Compact Electronic Air & Liquid Flow Switch
KSW and KSL
PRODUCT DATA
GENERAL
These highly reliable compact electronic flow switches are
designed for detecting the flow of water and/or air in ducts or
pipes.
As soon as the medium's flow speed rises above or drops
below a customer-selected value, the device switches an
electronic circuit.
FEATURES
• No moveable parts in the detection zone.
• Can be mounted directly to pipes and ducts.
• Immersion well also used for mounting the device.
• Temperature-compensated operating range.
• 2.5 mm
• Highly resistant to pollution and corrosion.
• Small pipe/duct connection.
2
screw terminals.
SPECIFICATIONS
Type KSW-230 KSW-24 KSL-230 KSL-24
Media liquids and air liquids and air air air
Power supply 230/240 Vac, +/- 10% 24 Vac, +/- 10% 230/240 Vac, +/- 10% 24 Vac, +/-10%
Power supply indication LED green LED green LED green LED green
Power consumption 3.5 VA 3.5 VA 4 VA 4 VA
Ambient temperature -20 °C ... +60 °C -20 °C ... +60 °C -20 °C ... +60 °C -20 °C ... +60 °C
Medium temperature -10 °C ... +80 °C -10 °C ... +80 °C -10 °C ... +80 °C -10 °C ... +80 °C
Relay contact SPDT SPDT SPDT SPDT
Contact load 250 Vac, 10(2) A 250 Vac, 10(2) A 250 Vac, 10(2) A 250 Vac, 10(2) A
Switch indication LED yellow LED yellow LED yellow LED yellow
Start retardation 60sec on/off (jumper) on/off (jumper) on/off (jumper) on/off (jumper)
Setpoint adjustment potentiometer potentiometer potentiometer potentiometer
Range 0.05 -3 m/sec 0.05 -3 m/sec 0.1 - 30 m/sec 0.1 - 30 m/sec
Response time 1-10 sec 1-10 sec 1-10 sec 1-10 sec
Immersion depth 45 mm 45 mm 130 mm 130 mm
Max. pressure 30 bar 30 bar 10 bar 10 bar
Process connection G 1/2" G 1/2" PG7 + mounting flange PG7 + mounting flange
Housing IP IP 65 IP 65 IP 65 IP 65
Sensor IP IP 67 IP 67 IP 67 IP 67
Protection class II II II II
Wiring terminals 5 x 2.5 mm
Sensor material 1.4305 1.4305 MS 58 nickel-plated MS 58 nickel-plated
Weight 350 g 350 g 400 g 400 g
2
5 x 2.5 mm
2
5 x 2.5 mm
2
5 x 2.5 mm
2
® U.S. Registered Trademark EN0B-0318 GE51R0501
Copyright © 2001 Honeywell Inc.
All Rights Reserved
KSW / KSL COMPACT ELECTRONIC AIR & LIQUID FLOW SWITCHES
MOUNTING
KSW
The sensor can be mounted in a standard T-piece with
connection R1/2". Calming distance upstream from the
sensor should be 10 times the pipe diameter and downstream from the sensor 5x the pipe diameter. The sensor
head must be placed in the center of the pipe. When
monitoring flow in vertical pipes, the flow direction should be
from bottom to top.
KSL
The sensor should be mounted so as to ensure that the air
flows through the lateral opening. To fix the sensor on the
duct, a circular mounting bracket must be fixed with at least
two attached screws on the duct. The centric hole of 10 mm
allows individual fastening of the sensor immersion well with
one screw. The red marking on the circular sensor immersion
well (approx. 4 mm from the housing bottom) indicates the
direction of flow and is intended as an assembly aid. Vertical
and horizontal mounting possible. The sensor must be
placed in an area of calm flow.
FIELD WIRING
KSW
Connect the power supply to terminals L and N. Connect
Common (15), Normally Closed (16), and Normally Open
(18) accordingly.
Fig. 1. Wiring diagram, KSW
KSL
Connect the power supply to terminals L and N. Connect
Common (11), Normally Closed (12), and Normally Open
(14) accordingly.
Fig. 2. Wiring diagram, KSL
NOTE: To ensure the protection standard after field wiring,
use only cables having a diameter of 6 to 9 mm.
DIMENSIONS
SWITCHPOINT ADJUSTMENT
KSW
Connect the KSW according to the mounting instructions and
as appropriate to the application conditions. Switch on the
power supply (green LED goes ON). Then switch on the
liquid flow. Turn the potentiometer marked "Rough" clockwise
until the yellow LED goes ON. To prevent malfunction at
short flow-peaks, the potentiometer marked "Fine" must be
turned until the switchpoint is slightly exceeded. Bypass
function (60 sec) during the start up phase can be realized by
internal DIP switch.
KSL
Connect the KSL according to the mounting instructions and
as appropriate to the application conditions. Turn the
potentiometer marked "Sensitivity" counterclockwise to the
end stop. Switch on the power supply (green LED goes ON).
Then switch on the air flow. Turn the potentiometer marked
"Sensitivity" clockwise towards maximum until the yellow LED
goes ON. To prevent malfunction at short flow-peaks, turn
the potentiometer slightly beyond the switchpoint. To verify
function, reduce or switch the air flow. The yellow LED must
go OFF and the internal relay must switch back. Bypass
function (60 sec) during the start up phase can be realized by
internal DIP switch.