SLATE™ brings configurable safety and programmable logic
together into one single platform. The platform can easily be
customized for almost any requirement or application–offering
virtually limitless development opportunities with far less
complexity.
The R8001U3001 SLATE Analog I/O module provides analog
input and output capability for all combustion applications.
Features
• 4 analog cells per module
• Multiple combination of analog functionality for each cell
• Supported sensors include voltage, current, PWM, tach, RTD,
NTC, and thermocouple
Specifications
Electrical Ratings:
See Table 3–Table 7
Environmental Ratings
Ambient Temperature:
Operating: -20°F to +150°F (-29°C to +66°C).
Shipping: -40°F to +150°F (-40°C to +66°C).
Underwriters Laboratories Inc. Listed, File: MP268
IRI Acceptable
Federal Communications Commission: Part 15, Class A
Must be mounted inside a grounded metal enclosure.
SLATE™ ANALOG I/O MODULE3
R8001U3001
Page 4
Mounting
DIN Rail (See Fig. 2)
Required Components
R8001A1001 SLATE Base Controller
R8001S9001 SLATE Sub-Base Module
7-3/32
(181)
2-11/16 (68)
4-19/32 (117)
Fig. 1.
Mounting dimensions of analog I/O module in in. (mm).
4 32-00009—01
M35382
Page 5
Principal Technical Features
The R8001D4001 analog I/O module provides analog input and
output capability for all combustion applications.
LED Array
There are four LEDs on the front of the analog I/O module that
provide quick identification of system status and problems. This
status is broadcast to other modules on the platform bus in case
they are affected by the inoperable module(s). There are also four
banks of LEDs for the analog cells. See Table 1 for descriptions.
LEDColorDescription
Power
CPU
Fault
Table 1. LED Descriptions.
No lightSystem does not have power
GreenSystem has power
RedNo wire sheet or problem with the
wire sheet
GreenRunning
RedFault
No lightRunning
LED Display
The SLATE system modules have a seven-segment, threeposition LED display used for indicating the module number of
the SLATE system. The LED colors indicate the terminal state as
shown in Table 2.
ColorDescription
GreenTerminal is on
RedFault
No lightNot in use
Table 2. Terminal LED Meanings.
SLATE™ ANALOG I/O MODULE5
R8001U3001
Page 6
Select and Reset Buttons
The SLATE system modules have a Select and Reset buttons
located on the front of the module and beneath the segment
display. The Reset button is used to clear a lockout and reset the
module. The Select button is used to scroll through the segment
display information.
Installation
WARNING
Fire or Explosion Hazard
Can cause severe injury, death, or property damage.
Verification of safety requirements must be performed
each time a control is installed on a burner to prevent
possible hazardous burner operation.
When Installing This Product
1. Read these instructions carefully. Failure to follow them could
damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product
to make sure the product is suitable for your application.
3. After installation is complete, check out the product operation
as provided in these instructions.
4. The SLATE module must be mounted in an electrical
enclosure with adequate clearance for servicing, installation
and removal of modules.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or equipment damage.
1. Disconnect the power supply before beginning installation to
prevent electrical shock and equipment damage. More than
one power supply disconnect can be involved.
6 32-00009—01
Page 7
M35383
Fig. 2.
Installing the Analog I/O Module on the Sub-Base Module.
2. Wiring must comply with all applicable codes, ordinances and
regulations.
3. Wiring must comply with NEC Class 1 (Line Voltage) wiring.
IMPORTANT
1. This equipment generates, uses and can radiate
radiofrequency energy and, if not installed and used in
accordance with these instructions, may cause interference
for radio communications. It has been tested and found to
comply with the limits of a Class A computing device of part
15 of FCC rules, which are designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment in a
residential area may cause interference; in which case, the
user, at their own expense, may be required to take whatever
measures are required to correct this interference.
SLATE™ ANALOG I/O MODULE7
R8001U3001
Page 8
2. This digital apparatus does not exceed the Class A limits for
radio noise, set out in the Radio Interfeence Regulations of
the Canadian Department of Communications.
3. Cable shield must be terminated to ground at both ends. If
shielded cable is NOT used, use three-wire twisted cable.
Wiring
WARNING
Electrical Shock Hazard.
Can cause severe injury, death, or equipment
damage.
Disconnect the power supply from the main disconnect
before beginning installation to prevent electrical shock
and equipment damage. More than one disconnect can
be required.
8 32-00009—01
Page 9
ANALOG INPUT
OUTPUT MODULE
4 CELLS
A
UNIVERSAL
LOW VOLTAGE
CELL
1
2
+
_
3
4
Fig. 3.
Wiring diagram for Analog I/O Module.
B
UNIVERSAL
LOW VOLTAGE
CELL
C
UNIVERSAL
LOW VOLTAGE
CELL
D
UNIVERSAL
LOW VOLTAGE
CELL
5
6
+
_
7
8
9
10
+
_
11
12
13
14
+
_
15
16
M35287
SLATE™ ANALOG I/O MODULE9
R8001U3001
Page 10
TerminalDescriptionRating
1Cell A (T1)See Tables Table 4-Table 7 for configuration
2Cell A (T2)See Tables Table 4-Table 7 for configuration
3Cell A (T3)See Tables Table 4-Table 7 for configuration
4Cell A (T4)See Tables Table 4-Table 7 for configuration
5Cell B (T5)See Tables Table 4-Table 7 for configuration
6Cell B (T6)See Tables Table 4-Table 7 for configuration
7Cell B (T7)See Tables Table 4-Table 7 for configuration
8Cell B (T8)See Tables Table 4-Table 7 for configuration
9Cell C (T9)See Tables Table 4-Table 7 for configuration
10Cell C (T10)See Tables Table 4-Table 7 for configuration
11Cell C (T11)See Tables Table 4-Table 7 for configuration
12Cell C (T12)See Tables Table 4-Table 7 for configuration
13Cell D (T13)See Tables Table 4-Table 7 for configuration
14Cell D (T14)See Tables Table 4-Table 7 for configuration
15Cell D (T15)See Tables Table 4-Table 7 for configuration
16Cell D (T16)See Tables Table 4-Table 7 for configuration
17Unused---
18Unused---
19Unused---
20Unused---
21Unused---
22Unused---
Table 3. Terminal Ratings.
options
options
options
options
options
options
options
options
options
options
options
options
options
options
options
options
10 32-00009—01
Page 11
Specifications based on worst case over ambient temperatures.
Basic FunctionsMinTypical Max Units
T1 Voltage InRange0.0-15.0 VDC
Resolution -2.43 -mV DC
Null-25.0 -25.0 mV DC
Accuracy-25.0 -25.0 mV DC Whichever is
-1.0-1.0%
Out Range0.0-15.0 VDC
Resolution -4.0 -mV DC
Null100.0 -100.0 mV DC
Accuracy-50.0 -50.0 mV DC Whichever is
-1.5-1.5%
Current InRange0.0-25.0 mA DC
Resolution -7.4 -uA DC
Null-0.5-0.5mA DC
Accuracy-1.5-1.5%0 to 25 mA
b
Range0.0-25.0 mA DC Max Load =
Out
Resolution -4.0-mA Ω
Null-0.5-0.5mA DC
Accuracy-300.0 -300.0 uA DC 0 to 25 mA
-50.0 -50.0 uA DC 4 to 20 mA
T2 Voltage InAmplitude0.0-15.0 VDC
Trip Point -3.0 -VDCComparator
Hysteresis -0.25 -VDC
Resolution -0.37 -mV DC
Null-25.0 -25.0 mV DC
Accuracy -25.0 -25.0 mV DC
T3 Voltage InRange0.0-15.0 VDC
Resolution -0.37 -mV DC
Null-25.0 -25.0 mV DC
Accuracy -25.0 -25.0 mV DC
Current InRange0.2-25.0 mA DC
Resolution-3.7-uA DC
Null-0.5-0.5mA DC
Accuracy-1.5-1.5%0 to 25 mA
a
T1 input terminal is held at constant 2.5VDC over allowable current range.
b
Accuracy specification given is for 100 Ω load. Resolution specification
can be converted to mA by dividing out load.
greater
greater
a
500 Ω
Only
Table 4. Specifications for Basic Cell Functions.
SLATE™ ANALOG I/O MODULE11
R8001U3001
Page 12
Complex Functions MinTypical MaxUnits
Thermocouple
T2
Type J Range-200.0 -1025.0 °C
&
T3
Resolution -0.1-°C
Accuracy-5.0-5.0°C
Type K Range-150.0 -1000.0 °C
Resolution -0.1-°C
Accuracy-5.0-5.0°C
RTD
T3
PT100 Range-135.0 -250.0 °C3 wire, 100 Ω
&
T4
Resolution -0.5-°C
Accuracy-2.0-2.0°C
Type
Range-135.0 -250.0 °C3 wire, 1000 Ω
Resolution0.5°C
PT1000
Accuracy-2.0-2.0°C
NTC
T3
Type
Range-40.0 -175.0 °C
10K
&
T4
Resolution -0.1-°C
a
Accuracy
-2.0-2.0°C-40 °C to 25 °C
-1.0-1.0°C 25 °C to 125 °C
-1.5-1.5 %
-3.0-3.0°C-40 °C to 175 °C
a
Temperatures refer to sense range.
Table 5. Specifications Cell Complex Functions.
12 32-00009—01
Page 13
Frequency / PWM
Functions
PWM Out
T1Amplitude5.0-10.0VDCLow output
Frequency100.0 -1000.0 Hz
Duty Cycle2.0-98.0%DC Allowable
Resolution-1.0-%
Accuracy-0.5 -0.5%DC 10V amplitude
Frequency In
T2Amplitude5.0 10.015.0VDC
Range2-1000Hz
Min. “on” pulse width
(low %DC)
Min. “off” pulse width
(high %DC)
Duty Cycle 2 – 100 Hz2.0-98.0%DC 10V amplitude
1000 Hz 5.0 -85.0%DC 10V amplitude
Resolution -1-Hz
Accuracy-5.0-0%Whichever is
PWM In
T2Amplitude5.0 10.015.0VDC
Frequency125-500Hz
Min. “on” pulse width
(low %DC)
Min. “off” pulse width
(high %DC)
Duty Cycle 125 –
500 Hz
Resolution -1.0 -%DC
Accuracy 125 Hz -1.5 -1.5%DC 10V amplitude
500 Hz-7.5 -7.5%DC 10V amplitude
Table 6. Specifications for Cell Frequency Functions.
MinTypical MaxUnits
state = 0V
output %DC
-50.0-usec10V amplitude
-130.0 -usec 10V amplitude
-1-0Hz
-50.0-usec10V amplitude
-130.0 -usec 10V amplitude
5.0 -90.0%DC 10V amplitude
greater
SLATE™ ANALOG I/O MODULE13
R8001U3001
Page 14
ConfigurationMinOptimum Range for Performance Max
Thermocouple J -50°C
K -50°C
RTD-135°C
NTC25°C
Current Out4 mA
Voltage: In / Out 2 V
Table 7. Suggested Sensor Selection Based on Application.
1025°C ± 4 °C
1000°C ± 4 °C
250°C ± 2 °C
125°C ± 1°C
20 mA ± .05 mA
10 V0.3 %,
typical
ApplicationRecommended Wire
Size
Analog Cell
terminals
18 AWG wire insulated for voltages and
temperatures for given
Recommended
Part Numbers
TTW60C,
THW75C,
THHN90C
application.
Table 8. Recommended Wire Sizes and Part Numbers.
Recommended Grounding Practices
Use an Earth ground or a signal ground as described below.
Earth ground (Base, Rectification Flame Amp
Module, other modules optional)
1. Use to provide a connection between the base and the
control panel of the equipment. Earth ground must be capable
of conducting enough current to blow the breaker in the event
of an internal short circuit.
2. Use wide straps or brackets to provide minimum length,
maximum surface area ground conductors. If a leadwire is
required, use 14 AWG copper wire.
3. Make sure that mechanically tightened joints along the ground
path are free of nonconductive coatings and protected against
corrosion on mating surfaces.
14 32-00009—01
Page 15
Signal ground
Note the 18V system ground is not electrically connected to earth
ground. Follow local codes and appliance recommendations to
determine if this should be connected to earth ground.
Be sure loads do not exceed the terminal ratings. Refer to the
labels or terminal ratings in Table 3.
The SLATE system must be mounted in an electrical enclosure.
When mounting in an electrical enclosure, provide adequate
clearance for servicing, installation and removal of SLATE
modules.
The maximum leadwire length is 300 feet to terminal inputs
(Control, Running/Lockout Interlock)
SLATE™ ANALOG I/O MODULE15
R8001U3001
Page 16
32-00009-01
For more information on the R8001U3001 and the entire SLATE
system please refer to the SLATE User Guide document located on
our website at http://combustion.honeywell.com/SLATE