Honeywell MGC2-K, PolyGard 2 User Manual

PolyGard is a registered trademark of MSR GAMGC2-K_E_0320
Phone 0049(0)8531/9004-0 Fax: 0049(0)8531/9004-54 Specification subject to change without notice MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
PolyGard2 Multi Gas Controller MGC2-K
Controller for Analog Sensors / Honeywell Sensors
User Manual
Version 26.03 2020 en
User Manual - PolyGard®2 Multi-Gas-Controller MGC2-K Honeywell
Page 2
PolyGard® is a registered trademark of MSR GAMGC2-K_E_0320
Phone 0049(0)8531/9004-0 Fax: 0049(0)8531/9004-54 Specification subject to change without notice MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
1 Intended Use .......................................................................................................... 4
2 Functional Description ......................................................................................... 4
2.1 General ................................................................................................................................... 4
3 Installation ............................................................................................................. 5
3.1 Mounting Instructions .............................................................................................................. 5
3.2 Installation Work ..................................................................................................................... 5
4 Electrical Connection ........................................................................................... 6
4.1 Wiring ...................................................................................................................................... 6
4.2 Wiring Diagrams ..................................................................................................................... 7
5 Intended Use for the Display Unit ........................................................................ 8
6 Description ............................................................................................................ 8
7 Operation ............................................................................................................... 8
7.1 Function of the Keys and LEDs on the Keypad ...................................................................... 8
7.2 Setting / Changing of Parameters and Set Points .................................................................. 9
7.3 Code Levels ............................................................................................................................ 9
8 Menu Overview .................................................................................................... 10
8.1 Fault Management ................................................................................................................ 12
8.1.1 Error Memory .................................................................................................................... 12
8.1.2 System Messages and System Errors .............................................................................. 12
8.2 Alarm Status ......................................................................................................................... 13
8.3 Relay Status .......................................................................................................................... 13
8.4 Menu Measuring Values ....................................................................................................... 14
8.5 Display Parameters .............................................................................................................. 14
8.5.1 Software Version ............................................................................................................... 14
8.5.2 Language .......................................................................................................................... 15
8.5.3 Service Phone Number ..................................................................................................... 15
8.5.4 Customer Password .......................................................................................................... 15
8.5.5 Error Time Delay ............................................................................................................... 15
8.5.6 LCD Function .................................................................................................................... 16
8.6 Menu Relay Parameters ....................................................................................................... 16
8.6.1 Relay Mode ....................................................................................................................... 16
8.6.2 Relay Operation Mode ...................................................................................................... 16
8.6.3 Relay Function Static / Flashing........................................................................................ 17
8.6.4 Alarm Quantity................................................................................................................... 17
8.6.5 Horn Function .................................................................................................................... 17
8.6.6 External Override .............................................................................................................. 18
8.6.7 Delay Mode of Alarm Relay .............................................................................................. 19
8.6.8 Assignment to Fault .......................................................................................................... 19
8.6.9 Assignment to Maintenance Message .............................................................................. 19
8.7 MP Parameters ..................................................................................................................... 20
8.7.1 Activate – Deactivate MP .................................................................................................. 20
8.7.2 Selection of Gas Type and Measuring Range .................................................................. 20
8.7.3 Alarm Thresholds / Hysteresis .......................................................................................... 23
8.7.4 Delay for Alarm ON and/or OFF........................................................................................ 24
8.7.5 Average Overlay ............................................................................................................... 24
8.7.6 Latching Mode Assigned to Alarm .................................................................................... 24
8.7.7 MP Fault Assigned to Alarm .............................................................................................. 25
User Manual - PolyGard®2 Multi-Gas-Controller MGC2-K Honeywell
Page 3
PolyGard® is a registered trademark of MSR GAMGC2-K_E_0320
Phone 0049(0)8531/9004-0 Fax: 0049(0)8531/9004-54 Specification subject to change without notice MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
8.7.8 Alarm Assigned to Alarm Relay ........................................................................................ 25
8.7.9 MP Assigned to Analog Output ......................................................................................... 25
8.8 Menu System Parameters .................................................................................................... 26
8.8.1 System Information ........................................................................................................... 26
8.8.2 Maintenance Interval ......................................................................................................... 26
8.8.3 Average Function .............................................................................................................. 26
8.8.4 Power On Time ................................................................................................................. 27
8.8.5 Deadband .......................................................................................................................... 27
8.8.6 AO Function ...................................................................................................................... 28
8.8.7 Relay Multiplication ........................................................................................................... 29
8.9 Operating Data...................................................................................................................... 30
8.10 Test Function for Relays ....................................................................................................... 31
8.11 Test Function for Analog Output ........................................................................................... 32
8.12 Calibration ............................................................................................................................. 33
8.12.1 Zero Calibration of Analog Output..................................................................................... 34
8.12.2 Calibration of the Digital Sensors ...................................................................................... 34
8.12.3 Credit Menu ....................................................................................................................... 34
8.13 Setting RS-485 Address ....................................................................................................... 34
9 Commissioning ................................................................................................... 35
9.1 General Notes ....................................................................................................................... 35
9.2 Visual Inspection ................................................................................................................... 35
9.3 Selection Gas Type with Unit ................................................................................................ 35
10 Configuration and Parameter Cards .................................................................. 36
10.1 Configuration Card System Parameters ............................................................................... 36
10.2 Configuration Card Alarm Relays / Signal Outputs .............................................................. 36
10.3 Configuration Card MC2 of Analog Measuring Points .......................................................... 37
11 Routine Maintenance and Scheduled Testing .................................................. 38
11.1 Routine Maintenance ............................................................................................................ 38
11.2 Routine Testing ..................................................................................................................... 38
12 Technical Data MGC2 ......................................................................................... 39
13 EC – Declaration of Conformity ......................................................................... 40
14 Part Disposal ....................................................................................................... 41
15 Notes and General Information .......................................................................... 41
15.1 Installers’ Responsibilities ..................................................................................................... 41
15.2 Disclaimer ............................................................................................................................. 41
15.3 Warranty ............................................................................................................................... 42
15.4 Copyright Notice ................................................................................................................... 42
User Manual - PolyGard®2 Multi-Gas-Controller MGC2-K Honeywell
Page 4
PolyGard® is a registered trademark of MSR GAMGC2-K_E_0320
Phone 0049(0)8531/9004-0 Fax: 0049(0)8531/9004-54 Specification subject to change without notice MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
1 Intended Use
The PolyGard2 MGC2 is designed for detection and warning detection of toxic, combustible or dangerous atmosphere in many commercial and industrial applications.
The intended sites are all areas being directly connected to the public low voltage supply, e.g. residential, commercial and industrial ranges as well as small enterprises (according to EN50 082).
The PolyGard2 Multi Gas Controller MGC2 must not be used in potentially explosive atmospheres. The sensor must only be employed in areas within the environmental conditions specified in the Technical Data.
2 Functional Description
2.1 General
The Multi-Gas-Controller is designed for the connection of max. three analog sensors with 4-20 mA signal and eight Honeywell sensors.
The controller monitors the measured values and activates the alarm relays if the set local alarm thresholds for pre-alarm and main alert have been exceeded or if there are the alarm messages coming from the eight digital sensors via RS-485 communication.
The SIL 2 compliant self-monitoring function in the MGC2 activates the fault message in case of an internal error as well as in case of a fault at the 4-20 mA input / output current signals or if there is a communication error to the digital sensors.
Other options such as three-color status LED, warning buzzer, digital input for acknowledgment or test function ensure proper adaptation to the wide range of applications in gas detection technology.
User Manual - PolyGard®2 Multi-Gas-Controller MGC2-K Honeywell
Page 5
PolyGard® is a registered trademark of MSR GAMGC2-K_E_0320
Phone 0049(0)8531/9004-0 Fax: 0049(0)8531/9004-54 Specification subject to change without notice MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
3 Installation
Electronics can be destroyed by electrostatic discharge (ESD). Therefore, the installation work should be done only by persons connected to ground, e. g. with a wrist strap connected to ground or by standing on a conductive floor (acc. to DIN EN 100015).
3.1 Mounting Instructions
When choosing the mounting site please pay attention to the following:
Choose mounting location of the sensor according to the local regulations.
Mount the sensor at a location with minimum vibration and minimum variation in temperature (avoid
direct sunlight).
Avoid locations where water, oil etc. may influence proper operation and where mechanical damage might be possible.
Provide adequate space around the sensor for maintenance and calibration work.
Observe possible local instructions.
3.2 Installation Work
Assembly work must only be carried out under gas-free conditions.
Do not drill holes in the housing. Use only the providing know-outs.
Open housing cover.
Break out the required pre-embossed knockouts on the housing for cable glands and Sensor
Cartridge.
Cables are introduced from above.
The MGC2 Controller is fixed to the wall through the four marked mounting points at the back side of
the housing. These mounting points are accessible after opening the housing. See figure below.
The dimensions XX depend on the type and can be read on the back of the housing, it is115 mm.
The mounting points are covered by closing the cover at the end of the assembly.
Close the cover.
Installation of Controller:
XX
XX
User Manual - PolyGard®2 Multi-Gas-Controller MGC2-K Honeywell
Page 6
PolyGard® is a registered trademark of MSR GAMGC2-K_E_0320
Phone 0049(0)8531/9004-0 Fax: 0049(0)8531/9004-54 Specification subject to change without notice MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
4 Electrical Connection
Assembly work must only be carried out under gas-free conditions!
Consider static electricity instructions (ESD)!
4.1 Wiring
The technical requirements and regulations for wiring, electrical safety, as well as project specific and environmental and local conditions etc. must be observed when mounting.
We recommend the following cable types1:
Europe USA / Canada Power supply 230 V NYM-J 3 x 1.5 mm
2
14 AWG / 300 V
Alarm message 230 V (also possible together with power supply) NYM-J X x 1.5 mm
2
14 AWG / 300 V Signal message, bus connection, warning devices 24 V J-Y(St)Y 2x2 x 0.8 mm2 min. 300 V Possibly connected external analog transmitters J-Y(St)Y 2x2 x 0.8 mm
2
min. 300 V
1
The recommendation does not consider local conditions such as fire protection etc.
Use copper conductors only for the terminal is only for connection to copper wire.
Avoid any influence of external interferences by using shielded cables for the bus line, but do not
connect the shield.
Remove the cable isolation as short as possible. It is important to ensure that bare wires, e.g. wire shields do not come into contact with the mounted PCB (risk of short-circuit).
Low voltage wire and mains connected wire must be fixed separately by cable ties or similar, to secure against looseness.
Analog sensors are connected directly to the spring type terminals of the module. The correct polarity must be observed.
The alarm signals are available as voltage-free change-over contacts. If required, the voltage supply is available at the terminal L.
The exact position of the terminals for the sensors and alarm relays is shown in the connection diagrams.
User Manual - PolyGard®2 Multi-Gas-Controller MGC2-K Honeywell
Page 7
PolyGard® is a registered trademark of MSR GAMGC2-K_E_0320
Phone 0049(0)8531/9004-0 Fax: 0049(0)8531/9004-54 Specification subject to change without notice MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
4.2 Wiring Diagrams
Wiring Diagram Example
+24 V
GND
NC
X2 X3 X41 1 12 2 23 3 3
Multi Gas Controller MGC2 24 VDC
Bus_A
Bus_B
4 - 20 mA
GND
Field Bus Analog
Input
Digital
Output
1 13 32 24 4 5 6 7
X12
X13
BUS_A
24 VDC
AI_01
AI_02
AI_03
GND
Beacon
Horn
AO_01
BUS_B
GND
Analog Output
24 VDC
24 VDC
24 VDC
GND
GND
GND
4-20mA
4-20mA
4-20mA
1 1 12 2 23 3 3
X1 23 1
Power Supply
24 VDC
Relay
Alarm 1
Relay
Alarm 2
Relay
Fault
Relay Voltage
Max. 230
Relay drawn de-energized
Relays Mode = Energized (Alarm ON = Relay OFF)
Digital
Input
DI_1
DI_2
1 2 3
Digital
Input
GND
X11
User Manual - PolyGard®2 Multi-Gas-Controller MGC2-K Honeywell
Page 8
PolyGard® is a registered trademark of MSR GAMGC2-K_E_0320
Phone 0049(0)8531/9004-0 Fax: 0049(0)8531/9004-54 Specification subject to change without notice MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
Display Unit for Series MGC2-K
5 Intended Use for the Display Unit
The display is used as visual indication, operating, commissioning and calibration unit for gas detecting and measuring instruments of the series PolyGard®2 (PG2).
6 Description
The parameters, gas types, units, etc. specified in the description are only examples.
7 Operation
The complete configuration and service are made via operating keys in combination with the LCD display screen. Security is provided via four password levels against unauthorized intervention
Version for PG2 series
Operation via 6 buttons
7.1 Function of the Keys and LEDs on the Keypad
Exits programming, returns to the previous menu level.
Enters sub menus, saves parameter settings.
Scrolls up & down within a menu, changes a value.
Changes cursor position.
The status LEDs indicate the operating state.
Green: Continuous: = Normal operation Flashing: = Maintenance message
Yellow: Continuous: = Failure Slowly flashing: = Warming-up Fast flashing: = Special mode
Red: =Alarm
The backlight of the display changes from green to red when an alarm is active.
User Manual - PolyGard®2 Multi-Gas-Controller MGC2-K Honeywell
Page 9
PolyGard® is a registered trademark of MSR GAMGC2-K_E_0320
Phone 0049(0)8531/9004-0 Fax: 0049(0)8531/9004-54 Specification subject to change without notice MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
7.2 Setting / Changing of Parameters and Set Points
Open desired menu window. Code input field opens automatically, if required.
After input of valid code, the cursor jumps onto the first position segment to be changed.
Push the cursor onto the position segment, which has to be changed.
Set the desired parameter / set point with the keys.
Input of value finished.
Change further parameters in the same menu.
Save the changed value?
YES, and back to higher menu level.
NO, (previous value isn’t overwritten) and back to higher menu level.
7.3 Code Levels
All inputs and changes are protected by a four-digit numeric code (= password) against unauthorized intervention according to the regulations of all national and international standards for gas warning systems. The menu windows of status messages and measuring values are visible without entering a code.
The access to a code level is cancelled if no button is pushed within 15 minutes or if there is no data communication between display and basic board.
The code levels are classified in order of priority: Priority 1 has top priority.
Priority 1: (code not changeable)
Code level priority 1 is intended for the service technician of the installer to change parameters and set-points. This password allows working on all settings. For opening the parameter menus, you must first activate the service mode after code release.
Priority 2: (code not changeable)
This functionality isn’t available.
Priority 3: (customer password is settable)
Customer password is inactive in delivery state and is activated by entering a value. Same behaviour as priority 1 password, only changing the customer password is not possible.
Normally the code is only known by the service technician who has last changed it since it can be changed individually via priority 1.
Priority 4: (password 1234) (code not changeable)
Code level priority 4 allows the operator after activation of the operation mode “Service Mode” to read all parameters as well as all test functions of the alarm relays, analog outputs and LCD.
- Manual test function of the alarm relays (functional test of the connected actuators),
- Manual test function of the analog outputs (functional test of the connected actuators),
- Manual test function of the LCD (functional test of the LCD display and the LEDs).
User Manual - PolyGard®2 Multi-Gas-Controller MGC2-K Honeywell
Page 10
PolyGard® is a registered trademark of MSR GAMGC2-K_E_0320
Phone 0049(0)8531/9004-0 Fax: 0049(0)8531/9004-54 Specification subject to change without notice MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
8 Menu Overview
Menu operation is done via a clear, intuitive and logical menu structure. The operating menu contains the following levels:
Starting menu with indication of the device type if no MP (Measuring Point) is registered. Otherwise scrolling display of the gas concentrations of all registered sensors in 5-second intervals. If alarms are active, only the values of the sensors currently in alarm status will be displayed.
Main menu
Submenu 1 to 3
Power On Time of the basic device
Second counter counts down, when communication between display <> basic device is OK. In case of communication error, the count-down will stop.
Seconds indicator = 0
MGC2-K = Multi Gas Controller Kompakt
After about 5 seconds
“Warn-up Time” is displayed. As soon as the sensor warm-up period has expired, the measured value is displayed = measuring mode.
Starting menu Main menu Submenu 1
Reading and acknowledgement of errors See from point 8.1
Display of the alarm status of active alarms See from point 8.2
Display of the relay status See from point 8.3
Display of measuring values See from point 8.4
General display parameters without safety relations
See from point 8.5
Reading and change of the relay, measuring point
and system parameters as well as test and calibration functions
D1 CH4 % LEL
Warm-up Time
System Errors
Alarm Status
Relay Status
Measuring Values
Display Parameter
Power On Time 19s
Honeywell MGC2-K
Installation & Calibration
Service Mode OFF
User Manual - PolyGard®2 Multi-Gas-Controller MGC2-K Honeywell
Page 11
PolyGard® is a registered trademark of MSR GAMGC2-K_E_0320
Phone 0049(0)8531/9004-0 Fax: 0049(0)8531/9004-54 Specification subject to change without notice MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
The following menu items are only accessible in Service ON mode (password protected)
!! Service ON = Special mode = Fault message is active!!
See from point 8.6
See from point 8.7
See from point 8.8
See from point 8.9
See from point 8.10
See from point 8.11
See from point 8.12
See from point 8.13
Relay Parameter
MP Parameter
System Parameter
Operating Data
Addressing
Calibration
Relay Test Function
Analog Outputs Test Function
User Manual - PolyGard®2 Multi-Gas-Controller MGC2-K Honeywell
Page 12
PolyGard® is a registered trademark of MSR GAMGC2-K_E_0320
Phone 0049(0)8531/9004-0 Fax: 0049(0)8531/9004-54 Specification subject to change without notice MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
MP 1 Comm.Error 1 1T 2h 6‘
8.1 Fault Management
A pending fault activates the yellow LED (Fault).
The integrated fault management records the first 50 occurred faults with time stamps in the menu System Errors. The timestamp shows the days, hours and minutes that have elapsed since the fault has occurred.
Additionally, a record of the faults occurs in the “Error memory”, which can only be read and deleted by the service technician (code level 1 (3)).
8.1.1 Error Memory
The menu Error Memory in the main menu System Errors can only be opened via the code level priority 1.
In the error memory, the first 50 faults that have occurred and have already been acknowledged in the menu “Error Status” are listed for the service technician in a power failure safe way.
Attention:
This memory should always be read during maintenance, relevant faults should be tracked and entered in the service logbook, and finally the memory should be emptied.
8.1.2 System Messages and System Errors
The warning device includes a diagnostic module for the continuous monitoring of the relevant functions and parameters as well as a processor-independent watchdog. These features set the device into the safe mode "Fault" in case of an internal or external error. The following table shows all possible errors, possible causes, the related troubleshooting and the resulting device status.
Once the cause has been eliminated, the warning device restarts with the diagnostic mode on its own. It isn’t necessary to acknowledge the error message. In the event of an error, the error is output as plain text in the version with display instead of the measured value and in the Error status menu. In case of two or more errors, the value is output with a cumulative, bit-coded error code.
Error Type
Cause
Remedy
Fault Relay
Analog Output
Centr. Bus
Display
Error Code
Text Mess.
Error messages from MGC2
DP1-
Sensor element defective Replace
sensor
Error
< 2 mA
Error code is sent
0x8 001 h
Sensor Temperature < -25 °C > +60 °C
Ambient temp.
Temp.!
Error
< 2 mA
Error code is sent
0x8 002 h
Overtemp.
Internal
Replace device
Measured value processing
0x8 002 h
ADC error
RAM / ROM / µC error
0x8 008 h
CPU error EEPROM error
0x8 010 h
EE error
No response alarm relay
0x8 020 h
I/O error
Deviation of analog output signal < 5 % >
Short-circuit or Interruption at the analog output
Check wiring / load
Error
X mA
0x8 020 h
I/O error
Internal
Replace device
Communication error to sensor Sensor head not
fitted correctly
Check
Error
< 2 mA
0x9 000 h
Comm. error Internal
Replace Sensor
Hardware Watch Dog triggered
Internal, < system voltage, µC defect.
Replace device Error
< 1 mA
Comm. STOP
Reset
Reset
Operating voltage limits exceeded too high / too low
External
Check voltage
Error
< 2 mA
Comm. STOP
0x8 008 h
Tension Internal
Replace device
Maintenance due
Maintenance date reached
Perform maintenance
No effect 0x8 080 h*
Maintenance
User Manual - PolyGard®2 Multi-Gas-Controller MGC2-K Honeywell
Page 13
PolyGard® is a registered trademark of MSR GAMGC2-K_E_0320
Phone 0049(0)8531/9004-0 Fax: 0049(0)8531/9004-54 Specification subject to change without notice MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
AP 1 ’’A1
AP 1 Reset?
Check if no Gas present?
8.2 Alarm Status
Display of the currently pending alarms in plain text in the order of their arrival. Only those measuring points are displayed, where at least one alarm is active. Alarms in latching mode and the overrange message can be acknowledged in this menu (only possible if the alarm isn’t active any more). Alarm 1 and Alarm 2 are evaluated both by the sensor (alarm bit transmitted by communication) and by the locally set thresholds.
Symbol
Description
Function
AP 1
Measuring Point No.
Analog measuring point 1 = 1 - 3, where an alarm is pending
DP 4
Measuring Point No.
Digital measuring point 4 = 4 - 11, where an alarm is pending
‘A1 ‘‘A1
Alarm status
‘A1 = Alarm 1 active ‘‘A1 = Alarm 1 in latching mode, can be acknowledged
8.3 Relay Status
Reading of the current status of alarm relays. The actual relay status is displayed, depending on the relay mode (energized <> de-energized).
Selection of the alarm relay 1 – 5
Selection of the next alarm relay
Symbol
Description
Function
1
Alarm Relay
Alarm relay = 1 - 5
OFF
Relay Status
Deenergized
ON
Relay Status
Energized
Alarm Status
Relay Status
Relay 1 Status OFF
Loading...
+ 29 hidden pages