Honeywell L4064B, L4064R Installation Instructions Manual

69-0115-11
L4064B, L4064R
WARNING
CAUTION
Universal Combination Fan and Limit Controllers
INSTALLATION INSTRUCTIONS

APPLICATION

INSTALLATION

These combination warm air fan and limit controllers are suitable for various types of forced air heating systems. The controllers have 2 switches; one which opens the limit circuit if the plenum temperature exceeds the preset safety limit; it resets automatically. The other switch turns the fan on and off. The fan is turned on and off according to plenum temperature. The L4064R has a special high temperature range suitable for gravity heating systems. All models may be used as limit controllers by wiring only the limit side. Limit contacts are suitable for both line voltage and low voltage. For low voltage applications, the brass jumper must be removed.

OPERATION

As the plenum temperature rises, the coiled bimetal sensing element of the control warps and mechanically makes the fan contacts (at the FAN ON temperature setting). During normal operation, the call for heat ends before the LIMIT setting is reached and the fan contacts break as the plenum temperature falls and the FAN OFF setting is reached. If the call for heat continues until the temperature in the plenum rises to the LIMIT setting, the bimetal element will mechanically break the limit contacts and de-energize the heating control circuit.

When Installing this Product...

1. Read these instructions carefully. Failure to fol-
low them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and
on the product to make sure the product is suit­able for your application.
3. Installer must be a trained, experienced service
technician.
4. For 230 VAC application, use of double insu-
lated cable is required.
5. After installation is complete, check out product
operation as provided in these instructions.
If limit switch is used on a low voltage circuit, failure to remove brass jumper can cause electrical shock hazard and/or damage to low voltage controls.
1. Disconnect power supply before connecting
wiring to prevent electrical shock or equipment damage.
2. When connecting cable or conduit to control,
avoid straining the control case.
Follow furnace or burner manufacturer’s instructions, if available. Maximum element temperature is: L4064B—350 ºF (177 ºC). L4064R—250 ºF (121 ºC) above limit setting. Maximum switch temperature is: L4064B,R—190 ºF (88 ºC).
L4064B, L4064R UNIVERSAL COMBINATION FAN AND LIMIT CONTROLLERS
M31164
FURNACE PLENUM
REQUIRE 1-9/16 IN [39.7mm] DIAMETER HOLE IN PLENUM
32612A SWIVEL BRACKET
Do not exceed the following electrical ratings (amper es):
Table 1. Electrical Ranges
120 Vac 240 Vac
FAN LIMIT FAN LIMIT
Full Load 14 8 7 4
Locked Rotor
Pilot Duty: 2 A at 24 Vac; 0.25 A at 0.25 to 12 Vdc. Maximum Combined Connected Load: 2000 VA. 75 ºC (167 ºF) (min.) field wiring required. Wiring must conform to NEC Class 1 requirements.
Approval
—IP20 compliance — Classified as TR/TW — CSA certified file #095329 — UL listed file #MP3387 — DVGW certified ID-No:
CE-0085BM0320 for B type only
84 48 42 24

LOCATION

If this is a replacement installation, locate the L4064 in the same location as the control being replaced. Sensing tube length should be same as old control. If this is a new installation, the element should be installed only by a trained, experienced service technician according to the furnace manufacturer’s instructions. The element must not touch any internal part of the furnace.
NOTE: The electrical rating is at maximum switch
temperature of 190 ºF (88 ºC). If plenum sur­face temperature exceeds 190 ºF (88 ºC), heat insulating material or mounting bracket must be used.

Surface Mounting (Fig. 1)

L4064B—Hole in plenum should be just large enough to accommodate the 3/4 in.(19.1 mm) diameter element tube. A 13/16 in. (20.6 mm) diameter hole is recommended.
1. Remove cover by removing screw, squeezing
sides and pulling off. Insert element in plenum and mark location of mounting holes. Make sure the case is snug against the plenum before marking the mounting holes.
2. Punch or drill holes for mounting screws.
3. Place insulation between plenum and case
if necessary.
4. Fasten controller securely with mounting
screws.

Swivel Mounting (Fig. 2)

The L4064B and L4064R may be swivel-mounted. The swivel bracket requires a 1-9/16 in. (39.7 mm) hole in the plenum.
1. Use bracket as a template to make the location
of mounting holes in plenum. Drill or punch holes for mounting screws.
2. Fasten the bracket in place with furnished
screws. Start the screws but do not tighten.
3. Insert element tube through bracket, straighten
controller, and fasten. Tighten the mounting screws securely. It may be necessary to rotate the bracket to tighten all screws securely.

MOUNTING

The devices may be mounted as follows: L4064B — Swivel mount L4064R — Swivel mount
FURNACE PLENUM
ADD HEAT INSULATING MATERIAL IF NEEDED
M31163
Fig. 1. Surface mounting for L4064B requires a
69-0115—11 2
13/16 in. (20.6 mm) hole.
Fig. 2. Swivel mounting requires a 1-9/16 in.
(40 mm) diameter mounting hole for element
insertion.
Loading...
+ 2 hidden pages