120 Vac, 60 Hz (220 Vac, 50 Hz on specific
model numbers).
Transformer:
Nominal 24 Vac (maximum 30 Vac, minimum 18 Vac).
5.0 VA plus external loads (gas valve, vent damper, etc.)
On/Off Circulator:
Full Load: 7.4A at 120 Vac (0.75 to 0.8 power factor
[PF]). (220 Vac TBD.)
Locked Rotor: 44.4A at 120 Vac (0.4 to 0.5 PF). (220
Vac TBD.)
Inducer (Optional):
Full Load: 6A at 120 Vac (0.75 to 0.8 PF). (220 Vac
TBD.)
Locked Rotor: 17.48A at 120 Vac (0.4 to 0.5 PF). (220
Vac TBD.)
Vent Damper (Optional):
Full Load: 0.5A at 24 Vac. In Rush: 1A at 24 Vac.
Main Valve:
Full Load: 2A at 24 Vac (0.5 to 0.6 PF). In Rush: 6A at 24 Vac (0.5 to 0.6 PF)
Pilot Valve (Optional):
Full Load: 2A at 24 Vac (0.5 to 0.6 PF) In Rush: 6A at 24 Vac (0.5 to 0.6 PF).
Hot Surface Igniter (HSI) (Optional):
2 x 61
220.5
2 x 15
1-3/8
(35)
5/8
(16)
M24217
Full Load: 4.5A at 120 Vac.
Warm-up Time:
18 seconds for first trial for ignition; this varies by
model, as does the time for the second trial for igni­tion (recommended for Norton igniter model 201 or 270 or equivalent)
Ambient Ratings:
Humidity: 0 to 95 percent relative humidity,
noncondensing. Operating Ambient Temperature: -30°F to +150°F. Shipping Ambient Temperature: -40°F to +175°F.
Flame Monitoring (May vary by model):
Flame Establishing Period (FEP): Maximum 2 seconds. Flame Failure Response Time (FFRT):
Maximum: 2 seconds @ 1 µA.
Flame Stabilization Time: 4 seconds. Time from ignit-
ing the main burner and detecting loss of flame (the flame current is allowed to be under the flame lost threshold for this time while waiting for burner to stabilize).
Flame Lost Threshold: 0.23 µA.
Ignition Cables:
Use cable types recommended in Table 1.
69-2076—01 2
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS
Table 1. Recommended Ignition Cables.
Cable Type
UL Style 3217
UL Style 3257
Transformer Requirement:
Add current ratings of module, pilot valve, main valve, vent damper and any other components of the control system to determine transformer size requirement.
Approvals:
Varies with control model. ANSI Z21.20 Automatic Gas Ignition Systems and
Components. ANSI Z21.23 Gas Appliance Thermostats. EN298: Automatic Gas Burner Control Systems ANSI Z21.87: Automatic Gas Shutoff Devices for Hot
Water Supply Systems. UL353 Limit Controls.
Vol tag e
Rating (rms)
10,000 150 302
10,000 250 484
Temperature Rating
°C °F
PLANNING THE INSTALLATION
Automatic Ignition Control domestic and commercial boiler systems are used on a wide variety of equipment. Some of these applications may make heavy demands on the controls, either because of frequent cycling, or because of moisture, corrosive chemicals, dust or excessive heat in the environment. In these situations, special steps may be required to prevent nuisance shutdowns and premature control failures. These applications require Honeywell Engineering review; contact your Honeywell Sales Representative for assistance.
Frequent Cycling
These controls are designed for use on domestic and commercial boiler systems that typically cycle less than 10,000 cycles per year. In an application with significantly greater cycling rates, we recommend monthly checkout because the controls may wear out more quickly.
High Humidity or Dripping Water
Over time, dripping water or high ambient humidity can create unwanted electrical paths on the module circuit board, causing the module to fail. Never install an appliance where water can drip on the controls.
In addition, high ambient humidity can cause the control to corrode and finally fail.
Where the appliance may be installed in a humid atmosphere, make sure air circulation around the module and gas control is adequate to prevent condensation. It is also important to regularly check out the system. A NEMA 4 enclosure may be needed.
Corrosive Chemicals
Corrosive chemicals can also attack the module and gas control and eventually cause a failure. Where chemicals may be used routinely for cleaning, make sure the cleaning solution cannot reach the controls. Where chemicals are likely to be suspended in the air, as in some industrial and agricultural applications, protect the module from exposure with a NEMA 4 enclosure.
Dust or Grease Accumulation
Heavy accumulation of dust or grease may cause the controls to malfunction. Where dust or grease may be a problem, provide covers for the module and gas control that limit environmental contamination. A NEMA 4 enclosure is recommended for the module.
Heat
The controls can be damaged by excessively high temperatures. Make sure the maximum ambient temperature at the control locations will not exceed the rating of the control. If the appliance normally operates at very high temperatures, insulation, shielding, and air circulation may be necessary to protect the controls. Proper insulation or shielding should b provided by the appliance manufacturer; make sure adequate air circulation is maintained when the appliance is installed.
INSTALLATION AND CHECKOUT
Water or Steam Cleaning
Once a module or gas control has been wet, it may operate unreliably and must be replaced. If the appliance is likely to be cleaned with water or steam, the controls and associated wiring should be covered so that water or steam cannot reach them. The controls should be high enough above the bottom of the cabinet so they will not be subjected to flooding or splashing during normal cleaning procedures. If necessary, shield the controls to protect them from splashing water. A NEMA 4 enclosure is recommended.
When Installing This Product…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure they are suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
3 69-2076—01
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS
WARNING
Fire or Explosion Hazard. Can cause severe injury, death or property damage.
1. The module can malfunction if it gets wet, leading to accumulation of explosive gas.
• Never install where water can flood, drip or
condense on module.
• Never try to use a module that has been
wet—replace it.
2. Liquefied petroleum (LP) gas is heavier than air and will not vent upward naturally.
• Do not light pilot or operate electric switches,
lights, or appliances until you are sure the appliance area is free of gas.
3. If a new gas control is to be installed, turn off gas supply before starting installation. Conduct Gas Leak Test according to gas control manufacturer instructions after the gas control is installed.
4. If module must be mounted near moisture or water, provide suitable waterproof enclosure.
WARNING
Electrical Shock Hazard. Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring to prevent electrical shock or equipment damage.
Perform Preinstallation Safety Inspection
The preinstallation checks described in ANSI Standard Z21.71 must be done before a replacement module is installed. If a condition which could result in unsafe operation is detected, the appliance should be shut off and the owner advised of the unsafe condition. Any potentially unsafe condition must be corrected before proceeding with the installation.
Maintenance Requirements in Severe Environments
Regular preventive maintenance is important in any application, but especially so in commercial, agricultural, and industrial applications, because:
1. In such applications, particularly commercial, the
equipment can operate 100,000 to 200,000 cycles per year. Such heavy cycling can wear out the gas control in one to two years. A normal boiler applica­tion, for which the controls were intended, typically operate fewer than 10,000 cycles per year.
2. Exposure to water, dirt, chemicals, and heat can
damage the module or the gas control and shut down the control system. A NEMA 4 enclosure can
reduce exposure to environmental contaminants. The maintenance program should include regular checkout of the system as outlined under Checkout.
WARNING
Fire or Explosion Hazard. Can cause severe injury, death or property damage.
Do not attempt to take the module apart or to clean it. Improper reassembly and cleaning may cause unreliable operation, leading to an accumulation of explosive gas.
Maintenance frequency must be determined individually for each application. Some considerations are:
Cycling frequency. Appliances that may cycle more than 10,000 times annually should be checked monthly.
Intermittent use. Appliances that are used seasonally should be checked before shutdown and again before the next use.
Consequence of unexpected shutdown. Where the cost of an unexpected shutdown would be high, the system should be checked more often.
Dusty, wet, or corrosive environment. Since these environments can cause the controls to deteriorate more rapidly, the system should be checked more often.
Any control should be replaced if it does not perform properly on checkout or troubleshooting. In addition, replace any module if it is wet or looks like it ever has been wet. Protective enclosures as outlined under Planning the Installation are recommended regardless of checkout frequency.
Mount Module
Select a location close enough to the burner to allow a short (3 ft. [0.9 m] maximum), direct cable route to the igniter. Ambient temperature at the module must be within the range listed under Specifications. The module must be protected from water, moisture, corrosive chemicals and excessive dust and grease. Refer to Fig. 2 and 3 for recommended slot/hole pattern in appliance.
99.5
16
100
4
16
4
69-2076—01 4
55
Fig. 2. Recommended slot/hole pattern in appliance
(in mm).
M24198
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS
WATER HEATER
M24229
Fig. 3. Align module with slots in control box.
CONTROL BOX
Wire the System
WARNING
Electrical Shock Hazard. Can cause severe injury, death or property damage.
Disconnect the power supply before making wiring connections to prevent electrical shock or equipment damage.
Check the wiring diagram furnished by the appliance manufacturer for circuits differing from the wiring hookup shown in Fig. 4 and 5. Carefully follow any special instructions affecting the general procedures outlined below.
IMPORTANT
1. All wiring must comply with applicable local electrical codes and ordinances.
2. When installing a hot surface igniter, the leadwires should be kept as short as possible and should not be allowed to rest against grounded metal surfaces.
3. A common ground is required for the S93XX and the main burner. The 24V “secondary” plug inter­nally grounds one side of the transformer. Any auxiliary controls or limits must not be in the grounded leg. In addition, the appliance should be earth-grounded.
4. Make sure the transformer has adequate VA. The ignition module requires at least 0.2A at 24 Vac. Add the current draws of all other devices in the control circuit, including the gas control, and multiply by 24 to determine the total VA requirements of these components. Add this total to 5.0 VA (for the module). The result is the minimum transformer VA rating. Use a Class II transformer if replacement is required.
5. Check that L1 (hot) and L2 (neutral) are wired to the proper terminals.
Connect Ignition Cable (S936XAXXXX)
Use Honeywell ignition cable or construct an ignition cable that conforms to suitable national standards, such as Underwriters Laboratories Inc. See Specifications section. To construct a cable, fit one end (the module end) with 1/4 in. connector receptacle and the other with a connector to match the pilot assembly. Protect both ends with insulated boots.
5 69-2076—01
Loading...
+ 11 hidden pages