Honeywell Q7300L User Manual

Q7300L
Series 2000 Commercial
Thermostat Subbases
INSTALLATION INSTRUCTIONS
APPLICATION
Table 1. Valve and Valve Actuator Combinations.
Valve Model Valve Actuator Model
V5011A, C ML7984A3019 V5011F, G ML7984A3001 V5013A, C ML7984A3019
V5013F ML7984A3001
IMPORTANT
The valve will not close if the wrong valve and valve actuator combination is used.
Electrical Rating:
20 to 30 Vac, 50/60 Hz.
System Current :
6 VA maximum at 30 Vac, 50 or 60 Hz.
Output Relay Current:
See Table 2.
Table 2. Maximum Amps at 30 Vac.
Relay Running (A) Inrush (A)
Fan 1.6 3.5 Heat 1.6 3.5 Cool 1.6 7.5
Auxillary (Economizer) 1.6 3.5
Temperature:
Ratings:
Operating Ambient: 40°F to 110°F (4°C to 43°C). Shipping: -30°F to +150°F (-34°C to +65°C).
Display Accuracy:
+1°F (+0.5°C).
Setpoint:
Range: 45°F to 95°F (7°C to 35°C). Differential: 2°F (1°C).
Humidity Ratings:
5% to 90% RH, noncondensing.
RECYCLING NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do n control in the trash
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat.
ot
place your old
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After completing installation, use these instructions to check out the product operation.
® U.S. Registered Trademark Copyright © 1996 Honeywell Inc. • • All Rights Reserved
X-XX UL
62-0131-2
Q7300L SERIES 2000 COMMERCIAL THERMOSTAT SUBBASE
NO
NO
Fig. 1. Typical location of thermostat or remote-mounted sensor.
Location
Subbase without Remote-Mounted Temperature Sensor
Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1.
Do not install the thermostat where it can be affected by: — drafts, or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.
Subbase with Remote-Mounted Temperature Sensor(s)
If only the remote-mounted temperature sensor(s) is used to sense and control room temperature, then install the thermostat in an area that is accessible for setting and adjusting the temperature and settings.
If both the subbase and remote-mounted temperature sensor(s) are used to sense and control room tempera­ture, then install the subbase about 5 ft above the floor in an area with good air circulation.
Install the remote-mounted sensor(s) about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1.
YES
5 FEET
(1.5 METERS)
Do not mount the sensor(s) where it can be affected by: — drafts, or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.
If more than one remote sensor are required, they must be arranged in a temperature averaging network consisting of two, three, four, five or nine sensors. See Fig. 2 through 6.
IMPORTANT
NO
M4823A
To avoid electrical interference, which can cause erratic performance, keep wiring runs as short as possible and do not run thermostat wires adjacent to the line voltage electrical distribution systems. Use shielded cable (Belden type 8762 or equivalent for 2-wire and Belden type 8772 or equivalent for 3-wire). The cable shield must be grounded only at the controlled equipment case.
SUBBASE
TT
T7047GT7047G
T
T
Fig. 2. Two T7047G Sensors providing
temperature averaging network for T7300/Q7300 Thermostat/Subbase.
T
T
M4838
62-0131—2
2
Q7300L SERIES 2000 COMMERCIAL THERMOSTAT SUBBASE
SUBBASE
TT
T7047C
TT
T7047G
T7047C
TT
Fig. 3. Two T7047C Sensors and one T7047G Sensor providing temperature averaging network for T7300/
Q7300 Thermostat/Subbase.
TT
T7047C
TT
T7047C
TT
Fig. 4. Four T7047C Sensors providing
temperature averaging network for T7300/Q7300 Thermostat/Subbase.
SUBBASE
TT
T7047G
T7047G
TT
M4839
SUBBASE
T7047C
TT
T7047C
TT
M4840
SUBBASE
TT
T7047C
TT
T7047C
TT
T7047C
TT
Fig. 6. Nine T7047C Sensors providing
temperature averaging network for T7300/Q7300 Thermostat/Subbase.
Mounting Subbase
The subbase mounts horizontally on the wall or a 2 in. x 4 in. wiring box. Position the subbase horizontally on the wall or on a 2 in. x 4 in. wiring box.
1. Position and level the subbase or wallplate (for appearance only). The thermostat functions properly even when not level.
2. Use a pencil to mark the mounting holes. See Fig. 7.
3. Remove the subbase or wallplate from the wall and
drill two 3/16 inch holes in the wall (if drywall) as marked. For firmer material such as plaster or wood, drill two 7/32 inch holes. Gently tap anchors (pro­vided) into the drilled holes until flush with the wall.
4. Position the subbase over the holes, pulling wires through the wiring opening.
5. Loosely insert the mounting screws into the holes.
6. Tighten mounting screws.
T7047C
TT
T7047C
TT
T7047C
TT
WIRES THROUGH WALL
T7047C
TT
T7047C
TT
T7047C
TT
M4842
WALL
T
T7047G
T
Fig. 5. Five T7047G Sensors providing
temperature averaging network for T7300/Q7300 Thermostat/Subbase.
T
T
T7047G
T
T
T7047G
T
T
WALL ANCHORS (2)
T
T
MOUNTING HOLES
M4841
LEDS
MOUNTING SCREWS
M10237
Fig. 7. Mounting the subbase.
3
62-0131—2
Loading...
+ 5 hidden pages