Honeywell N10010, N05010 PRODUCT DATA

N05010/N10010
NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR
MODULATING AND FLOATING / 2-POSITION CONTROL
PRODUCT DATA
SPECIFICATIONS
Supply voltage 24 Vac/dc -15%/+20%, 50/60 Hz Nominal voltage 24 Vac/dc, 50/60 Hz
All values stated hereinafter apply to operation under nominal voltage conditions.
Power consumption N05010 5 VA / 2 W N10010 5 VA / 2 W
Control signal Modulating 0...10 V Floating/2-Position 24 Vac/dc
Ambient limits
Ambient operating limits -20...+60 °C (-5...+140 °F) Ambient storage limits -30...+80 °C (-22...+176 °F) Relative humidity 5...95%, non-condensing
Safety
This non-spring return direct-coupled damper actuator provides modulating and floating/2-position control for:
air dampers,
VAV units,
air handlers,
ventilation flaps,
louvers, and
reliable control for air damper applications with up to 1 m
/ (5 Nm) and 2 m friction-dependent).
2
(10 Nm) (seal-less damper blades; air
FEATURES
Declutch for manual adjustment
Adjustable mechanical end limits
Removable access cover for direct wiring
Mountable in any orientation
Function selection switch for selecting modulating or
floating/2-position control
Protection standard IP54 Protection class II as per EN 60730-1 Overvoltage category II
Lifetime
Full strokes 60000 Repositions 1.5 million
Mounting
Round damper shaft 8...16 mm Square damper shaft 6...13 mm; 45° steps Shaft length min. 41 mm
2
End switches (when included) Rating 5 A (resistive), 3 A (inductive) Triggering points 5° / 85°
Torque rating 5 Nm / 10 Nm
Runtime for 90°
mod. (dc / 50/60 Hz ac) 90 sec floating (dc / 60 Hz ac) 90 sec floating (50 Hz ac) 110 sec
Rotation stroke 95° ± 3°
Dimensions see "Dimensions" on page 8
Weight (without cables) 450 g
Noise rating 35 dB(A) max. at 1 m
® U.S. Registered Trademark EN0B-0478GE51 R0408 Copyright © 2008 Honeywell Inc. • All rights reserved
N05010/N10010 DAMPER ACTUATORS FOR MODULATING AND FLOATING/2-POSITION CONTROL
PRODUCT IDENTIFICATION SYSTEM
Contents of Package
The delivery package includes the actuator, parts 1 through 6
N = non-spring return S = spring return
(see Fig. 2), plus two cable grommets and a spare cable grommet.
05 = 5 Nm 10 = 10 Nm
equipped with two
end switches
RUN MODES
The function selection switch (see Fig. 3) can be used to
W
SmartAct
N
5
0
0-0
010 = modulating + floating 24 = 24 V floating + ON/OFF 230 = 230 V ON/OFF
S
+ ON/OFF
21
Fig. 1. Product Identification System
place the actuator into any one of three different modes:
Service/Off;
the floating/2-position run mode ("Dir" for CCW-closing
dampers or "Rev" for CW-closing dampers); and
the modulating run mode.
modulating
MODELS
order no. supply voltage end switches torque
N05010 -­N05010-SW2 2 N10010 -­N10010-SW2
24 Vac/dc
2
BASIC FEATURES
1
2
N05010
3
2...10 V
0...10 V Dir
4
5
6
Fig. 2. Setting units and control elements
Legend for Fig. 2:
1) Universal shaft adapter
2) Mechanical end limits
3) Declutch button
4) Function selection switch
5) Removable access cover
6) Anti-rotation bracket
Service/Off
Rev
10...0 V
10...2 V
5 Nm
10 Nm
Power-Off Behavior
If power is removed, the shaft adapter remains in position.
Service/Off
If the function selection switch is set to the "Service/Off" position, then all rotary movement is cancelled, and all control signals are ignored, thus allowing the actuator to be manually operated safely.
Floating/2-Position Run Mode
Without Feedback Signal
If, however, the function selection switch has been set to one of the two floating/2-position control settings – but the actuator has not been wired for a feedback signal (see Fig. 12 and Fig. 13) – then as soon as operating power is applied, the shaft adapter will run according to the control signals applied.
With Feedback Signal
If the function selection switch has been set to one of the two floating/2-position control settings – and if the actuator has been wired for a feedback signal (see Fig. 12 and Fig. 13) – then as soon as operating power is applied, the shaft adapter will likewise run first completely counterclockwise and then completely clockwise (see also section "Adaption"), after which it will run according to the control signals applied.
Modulating Run Mode
If the function selection switch has been set to one of the four modulating control settings – and if the actuator is wired correspondingly (see Fig. 11) – then as soon as operating power is applied, the shaft adapter will run first completely counterclockwise and then completely clockwise (see also section "Adaption"), after which it will run according to the control signals applied.
floating/2-position
2...10 V
0...10 V
Dir
Service/Off
Rev
10...0 V
10...2 V
2...10 V
0...10 V
Dir
Service/Off
Rev
10...0 V
10...2 V
Fig. 3. Function selection switch
Service/Off
2...10 V
0...10 V
Service/Off
Rev
10...0 V
10...2 V
Dir
EN0B-0478GE51 R0408
2
N05010/N10010 DAMPER ACTUATORS FOR MODULATING AND FLOATING/2-POSITION CONTROL
Table 1 describes, for the floating mode, the shaft adapter behavior ("stops," rotates "CCW," or rotates "CW") in dependence upon the control signals applied to terminals 3 and 4 and upon the function selection switch setting.
Table 2 describes, for the 2-position mode, the shaft adapter behavior ("stops," rotates "CCW," or rotates "CW") in dependence upon the control signals applied to terminals 3 and 4 and upon the function selection switch setting.
Table 1. Shaft adapter behavior in the floating mode
control signal at switch settings
terminal 3 terminal 4 0[2]...10 V Dir Service / Off Rev 10...0[2] V
open open open 24 Vac/dc
24 Vac open
Table 2. Shaft adapter behavior in the 2-position mode
control signal at switch settings
terminal 3 terminal 4 0[2]...10 V Dir Service / Off Rev 10...0[2] V
24 Vac open 24 Vac 24 Vac/dc
Table 3. Shaft adapter behavior in the modulating mode
control signal at switch settings
terminal 3 terminal 4 0[2]...10 V Dir Service / Off Rev 10...0[2] V
open
< min. control signal plus 0.24 V
between min. control signal plus 0.24 V
and max. control signal minus 0.24 V
> max. control signal minus 0.24 V
open
24 Vac/dc
open
24 Vac/dc
open
24 Vac/dc
open
24 Vac/dc
Table 3 describes, for the modulating mode, the shaft adapter behavior ("stops," rotates "totally CCW," rotates "totally CW," runs to "proportional" position, or runs to "50%" of max. stroke) in dependence upon the control signals applied to terminals 3 and 4 and upon the function selection switch setting.
-- stops stops stops --
-- CCW stops CW --
-- CW stops CCW --
-- CW stops CCW --
-- CCW stops CW --
totally CCW -- stop -- totally CCW
50% -- stop -- 50%
totally CCW -- stop -- totally CW
50% -- stop -- 50%
proportional -- stop -- proportional
50% -- stop -- 50%
totally CW -- stop -- totally CCW
50% -- stop -- 50%
final position of shaft adapter (% of max. stroke)
100
50
0
upper dead band (9.76 to 10.0 V)
range of proportional
actuator movement
(0.24 to 9.76 V)
lower dead band (0 to 0.24 V)
00.24
control signal (V)
5.0 10.09.76
Fig. 4. Final shaft adapter position in dependence upon
control signal (example function selection switch setting
of 0...10 V)
100
50
0
0
current position of shaft adapter (% of max. stroke)
feedback signal (V)
510
Fig. 5. Feedback signal in dependence upon current
position of shaft adapter (example function selection
switch setting of 0...10 V)
3 EN0B-0478GE51 R0408
Loading...