Honeywell R8182D, R8182H Installation Manual

R8182D,H Combination
Protectorelay™ Primary Control
®
and Aquastat
INSTALLATION INSTRUCTIONS

APPLICATION

The R8182D,H Controllers combine a Protectorelay™ Primary Control and an Aquastat® Controller for use in oil-fired, hydronic heating systems. The Aquastat Controller provides high and low limit protection, circulator control, and minimum water temperature control for tankless domestic hot water service.
The Protectorelay Primary Control provides control of a line voltage, intermittent ignition oil burner when used with a C554A Cadmium Sulfide Flame Detector and a 24V thermostat.
The auxiliary ZC and ZR terminals provide zone control through an R845A Switching Relay. Each additional zone requires a separate 24V thermostat and an R845A Relay.
The R8182D,H also provide zone control using zone valves. Each additional zone requires a separate 24V thermostat and a V8043 or V8044 Zone Valve. The R8182D,H can be converted to provide only the high-limit to replace an R8182B,E or only the limit and circulator function to replace of the R8182C,F.
The R8182D mounts directly on the boiler. The R8182H mounts on a 4 by 4 in. junction box and has a 5 ft. (1.5m) capillary that allows a remote sensor location.
The R8182D includes
• Bag of heat-conductive compound for better heat transfer.
• High- and low-limit setting stops.
• One wire nut.
To order an immersion well or a well adapter, see form 68-0440, Wells and Fittings for Temperature Controllers, for part numbers and descriptions.

INSTALLATION

WARNING
Explosion Hazard. Can cause severe injury, death or property damage.
Use this product only in systems with a pressure relief valve.

When Installing this Product…

1. Read these instructions carefully. Failure to follow them could damage product or cause a hazardous condition.
2. Check the ratings given in these instructions and on the product to be sure product is suitable for your application.
3. Be sure the installer is a trained, experienced ser­vice technician.
4. After completing installation, use these instructions to check product operation.
WARNING
Electrical Shock Hazard and Explosion Hazard. Can cause severe injury, death or equipment damage.
1. Disconnect the power supply before beginning installation to prevent electrical shock or equipment damage.
2. Be sure that combustion chamber is clear of oil or oil vapor before starting burner.
3. Be sure that the ambient temperature at the element does not exceed 250°F (121°C).
IMPORTANT
Be sure that the sensing bulb fits snugly inside the immersion well and that the sensing bulb rests against the bottom of the immersion well. If the sensing bulb does not fit snugly inside the immersion well, use the heat-conductive compound as described below. See Fig. 3.

Mounting the R8182D

See Fig. 1 for R8182D installation dimensions and Fig. 4 for an internal view of the R8182D.
If existing immersion well does not fit the R8182D immersion well clamp, use a 124904 Immersion Well Adapter, ordered separately from form 68-0040.
1. Disconnect power supply.
2. Drain all water from boiler.
3. Fasten R8182D immersion well clamp to flange on
immersion well adapter. See Fig. 3.
4. Place adapter on capillary tube.
5. Put adapter end into hole in controller case and
tighten clamp screw.
® U.S. Registered Trademark Copyright © 2002 Honeywell • All Rights Reserved
69-0599-2
R8182D,H COMBINATION PROTECTORELAY™ PRIMARY CONTROL AND AQUASTAT® CONTROLLER
6. Insert sensing bulb into the immersion well and, if necessary, bend capillary tubing to hold sensing bulb against bottom of immersion well.
NOTE: Do not make sharp bends in capillary tubing. In
models with an adjustable tubing length, pull the extra tubing out of the controller case.
7. If necessary, apply heat-conductive compound into the immersion well. a. Fold plastic bag of heat-conductive compound
lengthwise and twist it gently.
b. Cut off end of plastic bag and work open end of
bag all the way into immersion well.
c. Slowly pull bag out of immersion well while
squeezing it firmly to distribute compound.
8. Wipe off any excess heat-conductive compound and tighten set screw against adapter.
If the existing immersion well is not usable, remove the existing immersion well and order a new one using form 68-0040.
1. Disconnect power supply.
2. Drain all water from boiler.
3. Install the new immersion well by threading it into
the threaded hole.
4. Loosen the immersion well clamp screw. See Fig.
3.
5. Insert sensing bulb into the immersion well and, if necessary, bend capillary tubing to hold sensing bulb against bottom of immersion well.
NOTE: Do not make sharp turns while bending the
capillary tubing. In models with an adjustable tubing length, pull the extra tubing out of the controller case.
6. If necessary, apply heat-conductive compound into immersion well. a. Fold plastic bag of heat-conductive compound
lengthwise and twist it gently.
b. Cut off end of plastic bag and work open end of
bag all the way into immersion well.
c. Slowly pull bag out of immersion well while
squeezing firmly to distribute compound.
7. Be sure immersion well fits hole in controller case.
8. Position immersion well clamp snugly over
immersion well flange. Tighten clamp screw securely.
9. Refill boiler and check for water leakage.
7-1/8 (181)
3-9/16
(91)
3/16
(5)
Fig. 1. R8182D installation dimensions in in. (mm).
1/2 (13)
7/8 (22)
3-7/16
(87)
7-1/8
(181)
KNOCKOUTS FOR 1/2 IN. (13 MM) CONDUIT (5)
2-7/16
(62)
1-5/16
(33)
VERTICAL MOUNT ONLY
HORIZONTIAL MOUNT ONLY
5-1/4 (133)
1 VERTICAL MOUNT SHOWN.
3-3/8 (86)
1
KNOCKOUTS FOR 1/2 IN. (13 MM) CONDUIT (5)
3-1/4 (83)
M4517
1

Mounting the R8182H

See Fig. 2 for R8182H installation dimensions and Fig. 5 for an internal view of R8182H.
1. Disconnect power supply.
2. Drain all water from boiler.
3. Most boilers are equipped with a tapping that
allows horizontal mounting of immersion well where average temperature boiler water circulates freely. If no tapping is provided, prepare one.
4. Install immersion well or compression fitting (ordered separately) by threading into tapped hole.
5. Loosen screw holding hinged backplate to controller case and swing backplate away from case.
6. Screw backplate to 4 by 4 inch junction box.
69-0599—2 2
1 SIDE MOUNTED HINGE SHOWN.
5-1/4 (133)
3-7/16 (87)
M4518
Fig. 2. R8182H installation dimensions in in. (mm).
7. Insert sensing bulb into immersion well and, if
necessary, bend capillary tubing to hold sensing bulb against bottom of immersion well.
NOTE: Do not make sharp turns while bending the
capillary tubing. In models with an adjustable tubing length, pull the extra tubing out of the controller case.
R8182D,H COMBINATION PROTECTORELAY™ PRIMARY CONTROL AND AQUASTAT® CONTROLLER
8. If necessary, apply heat-conductive compound into the immersion well. a. Fold plastic bag of heat-conductive compound
lengthwise and twist it gently.
b. Cut off end of plastic bag and work open end of
bag all the way into the immersion well.
c. Slowly pull bag out of the immersion well while
squeezing it firmly to distribute compound.
9. Tighten the immersion well screw over brass collar.
10. After wiring, swing control case against backplate
and refasten it with screw.
11. Refill the boiler and check for water leakage.
(C)
2
CONTROLLER CASE
ADAPTER
CAPILLARY TUBE
SETSCREW
IMMERSION WELL CLAMP SCREW
IMMERSION WELL CLAMP
IMMERSION WELL SPUD
BOILER
1
SHORT TUBE FITS IN CENTRAL RECESS OF ADAPTER
(A)
Fig. 3. Positioning the sensing bulb in the immersion well.
SAFETY SWITCH RESET BUTTON
TRANSFORMER FOR THERMOSTAT CIRCUIT

WIRING

IMPORTANT
• Use Underwriters Laboratories Inc. listed connectors when making external circuit connections to the orange and white line votage burner and ignition leadwires of the R8182H.
• Terminals on the R8182 are approved for copper wire only.
BACK OF
CONTROLLER
CASE
IMMERSION OLD IMMERSION WELL ASSEMBLY
HEAT-CONDUCTIVE COMPOUND
1
BEND THE CAPILLARY TUBE TO HOLD THE SENSING BULB IN GOOD THERMAL CONTACT WITH THE IMMERSION WELL AT POINTS (A) AND (B).
2
ASSURE THAT CAPILLARY TUBE FITS FREELY IN THE ADAPTER SO THE TENSION OF THE CAPILLARY TUBE AT POINT (C) HOLDS THE SENSING BULB IN GOOD THERMAL CONTACT WITH THE IMMERSION WELL AT POINT (D).
WELL CLAMP
SCREW
GROUNDING SCREW
ADAPTER
IMMERSION WELL CLAMP
SENSING BULB
SAFETY SWITCH RESET BUTTON
(D)
(B)
TRANSFORMER FOR THERMOSTAT CIRCUIT
M8830
HIGH LIMIT SETTING
CAD CELL LEADS (YELLOW)
TRANSFORMER FOR CAD CELL CIRCUIT
Fig. 4. Internal view of R8182D.
DIFFERENTIAL SETTING
CIRCULATOR RELAY (1K)
BURNER MOTOR AND IGNITION RELAY (2K)
LOW LIMIT SETTING
VOLTAGE BARRIER
M4524
DIFFERENTIAL SETTING
CIRCULATOR RELAY (1K)
BURNER MOTOR AND IGNITION RELAY (2K)
LOW LIMIT SETTING
VOLTAGE BARRIER
HIGH LIMIT SETTING
TRANSFORMER FOR CAD CELL CIRCUIT
M4525
Fig. 5. Internal view of R8182H.
3 69-0599—2
R8182D,H COMBINATION PROTECTORELAY™ PRIMARY CONTROL AND AQUASTAT® CONTROLLER
A
WARNING
Electrical Shock Hazard. Can cause severe injury, death or equipment damage.
Disconnect power supply before wiring to prevent electrical shock or equipment damage.
All wiring must comply with local codes, regulations, and ordinances.
Follow the wiring instructions furnished by the appliance manufacturer, if available, or see Fig. 6 through 9. For wiring multiple zoning systems, see Fig. 8 and 9.
The R8182 is equipped with special wiring terminals. Wires can be wrapped around the terminal screw or inserted from side.

Method 1

1. Strip 7/16 in. of insulation from wire end.
2. Wrap wire 3/4 of distance around screw as shown.
3. Using a standard, flat-head screwdriver, tighten screw until wire is snugly contacting screw and contact plate.
4. Tighten screw an additional half turn.
USING THE TRADELINE® R8182D TO REPLACE R8182F:
1. REMOVE BLUE WIRE FROM THIS TERMINAL AND INSULATE END TO PREVENT CONTACT.
2. REMOVE OTHER BLUE WIRE FROM THIS TERMINAL AND CONNECT AS SHOWN BELOW.
3. CONNECT CIRCULATOR TO ZC AND C2.
BLUE
COMPLETED WIRING TO REPLACE R8182C,F
H
I
WHITE
L
O
M8843

Method 2

1. Strip 5/16 in. of insulation from wire end.
2. Insert wire beneath screw as shown.
3. Follow steps 3 and 4 in Method
1.
NOTE: Do not use a push-type
ratchet screwdriver.
The TRADELINE® R8182D,H can be converted to replace an R8182B,C,E,F or a White Rodgers 6C92-2 or 6C92-3. When replacing a White Rodgers model, the immersion well must also be replaced. See Fig.5 for Aquastat limit connections necessary for each R8182D,H conversion.
To release the wires from the R8182, insert a screwdriver into the rectangular hole adjacent to the wire, push inward to release the locking-grip on the wire, and pull the wire out of the terminal hole.
To reinsert the wire into a new terminal hole, simply push the wire into the new slot.
USING THE TRADELINE® R8182D TO REPLACE R8182B,E OR WHITE RODGERS 6C92:
1. REMOVE WHITE ABD BLACK LEADS FROM THEIR TERMINAL AND CONNECT WITH A SODDERLESS CONNECTOR.
TO USE TRADELINE® R8182H TO REPLACE R8182J:
1. REMOVE RED AND WHITE LEADS FROM THEIR TERMINALS AND CONNECT WITH A SOLDERLESS CONNECTOR.
H
I
BLUEBLUE
COMPLETED WIRING TO REPLACE R8182B,E AND
WHITE RODGERS 6C92 L O
M4516
YELLOW
BLACK
Fig. 6. Converting R8182D,H to replace other controls.
69-0599—2 4
YELLOW
BLACK OR RED
M4526
Loading...
+ 8 hidden pages