Honeywell R7847, R7849, R7886, R7849B, R7861 User Manual

...
R7824, R7847, R7848, R7849,R7851,R7861,
R7886 Amplifiers for
7800 SERIES Relay Modules
PRODUCT DATA
The R7824C Rectification Flame Amplifier is a solid state plug-in amplifier that responds to a rectified signal from a C7024E,F Self­Check Ultraviolet Flame Detector to indicate the presence of flame when used with an RM7824 Relay Module.
The R7847A,B Rectification Flame Amplifiers are solid state plug­in amplifiers that respond to a rectified signal from a rectification type flame detector to indicate the presence of flame when used with 7800 SERIES Relay Modules.
The R7847C Self-Check Rectification Flame Amplifier is a solid state plug-in amplifier that responds to a rectified signal from a C7012E,F Self-Check Ultraviolet Flame Detector to indicate the presence of flame when used with 7800 SERIES Relay Modules. This is not European Community (CE) approved for EC7810, EC7820, EC/RM7830 or EC/RM7850 Relay Modules.
The R7848A,B Infrared Flame Amplifiers are solid state plug-in amplifiers that respond to an infrared signal from a C7015 Infrared Flame Detector to indicate the presence of flame when used with 7800 SERIES Relay Modules.
The R7849A,B Ultraviolet Flame Amplifiers are solid state plug-in amplifiers that respond to an ultraviolet signal from a C7027, C7035 or C7044 Ultraviolet Flame Detector to indicate the presence of flame when used with 7800 SERIES Relay Modules.
The R7851B Optical Flame Amplifiers are solid state plug-in amplifiers that respond to optical signals from C7927, C7935, C7915, and C7962 Flame Detectors to indicate the presence of flame when used with 7800 SERIES Relay Modules.
The R7851C Dynamic Self-Check Optical Flame Amplifier is a solid state plug-in amplifier that responds to ultraviolet signals from C7961E Dynamic Shutter-Check ultraviolet flame detectors to indicate the presence of flame when used with 7800 SERIES Relay Modules.
The R7861A Self-Check Ultraviolet Flame Amplifier is a solid state plug-in amplifier that responds to an ultraviolet signal from a C7061 Self-Check Ultraviolet Flame Detector to indicate the presence of flame when used with 7800 SERIES Relay Modules.
The R7886A Dynamic Self-Check Ultraviolet Amplifier is a solid state plug-in amplifier that responds to a pulsed direct current signal from a C7076A,C Ultraviolet Flame Detector with adjustable sensitivity to indicate the presence of flame when used with 7800 SERIES Relay Modules.

FEATURES

• Flame failure response time of 0.8 or 1 second; or 2.0 or
3.0 seconds, depending on the amplifier and relay module selected. See Table 1.
• Plug-in to 7800 SERIES Relay Module through printed circuit board edge connector keyed for proper orientation.
• Flame signal test jacks measure amplifier flame signal voltage.
• 0.0 to 5.0 Vdc Flame signal strength reading range.
• Color coded label identifies flame detection type:
— Green—rectification. Red—infrared. — Purple—ultraviolet. Blue—pulsed rectification. — White—optical.
• R7847B, R7848B, R7849B Dynamic Ampli-Check® circuitry tests all flame amplifier components 12 times per minute. The 7800 SERIES Relay Module locks out on safety shutdown with amplifier failure.
• R7824C and R7847C Dynamic Self-Check Rectification Amplifier, R7851C Dynamic Self-Check Optical Flame Amplifier, R7861 Self-Check Ultraviolet Flame Amplifier and R7886A Dynamic Self-Check Ultraviolet Amplifier test the detectors and all electronic components in the flame detection system 12 times per minute. The 7800 SERIES Relay Module locks out on safety shutdown with flame detection system failure.
NOTE: NOTE:R7824C, Series 2 or greater, and R7847C,
Series 4 or greater, pulse shutter when signal of
1.5 Vac is sensed.
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ......................................................... 2
Installation ........................................................................ 4
Checkout .......................................................................... 6
® U.S. Registered Trademark Copyright © 2002 Honeywell • All Rights Reserved
65- 0109- 8
R7824, R7847, R7848, R7849,R7851,R7861, R7886 AMPLIFIERS FOR 7800 SERIES RELAY MODULES

SPECIFICATIONS

Models:
Flame Detection Systems (see Table 2): Rectification:
R7824C for use with C7024E,F Solid State Ultraviolet
Detectors.
R7847A for use with flame rods, rectifying photocells or
C7012A,C Solid State Ultraviolet Detectors.
R7847B for use with flame rods, rectifying photocells or
C7012A,C Solid State Ultraviolet Detectors.
R7847C for use with C7012E,F Solid State
Ultraviolet Detectors.
Infrared:
R7848A for use with C7015 Infrared (lead sulfide) Detector. R7848B for use with C7015 Infrared (lead sulfide) Detector.
Ultraviolet:
R7849A for use with C7027/C7035/C7044 Minipeeper Ultravi-
olet Detectors.
R7849B for use with C7027/C7035/C7044 Minipeeper Ultravi-
olet Detectors. R7861A for use with C7061A Ultraviolet Detector. R7886A for use with C7076A,D Ultraviolet Detectors with
adjustable sensitivity.
Optical:
R7851B for use with C7927, C7935, C7915 and C7962 Flame
Detectors. R7851C for use with C7961E Flame Detectors.
Flame Failure Response Time:
See Table 1.
Flame Signal (Volts dc):
Minimum Acceptable: 1.25 Vdc. Flame Signal Voltage Range (displayed on Keyboard Display
Module or measured with a 1M ohm/volt meter plugged into amplifier test jacks): 0.0 to 5.0 Vdc.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to 140°F (-40°C to 60°C). Storage: -40°F to 150°F (-40°C to 65°C).
Humidity: Operating 85% rh continuous, noncondensing. Vibration: Continuous 0.5G environment.
Weight:
Dimensions:
2.5 oz (71g), unpacked.
See Fig. 1
Approvals:
Underwriters Laboratories Inc. Listed: File no. MP268, Guide no.
MCCZZ: R7847A, R7847B, R7847C, R7861A, R7886A, R7848A, R7848B, R7849A, R7849B, R7851B. (R7851C Pending.)
Underwriters Laboratories Inc. Component Recognized: File no.
MP268, Guide no. MCCZZ: R7824C.
Canadian Standards Association Certified: LR95329-3. (R7851C
Pending.)
Factory Mutual Approved: Report J.I.1V9A0.AF. (R7851C
Pending.)
Industrial Risk Insurers: Acceptable
Table 1. Relay Module Flame Failure
Response Time (FFRT).
Flame Failure Response
Time (FFRT) in seconds
Relay Module
EC7810, EC7820, EC/RM7830,
0.8 or 1 2.0 or 3.0
1.0 2.0
EC/RM7850
EC/RM7823, EC/RM7885, EC/
0.8 3.0 RM7890, EC/RM7895, RM7896, RM7888, RM7838, RM7800, RM7840
RM7824 N/A 3.0
S
3-9/16 (91)
–+
FLAME AMPLIFIER
3
(76)
3/8 (9)
7/8 (23)
M11460
Fig. 1. Flame amplifier dimensions in in. (mm).
NOTE: .NOTE: EN298 Approved: When these amplifiers are
used with an EC7810, EC7820, EC/RM7830, or EC/RM7850 Relay Module.
Accessories:
Flame Simulators:
Rectification: 123514A. Ultraviolet: 203659.
Flame Detectors (ordered separately): select from Table 2.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
Your local Home and Building Control Sales Office (check white pages of your phone directory).
1.
Home and Building Control Customer Relations
2.
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
65-0109—8 2
R7824, R7847, R7848, R7849,R7851,R7861, R7886 AMPLIFIERS FOR 7800 SERIES RELAY MODULES
Table 2. Flame Detection Systems.
Plug-in Flame Signal Amplifiers Applicable Flame Detectors
Flame
Failure
Response
Type Color Self-Checking Model
Rectification Green Dymanic Self-
Check
No
No
No
Dynamic Ampli­Check®
Dynamic Ampli­Check®
Dynamic Ampli­Check®
Dynamic Self­Check
R7824C
R7847A
R7847A
R7847A
R7847B
R7847B
R7847B
R7847C
Infrared Red No R7848A 2/3 Gas, oil,
Dynamic Ampli­Check®
R7848B
Ultraviolet Purple No R7849A 0.8/1 or
Dynamic Ampli­Check®
Dynamic Self­Check
Blue Dynamic Self-
Check
Optical White Dymanic Ampli-
R7849B
R7861A
R7886A
R7851B 0.8/1 or 2/3 Gas, oil,
Check®
Dynamic Self­Check
a
Flame Failure Response Time (FFRT) depends on selection of amplifier and 7800 SERIES Relay Module.
b
R7824C is used only with the 24 Vdc RM7824 Relay Module and C7024E,F Flame Detectors.
c
Circuitry tests all electronic components in flame detection system (amplifier and detector) 12 times a minute during burner operation and shuts down burner if detection system fails.
d
Use only Honeywell part no. 38316 Photocell.
e
Circuitry tests flame signal amplifier 12 times a minute during burner operation and shuts down burner if amplifier fails.
f
200/220/240 Vac applications require a 120 Vac, 10 VA minimum stepdown transformer (not provided) to drive the shutter. Applies to R7847C series 3 or greater; R7886A series 2 or greater; R7861 series 1 or greater. Fig. 2 shows flame detector wiring.
g
Use C7027, C7035 and C7044 Flame Detectors only on burners that cycle on-off at least once every twenty-four hours. Use C7012E,F Flame Detector with R7847C Amplifier, C7061A Ultraviolet Detector with R7861A Amplifier or C7076A Flame Detector with R7886A Amplifier as ultraviolet flame detection system for appliances with burners that remain on continuously for twenty-four hours or longer.
h
R7847A,B Amplifiers with 0.8/1 second FFRT should not be used with C7012A,C Solid State Ultraviolet Detectors.
i
R7824C Series 2 and greater and R7847C Series 4 and greater check flame detector system when flame reaches 1.5 Vdc or at 4.5 seconds, whichever occurs first.
j
Order flame rod separately; see flame detector Instructions for holder.
R7851C
Time (sec)aFuel Type Models
b,c, i
3 Gas, oil,
coal
h
0.8/1 or 2/3 Gas Rectifying Flame Rod
h
0.8/1 or
Oil Rectifying Photocell C7003, C7010, C7013,
2/3
h
2/3 Gas, oil,
coal
e,h
0.8/1 or
Gas Rectifying Flame Rod
2/3
e,h
0.8/1 or
Oil Rectifying Photocell C7003, C7010, C7013,
2/3
e,h
2/3 Gas, oil,
coal
c,f, i
2/3 Gas, oil,
coal
coal
e
3 Gas, oil,
coal
Gas, oil Ultraviolet
2/3
d
0.8/1 or
Gas, oil Ultraviolet
2/3
c,f
0.8/1 or 2/3
c,f
2/3 Gas, oil,
Gas, oil, coal
coal
coal
c
2/3 Gas, oil,
Ultraviolet (Purple
C7024E,F
Peeper®)
C7004, C7007, C7011
Holders
j
Complete Assemblies: C7008, C7009, Q179
C7014
Ultraviolet (Purple
C7012A,C.
Peeper®)
C7004, C7007, C7011
Holders
b
Complete Assemblies: C7008, C7009, Q179
C7014
Ultraviolet (Purple
C7012A,C
Peeper®)
Ultraviolet (Purple
C7012E,F
Peeper®)
Infrared (Lead
C7015
Sulfide)
Infrared (Lead
C7015
Sulfide)
(Minipeeper)
(Minipeeper)
C7027, C7035, C7044
C7027, C7035, C7044
Ultraviolet C7061
Ultraviolet (Adjustable
C7076
Sensitivity)
Optical (UV, IR, Visible Light)
C7927, C7935, C7915, C7962
Optical (UV only) C7961
coal
d
d
g
g
3 65-0109—8