Honeywell PLAN Quick Start Manual

Page 1
SUNDIAL Y PLAN
Y PLAN
FEATURES
Independent control of
heating zone
hot water temperature
Pump & boiler switched off when space
and hot water temperature requirements
are satisfied
Both systems can operate at
the same time
T6360
ROOM THERMOSTAT
L641
CYLINDER THERMOSTAT
T
SUNDIAL SYSTEMS
V4073
3 PORT MID POSITION VALVE
IMER
OPTIONS
Programmable thermostat in
heating zone to provide
‘Best Practice’ system
Radiator thermostats may be fitted
to provide temperature control
in selected rooms/areas
CM Zone can provide wireless boiler
interlock for individual radiator control
APPLICATION
The Sundial Y Plan is designed to provide independent temperature control of both heating and domestic hot water circuits in fully pumped central heating installations.
Sundial Y Plan satisfies the minimum standard requirements of the Building Regulations Part L1 when used in conjunction with radiator thermostats and an automatic bypass valve.
For systems in dwellings with a floor area greater than 150m Sundial S Plan Plus must be used (see 2.3).
2
,
© Honeywell Control Products and Systems, Issue 10
2.5
Page 2
SUNDIAL Y PLAN
Installation
Valve - Water flow must be into port AB. Port A is the outlet connection to the radiator circuit and port B to the cylinder primary circuit.
Room Thermostat - The thermostat must be located where not subject to extraneous heat gains, direct sunlight or draughts.
Cylinder Thermostat - For optimum performance the thermostat should be located between cylinder from the floor.
1
/4and1/3up the
Time Control
Standard Practice
A 2 channel programmer to control the HW and heating zones.
Best Practice
A time switch to control HW and a programmable thermostat for the heating zone.
Bypass Valve - An automatic bypass valve should be fitted to the system to stop wastage of energy and prevent increased pressure within the circuit. Even though there is always one valve outlet open: the bypass will guard against the possibility of the heating circuit being isolated by radiator thermostats or operation of manual radiator valves.
Specification
Standard Sundial Y Plan comprises:
V4073A1039 : 22mm 3 port mid-position valve
L641A1039 : Strap-on cylinder thermostat
T6360B1028 : Room thermostat
ST9400C1000 : 7 day full programmer or
ST9400A1002 : 1 day full programmer
Automatic Bypass Valve
DU144A1001 : 22mm straight auto bypass valve
DU145 –3/4B : 22mm angled auto bypass valve
Optional components
Y6630D1007 : Wireless analogue room thermostat
T6620B1008 : DT200 digital room thermostat
Best Practice
CMT901A1044 : 1 day programmable thermostat
CMT907A1041 : 7 day programmable thermostat
Frost protection
T4360A1009 : Frost Thermostat
L641B1004 : Low limit Pipe Thermostat
Typical Wiring
Operation
Hot Water Only Requirement - On a demand for heat from the cylinder thermostat, the valve remains open to DHW only and the pump and boiler are switched on.
Heating Only Requirement - On a demand for heat from the room thermostat, the valve motor is energised so that the CH port only is opened and the pump and boiler are switched on.
HTG and HW Requirement - When both thermostats demand heat, the valve ball is positioned to allow both ports to be open and the pump and boiler switched on. When neither thermostat is demanding heat, the pump and boiler are off. The valve remains in the last position of operation whilst the mains is switched on.
Note: It is recommended that the 10 way Junction Box or Sundial Wiring Centre should be used to ensure first time, fault free wiring.
© Honeywell Control Products and Systems, Issue 10, 2.5
Loading...