The R7824C Rectification Flame Amplifier is a solid state plug-in
amplifier that responds to a rectified signal from a C7024E,F SelfCheck Ultraviolet Flame Detector to indicate the presence of
flame when used with an RM7824 Relay Module.
The R7847A,B Rectification Flame Amplifiers are solid state plugin amplifiers that respond to a rectified signal from a rectification
type flame detector to indicate the presence of flame when used
with 7800 SERIES Relay Modules.
The R7847C Self-Check Rectification Flame Amplifier is a solid
state plug-in amplifier that responds to a rectified signal from a
C7012E,F Self-Check Ultraviolet Flame Detector to indicate the
presence of flame when used with 7800 SERIES Relay Modules.
This is not European Community (CE) approved for EC7810,
EC7820, EC/RM7830 or EC/RM7850 Relay Modules.
The R7848A,B Infrared Flame Amplifiers are solid state plug-in
amplifiers that respond to an infrared signal from a C7015
Infrared Flame Detector to indicate the presence of flame when
used with 7800 SERIES Relay Modules.
The R7849A,B Ultraviolet Flame Amplifiers are solid state plug-in
amplifiers that respond to an ultraviolet signal from a C7027,
C7035 or C7044 Ultraviolet Flame Detector to indicate the
presence of flame when used with 7800 SERIES Relay Modules.
The R7851B Optical Flame Amplifiers are solid state plug-in
amplifiers that respond to optical signals from C7927, C7935,
C7915, and C7962 Flame Detectors to indicate the presence of
flame when used with 7800 SERIES Relay Modules.
The R7851C Dynamic Self-Check Optical Flame Amplifier is a
solid state plug-in amplifier that responds to ultraviolet signals
from C7961E Dynamic Shutter-Check ultraviolet flame detectors
to indicate the presence of flame when used with 7800 SERIES
Relay Modules.
The R7861A Self-Check Ultraviolet Flame Amplifier is a solid
state plug-in amplifier that responds to an ultraviolet signal from a
C7061 Self-Check Ultraviolet Flame Detector to indicate the
presence of flame when used with 7800 SERIES Relay Modules.
The R7886A Dynamic Self-Check Ultraviolet Amplifier is a solid
state plug-in amplifier that responds to a pulsed direct current
signal from a C7076A,C Ultraviolet Flame Detector with
adjustable sensitivity to indicate the presence of flame when used
with 7800 SERIES Relay Modules.
FEATURES
• Flame failure response time of 0.8 or 1 second; or 2.0 or
3.0 seconds, depending on the amplifier and relay module
selected. See Table 1.
• Plug-in to 7800 SERIES Relay Module through printed
circuit board edge connector keyed for proper orientation.
• Flame signal test jacks measure amplifier flame signal
voltage.
• 0.0 to 5.0 Vdc Flame signal strength reading range.
• Color coded label identifies flame detection type:
• R7847B, R7848B, R7849B Dynamic Ampli-Check®
circuitry tests all flame amplifier components 12 times per
minute. The 7800 SERIES Relay Module locks out on
safety shutdown with amplifier failure.
• R7824C and R7847C Dynamic Self-Check Rectification
Amplifier, R7851C Dynamic Self-Check Optical Flame
Amplifier, R7861 Self-Check Ultraviolet Flame Amplifier
and R7886A Dynamic Self-Check Ultraviolet Amplifier test
the detectors and all electronic components in the flame
detection system 12 times per minute. The 7800 SERIES
Relay Module locks out on safety shutdown with flame
detection system failure.
NOTE: NOTE:R7824C, Series 2 or greater, and R7847C,
NOTE: .NOTE: EN298 Approved: When these amplifiers are
used with an EC7810, EC7820, EC/RM7830, or
EC/RM7850 Relay Module.
Accessories:
Flame Simulators:
Rectification: 123514A.
Ultraviolet: 203659.
Flame Detectors (ordered separately): select from Table 2.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
Your local Home and Building Control Sales Office (check white pages of your phone directory).
1.
Home and Building Control Customer Relations
2.
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
65-0109—82
R7824, R7847, R7848, R7849,R7851,R7861, R7886 AMPLIFIERS FOR 7800 SERIES RELAY MODULES
Table 2. Flame Detection Systems.
Plug-in Flame Signal AmplifiersApplicable Flame Detectors
Flame
Failure
Response
TypeColorSelf-CheckingModel
Rectification GreenDymanic Self-
Check
No
No
No
Dynamic AmpliCheck®
Dynamic AmpliCheck®
Dynamic AmpliCheck®
Dynamic SelfCheck
R7824C
R7847A
R7847A
R7847A
R7847B
R7847B
R7847B
R7847C
InfraredRedNoR7848A2/3Gas, oil,
Dynamic AmpliCheck®
R7848B
UltravioletPurple NoR7849A0.8/1 or
Dynamic AmpliCheck®
Dynamic SelfCheck
BlueDynamic Self-
Check
OpticalWhiteDymanic Ampli-
R7849B
R7861A
R7886A
R7851B0.8/1 or 2/3 Gas, oil,
Check®
Dynamic SelfCheck
a
Flame Failure Response Time (FFRT) depends on selection of amplifier and 7800 SERIES Relay Module.
b
R7824C is used only with the 24 Vdc RM7824 Relay Module and C7024E,F Flame Detectors.
c
Circuitry tests all electronic components in flame detection system (amplifier and detector) 12 times a minute during burner operation
and shuts down burner if detection system fails.
d
Use only Honeywell part no. 38316 Photocell.
e
Circuitry tests flame signal amplifier 12 times a minute during burner operation and shuts down burner if amplifier fails.
f
200/220/240 Vac applications require a 120 Vac, 10 VA minimum stepdown transformer (not provided) to drive the shutter. Applies to
R7847C series 3 or greater; R7886A series 2 or greater; R7861 series 1 or greater. Fig. 2 shows flame detector wiring.
g
Use C7027, C7035 and C7044 Flame Detectors only on burners that cycle on-off at least once every twenty-four hours. Use C7012E,F
Flame Detector with R7847C Amplifier, C7061A Ultraviolet Detector with R7861A Amplifier or C7076A Flame Detector with R7886A
Amplifier as ultraviolet flame detection system for appliances with burners that remain on continuously for twenty-four hours or longer.
h
R7847A,B Amplifiers with 0.8/1 second FFRT should not be used with C7012A,C Solid State Ultraviolet Detectors.
i
R7824C Series 2 and greater and R7847C Series 4 and greater check flame detector system when flame reaches 1.5 Vdc or at 4.5
seconds, whichever occurs first.
j
Order flame rod separately; see flame detector Instructions for holder.
R7851C
Time (sec)aFuelTypeModels
b,c, i
3Gas, oil,
coal
h
0.8/1 or 2/3 GasRectifying Flame Rod
h
0.8/1 or
OilRectifying PhotocellC7003, C7010, C7013,
2/3
h
2/3Gas, oil,
coal
e,h
0.8/1 or
GasRectifying Flame Rod
2/3
e,h
0.8/1 or
OilRectifying PhotocellC7003, C7010, C7013,
2/3
e,h
2/3 Gas, oil,
coal
c,f, i
2/3Gas, oil,
coal
coal
e
3 Gas, oil,
coal
Gas, oil Ultraviolet
2/3
d
0.8/1 or
Gas, oil Ultraviolet
2/3
c,f
0.8/1 or
2/3
c,f
2/3Gas, oil,
Gas, oil,
coal
coal
coal
c
2/3Gas, oil,
Ultraviolet (Purple
C7024E,F
Peeper®)
C7004, C7007, C7011
Holders
j
Complete Assemblies:
C7008, C7009, Q179
C7014
Ultraviolet (Purple
C7012A,C.
Peeper®)
C7004, C7007, C7011
Holders
b
Complete Assemblies:
C7008, C7009, Q179
C7014
Ultraviolet (Purple
C7012A,C
Peeper®)
Ultraviolet (Purple
C7012E,F
Peeper®)
Infrared (Lead
C7015
Sulfide)
Infrared (Lead
C7015
Sulfide)
(Minipeeper)
(Minipeeper)
C7027, C7035, C7044
C7027, C7035, C7044
UltravioletC7061
Ultraviolet (Adjustable
C7076
Sensitivity)
Optical (UV, IR,
Visible Light)
C7927, C7935, C7915,
C7962
Optical (UV only)C7961
coal
d
d
g
g
365-0109—8