Honeywell R8182D, R8182E, R8182F, R8182H, R8182J User Manual

R8182D,E,F,H,J Combination
Protectorelay™ Primary Control and
APPLICATION
The R8182 combines a Protectorelay™ primary control and immersion type Aquastat® controller in one unit for use in oil-fired, hydronic heating systems.
The Protectorelay™ primary control provides control of a line voltage, intermittent ignition oil burner when used with a C554A Cadmium Sulfide Flame Detector and a 24V thermostat.
The R8182 models provide switching as follows:
Model Switching
R8182D High limit, spst;
R8182E High limit, spst R8182F High limit, spst
R8182H (with remote bulb) High limit, spst
R8182J (with remote bulb) High limit, spst
The auxiliary ZC and ZR terminals on the R8182D,E,H,J provide zone control through an R845A Switching Relay.
All models are capable of zone control using zone valves. Each additional zone requires a separate 24V thermostat and a V8043 or V8044 Zone Valve.
The R8182D,E,F models mount directly on the boiler. The R8182H,J models mount directly on a 4 by 4 inch junction box and have a 5 foot (1.5 meter) armored capillary for remote sensor location.
To order an immersion well, use form 68-0040
Fittings for Temperature Controllers
and descriptions.
Refer to Fig. 1 through 3 for installation dimensions.
Refer to Fig. 4 through 8 for internal views of the R8182D,E,F,G,J.
Low limit/circulator, spdt
Circulator, spst
Low limit/circulator, spdt
, for part numbers
Wells and
Aquastat
®
Controller
INSTALLATION INSTRUCTIONS
KNOCKOUTS FOR 1/2 IN. (13 MM) CONDUIT (5)
2-7/16
(62)
1-5/16
(33)
7-1/8
(181)
3-9/16
(91)
3/16
(5)
1 VERTICAL MOUNT SHOWN.
Fig. 1. R8182D,E,F installation dimensions in inches
HORIZONTIAL MOUNT ONLY
5-1/4 (133)
(millimeters).
VERTICAL MOUNT ONLY
1
3-1/4 (83)
M4517
Copyright © 1995 Honeywell Inc. • All Rights Reserved
X-XX UL
69-0600-1
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ PRIMARY CONTROL AND AQUASTAT® CONTROLLER
SAFETY SWITCH RESET BUTTON
TRANSFORMER FOR THERMOSTAT CIRCUIT
DIFFERENTIAL SETTING
CIRCULATOR RELAY (1K)
BURNER MOTOR AND IGNITION RELAY (2K)
LOW LIMIT SETTING
VOLTAGE BARRIER
TRANSFORMER FOR CAD CELL CIRCUIT
M4525
1/2 (13)
7-1/8 (181)
7/8 (22)
3-7/16
(87)
3-3/8 (86)
KNOCKOUTS FOR 1/2 IN. (13 MM) CONDUIT (5)
GROUNDING SCREW
1
HIGH LIMIT SETTING
Fig. 4. Internal view of R8182D.
SAFETY SWITCH
1 SIDE MOUNTED HINGE SHOWN.
5-1/4 (133)
Fig. 2. R8182H,J installation dimensions in inches
(millimeters).
3-7/16 (87)
M4518
GROUNDING SCREW
RESET BUTTON
TRANSFORMER FOR THERMOSTAT CIRCUIT
AQUASTAT SWITCH
CIRCULATOR RELAY (1K)
R8182D,E,F
CONTROL MOUNT
INSULATION LENGTH 1-1/2 OR 3 IN. (38 OR 76 MM)
R8182H,J
SETSCREW
FITS BOILER TAPPED HOLE
1/2 OR 3/4 NPT
INSERTION LENGTH 3-3/8 IN. (86 MM)
FITS BOILER TAPPED HOLE
1/2 OR 3/4 NPT
INSULATION LENGTH 1-1/2 IN. (38 MM)
Fig. 3. Immersion well dimensions in inches
(millimeters).
INSERTION LENGTH 3-3/8 IN. (86 MM)
69-0600—1
M4530
BURNER MOTOR AND IGNITION RELAY (2K)
VOLTAGE BARRIER
HIGH LIMIT SETTING
TRANSFORMER FOR CAD CELL CIRCUIT
M4532
Fig. 5. Internal view of R8182E.
GROUNDING SCREW
SAFETY SWITCH RESET BUTTON
HIGH LIMIT SETTING
BURNER MOTOR AND IGNITION RELAY (2K)
LOW LIMIT SETTING
TRANSFORMER FOR CAD CELL CIRCUIT
VOLTAGE BARRIER
M4515
Fig. 6. Internal view of R8182F.
2
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ PRIMARY CONTROL AND AQUASTAT® CONTROLLER
SAFETY SWITCH RESET BUTTON
HIGH LIMIT SETTING
CAD CELL LEADS (YELLOW)
TRANSFORMER FOR CAD CELL CIRCUIT
Fig. 7. Internal view of R8182H.
CAD CELL LEADS (YELLOW)
Fig. 8. Internal view of R8182J.
INSTALLATION
When Installing this Product…
Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
Check the ratings given in these instructions and
on the product to be sure the product is suitable for your application.
Be sure the installer is a trained, experienced
service technician.
After completing installation, use these
instructions to check product operation.
VOLTAGE BARRIER
SAFETY SWITCH RESET BUTTON
TRANSFORMER FOR THERMOSTAT CIRCUIT
AQUASTAT SWITCH
2K RELAY
1K RELAY
VOLTAGE BARRIER
TRANSFORMER FOR CAD CELL CIRCUIT
HIGH LIMIT SETTING
TRANSFORMER FOR THERMOSTAT CIRCUIT
DIFFERENTIAL SETTING
CIRCULATOR RELAY (1K)
BURNER MOTOR AND IGNITION RELAY (2K)
LOW LIMIT SETTING
M4524
M4531
CAUTION
1. Disconnect the power supply before beginning installation to prevent electrical shock or equipment damage.
2. Be sure that the combustion chamber is clear of oil or oil vapor before starting burner.
3. Be sure that the ambient temperature at the element does not exceed 250°F (121°C).
IMPORTANT
Be sure that the sensing bulb fits snugly inside the immersion well and that the sensing bulb rests against the bottom of the immersion well. Refer to Fig. 3.
Mounting the R8182
Disconnect power supply.Drain all water from boiler.Most boilers are equipped with a tapping that
allows horizontal mounting of immersion well where average temperature boiler water circulates freely. If no tapping is provided, prepare one.
Install immersion well or compression fitting
(ordered separately) by threading immersion well into tapped hole.
For R8182D,E,F models:
a. Loosen immersion well clamp screw on side
of R8182 case. b. Insert bulb into immersion well until it bottoms. c. If necessary, bend capillary tube to hold
bulb against bottom of immersion well.
NOTE: Do not make sharp bends in the tubing.
A sharp bend can break the tubing and cause a loss of fill. In models with an adjustable tubing length, pull the extra tubing out of the controller case.
d. Fit controller case onto immersion well so
that immersion well clamp slides over flange
of immersion well. e. Securely tighten immersion well clamp screw.
For R8182H,J models:
a. Loosen the screw holding the hinged
backplate to the controller case and swing
the backplate away from the controller case. b. Screw the backplate to a 4 by 4 inch
junction box. c. Insert bulb into immersion well until it bottoms. d. If necessary, bend capillary tube to hold
bulb against bottom of immersion well.
NOTE: Do not make sharp bends in the tubing.
A sharp bend can break the tubing and cause a loss of fill. In models with an adjustable tubing length, pull the extra tubing out of the controller case.
e. Tighten immersion well screw over brass
collar. f. After wiring, swing the control against the
backplate and refasten the screw.
Refill the boiler and check for water leakage.
3
69-0600—1
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ PRIMARY CONTROL AND AQUASTAT® CONTROLLER
Wiring
IMPORTANT
Use Underwriters Laboratories Inc. listed connectors when making external circuit connections to the orange and white line voltage burner and ignition leadwires of the R8182H,J.
CAUTION
Disconnect power supply before wiring to prevent electrical shock or equipment damage.
All wiring must comply with local codes, regulations, and ordinances.
IMPORTANT
Terminals on the R8182 are approved for copper wire only.
Follow the wiring instructions furnished by the appliance manufacturer, if available, or refer to Fig. 9 through 15. For wiring multiple zoning systems, refer to Fig. 14 and 15.
The R8182 is equipped with special wiring terminals. Wires can be wrapped around the terminal screw or inserted from the side.
Method 1
Strip 7/16 inches of insulation
from the wire end.
Wrap wire 3/4 of distance
around screw as shown in Method 1.
Use a standard, flat-headed
screwdriver to tighten screw until wire is snugly in contact with screw and contact plate.
Tighten the screw an additional one half turn.
Method 2
Strip 5/16 inches of insulation from
the wire end.
Insert wire beneath screw as
shown in method 2.
Using a standard, flat-
headed screwdriver, tighten screw until wire is snuggly in contact with screw and contact plate.
Tighten screw an additional one half turn.
NOTE: Do not use a push-type ratchet screwdriver.
OPERATION
R8182D
A call for heat by the thermostat pulls in relays 1K and 2K to turn on the burner. Safety switch starts to heat. If burner ignites within safety switch timing, cad cell sees flame and safety switch heater circuit is bypassed. Burner operates until call for heat is satisfied. Circulator operates when relay 1K pulls in the Aquastat® controller.
When R to B (low-limit) is made by a drop in water temperature, it acts as a call for heat, pulling in relay 2K
only
if R to W is made in
M8843
M4516
1
L1
L2
(HOT)
4
1
G
1K2
BLACK
1K
T T F F
24 VOLT THERMOSTAT
120 VAC POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED.
WHEN THE BLACK AND WHITE WIRES ON THE TRADELINE® R8182D
2
AQUASTAT® CONTROLLER ASSEMBLY ARE DISCONNECTED FROM THE CIRCULATOR SWITCH AND ARE INTERCONNECTED, LOW LIMIT AND CIRCULATOR CONTROL ARE BYPASSED. CIRCULATOR OPERATES WITHY THEROMSTAT ONLY.
3
TO REPLACE R8182C,F, REMOVE BLUE WIRE AND INSULATE END. DISCONNECT THE THE OTHER BLUE WIRE AT 4 AND WIRE TO AT 3. WHEN CIRCULATOR IS CONNECTED BETWEEN ZC AND C2, LOW LIMIT FUNCTION IS REMOVED AND CIRCULATOR OPERATES WITH CIRCULATOR CONTROL (R TO W) ONLY.
4
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.
2
4
CIRCULATOR
R8182D
3
BLUE
ZR
BLUE
B
LOW LIMIT
R
C1
W
BILATERAL SWITCH
WHITE
SAFETY SWITCH HEATER
TRIAC
R2
C554A
3
B
2
2K2
HIGH LIMIT
ZC
1K1
2K1
B2 C2
C1
S.SW CONTACTS
2K
TO OIL
B1R
BURNER AND IGNITION
TO WATER CIRCULATOR
R1
B
M4519
Fig. 9. R8182D internal schematic and wiring diagram.
to turn on the burner. Circulator cannot operate. See Fig. 4, 9, 14, 15, and 17.
R8182E
Burner and circulator operate whenever thermostat calls for heat. Relay 2K pulls in. When cadmium sulfide cell sees flame, the safety switch heater circuit is bypassed. 2K is held in through 2K1. If temperature rises to high limit setpoint, R to B breaks, shutting off burner. Circulator continues operation under direction of thermostat. See Fig. 5, 10, 15, and 16.
R8182F
A thermostat call for heat pulls in relay 2K to turn on the burner. When cadmium sulfide cell sees flame, safety switch heater circuit is bypassed. Circulator is independent of thermostat circuit, being controlled only by Aquastat® controller switch. Refer to Figs. 6, 11, 15, and 18.
69-0600—1
4
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ PRIMARY CONTROL AND AQUASTAT® CONTROLLER
1
L1
L2
(HOT)
2
1
2
G
1K2
ZR
ZC
1K
T T F F
24 VOLT THERMOSTAT
120 VAC POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED.
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.
2
USE GROUNDING SCREW PROVIDED.
Fig. 10. R8182E internal schematic and wiring
C1
1K1
SAFETY SWITCH HEATER
TRIAC
BILATERAL SWITCH
R2
C554A
diagram.
HIGH LIMIT
B
2K1
R8182E
2K2
B2 C2
C1
S.SW CONTACTS
2K
R1
M4527
B1R
TO OIL BURNER AND IGNITION
TO WATER CIRCULATOR
R8182H
A call for heat by the thermostat pulls in relays 1K and 2K to turn on the burner. Safety switch starts to heat. If burner ignites within safety switch timing, cadmium sulfide cell sees flame and safety switch heater circuit is bypassed. Burner shuts off when call for heat is satisfied. Circulator operates when relay 1K pulls in if R to W in the Aquastat® controller is made.
When R to B (low-limit) is made by a drop in water temperature, it acts as a call for heat, pulling in relay 2K to turn on the burner. Circulator cannot operate. See Fig. 7, 12, 15, and 17.
only
R8182J
Burner and circulator operate whenever the thermostat calls for heat. Relay 2K pulls in. When cadmium sulfide cell sees flame, the safety switch heater circuit is bypassed. 2K is held in through 2K1. If temperature rises to high-limit setpoint, R to B breaks, shutting off burner. Circulator continues operation under direction of thermostat. See Fig. 8, 13, 15, and 16.
Multizone Control
In all multizone applications, a call for heat in any zone energizes the safety switch circuit and relay 2K pulls in. If burner ignites within safety switch timing, cad cell sees flame and safety switch heater is bypassed.
1
L1
L2
(HOT)
TRIAC
R8182F
W
C1
TO WATER
C2 B2
CIRCULATOR
TO BURNER AND
B1
IGNITION
M4528
2
1
2
G
JUMPER
R
B
SAFETY SWITCH CONTACTS
T
2K
24 VOLT THERMOSTAT
T
R1
120 VAC POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED.
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.
2
USE GROUNDING SCREW PROVIDED.
Fig. 11. R8182F internal schematic and wiring
In all multizone applications with R8182D and H, the low- limit controller in the Aquastat® acts independently to turn on the main burner on a drop in water temperature. When R to B (low-limit) is made, relay 2K pulls in to turn on the main burner, the same as for single-zone applications.
R
HIGH
CIRCULATOR
LIMIT
CONTROL
2K2
2K1
SAFETY SWITCH HEATER
BILATERAL SWITCH
R2 C1
F F
C554A
diagram.
Zone Circulator Control with R8182D,H
The relay for each zone is connected to the Aquastat® controller through terminals ZC and ZR. The R845 Relay and thermostat for each zone can energize the zone circulator through ZC Aquastat® controller is made. If R to B (high-limit) is made, the zone thermostat energizes the burner through ZR.
only
if R to W in the
Zone Circulator Control with R8182E,J
The relay for each zone is connected to the Aquastat® controller through terminals ZC and ZR. The R845A Relay and thermostat in each zone can energize the zone circulator through ZC on a call for heat. If R to B (high-limit) is made, the zone thermostat energizes the burner through ZR.
Zone Valve Control with R8182
The valve for each zone is connected to the Aquastat® controller by wiring end switches on the zone valve to T-T on the R8182. On a call for heat from any zone, the R8182 operates the same as in single-zone applications.
5
69-0600—1
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ PRIMARY CONTROL AND AQUASTAT® CONTROLLER
1
L1
L2
(HOT)
1
2
ZR
1K2
B
LOW LIMIT
R
CIRCULATOR
1K
T T
24 VOLT THERMOSTAT
120 VAC POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED.
C1
YELLOW
Fig. 12. R8182H internal schematic and wiring
W
SAFETY SWITCH HEATER
TRIAC
BILATERAL SWITCH
R2
C554A
diagram.
HIGH LIMIT
B
ZC
2K2
STARTUP AND CHECKOUT
WARNING
CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY OR DEATH.
This product is intended for use only in systems with a pressure relief valve.
Because heating systems differ, the correct temperature setting for one system may not be correct for another. Follow the boiler manufacturer recommendations for proper selection of settings.
High-Limit Setting—All Models
The high-limit opens and turns off the burner when the water temperature reaches the setpoint. The high-limit automatically resets after the water temperature drops past the setpoint and through the 10°F (6°C) (15°F [8°C] with R8182E,J) differential.
Set the indicator at desired shutoff temperature.
Low-Limit/Circulator Setting—D and H Models
R
1K1
S.SW CONTACTS
2K
2K1
ORANGE
WHITE
R1
YELLOW
R8182H
C1
C2
M4520
TO OIL BURNER AND IGNITION
TO WATER CIRCULATOR
At any differential setting greater than 10°F (6°C), the R­B make temperature and R-W break temperature remain the same—control setting minus 10°F (6°C). The R-B break and R-W make temperatures are the setpoint temperature plus the difference between the differential setting and 10°F (6°C).
EXAMPLE: Setpoint of 140°F (60°C), differential set at 25°F (14°C). On a temperature rise, R-B breaks and R­W makes at 155°F (68°C). On a temperature fall, R-B makes and R-W breaks at 130°F (54°C).
Set low-limit indicator at the minimum temperature recommended for domestic hot water supply. The setting setting to prevent one switch from locking out the other.
Set differential the desired number of degrees.
Circulator Setting—F MODELS (Fig. 18)
Set circulator indicator at the minimum water temperature recommended for hydronic heating comfort. Circulator breaks 10°F (6°C) below setpoint.
Startup
(Fig. 17)
On a temperature rise, with the adjustable differential at the minimum setting of 10°F (6°C), the burner circuit (R­B) breaks and the circulator circuit (R-W) makes at the low-limit setpoint. See Fig. 17. On a temperature drop of 10°F (6°C) below the setpoint, the R-B circuit makes and the R-W circuit breaks.
1
L1
L2
(HOT)
1
2
HIGH LIMIT
ZR
B
1K2
ZC
1K
C1
T T F F
YELLOW
24 VOLT THERMOSTAT
120 VAC POWER SUPPLY. PROVIDE DISCONNECT MEANS
1
AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 13. R8182J internal schematic and wiring
must
be at least 20°F (11°C) below high-limit
R
SAFETY SWITCH HEATER
TRIAC
BILATERAL SWITCH
R2
C554A
diagram.
R8182J
C1
C2
YELLOW
TO OIL BURNER AND IGNITION
TO WATER CIRCULATOR
R1
M4529
ORANGE
2K2
WHITE
1K1
S.SW CONTACTS
2K1
2K
CAUTION
Be sure combustion chamber is free of oil or vapor.
69-0600—1
6
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ PRIMARY CONTROL AND AQUASTAT® CONTROLLER
1
L1
L2
(HOT)
6
ZONE 2 THERMOSTAT
3
1
2
3
4
5
6
R845A SWITCHING RELAY ZONE 2
1K
2
ZONE 2 CIRCULATOR
1K1
5 3
6 4
1K2
TO ADDITIONAL ZONES 3, 4, ETC.
T
T
1
120 VAC POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
THERMOSTAT HEAT ANTICIPATOR SETTING,
0.2 AMP FOR R8182D.
THERMOSTAT HEAT ANTICIPATOR SETTING,
0.4 AMP FOR R845A.
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.
R8182E,H,J CONNECTIONS FROM ZC AND ZR ARE IDENTICAL FOR MULTIPLE CIRULATOR ZONING APPLICAITON.
EACH ADDITIONAL ZONE REQUIRES A SEPARATE, FIELD-ADDED 24V THERMOSTAT AND R845 RELAY.
Fig. 14. R8182D and R845A in a typical multiple circulator zoning application.
1. Push red reset button and release.
2. Open hand valve on oil supply line.
3. Set thermostat to call for heat.
4. Close line switch; burner will start.
5. Under normal conditions, burner operates until thermostat is satisfied or line switch is opened.
Make certain the system operates as described in the OPERATION section. Use the following procedure to verify that the Protectorelay™ control is controlling properly.
Flame Failure Check
Shut off oil supply hand valve while burner is on. After 45 seconds, the safety switch locks out, the motor stops, and the oil valve closes. Allow five minutes for burner to cool, then manually reset safety switch.
Ignition Failure Check
Test by closing oil supply while burner is off. Run through starting procedure but do not open the oil supply line hand valve. Safety switch locks out as for flame failure. Then turn oil back on, and reset safety switch.
Power Failure Check
Turn off power supply while burner is on. When burner goes out, restore power and burner will reset.
R8182D
4
1
2
G
1K2
1K
T T F F
24 VOLT THERMOSTAT
NOTE: If operation is not as described, see cover
BLUE
ZR
B
LOW LIMIT
R
CIRCULATOR
C1
2
insert for additional information and check wiring.
W
SAFETY SWITCH HEATER
TRIAC
BILATERAL SWITCH
R2
C554A
HIGH LIMIT
B
ZC
5
2K2
B2 C2
1K1
S.SW CONTACTS
2K
2K1
B1R
C1
R1
Aquastat® Replacement
The Aquastat® controller section of the Protectorelay™ control is field replaceable. When ordering a replacement assembly, specify the complete model number of the R8182.
To Replace the Aquastat® Limit:
1. Disconnect power supply.
2.
Note the position of the connecting wires
3. Remove fastening screws and wires.
4. Remove Aquastat controller and install new assembly.
TO OIL BURNER AND IGNITION
TO WATER CIRCULATOR
M4521
.
7
69-0600—1
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ PRIMARY CONTROL AND AQUASTAT® CONTROLLER
CIRCULATOR SETTING
HIGH LIMIT SETTING
R-B BREAKS ON TEMPERATURE RISE. BURNER TURNS OFF.
R-B MAKES ON TEMPERATURE FALL. BURNER OPERATES ON CALL FOR HEAT.
R-B BREAKS ON TEMPERATURE FALL. CIRCULATOR TURNS OFF.
R-W MAKES ON TEMPERATURE RISE. CIRCULATOR TURNS ON.
110°F (43°C)
240°F (116°C)
M1509
10°F (6°C) DIFFERENTIAL
10°F (6°C) DIFFERENTIAL
24 VOLT THERMOSTAT
1
2
3
4
5
HIGH LIMIT SETTING
24 VOLT THERMOSTAT
YELLOW
YELLOW
5 5 5
RED
RED
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
R8182H AND J HAVE WHITE AND ORANGE LEADWIRES FOR OIL BURNER AND IGNITION CONNECTIONS.
RED LEADWIRES PROVIDED ONLY ON MODLES WITH END SWITCH.
CHOOSE AT72, AT87, OR AT88 TRANSFORMER TO MATCH MAXIMUM SYSTEM LOAD.
USE V8043 OR V8044 ZONE VALVES WITH AUXILIARY END SWITCH ONLY.
Fig. 15. R8182D,E,F,H, and J in typical zoning
application using zone valves.
YELLOW
YELLOW
RED
RED
240°F (116°C)
15°F (8°C) DIFFERENTIAL
24 VOLT THERMOSTAT
YELLOW
YELLOW
RED
333
RED
4
L1 (HOT)
L2
L1 L2
TTB1
B2
C2
C1
CIRCULATOR
R-B BREAKS ON TEMPERATURE RISE. BURNER TURNS OFF. CIRCULATOR OPERATES ON A CALL FOR HEAT.
R-B MAKES ON TEMPERATURE FALL. BURNER AND CIRCULATOR OPERATE ON A CALL FOR HEAT.
1
2
M4522
TO OIL BURNER AND IGNITION
240°F (116°C)
HIGH LIMIT SETTING
LOW LIMIT AND CIRCULATOR SETTING
1
WHEN WATER REACHES PROPER TEMPERATURE, THE BURNER SHUTS OFF OR THE CIRCULATOR PUMP STARTS (WHEN CALLING FOR HEAT).
10°F (6°C) DIFFERENTIAL
25°F (14°C) DIFFERENTIAL
10°F (6°C) DIFFERENTIAL
110°F (43°C)
SWITCH BREAKS ON TEMPERATURE RISE. BURNER TURNS OFF. CIRCULATOR OPERATES ON A CALL FOR HEAT.
SWITCH MAKES ON TEMPERATURE FALL. BURNER OPERATES ON A CALL FOR HEAT.
SWITCH MAKES R-W AND BREAKS R-B ON TEMPERATURE RISE.
SWITCH MAKES R-W AND BREAKS R-B ON TEMPERATURE RISE.
SWITCH MAKES R-B AND BREAKS R-W ON TEMPERATURE FALL. BURNER IS ON TO MAINTAIN MINIMUM WATER TEMPERATURE. CIRCULATOR IS OFF.
Fig. 17. R8182D,H Aquastat® limit switching.
1
M1523
180°F (82°C)
Fig. 16. R8182E,J Aquastat® limit switching.
Automation and Control Solutions
Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422
69-0600—1
J.H. Rev. 5-95
M1510
Fig. 18. R8182F Aquastat® limit switching.
Honeywell Limited-Honeywell Limitée 35 Dynamic Drive Scarborough, Ontario M1V 4Z9
8
Loading...