The PUB6438S, PVB6436AS and PVB6438NS controllers are
part of the Spyder family. The three controllers are BACnet
MS/TP network devices designed to control HVAC equipment.
These controllers provide many options and advanced system
features that allow state-of-the-art commercial building
control. Each controller is programmable and configurable
through software.
These controllers are for use in VAV (Variable Air Volume) and
Unitary HVAC control applications. Each controller contains a
host micro controller to run the main HVAC application and a
second micro controller for BACnet MS/TP network
communications. Each controller has flexible, universal inputs
for external sensors, digital inputs, and a combination of
analog and digital Triac outputs. The three models are
described in Table 1. The photo to the left is the model
PVB6436AS, which includes the actuator.
Table 1. Controller configurations.
Controller
Model
PUB6438SUnitary6438NONO
PVB6436ASVAV6436YESYES
PVB6438NSVAV6438YESNO
Each controller communicates via an EIA-485 BACnet MS/TP network communications network, capable of baud rates between
9.6 and 115.2 kilobits.
Controllers are field-mountable to either a panel or a DIN rail.
Programmable
Typ e
Universal
Inputs
(UI)
SPECIFICATIONS
General Specifications
Rated Voltage: 20–30 Vac; 50/60 Hz
Power Consumption:
100 VA for controller and all connected loads (including the
actuator on model PVB6436AS).
Controller Only Load: 5 VA maximum; models PUB6438S
and PVB6438NS.
Controller and Actuator Load: 9 VA maximum; model
PVB6436AS.
Digital
Inputs
(DI)
Analog
Outputs
(AO)
External Sensors Power Output: 20 Vdc ±10% @ 75 mA
maximum.
VAV Operating & Storage Temperature Ambient Rating
(models PVB6436AS and PVB6438NS):
Minimum 32 ºF (0 ºC); Maximum 122 ºF (50 ºC)
Unitary Operating & Storage Temperature Ambient Rating
(model PUB6438S):
Minimum -40 ºF (-40 ºC); Maximum 150 ºF (65.5 ºC)
Relative Humidity: 5% to 95% non-condensing
LED: Provides status for normal operation, controller down-
load process, alarms, manual mode, and error conditions
Digital
Outputs
(DO)
BEFORE INSTALLATION
The controller is available in three models (see Table 1).
Review the power, input, and output specifications on page 1
before installing the controller.
— Hardware driven by Triac outputs must have a minimum
current draw, when energized, of 25 mA and a maximum
current draw of 500 mA.
— Hardware driven by the analog current outputs must have
a maximum resistance of 550 Ohms, resulting in a
maximum voltage of 11 volts when driven at 20 mA.
If resistance exceeds 550 Ohms, voltages up to 18 Vdc are
possible at the analog output terminal.
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power supply before beginning wiring or
making wiring connections to prevent electrical shock
or equipment damage.
INSTALLATION
The controller must be mounted in a position that allows
clearance for wiring, servicing, removal, connection of the
BACnet MS/TP Molex connector and access to the MS/TP
MAC address DIP switches.
reduce the rotation travel. Each “hash mark” indicator on the bracket represents approximately
6.5° of rotation per side.
2.The Declutch button, when pressed, allows you to
rotate the universal shaft adapter (see Fig. 1).
IMPORTANT
Determine the damper rotation and opening angle
prior to installation. See Fig. 2 below and Fig. 3 on
page 3 for examples.
UNIVERSAL SHAFT
CLAMPING BOLTS (2)
UNIVERSAL
SHAFT ADAPTER
MECHANICAL
END LIMIT SET
SCREWS (2)
DECLUTCH
BUTTON
The controller may be mounted in any orientation.
IMPORTANT
Avoid mounting in areas where acid fumes or other
deteriorating vapors can attack the metal parts of the
controller, or in areas where escaping gas or other
explosive vapors are present. Fig. 4–Fig. 5 on
page 4 for mounting dimensions.
For the PVB6436AS model, the actuator is mounted first and
then the controller is mounted. For the other models, go to
“Mount Controller” on page 3 to begin the installation.
Mount Actuator onto Damper Shaft
(PVB6436AS)
PVB6436AS controller includes the direct-coupled actuator
with Declutch mechanism, which is shipped hard-wired to the
controller.
The actuator mounts directly onto the VAV box damper shaft
and has up to 44 lb-in. (5 Nm) torque, 90-degree stroke, and
90 second timing at 60 Hz. The actuator is suitable for
mounting onto a 3/8 to 1/2 in. (10 to 13 mm) square or round
VAV box damper shaft. The minimum VAV box damper shaft
length is 1-9/16 in. (40 mm).
The two mechanical end-limit set screws control the amount
of rotation from 12° to 95°. These set screws must be securely
fastened in place. To ensure tight closing of the damper, the
shaft adapter has a total rotation stroke of 95° (see Fig. 1).
NOTES:
1.The actuator is shipped with the mechanical endlimit set screws set to 95 degrees of rotation.
Adjust the two set screws closer together to
M23568
Fig. 1. Series 60 Floating Actuator.
DAMPER
DAMPER SHAFT
ROTATES
CLOCKWISE
TO OPEN
M23569
Fig. 2. Damper with 90 degree CW rotation to open.
IMPORTANT
Mount actuator flush with damper housing or add a
spacer between the actuator mounting surface and
damper box housing.
Before Mounting Actuator onto Damper Shaft
(PVB6436AS)
Tools required:
— Phillips #2 screwdriver - end-limit set screw adjustment
— 8 mm wrench - centering clamp
Before mounting the actuator onto the VAV box damper shaft,
determine the following:
1. Determine the damper shaft diameter. It must be
between 3/8 in. to 1/2 in. (10 to 13 mm).
2. Determine the length of the damper shaft. If the length
of the VAV box damper shaft is less than 1-9/16 in.
(40 mm), the actuator cannot be used.
3.
Determine the direction the damper shaft rotates to open
the damper (CW or CCW) (see Fig. 3). Typically, there is
an etched line on the end of the damper shaft that indicates the position of the damper. In Fig. 2, the indicator
shows the damper open in a CW direction.
4. Determine the damper full opening angle (45, 60, or 90
degrees). In Fig. 2, the damper is open to its full open
position of 90 degrees.
Fig. 3. Determining the rotation direction (CW or CCW)
for damper opening.
Mounting Actuator Onto Damper Shaft (PVB6436AS)
The unit is shipped with the actuator set to rotate open in the
clockwise (CW) direction to a full 95 degrees. The extra 5
degrees ensures a full opening range for a 90 degree damper.
The installation procedure varies depending on the damper
opening direction and angle:
1. If the damper rotates clockwise (CW) to open, and the
angle of the damper open-to-closed is 90 degrees:
a. Manually open the damper fully (rotate clockwise).
b. Using the Declutch button, rotate the universal shaft
adapter fully clockwise.
c. Mount the actuator to the VAV damper box and shaft.
d. Tighten the two bolts on the centering clamp
(8 mm wrench; 70.8–88.5 lb-in. [8–10 Nm] torque).
When the actuator closes, the damper rotates CCW
2. If the damper rotates clockwise (CW) to open, and the
90 degrees to fully close.
angle of the damper open-to-closed is 45 or 60 degrees:
a. Manually open the damper fully (rotate clockwise).
b. The actuator is shipped with the mechanical
end-limits set at 95 degrees. Adjust the two
mechanical end-limit set screws to provide the
desired amount of rotation. Adjust the two set
screws closer together to reduce the rotation travel.
c. Tighten the two mechanical end-limit screws
Nm] torque).
d. Using the Declutch button, rotate the universal shaft
adapter fully clockwise.
e. Mount the actuator to the VAV damper box and shaft.
f. Tighten the two bolts on the centering clamp
(8 mm wrench; 70.8–88.5 lb-in. [8–10 Nm] torque).
g. When the actuator closes, the damper rotates CCW
either 45 or 60 degrees to fully close.
3.
If the damper rotates counterclockwise (CCW) to open,
and the angle of the damper open-to-closed is 90 degrees:
a. Manually open the damper fully (rotate counter-
clockwise).
b. Using the Declutch button, rotate the universal shaft
adapter fully counterclockwise.
c. Mount the actuator to the damper box and shaft.
d. Tighten the two bolts on the centering clamp (8 mm
wrench; 70.8–88.5 lb-in. [8–10 Nm] torque). When
the actuator closes, the damper rotates CW
90 degrees to fully close.
4.
If the damper rotates counterclockwise to open, and the
angle of the damper open-to-closed is 45 or 60 degrees:
a. Manually open the damper fully (rotate counter-
clockwise).
b. The actuator is shipped with the mechanical
end-limits set at 95 degrees. Adjust the two
mechanical end-limit set screws to provide the
desired amount of rotation. Adjust the two set
screws closer together to reduce the rotation travel.
c. Tighten the two mechanical end-limit screws
Nm] torque).
d. Using the Declutch button, rotate the universal shaft
adapter fully counter-clockwise.
e. Mount the actuator to the VAV damper box and shaft.
f. Tighten the two bolts on the centering clamp
(8 mm wrench; 70.8–88.5 lb-in. [8–10 Nm] torque).
g. When the actuator closes, the damper rotates CW
either 45 or 60 degrees to fully close.
Mount Controller
NOTE: The controller may be wired before mounting to a
panel or DIN rail.
Terminal blocks are used to make all wiring connections to the
controller. Attach all wiring to the appropriate terminal blocks
(see “Wiring” on page 5).
See Fig. 4–Fig. 5 for panel mounting dimensions. See Fig. 6
on page 4 for DIN rail mounting.
10-5/16 (262)
5-3/4
(146)
5-3/64
(128)
123456
NOTE: CONTROLLER CAN BE MOUNTED IN ANY ORIENTATION.
NOTE: CONTROLLER CAN BE MOUNTED IN ANY ORIENTATION.
6-27/32 (174)
1 1 1 1 1 1 1 1 1 2 1
1 0 9 2 3 4 5 6 7 8 0 9
5-29/64
(139)
DEPTH IS
2-1/ 4 (57 )
1 2 3 4 5 6
7 8
1 1 1 1 1 1 1 1 1 2 1
1 0 9 2 3 4 5 6 7 8 0 9
6-29/64 (164)
6-27/32 (174)
M29330
Fig. 5. Panel mounting - controller dimensions in inches (mm) for models PUB6438S and PVB6438NS only.
Panel Mounting
The controller enclosure is constructed of a plastic base plate
and a plastic factory-snap-on cover.
NOTE: The controller is designed so that the cover does not
need to be removed from the base plate for either
mounting or wiring.
The controller mounts using four screws inserted through the
corners of the base plate. Fasten securely with four No. 6 or
No. 8 machine or sheet metal screws.
The controller can be mounted in any orientation. Ventilation
openings are designed into the cover to allow proper heat
dissipation, regardless of the mounting orientation.
DIN Rail Mounting (PUB6438S and PVB6438NS)
To mount the PUB6438S or PVB6438NS controller on a DIN
rail [standard EN50022; 1-3/8 in. x 9/32 in. (7.5 mm x 35 mm)],
refer to Fig. 6 and perform the following steps:
1. Holding the controller with its top tilted in towards the
DIN rail, hook the two top tabs on the back of the controller onto the top of the DIN rail.
2. Push down and in to snap the two bottom flex connectors of the controller onto the DIN rail.
TOP TABS
BOTTOM FLEX
CONNECTORS
Fig. 6. Controller DIN rail mounting (models PUB6438S
and PVB6438NS).
Piping (PVB6436AS and PVB6438NS)
Air flow Pickup
For PVB6436AS and PVB6438NS, connect the air flow pickup
to the two restrictor ports on the controller (see Fig. 7).
DIN RAIL
M16815
IMPORTANT
To remove the controller from the DIN rail, perform
the following:
1. Push straight up from the bottom to release the top
tabs.
2. Rotate the top of the controller out towards you and
pull the controller down and away from the DIN rail to
release the bottom flex connectors.
—The tubing from the air flow pickup to the control-
ler should not exceed three feet (0.914 m). Any
length greater than this will degrade the flow
sensing accuracy.
—Use caution when removing tubing from a con-
nector. Always pull straight away from the connector or use diagonal cutters to cut the edge of
the tubing attached to the connector. Never
remove by pulling at an angle.
Fig. 7. Air flow pickup connections (PVB6436AS and
PVB6438NS).
Wiring
All wiring must comply with applicable electrical codes and
ordinances, or as specified on installation wiring diagrams.
Controller wiring is terminated to the screw terminal blocks
located on the top and the bottom of the device.
—Do not connect the universal input COM
terminals, analog output COM terminals or the
digital input/output COM terminals to earth
ground.
The 24 Vac power from an energy limited Class II power
source must be provided to the controller. To conform to Class
II restrictions (U.S. only), the transformer must not be larger
than 100 VA.
Fig. 8 depicts a single controller using one transformer.
IMPORTANT
Power must be off prior to connecting to or removing
connections from the 24 Vac power (24 Vac/24 Vac
COM), earth ground (EGND), and 20 Vdc power (20
Vdc) terminals.
IMPORTANT
Use the heaviest gauge wire available, up to
14 AWG (2.0 sq mm), with a minimum of 18 AWG
(1.0 sq mm), for all power and earth ground wiring.
Screw-type terminal blocks are designed to accept
up to one 14 AWG (2.0 sq mm) conductor or up to
two 18 AWG (1.0 sq mm) conductors. More than two
wires that are 18 AWG (2.0 sq mm) can be connected with a wire nut. Include a pigtail with this wire
group and attach the pigtail to the terminal block.
IMPORTANT
Connect terminal 2, (the 24 Vac common [24 VAC
COM] terminal) to earth ground (see Fig. 8).
NOTE: Unswitched 24 Vac power wiring can be run in the
same conduit as the BACnet MS/TP cable.
ΔP
2
2 2 2 2
2 2
1 2 3 4 5 6
7 8 0 9
2 2 3 3
3 3 3
3 3
1 2 3 4 5 6
3 3
3 4
7 8 0 9
NOTES:
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power supply before beginning wiring or
making wiring connections, to prevent electrical shock
or equipment damage.
—For multiple controllers operating from a single
transformer, the same side of the transformer
secondary must be connected to the same power
input terminal in each controller. Controller
configurations will not necessarily be limited to
three devices, but the total power draw, including
accessories, cannot exceed 100 VA when
powered by the same transformer (U.S. only).
The earth ground terminal (terminal 3) must be
connected to a verified earth ground for each
controller in the group (see Fig. 9 on page 6).
—All loads on the controller must be powered by the
same transformer that powers the controller itself.
A controller can use separate transformers for
controller power and output power.
—Keep the earth ground connection (terminal 3)
wire run as short as possible.
CONNECT POWER TO
TERMINALS 1 AND 2
7 8
1 2 3 4 5 6
TRANSFORMER
COM
24 VAC
LINE VOLTAGE
GREATER
THAN 150 VAC
1
WHEN CONNECTIONG POWER TO THE SPYDER BACnet
CONTROLLER, CONNECT THE COM LEG OF THE VAC SECONDARY
CIRCUIT TO A KNOWN EARTH GROUND.
1
EARTH
GROUND
OUTPUT
DEVICE
POWER
EARTH
GROUND
(TERMINAL 3)
1 1 1 1 1 1 1 1 1 2 1
1 0 9 2 3 4 5 6 7 8 0 9
M29684
Fig. 8. Power wiring details for one controller per
transformer.
More than one controller can be powered by a single
transformer. Fig. 9 shows power wiring details for multiple
controllers.
NOTE: Controller configurations are not necessarily limited
Communications
Each controller uses a BACnet MS/TP communications port.
The controller’s data is presented to other controllers over a
twisted-pair MS/TP network, which uses the EIA-485 signaling
standard capable of the following baud rates: 9.6, 19.2, 38.4,
76.8 or 115.2 Kilobits per second (configured at global
controller). The Spyder BACnet controllers are master devices
on the MS/TP network. Each Spyder BACnet controller uses a
high-quality EIA-485 transceiver and exerts 1/4 unit load on
the MS/TP network.
Cabling should be selected that meets or exceeds the BACnet
Standard which specifies the following: An MS/TP EIA-485
network shall use shielded, twisted-pair cable with
characteristic impedance between 100 and 130 ohms.
Distributed capacitance between conductors shall be less
than 100 pF per meter (30 pF per foot). Distributed
capacitance between conductors and shield shall be less that
200 pF per meter (60 pF per foot). Foil or braided shields are
acceptable. The Honeywell tested and recommended MS/TP
cable is Honeywell Cable 3322 (18 AWG, 1-Pair, Shielded,
Plenum cable), alternatively Honeywell Cable 3251 (22 AWG,
1-Pair, Shielded, Plenum cable) is available and meets the
BACnet Standard requirements (www.honeywellcable.com).
The maximum BACnet MS/TP network Bus segment length is
4,000 ft. (1,071 m) using recommended wire. Repeaters must
be used when making runs longer than 4,000 ft. (1,071 m). A
maximum of three repeaters can be used between any two
devices.
Setting the MS/TP MAC address
The MS/TP MAC address for each device must be set to a
unique value in the range of 0-127 on an MS/TP network
segment (address 0, 1, 2, & 3 should be avoided as they are
commonly used for the router, diagnostic tools, and as spare
addresses). DIP switches on the Spyder BACnet controller
are used to set the controller's MAC address.
62-0310—016
to three devices, but the total power draw, including
accessories, cannot exceed 100 VA when powered
by the same transformer (U.S. only).
Fig. 9. Power wiring details for two or more controllers per transformer.
To set the MS/TP MAC address of a Spyder BACnet
controller:
1. Find an unused MAC address on the MS/TP network to
which the Spyder BACnet controller connects.
2. Locate the DIP switch bank on the Spyder BACnet for
addressing. This is labeled MAC Address
3. With the Spyder BACnet Controller powered down, set
the DIP switches for the MAC Address you want. Add
the value of DIP switches set to ON to determine the
MAC address. See Table 2. Example, if only DIP
switches 1, 3, 5, and 7 are enabled the MAC address
would be 85 (1 + 4 + 16 + 64 = 85).
Table 2. DIP Switch Values For MS/TP MAC Address.
DIP7654321
VAL UE 6432168421
Setting the Device Instance Number
The Device Instance Number must be unique across the
entire BACnet system network because it is used to uniquely
identify the BACnet devices. It may be used to conveniently
identify the BACnet device from other devices during
installation. The Spyder BACnet Controllers Device Instance
Number is automatically set when it is added to a
WEBStation-AX project. The Device Instance Number can be
changed by the user, which may be necessary when
integrating with a third party or when attempting to replace an
existing controller and it is desired to maintain the existing
Device Instance Number.
To edit the Device Instance Number using WEBs AX:
1. Identify an unused Device Instance Number on the
BACnet Network, in the range of 0 - 4194302.
2. Open the Spyder Bacnet Device Mgr View
a. Double click on the BacnetNetwork located in the
Nav tree.
b. Select the Spyder Controller to be modified.
c. Click on the Edit button.
d. Enter an unused value in the Device Id field.
ADD APPROPRIATE TERMINATION
RESISTOR BETWEEN THE BAC+
AND THE BAC– TERMINALS.
BACnet MS/TP–
BAC+
SHLD
BAC–
NOTE: ALL BACnet MS/TP CONNECTIONS ARE MADE TO:
1 2 3 4 5 6
7 8
1 0 9 2 3 4 5 6 7 8 0 9
1 1 1 1 1 1 1 1 1 2 1
1 2 3 4 5 6
7 8 0 9
2
2 2
2 2 2 2
2 2 3 3
1 2 3 4 5 6
7 8 0 9
3 3 3
3 3
3 3
3 4
AO-1
COM
AO-2
AO-3
COM
UI-1
COM
UI-2
UI-3
COM
UI-4
UI-5
COM
UI-6
DI-1
DI-2
COM
DI-3
20V DC
DI-4
BAC –
BAC +
SHLD
EGND
24 VAC
24VAC COM
DO-1
COM
DO-2
DO-3
DO-4
DO-5
COM
DO-6
COM
1 2 3 4 5 6
7 8
1 0 9 2 3 4 5 6 7 8 0 9
1 1 1 1 1 1 1 1 1 2 1
1 2 3 4 5 6
7 8 0 9
2
2 2
2 2 2 2
2 2 3 3
1 2 3 4 5 6
7 8 0 9
3 3 3
3 3
3 3
3 4
AO-1
COM
AO-2
AO-3
COM
UI-1
COM
UI-2
UI-3
COM
UI-4
UI-5
COM
UI-6
DI-1
DI-2
COM
DI-3
20V DC
DI-4
BAC –
BAC +
SHLD
EGND
24 VAC
24VAC COM
DO-1
COM
DO-2
DO-3
DO-4
DO-5
COM
DO-6
COM
1 2 3 4 5 6
7 8
1 0 9 2 3 4 5 6 7 8 0 9
1 1 1 1 1 1 1 1 1 2 1
1 2 3 4 5 6
7 8 0 9
2
2 2
2 2 2 2
2 2 3 3
1 2 3 4 5 6
7 8 0 9
3 3 3
3 3
3 3
3 4
DO-7
DO-8
COM
DO-7
DO-8
COM
SBUS1
SBUS2
SBUS1
SBUS2
SBUS1
SBUS2
BACnet MS/TP+
SHIELD
BACnet MS/TP–
BACnet MS/TP+
SHIELD
e. Select OK
3. Right Click on the Spyder Controller and select Actions
> Write Device Instance to complete the update
Termination Resistors
Matched terminating resistors are required at each end of a
segment bus wired across (+) and (-). Use matched precision
resistors rated 1/4W ±1% / 80 - 130 Ohms. Ideally, the value
of the terminating resistors should match the rated
characteristic impedance of the installed cable. For example,
if the installed MS/TP cable has a a listed characteristic
impedance of 120 Ohm, install 120 Ohm matched precision
resistors.
Shield Terminating
Following proper MS/TP cabling shield grounding procedures
is important to minimize the risk of communication problems
and equipment damage caused by capacitive coupling.
Capacitive coupling is caused by placing MS/TP cabling close
to lines carrying higher voltage. The shield should be
grounded on only one end of the MS/TP segment (typically
the router end). Tie the shield through using the SHLD
(terminal 4) on the Spyder BACnet Controller.
Sylk™ Bus
Sylk is a two wire, polarity insensitive bus that provides both
18 VDC power and communications between a Sylk-enabled
sensor and a Sylk-enabled controller. Using Sylk-enabled
sensors saves I/O on the controller and is faster and cheaper
to install since only two wires are needed and the bus is
polarity insensitive. Sylk sensors are configured using the
latest release of the Spyder Tool for WEBPro and
WEBStation.
Wiring Method
NOTE: When attaching two or more wires to the same termi-
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power supply before beginning wiring, or
making wiring connections, to prevent electrical shock
or equipment damage.
nal, other than 14 AWG (2.0 sq mm), be sure to twist
them together. Deviation from this rule can result in
improper electrical contact (see Fig. 11).
Each terminal can accommodate the following gauges of wire:
— Single wire: from 22 AWG to 14 AWG solid or stranded
— Multiple wires: up to two 18 AWG stranded, with 1/4 watt
wire-wound resistor
Prepare wiring for the terminal blocks, as follows:
1. Strip 1/2 in. (13 mm) insulation from the conductor.
2. Cut a single wire to 3/16 in. (5 mm). Insert the wire in
the required terminal location and tighten the screw.
3. If two or more wires are being inserted into one terminal
location, twist the wires together a minimum of three
turns before inserting them (see Fig. 11).
4. Cut the twisted end of the wires to 3/16 in. (5 mm)
before inserting them into the terminal and tightening
762-0310—01
the screw.
5. Pull on each wire in all terminals to check for good
mechanical connection.
STRIP 1/2 IN. (13 MM)
FROM WIRES TO
BE ATTACHED AT
ONE TERMINAL.
1.
2.
TWIST WIRES
TOGETHER WITH
PLIERS (A MINIMUM
OF THREE TURNS).
3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM)
BEFORE INSERTING INTO TERMINAL AND
TIGHTENING SCREW. THEN PULL ON EACH
WIRE IN ALL TERMINALS TO CHECK FOR
GOOD MECHANICAL CONNECTION.
M17207
Fig. 11. Attaching two or more wires at terminal blocks.
Controller Replacement (PVB6436AS)
For PVB6436AS controllers, which are hard-wired to an
actuator, perform the following actions to replace the complete
assembly (controller and actuator):
1. Remove all power from the controller.
2. Remove the two air flow pickup connections from the
3. Remove the terminal blocks.
4. Remove the old controller and actuator assembly from
5. Mount the new controller and actuator assembly (See
6. Reconnect the two air flow pickup tubes to the pressure
7. Replace the terminal blocks:
pressure sensor.
its mounting.
• Loosen the two bolts on the actuator clamp to
release the actuator from the shaft.
• Remove the controller’s mounting screws.
• Gently pull the controller and actuator assembly
straight out, until the assembly is clear of the
actuator shaft.
“Installation” on page 2.).
sensor (See “Piping (PVB6436AS and PVB6438NS)”
on page 4.).
• Insert each terminal block onto its alignment pins.
• Press straight down to firmly seat it.
• Repeat for each terminal block.
8. Restore power to the controller.
Controller Replacement (PVB6438NS)
Perform the following to replace the PVB6438NS controller:
1. Remove all power from the controller.
2. Remove the two air flow pickup connections from the
pressure sensor.
3. Remove the terminal blocks.
4. Remove the old controller from its mounting.
IMPORTANT
(FOR CONTROLLERS MOUNTED TO A DIN RAIL):
1. Push straight up from the bottom to release the top
pins.
2. Rotate the top of the controller outwards to release
the bottom flex connectors (see Fig. 6 on page 4).
5. Mount the new controller.
• See “Installation” on page 2.
6. Reconnect the two air flow pickup tubes to the pressure
sensor (See “Piping (PVB6436AS and PVB6438NS)”
on page 4.).
7. Replace the terminal blocks:
• Insert each terminal block onto its alignment pins.
• Press straight down to firmly seat it.
• Repeat for each terminal block.
8. Restore power to the controller.
Controller Replacement (PUB6438S)
Perform the following to replace the PUB6438S controller:
1. Remove all power from the controller.
2. Remove the terminal blocks.
3. Remove the old controller from its mounting.
IMPORTANT
(FOR CONTROLLERS MOUNTED TO A DIN RAIL):
1. Push straight up from the bottom to release the top
pins.
2. Rotate the top of the controller outwards to release
the bottom flex connectors (see Fig. 6 on page 4).
4. Mount the new controller (See “Installation” on page 2.).
5. Replace the terminal blocks:
• Insert each terminal block onto its alignment pins.
• Press straight down to firmly seat it.
• Repeat for each terminal block.
6. Restore power to the controller.
Automation and Control Solutions
Honeywell International Inc.Honeywell Limited-Honeywell Limitée