Honeywell PRO TH4110D User Manual

Page 1
Installation Guide
TH4110D
Programmable Thermostat
Page 2
Product Application
This thermostat provides electronic control of 24 VAC single-stage heating and cool­ing systems, or 750 mV heating systems.
System Types
Warm air, hot water, high-efficiency furnaces, heat pumps, steam, gravi­ty
Heat only
Heat only with fan
Cool only
750 mV heating systems
Power Type
Battery power
Common wire
Common wire with battery backup
System Settings
Heat, Off, Cool
Fan Settings
Auto, On
Must be installed by a trained, experienced technician
Read these instructions carefully. Failure to follow these instructions can dam­age the product or cause a hazardous condition.
Check the ratings in this booklet to verify that this product is suitable for your application (see page 13).
Always test for proper operation after installation (see pages 8-9).
CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning installation.
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal.
® U.S. Registered Trademark. Patents pending.
Copyright © 2005 Honeywell International Inc. All rights reserved.
Page 3
PRO TH4110D Programmable Thermostat
1
Install the thermostat about 5 feet (1.5m) above the floor in an area with good air circulation at average temperature.
Do not install in locations where the thermostat can be affected by:
• Drafts or dead spots behind doors and in corners
• Hot or cold air from ducts
• Sunlight or radiant heat from appliances
• Concealed pipes or chimneys
• Unheated/uncooled areas such as an outside wall behind the thermostat
NO
NO
NO
Table of contents
Installation tips
IInnssttaallllaattiioonn
Pre-installation checklist ................2
Wallplate installation ......................3
Wiring..............................................4
Wiring diagrams ..............................5
IInnssttaalllleerr SSeettuupp
Fan operation settings ....................6
Battery installation ..........................7
Thermostat mounting ....................7
Installer setup..................................8
Installer system test ........................8
AAppppeennddiicceess
Adaptive Intelligent Recovery ......10
Compressor protection ................10
Quick reference to controls..........11
Quick reference to display............11
In case of difficulty ......................12
Accessories....................................13
Specifications ................................13
Page 4
Installation Guide
2
Pre-installation checklist
Package contents
Check to make sure your package includes the following items:
PRO TH4110D digital thermostat (wallplate attached to back)
Operating manual
Wall anchors and mounting screws (2 each)
AA alkaline batteries (2)
Quick reference card
Required tools & supplies
No. 2 Phillips screwdriver
Small pocket screwdriver
Drill
Drill bit (3/16” for drywall, 7/32” for plaster)
Hammer
Pencil
Electrical tape
Level (optional)
Page 5
PRO TH4110D Programmable Thermostat
3
Wallplate installation
Remove the wallplate from the ther­mostat as shown at left, then follow directions below for mounting.
1 Pull wires through wire hole.
2 Position wallplate on wall, level and
mark hole positions with pencil.
3 Drill holes at marked positions as
shown below, then tap in supplied wall anchors.
4 Place wallplate over anchors, insert
and tighten mounting screws.
5 Insert quick reference card in slot
in front of wall plate.
Grasp top and bottom of wallplate and pull to remove from thermostat.
Drill 3/16” holes for drywall. Drill 7/32” holes for plaster.
Wall anchors
Mounting screwsWire hole
Insert quick reference card after wallplate is mounted (see mounting instructions, below)
Page 6
Installation Guide
4
Wiring
1 Loosen screw terminals, insert
wires into terminal block, then re­tighten screws.
2 Push excess wire back into the
wall opening. Keep wires in shaded area as shown at left.
3 Plug the wall opening with non-
flammable insulation to prevent drafts from affecting thermostat operation.
Terminal Designations
WW
Heat relay.
YY
Compressor contactor.
GG
Fan relay.
OO
Heat pump changeover valve ener­gized in cooling.
RRcc
Cooling power. Connect to secondary side of cooling system transformer.
RR
Heating power. Connect to secondary side of heating system transformer.
BB
Heat pump changeover valve ener­gized in heating.
CC
Common wire from secondary side of cooling system transformer.
Terminal block
NOTES
R & Rc terminals
In single-transformer system, leave metal jumper in place between R & Rc. Remove metal jumper if two-transformer system
.
Heat pump systems
If wiring to a heat pump, use a small piece of wire (not supplied) to connect terminals W and Y.
C terminal
The C (common wire) terminal is optional when thermostat is powered by batteries.
Wire specifications
Use 18- to 22-gauge thermostat wire. Shielded cable is not required.
Keep wires in this shaded area
CAUTION: ELECTRICAL HAZARD. Can cause electrical shock or equipment damage. Disconnect power before wiring.
Wiring
Jumper
Page 7
PRO TH4110D Programmable Thermostat
5
Typical 1H/1C system: 1 transformer Typical 1H/1C system: 2 transformers
1 Power supply. Provide disconnect means and overload protection as required.
2 Factory-installed jumper. Remove for 2-transformer systems only.
3 Use either O or B terminals for changeover valve.
4 Use a small piece of wire (not supplied) to connect W and Y terminals.
5 Set fan operation switch to Heat Pump (see page 6) and configure for heat pump (see pg. 8).
6 Optional 24 VAC common connection.
Wiring diagrams
Typical 1H/1C heat pump system Typical heat-only system
Typical heat-only system with fan Typical cool-only system
Remove jumper
Page 8
Installation Guide
6
GGaass oorr OOiill::
For gas or oil heating systems, leave the fan operation switch in this factory-set position (This setting is for systems that control the fan in a call for heat.)
EElleeccttrriicc oorr HHeeaatt PPuummpp::
Change the switch to this setting for heat pump or electric heat systems. (This setting is for systems that allow the thermostat to control the fan in a call for heat, if a fan wire is connected to the
GG
terminal.)
Set fan operation switch
Fan operation settings
Page 9
PRO TH4110D Programmable Thermostat
7
AC Power
The thermostat can be powered by 24 VAC power, or by batteries.
To wire the thermostat for AC power, connect the common side of the cooling transformer to the “C” terminal as shown at left.
IImmppoorrttaanntt::
Remove R/Rc jumper for 2-transformer systems only. (See wiring diagram on page 5.)
Connect common side of transformer to “C” terminal
Install batteries in back of thermostat (optional if AC powered).
Battery Power
The thermostat can be powered by batteries alone or,if used with AC power, can provide backup power. During power interruptions the batteries will save time/day settings and power the display.
To Mount Thermostat
Align the 4 tabs on the wallplate with corresponding slots on the back of the thermostat, then push gently until the thermostat snaps in place.
Power options & mounting
Page 10
1
0
Installation Guide
8
1
5
9
13
14
15
System type
Heating cycle rate
(CPH: cycles/hour)
Compressor cycle rate (CPH)
Adaptive Intelligent Recovery
Temperature display
Compressor protection
0 Gas, oil or electric heat with air conditioning
1 Heat pump (5 minute compressor off time in heating and cooling)
5 For gas or oil furnaces of less than 90% efficiency
1 For steam or gravity systems 3 For hot water systems & furnaces of over 90% efficiency 9 For electric furnaces
[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
3 Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
1 On **See page 10
0Off
0 Fahrenheit
1 Celsius
5 Five-minute compressor off time **See page 10
[Other options: 0, 1, 2, 3 or 4-minute off time]
Setup Function Settings & Options
To begin, pr
ess and hold the and
buttons until the display changes
Function number
Press to change settings
Press to advance to next function
Pr
ess and hold to exit and save settings
Setting
Installer setup
Follow the procedure below to configure the thermostat to match the installed heating/cooling system, and customize feature operation as desired.
Setup
Installer system test
After completing the installer setup above, press the button again to begin a system test (see next page).
Press and hold both buttons
Page 11
PRO TH4110D Programmable Thermostat
9
10
0
Test
10
30
70
Heating system
Cooling system
Thermostat information
(for reference only)
0 Heat and fan turn off. 1 Heat turns on. Fan also turns on immediately if Fan Operation
Switch is set to Electric Heat/Heat Pump (see page 6).
0 Compressor and fan turn off. 1 Compressor and fan turn on.
71 Software revision number (major revisions) 72 Software revision number (minor revisions) 73 Configuration identification code (major) 74 Configuration identification code (minor) 75 Production configuration date code (week) 76 Production configuration date code (year)
System Test System Status
Installer system test
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection (minimum off time) is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.
System switch
System test number
System status
1 Set
SSYYSSTTEEMM
switch to Cool.
2 Press to turn on cooling system, then check system status (see table, below).
3 Press to turn off cooling system.
4 Set
SSYYSSTTEEMM
switch to Heat.
5 Press to turn on heating system, then check system status (see table, below).
6 Press to turn off heating system.
7 [Optional] Set
SSYYSSTTEEMM
switch to Off to display thermostat information (see table, below).
Press to display 71-76.
8Press and hold to terminate system test at any time.
Follow the procedure below to test the heating and cooling system.
Page 12
Installation Guide
10
Built-in compressor protection (Setup Function 15)
This feature helps prevent damage to the compressor in the air conditioning or heat pump system.
Damage can occur if the compressor is re­started too soon after shutdown.This feature forces the compressor to wait for a few minutes before restarting.
During the wait time, the message Cool On (or Heat On
if you have a heat pump) will flash on the display.When the safe wait time has elapsed, the message stops flashing and the compressor turns on.
Inside Set To
75
6:30
AM
75
Cool
On
°
°
Message flashes until safe restart time has elapsed
Wake
Wed
Adaptive Intelligent Recovery™(Setup Function 13)
Adaptive Intelligent Recovery eliminates guesswork when setting your schedule. It allows the thermostat to “learn” how long your furnace and air conditioner take to reach the temperature you want.
Just set your program schedule to the time you want the house to reach your desired temperature.The thermostat then turns on the heating or cooling at just the right time to reach your scheduled temperature at your scheduled time.
For example:Set the Wake time to 6 am, and the temperature to 70°.The heat will come on bef
or
e 6 am, so the temperature is 70° by the time you wake at 6.
Page 13
PRO TH4110D Programmable Thermostat
11
Quick reference to controls
Set: Press to set time/day/ schedule
Hold: Press to override programmed temperature control.
Run: Press to resume program schedule
System switch
Cool: Thermostat controls only the cooling system.
Heat: Thermostat controls only the heating system.
Off: Heating and cooling systems are off.
Fan switch On: Fan runs continuously. Auto: Fan runs only when heating
or cooling system is on.
Temperature adjustment
Inside Set To
75
6:30
AM
75
Wake
Cool
On
°
°
Replace Batt
Recovery
Quick reference to display screen
Current inside temperature
Low battery warning Adaptive Intelligent Recovery
Current program period
Wake/Leave/Return/Sleep
Temperature setting
System status (Heat On, Cool On)
Wed
Current day/time
Page 14
Installation Guide
12
In case of difficulty
If you have difficulty with your thermostat, please try the suggestions below. Most problems can be corrected quickly and easily.
Display is blank • Check circuit breaker and reset if necessary.
• Make sure heating & cooling power switches are on.
• Make sure equipment door is securely closed.
• If battery powered, make sure fresh AA alkaline batteries are installed.
Temperature settings do not change
Make sure heating and cooling temperatures are set to acceptable ranges:
• Heat: 40° to 90°F (4.5° to 32°C).
• Cool: 50° to 99°F (10° to 37°C).
Fan does not turn on in a call for heat
• Make sure the Fan Operation switch is set to the proper system.
Heating system does not respond (“Heat On” appears on screen)
• Check for 24 Vac at the equipment on the secondary side of the trans­former between power and common. If voltage is not present, check the heating equipment to find the cause of the problem.
• Check for 24 Vac between the heat terminal (W) and the transformer common. If 24 Vac is present, the thermostat is functional. Check the heating equipment to find the cause of the problem.
• Check for loose or broken wires between the thermostat and the heating equipment.
Cooling system does not respond (“Cool On” appears on screen)
• Check for 24 Vac at the equipment on the secondary side of the trans­former between power and common. If voltage is not present, check the cooling equipment to find the cause of the problem
• Check for 24 Vac between the cooling terminal (Y) and the transformer common. If 24 Vac is present, the thermostat is functional. Check the cooling system to find the cause of the problem.
• Check for loose or broken wires between the thermostat and the cooling equipment.
“Cool On” or “Heat On” is flashing
• Compressor protection timeout is engaged. Wait 5 minutes for the system to restart safely, without damage to the compressor.
“Heat On” is not displayed
• Set the System switch to Heat
, and set the temperature level above the
current room temperature.
“Cool On” is not displayed
• Set the System switch to Cool
, and set the temperature level below the
current room temperature.
Page 15
PRO TH4110D Programmable Thermostat
13
Accessories
Please contact your distributor to order accessories.
Cover plate assembly ............................................Part Number 50002883-001
(Used to cover marks left by old thermostats.)
Specifications
Temperature Ranges
• Heat: 40° to 90°F (4.5° to 32°C)
• Cool: 50° to 99°F (10° to 37°C)
Operating Ambient Temperature
• 32° to 120°F (0° to 48.9°C)
Shipping Temperature
• -20° to 120°F (-28.9° to 48.9°C)
Operating Relative Humidity
• 5% to 90% (non-condensing)
Physical Dimensions
• 3-13/16” H x 5-3/8” W x 1-1/4” D
• 97 mm H x 137 mm W x 32 mm D
Electrical Ratings
System Voltage (50/60Hz) Running Current
Heating 20-30 Vac 0.02-1.0 A
(Powerpile) 750 mV DC 100 mA DC
Cooling 20-30 Vac 0.02-1.0 A
Page 16
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
http://yourhome.honeywell.com
Automation and Control Solutions
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.
® U.S. Registered Trademark. © 2005 Honeywell International Inc. Patents pending. All rights reserved. 69-1849 • 06-2005
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario M1V 4Z9
Loading...