
D
L404A
F
INSTALLATION
Mounting
If
it
the
pressure
fitting
fitting
the
boiler
steam
Mounting
If
there
adversely
controller
must
be
properly
boiler
tween
controller
on
is
not
gauge
provided
mount
manufacturer
and
trap
at
is
affect
ataremote
suitable
pitched
A
steam
the
remote
after
M
L604A
L
a
Boiler
convenient
install
the
by
the
steam
level
a
Remote
excessive
the
operation
and
solidly
to
trap
piping
installation
to
a
boiler
trap
Screw
the
controller
Location
vibration at
location
drain
siphon
mount
steam
manufactUrer
at
a
location
the
of
the
All
mounted
all
condensation
loop
and
the
the
controller
trap
siphon
controller
the
controller
piping
The
must
controller
alongside
loop
If
there
recommended
directly
boiler
that
mount
from
the
must
piping
backtothe
be
mounted
Level
in
is
to
can
the
boiler
be
the
the
no
by
the
be
3
Fig
schematics
L404A
BREAKS
ON
PRESSURE
TO
SETPOINT
L404
C
RISE
terminal
blocks
RISE
L404B
MAKE ON
PRESSURE
TO
SETPOINT
and
internal
RISE
B
D
RISE
L404F
SNAP ACTING
BREAKSRa
MAKESRWON
PRESSURE
TO
SETPOINT
RISE
M8941
SupervisionofAtomizing
Air
or
When
oil
burner
bodies
opening
sure
is
atomizing
The
makesacircuit
breaks
differential
WlRING
1
to
preventelectrical
2
Assume
co
ordinances
voltage
3
Fornormalinstallations
wire
sUitable
the
controller
least
1940F
control
4
For
tant
No
maximum
All
5
3
and4anda7 8in22
condui
tIi
e
screw
ing
6
Refer
the
burnerorboiler
vided
7
Make
Ratings
8
Replace
Steam
L404B
air
or
steam
system
and
codes
the
main
oil
present
andtoshut
pressure
L404B
is
when
when
the
pressure
10
Fig
t
the
DiscoDDe
all
wiring
wiring
foratleast
withaflame
900C
high
temperature
14
wire
selected
operating
have
models
cableorwires
the
at
to
Fig
the
sure
the
in
Specifications
front
the
is used
authorities
often
valve
falls
recommended
the
power
shock
and
regulations
when
temperature
a
bottom
5
through
manufacturer
loads
cover
Medium
require
until
too
low
pressure
falls
supply
or
equipment
complies
1670
1
safeguard
using
installations
for
a
terminal
2
mm
Remove
of
9
do
not
section
when
as
the
Pressure
an
atomizing
jurisdiction
having
a
low
limit
sufficient
down
the
system
for
this
to
rises
the
to
set
the
point
before
beginning
damage
with
applicable
Use
NEC
use
moisture
when
750C
primary
it
with
a
use
temperature
block
hole
the
main
for
typical
s
exceed the
inside
in
one
front
scale
wiring
wiring
rating
cover
hookups
diagram
Switch
is
medium
in
approval
to
prevent
atomizing
pres
when
application
set
point
minus
wiring
electrical
Class 1
resistant
you
control
are
line
No
using
or
programming
moisture
the
side
completed
above
cover
for12
loosen
by
Follow
if
Contact
resis
Fig
pro
the
and
the
the
in
4
L404
an
schematic
Fig
terminal
block
and
Internal
It
L604A
MAKES
BREAKSR28
ON
SPDT
OTHERWISE
W
Rl
PRESSURE RISETOSETPOINT
SWITCH
ACTION
TWO
WITH
ISOLATED
JUMPER
SPST SWITCHES
INSTALLED
L604L
M
M8935
14
at
Fig
controller
POWER
SUPPLY
PROVIDE
AS
HIGH
TO
LOW
MINUS
OPERATING
TO
SETPOINT
Ll
U
HOT
1
Lll
DISCONNECT
REQUIRED
l
404A
UMIT
SETPOINT
UMIT
t
DIFFERENTIAL
SETPOINT AND
MINUS
4048
L404 used
S
SPST
CONTROLLER
MEANS
C
OR
BREAKS WHEN
MAKES
DIFFERENTIAL
as
a
AND
BREAKS
404A
CONTROLLER
t
AGAIN WHEN
limit
OVERLOAD
WHEN
PRESSURE
BREAKS
orasan
PROTECTION
PRESSURE
FALLSTOSETPOINT
WHEN
PRESSURE
operating
FlAME
SAFEGUARD
CONTROL
MOTOR
OTHER
RISES
PRESSURE
FALLS
OR
LOAD
RISES
TO
M8936