Honeywell PUB6438S, PVB6436AS, PVB6438NS Installation Instructions Manual

Page 1
®
Spyder® BACnet Programmable, VAV/Unitary Controllers
INSTALLATION INSTRUCTIONS

PRODUCT DESCRIPTION

These controllers are for use in VAV (Variable Air Volume) and Unitary HVAC control applications. Each controller contains a host micro controller to run the main HVAC application and a second micro controller for BACnet MS/TP network communications. Each controller has flexible, universal inputs for external sensors, digital inputs, and a combination of analog and digital Triac outputs. The three models are described in Table 1. The photo to the left is the model PVB6436AS, which includes the actuator.
Table 1. Controller configurations.
Controller
Model
PUB6438S Unitary 6 4 3 8 NO NO
PVB6436AS VAV 6 4 3 6 YES YES
PVB6438NS VAV 6 4 3 8 YES NO
Each controller communicates via an EIA-485 BACnet MS/TP network communications network, capable of baud rates between
9.6 and 115.2 kilobits. Controllers are field-mountable to either a panel or a DIN rail.
Programmable
Typ e
Universal
Inputs
(UI)

SPECIFICATIONS

General Specifications
Rated Voltage: 20–30 Vac; 50/60 Hz Power Consumption:
100 VA for controller and all connected loads (including the
actuator on model PVB6436AS).
Controller Only Load: 5 VA maximum; models PUB6438S
and PVB6438NS.
Controller and Actuator Load: 9 VA maximum; model
PVB6436AS.
Digital Inputs
(DI)
Analog
Outputs
(AO)
External Sensors Power Output: 20 Vdc ±10% @ 75 mA
maximum.
VAV Operating & Storage Temperature Ambient Rating
(models PVB6436AS and PVB6438NS):
Minimum 32 ºF (0 ºC); Maximum 122 ºF (50 ºC)
Unitary Operating & Storage Temperature Ambient Rating
(model PUB6438S):
Minimum -40 ºF (-40 ºC); Maximum 150 ºF (65.5 ºC)
Relative Humidity: 5% to 95% non-condensing LED: Provides status for normal operation, controller down-
load process, alarms, manual mode, and error conditions
Digital
Outputs
(DO)

BEFORE INSTALLATION

The controller is available in three models (see Table 1).
Veloc ity
Pressure
Sensor
(Microbridge)
Series 60
Floating
Actuator
62-0310-01
Page 2
SPYDER® BACNET® PROGRAMMABLE, VAV/UNITARY CONTROLLERS
WARNING
Review the power, input, and output specifications on page 1 before installing the controller. — Hardware driven by Triac outputs must have a minimum
current draw, when energized, of 25 mA and a maximum current draw of 500 mA.
— Hardware driven by the analog current outputs must have
a maximum resistance of 550 Ohms, resulting in a maximum voltage of 11 volts when driven at 20 mA. If resistance exceeds 550 Ohms, voltages up to 18 Vdc are possible at the analog output terminal.
Electrical Shock Hazard. Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring or making wiring connections to prevent electrical shock or equipment damage.

INSTALLATION

The controller must be mounted in a position that allows clearance for wiring, servicing, removal, connection of the BACnet MS/TP Molex connector and access to the MS/TP MAC address DIP switches.
reduce the rotation travel. Each “hash mark” indi­cator on the bracket represents approximately
6.5° of rotation per side.
2. The Declutch button, when pressed, allows you to rotate the universal shaft adapter (see Fig. 1).
IMPORTANT
Determine the damper rotation and opening angle prior to installation. See Fig. 2 below and Fig. 3 on page 3 for examples.
UNIVERSAL SHAFT
CLAMPING BOLTS (2)
UNIVERSAL
SHAFT ADAPTER
MECHANICAL
END LIMIT SET
SCREWS (2)
DECLUTCH
BUTTON
The controller may be mounted in any orientation.
IMPORTANT
Avoid mounting in areas where acid fumes or other deteriorating vapors can attack the metal parts of the controller, or in areas where escaping gas or other explosive vapors are present. Fig. 4–Fig. 5 on page 4 for mounting dimensions.
For the PVB6436AS model, the actuator is mounted first and then the controller is mounted. For the other models, go to “Mount Controller” on page 3 to begin the installation.

Mount Actuator onto Damper Shaft (PVB6436AS)

PVB6436AS controller includes the direct-coupled actuator with Declutch mechanism, which is shipped hard-wired to the controller.
The actuator mounts directly onto the VAV box damper shaft and has up to 44 lb-in. (5 Nm) torque, 90-degree stroke, and 90 second timing at 60 Hz. The actuator is suitable for mounting onto a 3/8 to 1/2 in. (10 to 13 mm) square or round VAV box damper shaft. The minimum VAV box damper shaft length is 1-9/16 in. (40 mm).
The two mechanical end-limit set screws control the amount of rotation from 12° to 95°. These set screws must be securely fastened in place. To ensure tight closing of the damper, the shaft adapter has a total rotation stroke of 95° (see Fig. 1).
NOTES:
1. The actuator is shipped with the mechanical end­limit set screws set to 95 degrees of rotation. Adjust the two set screws closer together to
M23568
Fig. 1. Series 60 Floating Actuator.
DAMPER
DAMPER SHAFT ROTATES CLOCKWISE TO OPEN
M23569
Fig. 2. Damper with 90 degree CW rotation to open.
IMPORTANT
Mount actuator flush with damper housing or add a spacer between the actuator mounting surface and damper box housing.
Before Mounting Actuator onto Damper Shaft (PVB6436AS)
Tools required: — Phillips #2 screwdriver - end-limit set screw adjustment — 8 mm wrench - centering clamp
62-0310—01 2
Page 3
SPYDER® BACNET® PROGRAMMABLE, VAV/UNITARY CONTROLLERS
AIR FLOW
AIR FLOW
CW TO OPEN, CCW TO CLOSE
CCW TO OPEN, CW TO CLOSE
M2067B
TYPE A DAMPER
TYPE B DAMPER
Before mounting the actuator onto the VAV box damper shaft, determine the following:
1. Determine the damper shaft diameter. It must be between 3/8 in. to 1/2 in. (10 to 13 mm).
2. Determine the length of the damper shaft. If the length of the VAV box damper shaft is less than 1-9/16 in. (40 mm), the actuator cannot be used.
3.
Determine the direction the damper shaft rotates to open the damper (CW or CCW) (see Fig. 3). Typically, there is an etched line on the end of the damper shaft that indi­cates the position of the damper. In Fig. 2, the indicator shows the damper open in a CW direction.
4. Determine the damper full opening angle (45, 60, or 90 degrees). In Fig. 2, the damper is open to its full open position of 90 degrees.
Fig. 3. Determining the rotation direction (CW or CCW)
for damper opening.
Mounting Actuator Onto Damper Shaft (PVB6436AS)
The unit is shipped with the actuator set to rotate open in the clockwise (CW) direction to a full 95 degrees. The extra 5 degrees ensures a full opening range for a 90 degree damper. The installation procedure varies depending on the damper opening direction and angle:
1. If the damper rotates clockwise (CW) to open, and the angle of the damper open-to-closed is 90 degrees: a. Manually open the damper fully (rotate clockwise). b. Using the Declutch button, rotate the universal shaft
adapter fully clockwise. c. Mount the actuator to the VAV damper box and shaft. d. Tighten the two bolts on the centering clamp
(8 mm wrench; 70.8–88.5 lb-in. [8–10 Nm] torque).
When the actuator closes, the damper rotates CCW
2. If the damper rotates clockwise (CW) to open, and the
90 degrees to fully close.
angle of the damper open-to-closed is 45 or 60 degrees: a. Manually open the damper fully (rotate clockwise). b. The actuator is shipped with the mechanical
end-limits set at 95 degrees. Adjust the two
mechanical end-limit set screws to provide the
desired amount of rotation. Adjust the two set
screws closer together to reduce the rotation travel. c. Tighten the two mechanical end-limit screws
(Phillips #2 screwdriver; (26.5–31 lb-in. [3.0–3.5
Nm] torque). d. Using the Declutch button, rotate the universal shaft
adapter fully clockwise. e. Mount the actuator to the VAV damper box and shaft.
f. Tighten the two bolts on the centering clamp
(8 mm wrench; 70.8–88.5 lb-in. [8–10 Nm] torque).
g. When the actuator closes, the damper rotates CCW
either 45 or 60 degrees to fully close.
3.
If the damper rotates counterclockwise (CCW) to open, and the angle of the damper open-to-closed is 90 degrees: a. Manually open the damper fully (rotate counter-
clockwise).
b. Using the Declutch button, rotate the universal shaft
adapter fully counterclockwise. c. Mount the actuator to the damper box and shaft. d. Tighten the two bolts on the centering clamp (8 mm
wrench; 70.8–88.5 lb-in. [8–10 Nm] torque). When
the actuator closes, the damper rotates CW
90 degrees to fully close.
4.
If the damper rotates counterclockwise to open, and the angle of the damper open-to-closed is 45 or 60 degrees: a. Manually open the damper fully (rotate counter-
clockwise). b. The actuator is shipped with the mechanical
end-limits set at 95 degrees. Adjust the two
mechanical end-limit set screws to provide the
desired amount of rotation. Adjust the two set
screws closer together to reduce the rotation travel. c. Tighten the two mechanical end-limit screws
(Phillips #2 screwdriver; (26.5–31 lb-in. [3.0–3.5
Nm] torque). d. Using the Declutch button, rotate the universal shaft
adapter fully counter-clockwise. e. Mount the actuator to the VAV damper box and shaft. f. Tighten the two bolts on the centering clamp
(8 mm wrench; 70.8–88.5 lb-in. [8–10 Nm] torque). g. When the actuator closes, the damper rotates CW
either 45 or 60 degrees to fully close.

Mount Controller

NOTE: The controller may be wired before mounting to a
panel or DIN rail.
Terminal blocks are used to make all wiring connections to the controller. Attach all wiring to the appropriate terminal blocks (see “Wiring” on page 5).
See Fig. 4–Fig. 5 for panel mounting dimensions. See Fig. 6 on page 4 for DIN rail mounting.
10-5/16 (262)
5-3/4 (146)
5-3/64
(128)
123456
NOTE: CONTROLLER CAN BE MOUNTED IN ANY ORIENTATION.
Fig. 4. Panel mounting - controller and actuator
dimensions in inches (mm) for PVB6436AS only.
8-5/16 (211)
6-29/64 (164)
2222222223
123456780
78
3
9
11 111111 109 234567
PANEL MOUNTING HOLE
(4X) 3/16 IN. (4.5)
333
33
33
34
123456780
1-55/64
(47)
9
DEPTH IS 2-1/ 4 (57 )
7/16 (11)
6-17/64
(159)
M29329
3 62-0310—01
Page 4
SPYDER® BACNET® PROGRAMMABLE, VAV/UNITARY CONTROLLERS
PANEL MOUNTING HOLE
(4X) 29/64 IN. (12)
PVB6438NS
2
5-3/4 (146)
5-3/64
(128)
2 2 2 2
2 2 1 2 3 4 5 6
7 8 0 9
2 2 3 3
3 3 3
3 3
1 2 3 4 5 6
3 3
3 4
7 8 0 9
5-3/64
(128)
PUB6438S
2
2 2 2 2
2 2 1 2 3 4 5 6
7 8 0 9
2 2 3 3
3 3 3
3 3
1 2 3 4 5 6
3 3
3 4
7 8 0 9
5-29/64
(139)
7 8
1 2 3 4 5 6
6-29/64 (164)
NOTE: CONTROLLER CAN BE MOUNTED IN ANY ORIENTATION.
6-27/32 (174)
1 1 1 1 1 1 1 1 1 2 1 1 0 9 2 3 4 5 6 7 8 0 9
5-29/64
(139)
DEPTH IS 2-1/ 4 (57 )
1 2 3 4 5 6
7 8
1 1 1 1 1 1 1 1 1 2 1 1 0 9 2 3 4 5 6 7 8 0 9
6-29/64 (164) 6-27/32 (174)
M29330
Fig. 5. Panel mounting - controller dimensions in inches (mm) for models PUB6438S and PVB6438NS only.
Panel Mounting
The controller enclosure is constructed of a plastic base plate and a plastic factory-snap-on cover.
NOTE: The controller is designed so that the cover does not
need to be removed from the base plate for either mounting or wiring.
The controller mounts using four screws inserted through the corners of the base plate. Fasten securely with four No. 6 or No. 8 machine or sheet metal screws.
The controller can be mounted in any orientation. Ventilation openings are designed into the cover to allow proper heat dissipation, regardless of the mounting orientation.
DIN Rail Mounting (PUB6438S and PVB6438NS)
To mount the PUB6438S or PVB6438NS controller on a DIN rail [standard EN50022; 1-3/8 in. x 9/32 in. (7.5 mm x 35 mm)], refer to Fig. 6 and perform the following steps:
1. Holding the controller with its top tilted in towards the DIN rail, hook the two top tabs on the back of the con­troller onto the top of the DIN rail.
2. Push down and in to snap the two bottom flex connec­tors of the controller onto the DIN rail.
TOP TABS
BOTTOM FLEX CONNECTORS
Fig. 6. Controller DIN rail mounting (models PUB6438S
and PVB6438NS).

Piping (PVB6436AS and PVB6438NS)

Air flow Pickup
For PVB6436AS and PVB6438NS, connect the air flow pickup to the two restrictor ports on the controller (see Fig. 7).
DIN RAIL
M16815
IMPORTANT
To remove the controller from the DIN rail, perform the following:
1. Push straight up from the bottom to release the top
tabs.
2. Rotate the top of the controller out towards you and
pull the controller down and away from the DIN rail to release the bottom flex connectors.
62-0310—01 4
NOTES:
Use 1/4 inch (6 mm) outside diameter, with a
0.040 in. (1 mm) wall thickness, plenum-rated 1219 FR (94V-2) tubing.
Always use a fresh cut on the end of the tubing
that connects to the air flow pickups and the restrictor ports on the controller.
Connect the high pressure or upstream tube to the plastic restrictor port labeled ( stream tube to the restrictor port labeled (
+), and the low pressure or down-
-). See labeling in
Fig. 7. When twin tubing is used from the pickup, split the pickup tubing a short length to accommodate the connections.
NOTES:
If controllers are mounted in unusually dusty or dirty
environments, an inline, 5-micron disposable air filter (
use 5-micron filters compatible with
Page 5
SPYDER® BACNET® PROGRAMMABLE, VAV/UNITARY CONTROLLERS
WARNING
M23556A
AIR FLOW PICKUP
ΔP
1 2 3 4 5 6
7 8
1 0 9 2 3 4 5 6 7 8 0 9
1 1 1 1 1 1 1 1 1 2 1
1 2 3 4 5 6
7 8 0 9
2
2 2
2 2 2 2
2 2 3 3
1 2 3 4 5 6
7 8 0 9
3 3 3
3 3
3 3
3 4
RESTRICTOR PORT
RESTRICTOR
PORT
CONNECTOR TUBING
pneumatic controls) pressure line (marked as
is recommended for the high
+
) connected to the air
flow pickup.
The tubing from the air flow pickup to the control-
ler should not exceed three feet (0.914 m). Any length greater than this will degrade the flow sensing accuracy.
Use caution when removing tubing from a con-
nector. Always pull straight away from the con­nector or use diagonal cutters to cut the edge of the tubing attached to the connector. Never remove by pulling at an angle.
Fig. 7. Air flow pickup connections (PVB6436AS and
PVB6438NS).

Wiring

All wiring must comply with applicable electrical codes and ordinances, or as specified on installation wiring diagrams. Controller wiring is terminated to the screw terminal blocks located on the top and the bottom of the device.
Do not connect the universal input COM
terminals, analog output COM terminals or the digital input/output COM terminals to earth ground.
The 24 Vac power from an energy limited Class II power source must be provided to the controller. To conform to Class II restrictions (U.S. only), the transformer must not be larger than 100 VA.
Fig. 8 depicts a single controller using one transformer.
IMPORTANT
Power must be off prior to connecting to or removing connections from the 24 Vac power (24 Vac/24 Vac COM), earth ground (EGND), and 20 Vdc power (20 Vdc) terminals.
IMPORTANT
Use the heaviest gauge wire available, up to 14 AWG (2.0 sq mm), with a minimum of 18 AWG (1.0 sq mm), for all power and earth ground wiring.
Screw-type terminal blocks are designed to accept up to one 14 AWG (2.0 sq mm) conductor or up to two 18 AWG (1.0 sq mm) conductors. More than two wires that are 18 AWG (2.0 sq mm) can be con­nected with a wire nut. Include a pigtail with this wire group and attach the pigtail to the terminal block.
IMPORTANT
Connect terminal 2, (the 24 Vac common [24 VAC COM] terminal) to earth ground (see Fig. 8).
NOTE: Unswitched 24 Vac power wiring can be run in the
same conduit as the BACnet MS/TP cable.
ΔP
2
2 2 2 2
2 2 1 2 3 4 5 6
7 8 0 9
2 2 3 3
3 3 3
3 3
1 2 3 4 5 6
3 3
3 4
7 8 0 9
NOTES:
Electrical Shock Hazard. Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring or making wiring connections, to prevent electrical shock or equipment damage.
For multiple controllers operating from a single
transformer, the same side of the transformer secondary must be connected to the same power input terminal in each controller. Controller configurations will not necessarily be limited to three devices, but the total power draw, including accessories, cannot exceed 100 VA when powered by the same transformer (U.S. only). The earth ground terminal (terminal 3) must be connected to a verified earth ground for each controller in the group (see Fig. 9 on page 6).
All loads on the controller must be powered by the
same transformer that powers the controller itself. A controller can use separate transformers for controller power and output power.
Keep the earth ground connection (terminal 3)
wire run as short as possible.
CONNECT POWER TO TERMINALS 1 AND 2
7 8
1 2 3 4 5 6
TRANSFORMER
COM
24 VAC
LINE VOLTAGE GREATER THAN 150 VAC
1
WHEN CONNECTIONG POWER TO THE SPYDER BACnet CONTROLLER, CONNECT THE COM LEG OF THE VAC SECONDARY CIRCUIT TO A KNOWN EARTH GROUND.
1
EARTH GROUND
OUTPUT DEVICE POWER
EARTH GROUND (TERMINAL 3)
1 1 1 1 1 1 1 1 1 2 1 1 0 9 2 3 4 5 6 7 8 0 9
M29684
Fig. 8. Power wiring details for one controller per
transformer.
More than one controller can be powered by a single transformer. Fig. 9 shows power wiring details for multiple controllers.
5 62-0310—01
Page 6
SPYDER® BACNET® PROGRAMMABLE, VAV/UNITARY CONTROLLERS
M29685
120/240
VAC
TRANSFORMER
OUTPUT DEVICE POWER
ΔP
1 2 3 4 5 6
7 8
1 0 9 2 3 4 5 6 7 8 0 9
1 1 1 1 1 1 1 1 1 2 1
1 2 3 4 5 6
7 8 0 9
2
2 2
2 2 2 2
2 2 3 3
1 2 3 4 5 6
7 8 0 9
3 3 3
3 3
3 3
3 4
COM
24 VAC
ΔP
1 2 3 4 5 6
7 8
1 0 9 2 3 4 5 6 7 8 0 9
1 1 1 1 1 1 1 1 1 2 1
1 2 3 4 5 6
7 8 0 9
2
2 2
2 2 2 2
2 2 3 3
1 2 3 4 5 6
7 8 0 9
3 3 3
3 3
3 3
3 4
EARTH GROUND (TERMINAL 3)
ΔP
1 2 3 4 5 6
7 8
1 0 9 2 3 4 5 6 7 8 0 9
1 1 1 1 1 1 1 1 1 2 1
1 2 3 4 5 6
7 8 0 9
2
2 2
2 2 2 2
2 2 3 3
1 2 3 4 5 6
7 8 0 9
3 3 3
3 3
3 3
3 4
EARTH GROUND (TERMINAL 3)
EARTH GROUND (TERMINAL 3)
CONNECT POWER TO TERMINALS 1 AND 2
EARTH GROUND
NOTE: Controller configurations are not necessarily limited
Communications
Each controller uses a BACnet MS/TP communications port. The controller’s data is presented to other controllers over a twisted-pair MS/TP network, which uses the EIA-485 signaling standard capable of the following baud rates: 9.6, 19.2, 38.4,
76.8 or 115.2 Kilobits per second (configured at global controller). The Spyder BACnet controllers are master devices on the MS/TP network. Each Spyder BACnet controller uses a high-quality EIA-485 transceiver and exerts 1/4 unit load on the MS/TP network.
Cabling should be selected that meets or exceeds the BACnet Standard which specifies the following: An MS/TP EIA-485 network shall use shielded, twisted-pair cable with characteristic impedance between 100 and 130 ohms. Distributed capacitance between conductors shall be less than 100 pF per meter (30 pF per foot). Distributed capacitance between conductors and shield shall be less that 200 pF per meter (60 pF per foot). Foil or braided shields are acceptable. The Honeywell tested and recommended MS/TP cable is Honeywell Cable 3322 (18 AWG, 1-Pair, Shielded, Plenum cable), alternatively Honeywell Cable 3251 (22 AWG, 1-Pair, Shielded, Plenum cable) is available and meets the BACnet Standard requirements (www.honeywellcable.com).
The maximum BACnet MS/TP network Bus segment length is 4,000 ft. (1,071 m) using recommended wire. Repeaters must be used when making runs longer than 4,000 ft. (1,071 m). A maximum of three repeaters can be used between any two devices.

Setting the MS/TP MAC address

The MS/TP MAC address for each device must be set to a unique value in the range of 0-127 on an MS/TP network segment (address 0, 1, 2, & 3 should be avoided as they are commonly used for the router, diagnostic tools, and as spare addresses). DIP switches on the Spyder BACnet controller are used to set the controller's MAC address.
62-0310—01 6
to three devices, but the total power draw, including accessories, cannot exceed 100 VA when powered by the same transformer (U.S. only).
Fig. 9. Power wiring details for two or more controllers per transformer.
To set the MS/TP MAC address of a Spyder BACnet controller:
1. Find an unused MAC address on the MS/TP network to which the Spyder BACnet controller connects.
2. Locate the DIP switch bank on the Spyder BACnet for addressing. This is labeled MAC Address
3. With the Spyder BACnet Controller powered down, set the DIP switches for the MAC Address you want. Add the value of DIP switches set to ON to determine the MAC address. See Table 2. Example, if only DIP switches 1, 3, 5, and 7 are enabled the MAC address would be 85 (1 + 4 + 16 + 64 = 85).
Table 2. DIP Switch Values For MS/TP MAC Address.
DIP 7654321
VAL UE 6432168421

Setting the Device Instance Number

The Device Instance Number must be unique across the entire BACnet system network because it is used to uniquely identify the BACnet devices. It may be used to conveniently identify the BACnet device from other devices during installation. The Spyder BACnet Controllers Device Instance Number is automatically set when it is added to a WEBStation-AX project. The Device Instance Number can be changed by the user, which may be necessary when integrating with a third party or when attempting to replace an existing controller and it is desired to maintain the existing Device Instance Number.
To edit the Device Instance Number using WEBs AX:
1. Identify an unused Device Instance Number on the BACnet Network, in the range of 0 - 4194302.
2. Open the Spyder Bacnet Device Mgr View a. Double click on the BacnetNetwork located in the
Nav tree. b. Select the Spyder Controller to be modified. c. Click on the Edit button. d. Enter an unused value in the Device Id field.
Page 7
SPYDER® BACNET® PROGRAMMABLE, VAV/UNITARY CONTROLLERS
WARNING
AO-1
COM
AO-2
AO-3
COM
UI-1
COM
UI-2
UI-3
COM
UI-4
UI-5
COM
UI-6
DI-1
DI-2
COM
DI-3
20V DC
DI-4
BAC –
BAC +
SHLD
EGND
24 VAC
24VAC COM
DO-1
COM
DO-2
DO-3
DO-4
DO-5
COM
DO-6
COM
M29331
ADD APPROPRIATE TERMINATION RESISTOR BETWEEN THE BAC+ AND THE BAC– TERMINALS.
BACnet MS/TP–
BAC+ SHLD
BAC–
NOTE: ALL BACnet MS/TP CONNECTIONS ARE MADE TO:
1 2 3 4 5 6
7 8
1 0 9 2 3 4 5 6 7 8 0 9
1 1 1 1 1 1 1 1 1 2 1
1 2 3 4 5 6
7 8 0 9
2
2 2
2 2 2 2
2 2 3 3
1 2 3 4 5 6
7 8 0 9
3 3 3
3 3
3 3
3 4
AO-1
COM
AO-2
AO-3
COM
UI-1
COM
UI-2
UI-3
COM
UI-4
UI-5
COM
UI-6
DI-1
DI-2
COM
DI-3
20V DC
DI-4
BAC –
BAC +
SHLD
EGND
24 VAC
24VAC COM
DO-1
COM
DO-2
DO-3
DO-4
DO-5
COM
DO-6
COM
1 2 3 4 5 6
7 8
1 0 9 2 3 4 5 6 7 8 0 9
1 1 1 1 1 1 1 1 1 2 1
1 2 3 4 5 6
7 8 0 9
2
2 2
2 2 2 2
2 2 3 3
1 2 3 4 5 6
7 8 0 9
3 3 3
3 3
3 3
3 4
AO-1
COM
AO-2
AO-3
COM
UI-1
COM
UI-2
UI-3
COM
UI-4
UI-5
COM
UI-6
DI-1
DI-2
COM
DI-3
20V DC
DI-4
BAC –
BAC +
SHLD
EGND
24 VAC
24VAC COM
DO-1
COM
DO-2
DO-3
DO-4
DO-5
COM
DO-6
COM
1 2 3 4 5 6
7 8
1 0 9 2 3 4 5 6 7 8 0 9
1 1 1 1 1 1 1 1 1 2 1
1 2 3 4 5 6
7 8 0 9
2
2 2
2 2 2 2
2 2 3 3
1 2 3 4 5 6
7 8 0 9
3 3 3
3 3
3 3
3 4
DO-7
DO-8
COM
DO-7
DO-8
COM
SBUS1
SBUS2
SBUS1
SBUS2
SBUS1
SBUS2
BACnet MS/TP+ SHIELD
BACnet MS/TP– BACnet MS/TP+ SHIELD
e. Select OK
3. Right Click on the Spyder Controller and select Actions > Write Device Instance to complete the update
Termination Resistors
Matched terminating resistors are required at each end of a segment bus wired across (+) and (-). Use matched precision resistors rated 1/4W ±1% / 80 - 130 Ohms. Ideally, the value of the terminating resistors should match the rated characteristic impedance of the installed cable. For example, if the installed MS/TP cable has a a listed characteristic impedance of 120 Ohm, install 120 Ohm matched precision resistors.
Shield Terminating
Following proper MS/TP cabling shield grounding procedures is important to minimize the risk of communication problems and equipment damage caused by capacitive coupling.
Capacitive coupling is caused by placing MS/TP cabling close to lines carrying higher voltage. The shield should be grounded on only one end of the MS/TP segment (typically the router end). Tie the shield through using the SHLD (terminal 4) on the Spyder BACnet Controller.
Sylk™ Bus
Sylk is a two wire, polarity insensitive bus that provides both 18 VDC power and communications between a Sylk-enabled sensor and a Sylk-enabled controller. Using Sylk-enabled sensors saves I/O on the controller and is faster and cheaper to install since only two wires are needed and the bus is polarity insensitive. Sylk sensors are configured using the latest release of the Spyder Tool for WEBPro and WEBStation.
Wiring Method
NOTE: When attaching two or more wires to the same termi-
Fig. 10. Termination modules (BACnet MS/TP daisy chain connections).
Electrical Shock Hazard. Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring, or making wiring connections, to prevent electrical shock or equipment damage.
nal, other than 14 AWG (2.0 sq mm), be sure to twist them together. Deviation from this rule can result in improper electrical contact (see Fig. 11).
Each terminal can accommodate the following gauges of wire: — Single wire: from 22 AWG to 14 AWG solid or stranded — Multiple wires: up to two 18 AWG stranded, with 1/4 watt
wire-wound resistor
Prepare wiring for the terminal blocks, as follows:
1. Strip 1/2 in. (13 mm) insulation from the conductor.
2. Cut a single wire to 3/16 in. (5 mm). Insert the wire in
the required terminal location and tighten the screw.
3. If two or more wires are being inserted into one terminal location, twist the wires together a minimum of three turns before inserting them (see Fig. 11).
4. Cut the twisted end of the wires to 3/16 in. (5 mm) before inserting them into the terminal and tightening
7 62-0310—01
the screw.
5. Pull on each wire in all terminals to check for good mechanical connection.
Page 8
SPYDER® BACNET® PROGRAMMABLE, VAV/UNITARY CONTROLLERS
1/2
(13)
STRIP 1/2 IN. (13 MM) FROM WIRES TO BE ATTACHED AT ONE TERMINAL.
1.
2.
TWIST WIRES TOGETHER WITH PLIERS (A MINIMUM OF THREE TURNS).
3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM)
BEFORE INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION.
M17207
Fig. 11. Attaching two or more wires at terminal blocks.

Controller Replacement (PVB6436AS)

For PVB6436AS controllers, which are hard-wired to an actuator, perform the following actions to replace the complete assembly (controller and actuator):
1. Remove all power from the controller.
2. Remove the two air flow pickup connections from the
3. Remove the terminal blocks.
4. Remove the old controller and actuator assembly from
5. Mount the new controller and actuator assembly (See
6. Reconnect the two air flow pickup tubes to the pressure
7. Replace the terminal blocks:
pressure sensor.
its mounting.
• Loosen the two bolts on the actuator clamp to release the actuator from the shaft.
• Remove the controller’s mounting screws.
• Gently pull the controller and actuator assembly straight out, until the assembly is clear of the actuator shaft.
“Installation” on page 2.).
sensor (See “Piping (PVB6436AS and PVB6438NS)” on page 4.).
• Insert each terminal block onto its alignment pins.
• Press straight down to firmly seat it.
• Repeat for each terminal block.
8. Restore power to the controller.

Controller Replacement (PVB6438NS)

Perform the following to replace the PVB6438NS controller:
1. Remove all power from the controller.
2. Remove the two air flow pickup connections from the
pressure sensor.
3. Remove the terminal blocks.
4. Remove the old controller from its mounting.
IMPORTANT
(FOR CONTROLLERS MOUNTED TO A DIN RAIL):
1. Push straight up from the bottom to release the top pins.
2. Rotate the top of the controller outwards to release the bottom flex connectors (see Fig. 6 on page 4).
5. Mount the new controller.
• See “Installation” on page 2.
6. Reconnect the two air flow pickup tubes to the pressure sensor (See “Piping (PVB6436AS and PVB6438NS)” on page 4.).
7. Replace the terminal blocks:
• Insert each terminal block onto its alignment pins.
• Press straight down to firmly seat it.
• Repeat for each terminal block.
8. Restore power to the controller.

Controller Replacement (PUB6438S)

Perform the following to replace the PUB6438S controller:
1. Remove all power from the controller.
2. Remove the terminal blocks.
3. Remove the old controller from its mounting.
IMPORTANT
(FOR CONTROLLERS MOUNTED TO A DIN RAIL):
1. Push straight up from the bottom to release the top
pins.
2. Rotate the top of the controller outwards to release
the bottom flex connectors (see Fig. 6 on page 4).
4. Mount the new controller (See “Installation” on page 2.).
5. Replace the terminal blocks:
• Insert each terminal block onto its alignment pins.
• Press straight down to firmly seat it.
• Repeat for each terminal block.
6. Restore power to the controller.
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark © 2009 Honeywell International Inc. 62-0310—01 M.S. 08-09
Loading...