Honeywell R8001M1050, R8001M4050, R8001M1150, R8001M4150 Installation Instructions Manual

32M-06009-06
SLATE™ Low Torque Actuator
SLATE Commercial Model
Series
FOR COMMERCIAL AND INDUSTRIAL MODELS R8001M1050, R8001M1150, R8001M4050, R8001M4150
INSTALLATION INSTRUCTIONS

FEATURES AND BENEFITS

• Offered in two different configuration options: — NEMA 1 rated, operating in a temperature
range of -18 to 158 °F (-28 to 70 °C) with 450 positions over a 90° span
NEMA 4 rated, operating in a temperature
range of -40 to 158 °F (-40 to 70 °C) with 900 positions over a 90° span
• Field-reversible clockwise and counterclockwise rotation operation.
• Internal temperature, valve status, health diagnostics, and error codes reporting.
• Robust, heavy-duty construction, continuous duty cycle-rated.
• Closed loop position control via Modbus RS-485 communications as an input to the SLATE Fuel Air Ratio Module, part R8001C6001.
• Dual 1/2-in knockout conduit connections.
• 1/2-in keyed output shaft with a 1/8-in square key.

APPLICATION

• Die-cast aluminum base with high-impact resistant, reinforced plastic cover.
• Meets UL353 Safety for Limit Controls.
• Meets UL1998 when used with R8001C6001 SLATE Fuel Air Ratio Module.
The SLATE Low Torque Actuator series includes commercial- and industrial-grade 1/4-turn actuators available in 50 and 150 in/lb models with highly repeatable position accuracy designed specifically to integrate with the SLATE system. This series is well suited for the precise control of air and gas flow and can operate in a wide range of temperatures and environmental conditions.
SLATE™ Low Torque Actuator can be easily mounted to the following valves using the mounting kits noted below. These kits can be ordered via www.customer.honeywell.com.
• Maxon CV Valve Series (1/2"–2") mounting kit #50123928-001
• Honeywell V51E Valve Series (1-1/2"–2") mounting kit #50124386-001 and mounting kit #32003396-001
• Honeywell V51E Valve Series (2-1/2"–4") mounting kit #50124386-001 and mounting kit #32003396-002
• Honeywell V5197A Valve Series (3/4"–3") mounting kit #50124386-001

APPROVALS

Underwriters Laboratories
CE 2009/142/EC: Gas Appliance
Meets UL353 Safety for Limit Controls. Meets UL1998 when used with R8001C6001 SLATE Fuel Air Ratio Module.
Directive (EN 12067-2:2004, EN298-2012)
SLATE™ LOW TORQUE ACTUATOR SERIES

SPECIFICATIONS

Supply Voltage (Peak Current):
DC model: 24VDC +10/-20%
Power:
50 in/lb: 10 Watts maximum 150 in/lb: 25 Watts maximum
Rotation: Max span: 90° usable
Resolution:
Commercial: 450 positions (0.2° resolution) Industrial: 900 positions (0.1° resolution)
Control Deadband:
Commercial: ±0.2 degrees Industrial ±0.1 degrees
Dimensions in in (mm): 6-11/16 x 5-29/64 x 5-
29/64 (170 x 138 x 138); See Fig. 1
Weight: 3 Lbs. (1.4 Kg)
Operating Temperature:
-28 to +70 °C (-18 to +158 °F) for commercial mod­els; -40 to +70 °C (-40 to +158 °F) for industrial models
Storage Temperature: -40 to +80 °C (-40°F to
+176°F)
Vibration: Honeywell V2 test specification; 3 axes
tested as follows: 2-Hour Performance/Resonant Detection Sweep: Vibration sinusoidal: 5 Hz - 30 Hz; Amplitude: 0.012mil pk/pk75 mm Vibration sinusoidal: 30 Hz – 300 Hz at 0.6G Endurance: 1.1G for 2 hours at resonant frequen­cies
EMC: EN61000-6-1/2/3 (See Safety and Agency
Approval Requirements), FCC Part 15, Level A EN55022, Level A
Enclosure:
NEMA1 (commercial models) NEMA 4 (industrial models)
Models:
Model
Number Description
Commercial
R8001M1050 50 in/lb Actuator NEMA 1 Enclosure
R8001M1150 150 in/lb Actuator NEMA 1
Enclosure
Industrial
R8001M4050 50 in/lb Actuator NEMA 4 Enclosure
R8001M4150 150 in/lb Actuator NEMA 4
Enclosure
Relative Humidity:
0 to 99% non condensing (for commercial models)
Table 1. Model Specifications.
Commercial Model Industrial Model
50 in-lb
Actuator Options/Specs
Communication RS-485 non-
Fault Annunciation Generic Alarm Generic Alarm Yes Yes
Enhanced Data Logging None None Yes Yes
Resolution .2 Degree .2 Degree .1 Degree .1 Degree
Repeatability .2 Degree .2 Degree .1 Degree .1 Degree
Duty Cycle (Act Availability) 100% 100% 100% 100%
Opening Span 90 Degrees 90 Degrees 90 Degrees 90 Degrees
90 Degree Travel Time 30 sec 30 sec 15 sec max 15 sec max
Minimum Operating Tem per ature
Maximum Operating Tem per ature
Temp Sensor Yes; Alarm Only Yes; Alarm Only Yes; Alarm and
Output 1/2-in Keyed
Keyed Connection 1/8-in Square Key 1/8-in Square Key 1/8-in Square Key 1/8-in Square Key
Conduit Connections 1/2-in Conduit
R8001M1050
isolated
-28 °C (-18 °F) -28 °C (-18 °F) -40 °C (-40 °F) -40 °C (-40 °F)
70 °C (158 °F) 70 °C (158 °F) 70 °C (158 °F) 70 °C (158 °F)
Output Shaft
Knockouts (2) (Shipped Closed)
150 in-lb
R8001M1150
RS-485 non­isolated
1/2-in Keyed Output Shaft
1/2-in Conduit Knockouts (2) (Shipped Closed)
50 in-lb
R8001M4050
RS-485 Isolated RS-485 Isolated
Real Time Data
1/2-in Keyed Output Shaft
1/2-in Conduit Knockouts (2) (Shipped Closed)
150 in-lb
R8001M4150
Yes; Alarm and Real Time Data
1/2-in Keyed Output Shaft
1/2-in Conduit Knockouts (2) (Shipped Closed)
32M-06009—06 2
SLATE™ LOW TORQUE ACTUATOR SERIES
WARNING
WARNING
WARNING
M35299
(2) Ø 7/8 (22)
KNOCKOUTS
FOR 1/2”
CONDUIT
ENTRANCE
KEYWAY FOR 1/8” SQ. X 1/2” LG. KEY
6-11/16 (170)
2-47/64
(69)
5-29/64
(138)
2-33/64 (64)
Ø 1/2 (13)
3/32 (3)
5/8 (16)
61/64 (24)
5-29/64
(138)
7/8 (22)
7/8 (22)
1-11/32
(34)
Fig. 1. Dimensions in in (mm).

INSTALLATION INSTRUCTIONS

Read Carefully
Please read the operating and mounting instructions before using the equipment. Install the equipment in compliance with the prevailing regulations.
Bedrijfs- en montagehandleiding voor gebruik goed lezen! Apparaat moet volgens de geldende voorschriften worden geïnstalleerd.
Lire les instructions de montage et de service avant utilisation! L’appareil doit imperativement être installé selon les règlementations en vigueur.
Betriebs- und Montageanleitung vor Gebrauch lesen! Gerät muß nach den geltenden Vorschriften installiert werden.
NOTICE
Language translations for this document are available at www.customer.honeywell.com.

Safety requirements

Safety Notice
The SLATE Actuator has been independently evaluated by Underwriters Laboratories to provide position feedback to the SLATE Fuel Air Ratio Module. The safety of the overall system is ultimately the responsibility of: 1) The upstream safety control that commands and monitors the SLATE Actuator, and 2) the trained commissioning engineer that configures the unit for system operation.
Safety Hazard
Before operating this product, check all specifications and safety requirements to ensure the product is suitable and safe for the intended application. In addition, read all installation, commissioning, and operating instructions. The SLATE Actuator must be set up and maintained in the field by qualified personnel. If the equipment is used in a manner not specified, the protection provided by the equipment may be impaired.
3 32M-06009—06