Honeywell L4064B Installation Manual

Page 1
SUPER TRADELINE L4064B
ADD HEAT INSULATING MATERIAL IF
NEEDED
FURNACE
PLENUM
11,219
Universal Combination Fan and Limit Controllers
APPLICATION
The L4064B controls the on and off operation of the heating unit’s fan motor and provides high limit control of the main burner. It is suitable for all types of forced air heating systems. The L4064B’s bimetal sensing element turns fan on and off according to plenum temperature. The L4064B has a manual switch to provide continuous fan operation, mounting adapters for replacing competitive devices, adapters for wiring convenience, and a strain relief bushing for protecting the wiring from damage due to field abuse. Limit contacts are suitable for line voltage, low voltage or millivoltage circuits. The fan-on timing can vary depending on applied voltage and switch ambient.
INSTALLATION When installing this product...
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
WARNING
!
Failure to remove brass jumper, if limit switch is in low voltage circuit, can cause electrical shock hazard or damage low voltage controls.
CAUTION
!
1. Disconnect power supply before connecting wiring to prevent electrical shock or equipment damage.
2. When connecting cable or conduit to control, avoid straining the control case.
Follow furnace or burner manufacturer’s instructions, if available. The L4064B has a maximum switch temperature of 190
O
F (88OC), maximum element temperature of 350OF (177OC). Do not exceed these temperatures or the following electrical ratings (amperes):
240 Vac
FAN
7 4
42
54
Full Load
Locked Rotor
120 Vac
FAN LIMIT
LIMIT
8
14
84
48
Pilot Duty: 2 A at 24 Vac; 0.25 A at 0.25 to 12 Vdc. Maximum Combined Connected Load: 2000 VA.
O
C (167OF) (min.) field wiring required. Wiring must
75 conform to NEC Class 1 requirements.
LOCATION
If this is a replacement installation, locate the L4064 in the same location as the control being replaced. Sensing tube length should be same as old control. If this is a new installation, the element should be installed only by a trained, experienced service technician according to the furnace manufacturer’s instructions. The element must not touch any internal part of the furnace.
NOTE:
The electrical rating is at maximum switch temperature of 190 temperature exceeds 190 insulating material or a mounting bracket must be used.
MOUNTING
The device may be mounted either on the plenum surface or with a bracket (rigid or swivel).
SURFACE MOUNTING
Hole in plenum should be just large enough to accommodate the 3/4 in. (19.1 mm) diameter element tube, Fig. 1. For adequate clearance, a 13/16 in. (20.6 mm) diameter hole is reccomended.
1. Remove cover by squeezing sides and pulling off. Insert element in plenum and mark location of mounting holes. Make sure the case is snug against the plenum before marking the mounting screws.
2. Punch or drill holes for mounting screws.
3. Place insulation between plenum and case if necessary.
4. Fasten controller securely with mounting screws.
Fig. 1 - Surface mounting requires a hole 13/16 in. (20.6 mm) diameter for element insertion.
PRODUCT DATA
O
F (88OC). If plenum surface
O
F (88OC), heat
Page 2
SWIVEL MOUNTING
50
100
150
200
250
ON/OFF
FAN LIMIT
DO NOT ROTATE HOLD
DIAL WHEN SETTING
CAUTION
FAN
LIMIT
PUSH MAN PULL AUTO
REMOVABLE
BRASS
JUMPER
STANDARD WIRE PUSH IN CONNECTORS
(4)
FEMALE
RECEPTACLE FOR
CONNECTION OF
1/4 IN. (6.4 MM)
MALE SPADE
TERMINAL (4)
WIRING GUARD
TO RELEASE
STANDARD WIRE -
PUSH SCREW DRIVER IN AND PULL WIRE OUT
STANDARD
WIRE TO
CONTROLLED
EQUIPMENT
LEADWIRE WITH 1/4
IN. (6.4 MM) MALE SPADE TERMINAL
(FORCE SPADE TO
BOTTOM OF CAVITY)
11,204B
L4064 may also be swivel-mounted. The swivel bracket requires a 1-9/16 in. (39.7 mm) hole in the plenum (Fig. 2).
1. Use bracket as a template to mark the location of mounting holes in plenum. Drill or punch holes for mounting screws.
2. Fasten the brackets in place with furnished screws. Start the screws but do not tighten.
3. Insert element tube through bracket, straighten controller, and fasten. Tighten the mounting screws securely. It may be necessary to rotate the bracket to tighten all screws securely.
5. Insert element tube with adapter through bracket, straighten controller and fasten. Tighten setscrew. Be sure screw strikes bushing not coiled bimetal sensing element.
FURNACE
PLENUM
32612A SWIVEL
BRACKET
REQUIRE 1-9/16
IN. (39.7 MM)
DIAMETER HOLE
IN PLENUM
FURNACE
PLENUM
Fig. 2 - Swivel mounting requires a 1-9/16 in. (39.7 mm) diameter mounting hole for element insertion.
RIGID BRACKET MOUNTING
WARNING
!
When mounting control on bracket, setscrew must
not
strike tube frame
sensing element to prevent
bypassing the safety limit function.
L4064 may be mounted using a rigid bracket. The rigid bracket requires a hole 13/16 in. (20.6 mm) diameter for element insertion (Fig. 3).
1. Use bracket as a template to mark the location of mounting holes in plenum. Drill or punch holes for mounting screws.
2. Fasten bracket in place with furnished screws. Tighten the screws securely.
3. Insert element tube through bracket, straighten controller and fasten by tightening setscrew. Be sure screw strikes tube frame and does not strike sensing element.
4. For replacement installations with existing 1 in. (25.4 mm) diameter hole. SUPER TRADELINE models are supplied with split steel bushings and wire snap ring. Follow the instructions below for using the steel bushing adapter.
STEEL BUSHING ADAPTER
1. Insert one-half of the split steel bushing (Fig. 4), through the wire ring. It may be necessary to spread the ring slightly.
2. Insert the other half of the steel bushing into the ring making sure tabs and ears are at the same ends.
3. Place bushing assembly on element, ear end first.
4. Holding bushing at seams, push firmly to the control end of element.
11,220
SETSCREW
RIGID BRACKET
11,205
Fig. 3 - Rigid bracket mounting requires a hole 13/ 16 in. (20.6 mm) diameter for element insertion.
TAB
L4064 HELICAL ELEMENT
EAR
2696A
Fig. 4 - Using SUPER TRADELINE adapter.
WIRING
Disconnect power supply before beginning installation to prevent electrical shock or equipment damage. All wiring must comply with local electrical codes and ordinances or in the absence of local codes with the National Electrical Code ANSI C1-1981-NFPA 70. Follow burner or furnace manufacturer’s instructions if available; otherwise, see Fig. 10 and proceed as follows.
IMPORTANT
The brass jumper is the breakaway type. It must be removed when the limit is used in the low voltage circuit. To remove jumper, break with a needlenose pliers and remove completely, Once removed, it is not replaceable. See Fig. 8 for location.
The slotted knockouts on the bottom of the case and the strain relief bushing are provided to simplify the installation procedure and to protect the wires.
1. To remove the slotted knockout(s), use a needlenose pliers as shown in Fig. 5 and pull straight down.
2. If cable is used, we recommend using a strain relief bushing in the knockout (Fig. 6). Pass the wires through bushing before connecting.
2 69-0117-3
Page 3
Fig. 5 - Removing slotted knockouts.
50
100
150
200
250
ON/OFF
FAN LIMIT
DO NOT ROTATE HOLD
DIAL WHEN SETTING
CAUTION
FAN
LIMIT
PUSH MAN PULL AUTO
REMOVABLE
BRASS
JUMPER
STANDARD WIRE PUSH IN CONNECTORS
(4)
FEMALE
RECEPTACLE FOR
CONNECTION OF
1/4 IN. (6.4 MM)
MALE SPADE TERMINAL (4)
WIRING GUARD
TO RELEASE
STANDARD WIRE -
PUSH SCREW DRIVER IN AND PULL WIRE OUT
STANDARD
WIRE TO
CONTROLLED
EQUIPMENT
LEADWIRE WITH 1/4
IN. (6.4 MM) MALE SPADE TERMINAL
(FORCE SPADE TO
BOTTOM OF CAVITY)
11,204B
Fig. 6 - Insert strain relief bushing.
3. Refer to the following section for type of wiring
connections (standard wire push-in terminals or female receptacle).
WIRING CONNECTIONS
When connecting cable or conduit to this controller, use care to avoid strain on the control case. Connections can be made to standard wire push-in terminals or female receptacles for 1/4 in. (6.4 mm) male flag connectors on both the fan and limit switches (Fig. 8).
FOR STANDARD WIRE PUSH-IN TERMINALS Connect wires to the terminals as follows:
1. Use Nos. 14,16, or 18 solid wire or Nos. 14 or 16 stranded wire, depending on electrical requirement.
2. Strip insulation from wires the distance shown by the strip gauge on the controller.
3. Solid wire may be inserted directly into the terminal holes. If stranded wire is used, insert a small screwdriver into the slot next to the terminal. Push screwdriver in and hold while inserting wire into terminal (Fig. 8). Remove screwdriver. If stranded wire is solder-dipped, it can be pushed directly into
terminal holes.
Fig. 7 - Closing the strain relief bushing.
FOR FEMALE RECEPTACLES ­ It is recommended that the female receptacles be used for wiring accessory equipment; i.e., electronic air cleaner, humidifier, etc. Connect wires to the receptacles as follows:
1. Use Nos. 14 to 18 size wire, depending on electrical requirement.
2. Attach 1/4 in. (6.4 mm) male flag connector to each wire. Two male connectors with leadwires are supplied.
3. Push male flag connector directly into the female receptacle. Make sure that the flag is forced to the bottom of cavity and wire is in the channel (Fig. 8).
IMPORTANT
Make certain all wires are clear of rotating scaleplate.
Fig. 8 - Location of wiring connections.
3
69-0117-3
Page 4
11,221
ADD HEAT
INSULATING
MATERIAL IF
NEEDED
FURNACE
PLENUM
11,219
A
L4064
LIMIT
FAN
SIDE
SIDE
JUMPER
REMOVED
(HOT)
L1
POWER
1
SUPPLY
L2
1
ADD DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED
TO CONTROL LOW VOLTAGE EQUIPMENT
2
3
TO CONTROL LINE VOLTAGE
FAN
MOTOR
2
Fig. 9 - A: Limit in low voltage circuit. B: Limit in line voltage circuit. C: Limit in line voltage circuit without jumper.
SIDE
L4064
FAN
LIMIT SIDE
FAN
MOTOR
B
SETTINGS AND ADJUSTMENTS
CAUTION
!
When adjusting the fan and limit set point levers (Fig. 10), hold the scalepale dial to keep it from turning and straining the sensing element. Move each indicator lever to the control point recommended by the burner or furnace manufacturer. Use gentle finger pressure.
FAN SETTING ADJUSTMENT
1. Move the FAN OFF lever to the temperature at which the fan is to stop to prevent circulation of cool air.
2. L4064B - Move the FAN ON lever to the temperature at which the fan is to come on.
MANUAL FAN SWITCH
For constant fan operation, push the FAN switch button in. For fan to cycle automatically, pull button out.
LIMIT SETTING ADJUSTMENT
These controllers have a limit stop which prevents the limit indicator lever from being adjusted beyond the equipment manufacturer’s specifications.
1. Push the small end of Limit Adjust Tool (196722) through hole in scaleplate (located at caution marking) to depress the stop disc not more than 1/16 in. (1.6 mm) to release stop lock (Fig. 10). Stop disc is on back of scaleplate.
2. While depressing the stop disc, insert the long end of Limit Adjust Tool next to limit stop (Fig. 10) and move the stop to desired setting.
If the L4064 is a replacement control, high limit stop setting should be the same as that of the control being replaced.
(Move stop clockwise to lower the setting, counterclockwise to raise it.) Then remove the limit stop adjust tool.
3. Set the LIMIT OFF lever to the temperature at which the high limit switch is to open to stop the burner. If the high limit stop has been properly set, the LIMIT OFF lever should be as high as the stop permits.
Automation and Control Solutions
Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN, 55422 www.honeywell.com/building/components 07/06 RB © Honeywell 2006 Printed in Canada 69-0117-3
C
FAN
MOTOR
FAN SIDE
L4064
LIMIT SIDE
JUMPER
REMOVED
120V
HEATING SYSTEM
TRANSFORMER
24V
JUMPER IN
PLACE
3
POWER SUPPLY
(HOT)
(HOT)
1
L1
L1
POWER
1
SUPPLY
L2
L2
OPERATION
As the plenum temperature rises, the bimetal sensing element of the control wraps and mechanically makes
TO RELEASE STOP, PRESS STIFF WIRE
IN HOLE
SCALEPLATE
CAUTION
DO NOT ROTATE - HOLD DIAL
WHEN SETTING POINTERS
50
F
AN
OFF
FAN OFF SET
POINT LEVER
FAN ON SET
POINT LEVER
HOMEOWNER: THIS IS A "SAFETY STOP". DO NOT ALTER
1
100
F
ON
150
250
AN OFF
200
LIMIT SET POINT LEVER (FACTORY-SET AT 200
ADJUSTABLE
LIMIT STOP
O
(93
Fig. 10 - Changing the high limit stop.
the fan contacts (at the FAN ON temperature setting). During normal operation, the call for heat end before the LIMIT setting is reached, and the fan contacts break as the plenum temperature falls and the FAN OFF setting is reached. If the call for heat continues until the temperature in the plenum rises to the LIMIT setting, the bimetal element will mechanically break the limit contacts and de-energize the gas control circuit.
CHECKOUT
When installation is complete, disconnect the fan motor circuit at the L4064. Turn on power and set thermostat to call for heat. Burner should come on and limit controller should shut burner off when plenum temperature reaches the limit set point. Turn off power, recconnect the fan switch, turn on power and again set thermostat to call for heat. Fan should come on when plenum temperature has reached fan-on setting.
C)
2
LIMIT STOP
TOOL
O
F
1
2704E