Honeywell IFS-2600 User Manual

IFS-2600
8/05/08
3.01
Fire Indicator Panel
TECHNICAL, PROGRAMMING
& INSTALLATION MANUAL
P/N 10069 ECN08-0066
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before
servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location.
Do not over tighten screw terminals. Over tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These
instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
This equipment must be correctly programmed and installed to suit the specific application.
Please ensure correct operational parameters are set prior to commissioning. If further details on programming options are required, please consult the programming manual or contact our helpful technical support personnel.
EMC WARNING:
This equipment may radiate radio frequency energy. It may also be affected by radio frequency energy and, if not installed and operated in accordance with the manufacturers instructions, may cause interference to radio communications. It has been tested and found to comply with the Class A radiated and conducted EMI requirements of AS/NZ 3548:1995 (including Amendments 1 & 2) as well as the EMI susceptibility requirements of Clause C3.5 in AS4428.0:1997.
Radio communication devices should not be used in the vicinity of fire panels or associated ancillary devices and systems.
Documentation Feedback
Your feedback helps us keep our documentation up to date and accurate. If you have any comments or suggestions about our printed manuals you can email us.
Please include the following information:
Product name and version number (if applicable)Manual part number and revision (found on the front cover)Page numberBrief description of the content you think should be improved or correctedYour suggestion for how to correct/improve documentation
Send email messages to:
techpubs@notifier.com.au
Please note this email address is for documentation feedback only. If you have any technical issues, please contact you nearest branch for technical support.
IFS-2600 Installation & Programming Manual Page 1
TABLE OF CONTENTS
COMPATIBLE DETECTORS................................................................................................5
OVERVIEW...........................................................................................................................6
CAUTION ........................................................................................................................................................................... 6
SPECIFICATION...................................................................................................................7
APPROVALS...................................................................................................................................................................... 7
ENVIRONMENTAL LIMITS........................................................................................................................................... 7
POWER SUPPLY RATINGS AND SETTINGS ............................................................................................................. 9
INTERNAL 24 VDC (nom) 3.0A MAIN POWER SUPPLY .......................................................................................... 9
INTERNAL 27.3V DC 1.5A BATTERY CHARGER..................................................................................................... 9
Internal 5VDC 2A Power Supply ..................................................................................................................................... 9
EXTERNAL 27VDC POWER SUPPLY ....................................................................................................................... 10
BATTERY TYPE AND CAPACITIES .......................................................................................................................... 10
TECHNICAL DESCRIPTION..............................................................................................11
GENERAL ........................................................................................................................................................................ 11
TRANSIENT SUPPRESSION......................................................................................................................................... 11
CURRENT CONSUMPTION ......................................................................................................................................... 11
AZF DESCRIPTION........................................................................................................................................................ 12
AZF SUPERVISORY CURRENT .................................................................................................................................. 12
OVERLOAD PROTECTION.......................................................................................................................................... 12
ZONE OVERLOAD SELF RESET ................................................................................................................................ 12
PRINTER OUTPUT......................................................................................................................................................... 13
CABLE CONNECTION.................................................................................................................................................. 13
PROGRAMMING BY COMPUTER............................................................................................................................. 13
ALIGNMENT AND ADJUSTMENT.....................................................................................14
PCB2006 POWER SUPPLY BOARD ............................................................................................................................ 14
INTERNAL 24VDC (nom) POWER SUPPLY.............................................................................................................. 14
INTERNAL 27.3 VDC BATTERY CHARGER............................................................................................................ 14
EXTERNAL 24VDC (nom) POWER SUPPLY (if fitted)............................................................................................. 14
P/N 10069 ECN08-0066
Page 2 IFS-2600 Installation & Programming Manual
PCB2005 TERMINATION BOARD...............................................................................................................................14
INTERNAL 5VDC POWER SUPPLY TP8...................................................................................................................14
POWER SUPPLY COMPARATOR REFERENCE VOLTAGE TP10 ......................................................................... 14
NON ADJUSTABLE TEST POINTS..............................................................................................................................14
ALARM THRESHOLD COMPARATOR TP7.............................................................................................................15
FAULT THRESHOLD COMPARATOR TP6 ..............................................................................................................15
CONFIGURATION JUMPERS......................................................................................................................................16
IFS2004 - JP3 DEFAULT .............................................................................................................................................16
IFS2004 - JP4 PROGRAM DISABLE ..........................................................................................................................16
IFS2004 - JP5 CPU RESET...........................................................................................................................................16
IFS2005 – JP2 DOOR HOLDER BYPASS...................................................................................................................16
IFS2006 – JP1 EXTERNAL PS MONITORING..........................................................................................................16
IFS804 - JP1-7 ZONE BOARD ADDRESSING...........................................................................................................16
PLACING INTO OPERATION............................................................................................ 17
EQUIPMENT AS FITTED..............................................................................................................................................17
INITIAL CHECKLIST....................................................................................................................................................17
POWER UP CHECKLIST...............................................................................................................................................18
FUNCTIONAL TESTING...............................................................................................................................................18
FAULT RECORD.............................................................................................................................................................19
INSTRUCTIONS TO OPERATORS....................................................................................20
INDICATORS...................................................................................................................................................................20
SUGGESTED ALARM PROCEDURE.......................................................................................................................... 21
OPERATOR INSTRUCTIONS.......................................................................................................................................21
FIREFIGHTER FUNCTIONS........................................................................................................................................21
GLOBAL FUNCTIONS.................................................................................................................................................22
ZONE FUNCTIONS.......................................................................................................................................................24
PROGRAMMING................................................................................................................27
GLOBAL OPTIONS.........................................................................................................................................................27
ZONE OPTIONS ..............................................................................................................................................................27
OUTPUT RELAY OPTIONS ..........................................................................................................................................28
DEFAULT SETTINGS.....................................................................................................................................................28
PROGRAM MODE..........................................................................................................................................................29
PROGRAMMING MODE..............................................................................................................................................29
PROGRAMMING HIERARCHY..................................................................................................................................29
ZONES............................................................................................................................................................................29
RELAYS.........................................................................................................................................................................30
GLOBAL ........................................................................................................................................................................ 30
PRINT.............................................................................................................................................................................30
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 3
MAIN MENU.................................................................................................................................................................... 30
EXIT PROGRAMMING MODE................................................................................................................................... 31
ZONE PROGRAMMING................................................................................................................................................ 31
SELECT ZONE #........................................................................................................................................................... 31
ZONE SELECTED......................................................................................................................................................... 31
ZONE TYPE .................................................................................................................................................................. 31
ZONE OUTPUT CONFIGURATION ........................................................................................................................... 32
RELAY PROGRAMMING MODE................................................................................................................................ 32
SELECT RELAY # ........................................................................................................................................................ 32
RELAY SELECTED...................................................................................................................................................... 32
RELAY TYPE................................................................................................................................................................ 33
RELAY MAPPING........................................................................................................................................................ 33
GLOBAL PROGRAMMING.......................................................................................................................................... 33
ACF OUTPUT................................................................................................................................................................ 34
AVF................................................................................................................................................................................ 34
RELAY (GLOBAL RELAY UNITY MAP) .................................................................................................................. 34
PRINT PROGRAMMING DATA.................................................................................................................................. 35
TIME (DATE & TIME)................................................................................................................................................... 35
APPENDIX A ......................................................................................................................36
DESCRIPTION OF ALARM ZONE TYPES................................................................................................................ 36
LATCHING TYPE......................................................................................................................................................... 36
NON LATCHING TYPE ............................................................................................................................................... 36
TIME DELAY AZF........................................................................................................................................................ 37
APPENDIX B ......................................................................................................................38
ZONE OUTPUT CONFIGURATIONS.......................................................................................................................... 38
APPENDIX C ......................................................................................................................39
ALARM VERIFICATION FACILITY (AVF).............................................................................................................. 39
GLOBAL PROGRAMMABLE OPTIONS.................................................................................................................... 39
APPENDIX D ......................................................................................................................40
ANCILLARY TRIP (ACF).............................................................................................................................................. 40
GLOBAL PROGRAMMABLE OPTIONS.................................................................................................................... 40
APPENDIX E.......................................................................................................................41
RELAY OUTPUT MAPPING......................................................................................................................................... 41
AND MAPPING ............................................................................................................................................................... 41
OR MAPPING.................................................................................................................................................................. 41
FAULT MAPPING........................................................................................................................................................... 41
FAULT/ISOLATE MAPPING........................................................................................................................................ 42
ISOLATE MAPPING ...................................................................................................................................................... 42
P/N 10069 ECN08-0066
Page 4 IFS-2600 Installation & Programming Manual
APPENDIX F ......................................................................................................................43
GLOSSARY OF TERMS.................................................................................................................................................43
APPENDIX G...................................................................................................................... 44
SUMMARY OF TERMINATIONS AND CAUTIONS.................................................................................................44
MCP LOOP..................................................................................................................................................................... 44
DETECTION ZONES ....................................................................................................................................................44
RELAY OUTPUTS ........................................................................................................................................................44
BELL OUTPUTS ...........................................................................................................................................................44
ACF OUTPUTS..............................................................................................................................................................44
WARNING SYSTEM.....................................................................................................................................................44
DOOR HOLDER OUTPUTS.........................................................................................................................................44
AUXILIARY POWER & MIMIC POWER ................................................................................................................... 44
MAF ISOL & TRANSPONDER 0V ..............................................................................................................................44
MIMIC DATA & CLOCK..............................................................................................................................................44
AC INPUT......................................................................................................................................................................44
BATTERY......................................................................................................................................................................45
DOOR HOLDER AC INPUT.........................................................................................................................................45
OUTPUT RELAYS ........................................................................................................................................................45
APPENDIX H...................................................................................................................... 46
IFS-2600 PROGRAMMED OPTIONS...........................................................................................................................46
APPENDIX I........................................................................................................................ 53
TECHNICAL DRAWINGS.............................................................................................................................................53
MAIN KEYPAD AND DISPLAY..................................................................................................................................53
EXPANSION DISPLAY ................................................................................................................................................ 53
Block Connection Diagram.............................................................................................................................................54
System Sensor Conventional Detector Connection Diagram.......................................................................................... 54
System Sensor Conventional Detector Connection Diagram.......................................................................................... 55
Hochiki Conventional Detector Connection Diagram.....................................................................................................55
Hochiki Conventional Detector Connection Diagram.....................................................................................................56
Ancillary Connection Diagram........................................................................................................................................57
ASE Connection Diagram...............................................................................................................................................58
Auto Changeover Dual Sounder Connection Diagram....................................................................................................59
Auto Change Over Dual Sounder Connection Diagram.................................................................................................. 60
MIMIC Connection Diagram..........................................................................................................................................61
Single Fan Connection Diagram .....................................................................................................................................62
Dual Fan Connection Diagram........................................................................................................................................63
Exhaust Fan Connection Diagram...................................................................................................................................64
Supply Fan Connection Diagram ....................................................................................................................................65
Smoke Spill Fan Connection Diagram............................................................................................................................66
10W EVAC Connection Diagram...................................................................................................................................67
10W EVAC Slave Connection Diagram.........................................................................................................................68
30W EVAC Connection Diagram...................................................................................................................................69
30W EVAC Slave Connection Diagram.........................................................................................................................70
50W EVAC Connection Diagram...................................................................................................................................71
50W EVAC Slave Connection Diagram.........................................................................................................................72
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 5
COMPATIBLE DETECTORS
Make Model Type Model Number
System Sensor Thermal Type A 5451 AUS System Sensor Thermal Type A 51A51 System Sensor Thermal Type B 4451 AUS System Sensor Thermal Type B 51B51 System Sensor Thermal Type B Sealed 51B51S System Sensor Thermal Type C 51C51 System Sensor Thermal Type D 51D51 System Sensor Smoke Photo-Optical 2151 AUS System Sensor Smoke Photo-Optical 2151B AUS System Sensor Smoke Ionisation 1151 AUS System Sensor Thermal Type D 51D51 System Sensor Smoke Beam BEAM1224 System Sensor Smoke Duct DHP-100
Apollo Thermal Type A Series 60 Apollo Thermal Type B Series 60 Apollo Thermal Type C Series 60 Apollo Thermal Type D Series 60 Apollo Smoke Ionisation Series 60 Apollo Smoke Photo Optical Series 60
Hochiki Thermal Type A DCA-B-60R MkV Hochiki Thermal Type A DCC-A Hochiki Thermal Type A DCD-A Hochiki Thermal Type B DFE-60B Hochiki Thermal Type B DFJ-60B Hochiki Thermal Type C DCA-B-90R Mk1 Hochiki Thermal Type C DCC-C Hochiki Thermal Type C DCD-C Hochiki Thermal Type D DFE-90D Hochiki Thermal Type D FDJ-90D Hochiki Thermal Cool Room Type B sealed DFG-60BLKJ Hochiki Smoke Ionisation SIH-AM Hochiki Smoke Ionisation SIJ-ASN Hochiki Smoke Photo Optical SLK-A Hochiki Smoke Photo Optical SLR-AS
Olsen Thermal Type A T56B-T6A Olsen Thermal Type B T56B-T6B Olsen Thermal Type C T56B-T6C Olsen Thermal Type D T56B-T6D Olsen Smoke Ionisation C24B Olsen Smoke Photo Optical P24B
Panelect Thermal Type A PFS-A Panelect Thermal Type B PFS-B Panelect Thermal Type C PFS-C Panelect Thermal Type D PFS-D Panelect Smoke Ionisation PFS-I Panelect Smoke Ionisation PFS-I , MkII Panelect Smoke Photo Optical PFS-P Panelect Smoke Photo Optical PFS-P, MkII
IEI VESDA E700, E70D CONTACT DEVICE Please contact NOTIFIER INERTIA for any additional detectors.
P/N 10069 ECN08-0066
Page 6 IFS-2600 Installation & Programming Manual
OVERVIEW
IFS-2600 Fire Indicator Panel (FIP) is designed to provide simplicity to the end user. The FIP uses both a liquid crystal display and conventional LED displays for fast and accurate display of system status and changing events.
A custom designed membrane keypad is used together with the liquid crystal display and LED indicators to provide fast, efficient and simple modes of operation. The keypad also provides the required flexibility for the programming of the many user configurable options of this FIP. The FIP can be configured on-site without the need of expensive programmers or components.
A serial printer can also be connected if required. The printer can be used to output programming information for ease of modification, for safekeeping and to assist in the commissioning of the installation.
IFS-2600 uses serial chain mimic outputs which significantly saves time and costs of cabling to mimic panels.
A door holder power supply (using optional transformer) is incorporated into the system for the release of smoke and fire doors on alarm.
IFS-2600 is available in a standard 8-zone configuration and can be expandable to its fully expanded state as required. The IFS-2600 in its fully expanded state can;
Monitor 64 detection zones
Control 64 optional "mapped" relay outputs
Output to a serial printer
Output serially to a mimic panel
Control to door holders
Interface as required to any Australian Fire Brigade
IFS-2600 has been designed to be functional, flexible and reliable whilst maintaining a user-friendly interface.
CAUTION
IFS-2600 FIP has been tested and approved to AS4428.1 and meets the requirements of AS1670 and AS1668 Parts 1 &
2.
However, the equipment must be correctly programmed and installed to suit the specific application. Please ensure correct operational parameters are set prior to commissioning. If further details on programming options are required, please consult the programming manual or contact our helpful technical support personnel.
WARNING:
This equipment may radiate radio frequency energy. It may also be affected by radio frequency energy and, if not installed and operated in accordance with the manufacturers instructions, may cause interference to radio communications. It has been tested and found to comply with the Class A radiated and conducted EMI requirements of AS/NZ 3548:1995 (including Amendments 1 & 2) as well as the EMI susceptibility requirements of Clause C3.5 in AS4428.0:1997
CAUTION: Radio communication devices should not be used in the vicinity of fire panels or associated ancillary devices and systems
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 7
SPECIFICATION
Cabinet Zinc Sealed Steel 1.6mm
Powder Coated Hinged Inner Door Hinged Outer Door
Outside Dimensions 2608 (8 zones) 394mm H x 390mm W x 180mm D*
2624 (24 zones) 750mm H x 390mm W x 180mm D* 2600 (32 to 64 zones) 18U, 28U & 40U Cabinets Battery Box
*Note: the depth quoted is including the door and break glass. The internal cabinet depth not including he door and break glass
is 140mm. AC Operational Voltage 240 VAC 50Hz + 10% Internal Power Supplies Battery Charger 27.3 VDC 1.5AMP
Panel Supply 24 VDC(nom) 3.0AMP
Logic Supply 5 VDC 2.0AMP Microprocessor 80C52
Memory Type Non-volatile E2ROM Liquid Crystal Display 2 Lines x 16 Characters LED Backlit Fuses F1: Panel Supply M205 5A
F2: Battery Charger M205 3A
F3: Battery Protection Polyfuse 3A
F4: External Supply M205 7A
F5: Door Holder M205 3A
F6: Aux Power Output M205 1A Slow Blow
F7: Bell M205 1A
F8: Warning System M205 1A
F9: ACF M205 1A E.O.L Resistor On AZFs, monitored
outputs, Bells, Warning system, ACF
4K7 Ohms
APPROVALS
Australian Standard AS4428.1 1998 SSL Approval No AFP-1553 C-Tick Approval No. N1336
ENVIRONMENTAL LIMITS
-10 Deg. C to +55 Deg. C Dry heat. +40 Deg. C @ 93% Relative Humidity.
P/N 10069 ECN08-0066
Page 8 IFS-2600 Installation & Programming Manual
SYSTEM EXPANSION
Zones Qty Hardware Required Product Code 8 1 Main Control Board PCB-2004
1 Main Termination board PCB-2005 1 Power Supply board PCB-2006
16 1 Main Control board PCB-2004
1 Main Termination board PCB-2005 1 Power Supply board PCB-2006 1 8 Zone Expansion board PCB-804G3 1 16 Zone Indicator board PCB-816
24 1 Main Control board PCB-2004
1 Main Termination board PCB-2005 1 Power Supply board PCB-2006 2 8 Zone Expansion board PCB-804G3 1 16 Zone Indicator board PCB-816
32 1 Main Control board PCB-2004
1 Main Termination board PCB-2005 1 Power Supply board PCB-2006 3 8 Zone Expansion board PCB-804G3 2 16 Zone Indicator board PCB-816
40 1 Main Control board PCB-2004
1 Main Termination board PCB-2005 1 Power Supply board PCB-2006 4 8 Zone Expansion board PCB-804G3 2 16 Zone Indicator board PCB-816
48 1 Main Control board PCB-2004
1 Main Termination board PCB-2005 1 Power Supply board PCB-2006 5 8 Zone Expansion board PCB-804G3 3 16 Zone Indicator board PCB-816
56 1 Main Control board PCB-2004
1 Main Termination board PCB-2005 1 Power Supply board PCB-2006 6 8 Zone Expansion board PCB-804G3 3 16 Zone Indicator board PCB-816
64 1 Main Control board PCB-2004
1 Main Termination board PCB-2005 1 Power Supply board PCB-2006 7 8 Zone Expansion board PCB-804G3 4 16 Zone Indicator board PCB-816
Additional relay outputs:
Relays Qty Hardware Required Product Code 8 1 Relay board containing 8 relays 24VDC 1A IFS-717 16 2 Relay board containing 8 relays 24VDC 1A IFS-717 24 3 Relay board containing 8 relays 24VDC 1A IFS-717 32 4 Relay board containing 8 relays 24VDC 1A IFS-717 40 5 Relay board containing 8 relays 24VDC 1A IFS-717 48 6 Relay board containing 8 relays 24VDC 1A IFS-717 56 7 Relay board containing 8 relays 24VDC 1A IFS-717 64 8 Relay board containing 8 relays 24VDC 1A IFS-717
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 9
POWER SUPPLY RATINGS AND SETTINGS
INTERNAL 24 VDC (nom) 3.0A MAIN POWER SUPPLY
This supply's primary function is to power panel logic and all external operations of the FIP, i.e.: detection circuits, ancillary circuits, etc. This supply meets the requirements of AS4428.5.
AC Input 30 VAC +10% - 15% Output Current 3.0 AMPS Output Voltage 26.5 VDC Current Limit 3.0 AMPS Output Ripple 50 mV
INTERNAL 27.3V DC 1.5A BATTERY CHARGER
Its primary function is to charge the batteries. This supply meets the requirements of AS4428.5.
AC Input 30 VAC +10% -15% Output Current 1.5 AMPS Output Voltage 27.3 VDC Current Limit 1.5 AMPS Output Ripple 200 mV
Important Note:
After a power failure, the battery will only reconnect to the charger if the battery voltage is above approximately 20V +/- 2V.
A battery fault will be generated in the event that the battery does not automatically reconnect. This is to ensure that a faulty or dead flat battery (due to an extended power failure) does not bring the entire system down.
In order to reconnect a flat battery, it is necessary to disconnect the battery from the panel and charge it externally. The battery should be thoroughly tested before returning it to service.
In the event that an external charger is not available, the battery may be trickle charged above 22V via a 30 ohm, 5W resistor connected between the 24v Aux Output and the battery positive terminal. A 1N4004 Diode (Notifier part number #286) or similar should also be fitted in series with the resistor to stop the battery from pulling down the main panel voltage. Trickle charging the battery by this method may take several hours to bring it up to the minimum level.
The battery can then be reconnected to the panel for charging via the internal battery charger. It is important that the voltage on the battery be monitored to ensure that it is charging. The battery should then be left for 24 hours and then fully tested to ensure that no damage has occurred due to the deep discharge.
Internal 5VDC 2A Power Supply
This supply's primary function is to power all internal operations of the FIP, i.e.: Microprocessor, liquid crystal display, LED's keypad etc.
AC Input 30 VAC +15% or 27.6VDC+15% Output Current 2.0 AMPS Output Voltage 5.0 VDC Current Limit 2.0 AMPS Output Ripple 150 mV
P/N 10069 ECN08-0066
Page 10 IFS-2600 Installation & Programming Manual
INPUT
INPUT
24V0V
IFS-2600 TERMINATION BOARD
EXTERNAL 27VDC POWER SUPPLY
This supply is used in addition to the internal power supply for large systems. Its primary function is to power any additional ancillary loads of the FIP up to 7 amps. This supply meets the requirements of AS4428.5
Important Notes:
When using external power supply, JP1 link on IFS2006E must be fitted to enable external PSU monitoring. If this supply is used to power a NI-2008 gas module, the following additional components are required to
ensure a break free change over from the mains supply to the panel battery in case of mains fail condition.
1. A 6A4 or P600G rectifier diode (Notifier part number #266) is to be installed in series with the
external +27V output of the IFS-2600 termination board.
2. A 3300µF 50V Electrolytic Capacitor (Notifier part number #1248) should be installed across the
+27V and 0V of the ancillary device.
AC
REMOTE
REMOTE
OUTPUT
24V 0V-+24V 0V
BATT INPUT
EXTERNAL
POWER SUPPLY
OUTPUT
0V
24V
6A4
+
3300uF
POWER IN
NI-2008 GAS
SUPPRESSION
MODULE
BATTERY TYPE AND CAPACITIES
In general, any Sealed Lead Acid Battery, or Wet Lead Acid Battery designed for stationary use is compatible with the IFS-2600 Fire Indicator Panel. Automotive batteries must not be used. The use of Nickel Cadmium batteries is not recommended.
Manufacturer Type Number Voltage Capacity (Ah) Qty Required
Best and Best Sealed LA BP17-12 12 17 2 Best and Best Sealed LA BP24-12 12 24 2 Best and Best Sealed LA BP40-12 12 40 2 Olympic Batteries Sealed LA CJ12-7 12 7 2 Olympic Batteries Sealed LA CJ12-12 12 12 2 Olympic Batteries Sealed LA CJ12-18 12 18 2 Olympic Batteries Sealed LA CJ12-26 12 26 2 Olympic Batteries Sealed LA CJ12-33 12 33 2 Olympic Batteries Sealed LA CJ12-40 12 40 2 Olympic Batteries Sealed LA CJ12-88 12 88 2 Olympic Batteries Sealed LA CJ12-100 12 100 2
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 11
TECHNICAL DESCRIPTION
GENERAL
The IFS-2600 in its most basic form comprises of three boards, the main control board, the main termination board and the power supply board.
The main control board contains the Microprocessor, EPROM, RAM and E2ROM. The main control board also has the liquid crystal display and keypad attached. All of the "delicate" electronics have been placed on this board. The main control board complete with the inner door is easily removed during installation to avoid damage and allow greater access to the field terminals.
The main termination board contains the one power supply for 5V logic, and connectors for a Power Supply and Battery Charger daughter board, the first eight zones, all common outputs and the printer interface. All charger settings, fuses etc are located on this board. The Power Supply and Battery Charger board contains two switch mode regulators, 26.5V for the panel power, 27.3V for the battery charger.
Up to seven (7) zone expansion boards can be added to the system to increase its detection capability. These boards contain the same electronics as on the main termination board for zone scanning. Addressing is by a jumper that selects which group of eight zones the board refers to.
Up to four (4) zone indicator boards can also be added. These boards will display the status of the zone expansion boards fitted.
Up to eight (8) relay boards can be added. These boards contain 8 change-over relay contacts, each rated at 1 amp. These boards require no addressing, as they work on a serial data chain. Output 1 is the closest output to the main board.
NOTE This product utilises state of the art components and materials and therefore boards must be returned
to our factory for proper troubleshooting, repair and retesting. Field component level repairs are not recommended and would void all warranties on the product.
TRANSIENT SUPPRESSION
The IFS-2600's superior transient protection comprises of Dual Transorb input traps, inductive paths on incoming PCB tracks, circuit board planes and metal oxide varistors on outputs. These devices are all self­resetting.
CURRENT CONSUMPTION
Zones Fitted Quiescent Current Quiescent + 2 AZF'S in alarm +1A of Bell +1 Amp ACF
8 150 mA 2.23 AMPS 16 250 mA 2.33 AMPS 24 350 mA 2.43 AMPS 32 450 mA 2.53 AMPS 40 550 mA 2.63 AMPS 48 650 mA 2.73 AMPS 56 750 mA 2.83 AMPS 64 850 mA 2.93 AMPS
Note: 1: Each installation would require individual battery calculations to be performed for load capacity and power supply capacity. 2: Each IFS-717 relay board, can add 370 mA (in alarm and quiescent) current per board.
P/N 10069 ECN08-0066
Page 12 IFS-2600 Installation & Programming Manual
AZF DESCRIPTION
The AZF's on the IFS-2600 are monitored and scanned by custom thick film hybrids. These hybrid IC's significantly reduce the possibility of false alarms and improve product efficiency and reliability.
The total Alarm Zone loop resistance is the sum of the end of line resistor (EOLR 4K7) plus all the parallel connected detector loads.
AZF SUPERVISORY CURRENT
The supervisory current flows through the external terminal AZF+, through the field cable and to the end of line resistor (EOLR), returning to the panel at AZF- terminal. Parallel connected, across the 2-wire pair field cable, are a number of the previously listed detectors. During the quiescent state there is essentially an open circuit across the + and - terminals of the detector base. The maximum number of detectors that can be installed on each AZF is dependant on the type of detector and is listed in the IFS-2600 ActivFire®listing.
In an alarm state, a 560-ohm resistor is connected across the detector base causing additional loop current to flow. This is sensed by the AZF to produce an alarm output. Removal of the E.O.L. resistor (in a non alarm state) or the interruption of the supervisory current will produce a fault signal in the AZF.
As described above, the level of current is used to define the status of the alarm zone: -
I = 3.5 mA and below FAULT I = 4.0 - 5.0mA at 24V QUIESCENT I = 16 mA to 40 mA (current limited) ALARM
The zone current is used by the hybrid IC to determine the condition of the zone as above. This information is then transferred to the microprocessor for processing.
OVERLOAD PROTECTION
Panel Supply Fuse F1 M205 5A Battery Charger Fuse F2 M205 3A Battery Protection Fuse F3 Polyfuse 3A External Supply Fuse F4 M205 7A Door Holder Fuse F5 M205 3A Aux Power Output Fuse F6 M205 1A Slow Blow Bell Fuse F7 M205 1A Warning System Fuse F8 M205 1A ACF Fuse F9 M205 1A AZF Circuits Current Limited 40mA
ZONE OVERLOAD SELF RESET
If a zone is overloaded by an accidental short to earth on an AZF circuit, the zone will automatically shut down and produce a fault. Once this happens the panel will automatically recheck the zone every 60 seconds and once the overload is removed, restore power and the fault will clear.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 13
PRINTER OUTPUT
The printer port is designed to be used during testing and commissioning of the panel. The serial printer will report alarms and faults together with the date and time of the event. The printer can also be used during “walk test” mode to produce a history of the test and can also be used to print current programming configuration.
A DB9 plug male is provided at the top of the main termination board. This communication port will communicate with an IBM compatible serial printer (ASCII printer) with the following settings.
Baud Rate 1200 bps Data Bits 8 Stop Bits 1 Parity None Handshaking DTR
CABLE CONNECTION
Cabling to the printer requires a 4-core telephone style cable with a maximum length of 10 metres. A DB9 socket is required at the panel end. The printer end is dependent on the type of printer used but is usually a male DB25. Connection is as follows. A 5-core cable can be used for both comms and printer functions
IFS-2600 END PRINTER END
DB9 FEMALE DB25 MALE DB9 MALE
2 RX (only for programming) 2 3 3 TX 3 2 5 GND 7 5 7 RTS ( do not use) (5) (8) 8 CTS ( only for printer) 4 7
PROGRAMMING BY COMPUTER
Programming of the zones, relays, global functions and time can by set with the DOS based program “2600/SW” using the printer port. (Cannot be used with Windows XP) After the cable is installed, the program can be run and the menu will prompt for the available functions.
2600
P/N 10069 ECN08-0066
Page 14 IFS-2600 Installation & Programming Manual
ALIGNMENT AND ADJUSTMENT
PCB2006 POWER SUPPLY BOARD
INTERNAL 24VDC (nom) POWER SUPPLY
With batteries disconnected and no alarms present, measure voltage across the 0V and MAIN test points on the 2006 power supply board and, if necessary, adjust the multi-turn potentiometer VR2 until voltage is 26.5V 0.05V (26.45V – 26.55V).
Current limiting is fixed and field adjustment is not possible.
INTERNAL 27.3 VDC BATTERY CHARGER
With batteries disconnected and no alarms present, measure voltage across the 0V and CHARG test points on the 2006 power supply board and, if necessary, adjust the multi-turn potentiometer VR1 until voltage is 27.3V 0.05V (27.25V – 27.35V).
Current limiting is factory preset and field adjustment is not required.
EXTERNAL 24VDC (nom) POWER SUPPLY (if fitted)
With batteries disconnected and no alarms present, measure voltage across Remote Input terminals on PCB2005 and adjust the voltage on the external power supply until the voltage is 26.5V 0.5V (26.0V – 27.0V). Note: This voltage is not critical for the operation of the IFS-2600 panel, but the voltage must not go outside the limits as specified for the field ancillaries that it powers.
PCB2005 TERMINATION BOARD
INTERNAL 5VDC POWER SUPPLY TP8
All parameters are fixed and field adjustment is not possible.
POWER SUPPLY COMPARATOR REFERENCE VOLTAGE TP10
With the panel in the quiescent mode, measure voltage between system 0V and TP10. Adjust multi­turn potentiometer VR3 until voltage is 7.0V 1% (6.93V – 7.07V)
NON ADJUSTABLE TEST POINTS
TP8 = 5.0 VDC 5% 5VDC POWER SUPPLY TP5 = 12.0 VDC 5% 12VDC POWER SUPPLY
(If these test point voltages are not correct, please return the main termination board to the factory for repair.)
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 15
ALARM THRESHOLD COMPARATOR TP7
With the panel in the quiescent mode, measure and take note of the INTERNAL 24V DC POWER SUPPLY as above.
Measure voltage between system 0V and TP7. Adjust multi-turn potentiometer VR4, and adjust until the voltage is as per the following table.
Rail Voltage 3.3V Setting Range
20.6 2.833 2.80 to 2.86
21.0 2.888 2.86 to 2.92
21.5 2.956 2.93 to 2.99
22.0 3.025 2.99 to 3.06
22.5 3.094 3.06 to 3.12
23.0 3.163 3.13 to 3.19
23.5 3.231 3.20 to 3.26
24.0 3.300 3.27 to 3.33
24.5 3.369 3.34 to 3.40
25.0 3.438 3.40 to 3.47
25.5 3.506 3.47 to 3.54
26.0 3.575 3.54 to 3.61
26.5 3.644 3.61 to 3.68
27.0 3.713 3.68 to 3.75
27.5 3.781 3.74 to 3.82
27.6 3.795 3.76 to 3.83
28.0 3.850 3.81 to 3.89
FAULT THRESHOLD COMPARATOR TP6
With the panel in the quiescent mode, measure and take note of the INTERNAL 24V DC POWER SUPPLY as above.
Measure the voltage between system 0V and TP6. Adjust multi-turn potentiometer VR1, and adjust until the voltage is as per the following table.
Rail Voltage 0.6V Setting Range
20.6 0.600 0.59 to 0.61
21.0 0.612 0.61 to 0.62
21.5 0.626 0.62 to 0.63
22.0 0.641 0.63 to 0.65
22.5 0.655 0.65 to 0.66
23.0 0.670 0.66 to 0.68
23.5 0.684 0.68 to 0.69
24.0 0.699 0.69 to 0.71
24.5 0.714 0.71 to 0.72
25.0 0.728 0.72 to 0.74
25.5 0.743 0.74 to 0.75
26.0 0.757 0.75 to 0.76
26.5 0.772 0.76 to 0.78
27.0 0.786 0.78 to 0.79
27.5 0.801 0.79 to 0.81
27.6 0.804 0.80 to 0.81
28.0 0.816 0.81 to 0.82
P/N 10069 ECN08-0066
Page 16 IFS-2600 Installation & Programming Manual
CONFIGURATION JUMPERS
IFS2004 - JP3 DEFAULT
Holding a short across these pins for 5 seconds during start-up causes the panel to reset to standard factory defaults. The panel will give 4 beeps after reset, to acknowledge default on start-up.
IFS2004 - JP4 PROGRAM DISABLE
When fitted, jumper between these pins to inhibit program changes.
IFS2004 - JP5 CPU RESET
With panel operating, a momentary short across these pins will cause a CPU restart.
IFS2005 – JP2 DOOR HOLDER BYPASS
If zoned door holder outputs are required and is to be done external to the main termination board, then the main door holder release needs to be disabled. Fitting a link across JP2 on IFS2005 PCB does this.
Note: Door holder output is only enabled if optional door holder transformer is fitted. SW1 must be linked on PCB2004 CPU board prior to Version 6 Firmware.
IFS2006 – JP1 EXTERNAL PS MONITORING
When using external power supply, JP1 link on IFS2006E must be fitted to enable external PSU monitoring.
IFS804 - JP1-7 ZONE BOARD ADDRESSING
Jumper JP1 to JP7 on zone expansion board IFS-804 selects the addressing for the zones. Place jumper in link position for the appropriate 8 zones to which the expansion board applies.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 17
PLACING INTO OPERATION
Suitably qualified technicians must install the panel. The following check procedures are recommended after every installation and prior to initial power-up.
A thorough visual inspection should be made to every aspect of the fire panel. This includes loose wire, metal filings, loose circuit boards, loose cabling, damage in transit etc.
All problems must be rectified immediately as they could cause incorrect operation or permanent damage to the equipment.
EQUIPMENT AS FITTED
QTY Description Code
1 MAIN CONTROL BOARD IFS -2004
1 MAIN TERMINATION BOARD IFS -2005
1 MAIN POWER SUPPLY IFS -2006
8 ZONE EXPANSION BOARD IFS -804
16 ZONE INDICATOR BOARD IFS -816
ADD ON, 8 WAY RELAY BOARD IFS-717
EXTERNAL POWER SUPPLY BOOSTER PS244, PS249, NPS-3,
3A DOOR HOLDER P/SUPPLY TRANSFORMER 2600/DHTX
INITIAL CHECKLIST
System general appearance good Cabinet colour and condition good Cabinet keyed 003 All circuit boards firmly fastened Manual call point fitted & functional Viewing window clear and firmly secured Cable entries adequately sealed 240VAC mains cabling is correctly terminated All earthing secured Transformer securely mounted Transformer correctly wired All ribbon cables firmly secured All operational zones adequately identified All fuses correct value and fitted properly All other modules securely fitted Manufacturing label affixed
NPS-5, NPS-11
You are now ready to power up the IFS-2600 Fire Indicator Panel.
P/N 10069 ECN08-0066
Page 18 IFS-2600 Installation & Programming Manual
POWER UP CHECKLIST
Ensure batteries are disconnected. Turn mains switch to "on" The "mains on" led should light. Allow 15 seconds for the panel to perform its start up tests. Connect batteries
FUNCTIONAL TESTING
Primary ac supply voltage: 200 or 220 or 240vac +10% as required Charger output voltage without batteries: 27.3v dc Keypad functional Perform auto test
Led’s all functional LCD backlighting functional Liquid crystal display functional Zone fault detection Zone alarm detection
Internal sounder operating MCP loop wired to zone number ______ (if applicable) Test auxiliary power output Test bell output Test warning system output Test ACF output Test door holder output (optional) Test bell output supervision Test warning system output supervision Test ACF output supervision Test brigade alarm relay #1 Test brigade alarm relay #2 Test standby relay (normally energised) Test fault relay (normally energised) Test mains fail relay Test isolate relay Test general alarm relays (2) Test relay boards (if fitted) Test open collector output boards (if fitted) Press "battery test" once If batteries are flat, allow 24hrs to charge and then re-test.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 19
FAULT RECORD
FAULT CORRECTION DATE
TESTS SATISFACTORILY COMPLETED. TESTED BY _______________________________ SIGNATURE _______________________________ DATE OF TEST ____________________________ If all faults have been rectified and all tests are completed satisfactorily, the 2600 fire indicator panel is now
ready for operation.
P/N 10069 ECN08-0066
Page 20 IFS-2600 Installation & Programming Manual
INSTRUCTIONS TO OPERATORS
INDICATORS
Qty Descriptor Colour Function Buzzer
1 MAINS ON Green Illuminates when there is 200/220/240 VAC supply to
the panel.
1 BATTERY
FAULT
1 PSU FAULT Yellow Illuminates if the power supply is outside the
1 CHARGER
LOW
1 COMMON
FAULT
1 ACF ACT Red Illuminates if the ACF output has been activated. 1 ACF FLT Yellow Illuminates if the ancillary circuit is open or short
1 ACF ISO Yellow Illuminates if the ancillary output has been manually
1 Bell ACT Red Illuminates when the bell output has been energised. 1 Bell FLT Yellow Illuminates if the bell circuit is open or short circuit.
1 Bell ISO Yellow Illuminates if the bell output has been manually
1 Warning
System ACT
1 Warning
System FLT
1 Warning
System ISO
8 ALARM LEDS Red This LED will flash if it's corresponding zone goes
8 FAULT LEDS Yellow This LED illuminates if it's corresponding zone goes
8 ISOLATE LEDS Yellow This LED illuminates if its corresponding zone is
Yellow Illuminates if the battery fails a battery test.
Illuminates if batteries are disconnected >30 seconds. Illuminates if batteries are short circuit >30 seconds.
manufacturers range.
Yellow Illuminates if the battery charger is outside the
recommended float charge voltage.
Yellow Illuminates if;
Any un-isolated zone goes into fault. ACF output is open or short circuit Bell output is open or short circuit Warning System output is open or short circuit Battery Fault Charger Fault Power Supply Fault MAF Isolate Input is Open Circuit Configuration Fault
circuit. The LED will extinguish when the load is restored.
isolated.
The LED will extinguish when the load is restored.
isolated.
Red Illuminates if the Warning System output has been
energised.
Yellow Illuminates if the Warning System circuit is open or
short circuit. The LED will extinguish if the load is restored.
Yellow Illuminates if the Warning System has been manually
isolated.
into alarm. It will remain flashing until it is Acknowledged at which time it will go steady and remain on until the alarm is reset. If the zone is programmed as a time delay type, a steady LED indicates the “pre-alarm” condition. If the zone is isolated and in alarm it will also be steady.
into fault. It will remain on until the fault is removed.
isolated. It will remain on until the zone is de­isolated.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 21
SUGGESTED ALARM PROCEDURE
The following is a suggested alarm procedure for use by building fire officers or duty wardens. The fire indicator panel is designed for use by qualified fire fighters and it is strongly recommended that the fire panel not be operated in an emergency situation by anyone other than suitably qualified fire fighters.
Do not open fire indicator panel door or press any buttons until fire officers arrives. Determine location of the fire by inspecting the label beside any lit red zone alarm LEDs on the panel. Visually inspect area at a safe distance for actual fire or false alarm. Notify fire-monitoring station of either result. Perform evacuation and extinguishing operations as required. IF a FIRE, direct fire fighters to the fire indicator panel and cause of alarm as they arrive. IF a FALSE ALARM, advise maintenance technicians to determine and rectify cause. Record all events in logbook.
NOTE A suitably qualified fire officer should perform the above procedure. These are suggested procedures
only, and if specific fire procedures are available or issued, they MUST prevail.
OPERATOR INSTRUCTIONS
The functions of the IFS-2600 are divided into three (3) categories
Fire Fighter Functions Global Functions Zone Functions
FIREFIGHTER FUNCTIONS
Fire Fighter Functions are those specifically used by the Fire Brigade on attendance. Following is an explanation of their operation and the keystrokes required to perform the function required. These keys are located at the top of the keypad marked FIREFIGHTER’S FACILITY and bordered in red.
ACKNOWLEDGE
The purpose of the internal buzzer is to alert persons of a new event on the panel, and a new potential fire danger. Once the fire's location has been determined, the fire-fighter may wish to silence the internal buzzer without having to totally reset the alarm.
When the buzzer is operating, pressing the "ACK" key once will silence it, however the External Alarm Bell will continue to sound. If a subsequent alarm arises, the buzzer will be reactivated and a second ACK operation will be required to silence it.
When an alarm is acknowledged, the Alarm LED will stop flashing and light continuously.
ACK
RESET
The reset function momentarily disconnects power, and resets all alarm parameters for the zone(s) that have been acknowledged. This returns the zone back to its "normal" state. The reset key only operates on zones with acknowledged alarms.
ISOLATE
The isolate function prevents the transmission of alarms or faults from the zones to the master alarm facility. The isolate key only operates on zones with acknowledged alarms.
P/N 10069 ECN08-0066
RESET
ISOLATE
Page 22 IFS-2600 Installation & Programming Manual
EXT BELL
BELL ISOLATE
Depressing the "EXT BELL ISOLATE" key will isolate the bells. The "Ext Bells Isolate" LED will illuminate and the bells will not sound until the bells are de-isolated. Pressing "EXT BELL ISOLATE" a second time will de­isolate the bell.
WARN SYS ISOLATE
ISOL
WARN SYS ISOL
Depressing the "WARN SYS ISOLATE" key will isolate the warning system. The "Warn Sys Isolate" LED will illuminate and the warning system will not operate in the event of an alarm. Pressing "WARN SYS ISOLATE" a second time will de-isolate the warning system.
GLOBAL FUNCTIONS
Global functions are those relating to the overall system and are not specific to particular zones. Following is an explanation of their operation and the keystrokes required to perform the function.
BATTERY TEST BATT
TEST
This function tests the performance of the batteries fitted to the system. Pressing this button will initiate a battery test as specified in AS4428. The test will temporarily disconnect the batteries from the panel and apply load on the batteries for 15 seconds.
The result of the test will be displayed on the LED's. If the "Battery Fault" LED is on, only a successful battery test will turn the LED off. The pressing of any key during the test period will abort the battery test and return the system back to normal mode.
Battery test function is disabled when the panel is in alarm condition.
AUTO
AUTO TEST MODE
This function will perform a fixed automatic test procedure to the panel. This mode cannot be selected if any zone(s) is in alarm. Auto test will perform the following test functions;
Turn on ALL LEDs for 0.5 seconds Test LCD backlighting Test panel memory (E2ROM & RAM)  Test LCD Isolate all alarm zones Fault test all alarm zones Alarm test all alarm zones Test buzzer
TEST
The pressing of any key during "AUTO TEST" will abort the tests and return the system back to normal mode once the current test is complete.
Note During "AUTO TEST", all zones are treated as zone type #1 (standard latching type with 2 second
delay). Once AUTO TEST has finished, all zones will be reset and returned back to their previously configured types.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 23
WALK TEST MODE
WALK TEST
This function will place the panel into "walk test" mode. Walk test mode is used for the on-site testing of detector zones. This mode cannot be selected if any zone(s) is in alarm. Entry to walk test mode will be acknowledged by three beeps and the LCD will display "WALK TEST MODE".
For the duration of walk test mode, all zones are changed to output configuration #2 (indicate and ring bells only) and all zones are set to type #1 (standard latching, 2 second).
If the bells are not required to ring during walk test, simply press the "EXT BELL ISOLATE" key once. The EXT BELL ISOLATE LED will illuminate to verify that the bells have been isolated.
Any alarm signal from detectors etc. will be received by the panel on its appropriate zone. The panel will beep to acknowledge receipt of the alarm and indicate the alarm by illuminating the appropriate alarm LED for 4 seconds (the bells will also ring for a 3 second period unless previously isolated).
The zone and detector will then be automatically reset for 15 seconds If the optional printer is connected, the alarm will be printed out as it is received. This can eliminate the need
for a second serviceman to record zone numbers during walk test and the printout can be retained for verification at a later date.
Pressing any key will terminate the walk test mode and return the panel back to normal operation, restoring all zone types and output configurations also ensuring that bell and ancillary outputs are de-isolated. The bells will give three pulses of 1 second each to warn any testers still in the building that walk test mode has been terminated.
Failure to receive any alarms or keystrokes within a 15 minutes period will result in the panel automatically exiting walk test mode and returning back to normal as follows:
Bell outputs to be de-isolated. Ancillary outputs to be de-isolated. Bell will sound 3 times, each of 1-second duration. Exit from walk test mode. Zone types and output configurations restored
ACF ISOLATE
ACF ISOL
Depressing the "ACF ISOLATE" key will isolate the ACF (Ancillary output) and the Door Holder Output. The ACF isolated LED will illuminate and the output will not operate until de-isolated. Pressing "ACF ISOLATE" for a second time will de-isolate the output.
If the ancillary output has already been tripped and is programmed as latching, isolating the ACF will not affect the existing ancillary output. If the ACF is isolated prior to the alarm, it will prevent the ancillary output from tripping. This does not apply to the Door Holder output.
ACF RESET
ACF RESET
Resetting of the ancillary output (ACF) is only required if the ancillary output was programmed as latching. The ancillary alarm will remain latched until manually reset. Pressing the "ACF RESET" button will extinguish
the 'ACF Activated' LED and de-energise the ancillary output. Pressing "ACF RESET" when the ACF is not tripped will have no effect.
P/N 10069 ECN08-0066
Page 24 IFS-2600 Installation & Programming Manual
ZONE FUNCTIONS
Zone functions are those relating specifically to the detection zones. Following is an explanation of their operation and the keystrokes required to perform the function required.
ALARM TEST
The alarm test function momentarily disconnects the detector lines of the zone(s) under test and simulates a detector going into alarm, therefore testing the zone(s) alarm detection capability.
A resistive load equal to worst case alarm condition is placed on the zone for a period of 120 seconds and then removed, if the zone being tested is not a latching type, the alarm will reset automatically once the load is removed. Acknowledging and resetting the alarm will terminate an alarm test.
Once the zone has alarmed, all outputs are initiated (as programmed) similar to a real alarm. The zone may be isolated prior to an alarm test if desired; this will prevent any outputs from operating. ‘#’ in the above key sequence is the zone number. If only one zone is to be tested, use the appropriate number. Alternatively the "ALL" button can be used to
simultaneously test all zones. To perform an alarm test:
1. Press the "ALARM TEST" button once; the buzzer will give 2 short beeps to indicate that alarm test mode has been entered.
2. The LCD display will read "ALARM TEST MODE, ENTER ZONE No.".
ALARM TEST # ENT
3. Now enter the zone number ("#") 1-64 or “all”
4. Press "ENT"
If a correct entry is made, alarm testing on the zone commences immediately. However remember there is a 2 second transient delay on all zones. It will therefore take approximately 2 seconds before the zone registers an alarm (this could be longer, depending on zone type).
A long beep will signify an incorrect entry and will revert back to normal operating mode. The "ALARM TEST" button will need to be depressed again to re-enter alarm test mode.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 25
FAULT TEST
The fault test function momentarily disconnects the detection zone(s) under test and simulates the worst-case condition for fault.
A resistor load equal to worst case fault is placed on the zone continuously for 5 seconds then the zone is returned back to its normal condition.
If several zones are being tested consecutively and are being entered at a rate faster than the 5-second fault timer, the fault timeout will occur 5 seconds after the last entry was completed.
Once the zone has registered a fault, all outputs relating to that zone are initiated similar to a real fault. The zone may be isolated prior to a fault test if desired. This will prevent any outputs from operating. ‘#’ in the above key sequence is the zone number. If only one zone is to be tested, use the appropriate zone number. Alternatively the "ALL" button can be used
to simultaneously test all zones. To perform a fault test on a particular zone or on all zones:
1. Press the "FAULT TEST" button once. The buzzer will give 2 short beeps to indicate that fault test mode has been entered.
FAULT TEST # ENTER
2. The LCD display will read "FAULT TEST MODE, ENTER ZONE No.".
3. Enter the zone number ("#") 1-64 or “all”.
4. Press "ENTER".
A long beep will signify an incorrect entry and the panel will revert back to normal operating mode. The "FAULT TEST" button will need to be pressed again to re-enter fault test mode.
If a correct entry is made, fault testing on the zone commences and the fault LED will illuminate.
P/N 10069 ECN08-0066
Page 26 IFS-2600 Installation & Programming Manual
ISOLATE
The isolate function prevents the transmission of alarms or faults from the zones, to the master alarm facility. ‘#’ in the above key sequence is the zone number. If only one zone is to be isolated, use the appropriate zone number. Alternatively the "ALL" button can be used
to simultaneously isolate all zones. To isolate a particular zone or all zones:
1. Press the "ISOLATE" button. The buzzer will give 2 short beeps to indicate that isolate mode has been entered.
2. The LCD display will read "ALARM ISOL. MODE, ENTER ZONE No.".
3. Enter the zone number ("#")1-64 or “all”.
4. Press "ENTER".
A long beep will signify an incorrect entry and will revert back to normal operating mode. The "ISOLATE" button will need to be depressed again to re-enter isolate mode.
If a correct entry is made, the zone is immediately isolated. If the zone is already in alarm, all of its alarm outputs are isolated and indicators remain visible.
ISOLATE # ENTER
If the "ALL" function is performed, all zones will be isolated, regardless of their previous state. Performing the "ALL" function for a second time will de-isolate all zones.
RESET
The reset function momentarily disconnects power, and resets all alarm parameters for the zone(s) being reset. This returns the zone back to its "normal" state.
‘#’ in the above key sequence is the zone number. If only one zone is to be reset, type in the zone number. Alternatively the "ALL" button can be used to
simultaneously reset all zones. To perform a reset on a particular zone or on all zones:
1. Press the "RESET" button. The buzzer will give 2 short beeps to indicate that reset mode has been entered.
2. The LCD display will read "ALARM RESET MODE, ENTER ZONE NO".
3. Enter the zone number ("#") 1-64 or “all”.
4. Press "ENTER".
RESET # ENTER
A long beep will signify an incorrect entry and will revert back to normal operating mode. The "RESET" button will need to be depressed again to re-enter reset mode.
If a correct entry is made, resetting of the zone begins immediately. Any alarm indication will be removed immediately; also resetting the zone(s) programmed outputs.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 27
PROGRAMMING
GLOBAL OPTIONS
ANCILLARY TRIP
1 LATCHING NORMALLY DE-ENERGISED 2 NON-LATCHING NORMALLYDE-ENERGISED 3 LATCHING NORMALLY ENERGISED 4 NON-LATCHING NORMALLY ENERGISED
ALARM VERIFICATION
1 DISABLED 2 2 MINUTES 3 3 MINUTES 4 4 MINUTES 5 5 MINUTES
ZONE OPTIONS
1 Standard Latching 2 seconds 2 Standard Latching 2 seconds with AVF 3 Non Latching 2 seconds 4 Non Latching 20 seconds 5 Time Delay 10 seconds 6 Time Delay 20 seconds 7 Time Delay 30 seconds 8 Time Delay 40 seconds 9 Time Delay 50 seconds 10 Time Delay 60 seconds
TIME
(DD) / (MM) / (YY)
(HH) : (MM)
DESCRIPTION INPUT DELAY
Type Output Description
1 Indicate Only 2 Indicate, Bell 3 Indicate, Bell, General Alarm 4 Indicate, Bell, General Alarm, Ancillary 5 Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1 6 Indicate, Bell, General Alarm, Ancillary Brigade Relay #2 7 Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1, & Brigade Relay #2
P/N 10069 ECN08-0066
Page 28 IFS-2600 Installation & Programming Manual
OUTPUT RELAY OPTIONS
Optional Relays can be programmed to simulate: -
Isolate Relay ACF Output Brigade Relay #1 Brigade Relay #2 Fault Relay Mains Fail Relay General Alarm Relay Bell Output Door Holder Relay Door Switch Reset
Or Can Be Used To:
"MAP AND" Up to 5 Zones in Alarm "MAP OR" Up to 5 Zones in Alarm “MAP FAULT” Up to 5 Zones in Fault “MAP ISOLATE” Up to 5 Zones in Isolate “MAP ISO/FAULT” Up to 5 Zones in Isolate/Fault
DEFAULT SETTINGS
ACF OUTPUT NON-LATCHING, NORMALLY DE-ENERGISED ALARM VERIFICATION (AVF) 3 MINUTES TIME 1/1/11 11:11 ZONE TYPES STANDARD LATCH 2S ZONE OUTPUT CONFIG I-B-G-A-BR1 & BR2 RELAY MAPPING MAP-OR-, MAPPING = 1 TO 1
The 2600 PANEL is self-configuring on power-up therefore it is not necessary to program the number of relay boards. Zone expansion boards fitted must have the correct jumper selected.
IE: RELAY 1 = ZONE 1, RELAY 2 = ZONE 2.............
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 29
PROGRAM MODE
Press the following buttons in order shown to enter programming mode.
PREVIOUS
NEXT
SELECT
EXIT
ENTER
PROGRAMMING MODE
The liquid crystal display will display all messages and prompts required to program the 2600. ONLY the "PREVIOUS","NEXT","SELECT","EXIT" AND "ENTER" keys are used in programming mode. All
other keys will give an error beep and are ignored. Alarm detection is not affected during the programming function but you must exit programming mode if any
other panel functions are to be performed including acknowledge and reset of alarms. Note: Refer to appendices for detailed explanation of functions
PROGRAMMING HIERARCHY
EXIT
SAVE CHANGES
YES NO
ZONES RELAY
GLOBAL PRINT
ZONES
TYPE OUTPUT
STD LATCHING INDICATE STANDARD LATCHING AVF I BELL NON LATCH IB GENERAL NON LATCH 20S IBG ACF OUT TIME DELAY 10S IBGA BRIGADE 1 TIME DELAY 20S IBGA BRIGADE 2 TIME DELAY 30S IBGA BRIGADE 1 & 2 TIME DELAY 40S TIME DELAY 50S TIME DELAY 60S
P/N 10069 ECN08-0066
Page 30 IFS-2600 Installation & Programming Manual
RELAYS
TYPE MAPPING ISOLATE RELAY ANCILLARY OUTPUT (ACF) BRIGADE RELAY #1 BRIGADE RELAY #2 FAULT RELAY MAINS FAIL RELAY GENERAL ALARM RELAY BELL OUTPUT DOOR HOLDER RELAY MAP - AND (00)(00)(00)(00)(00) MAP - OR (00)(00)(00)(00)(00) MAP - FAULT (00)(00)(00)(00)(00) MAP – ISOLATE (00)(00)(00)(00)(00) MAP – ISOLATE / FAULT (00)(00)(00)(00)(00) DOOR SWITCH RESET
GLOBAL
ACF AVF RELAY TIME
NON-LATCHING ND DISABLED MAP RELAY (XX) >>> (DD) / (MM) / (YY) LATCHING ND 2 MINUTES FROM ZONE XX (HH) : (MM) NON-LATCHING NE 3 MINUTES LATCHING NE 4 MINUTES
5 MINUTES
ND: = NORMALLY DE-ENERGISED NE: = NORMALLY ENERGISED
PRINT
PRINT
PRINTS OUT CURRENT CONFIGURATION
MAIN MENU
(ZONES) RELAYS
GLOBAL PRINT
Use the "NEXT" & "PREVIOUS" keys to scroll through "ZONES" "RELAYS" "GLOBAL" "PRINT" and wrap around. Once the desired option has been highlighted, pressing the "SELECT" button will select it.
Pressing "EXIT" at this stage will exit programming mode.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 31
EXIT PROGRAMMING MODE
SAVE CHANGES YES (NO)
Use the "NEXT" & "PREVIOUS" keys to scroll through "YES" & "NO". Once the desired option has been highlighted, pressing the "SELECT" button will select it.
Highlighting "YES" and pressing "SELECT" will write all changes made to the system memory (E2ROM) and the panel will then restart.
WARNING!! The above action cause the panel to drop any door holders / air-conditioning if connected. Highlighting "NO" and pressing "SELECT" will ignore any changes made to the programming and exit back to
normal panel operation without restarting.
Note: This does not apply to saving changes to the time. Changes to time are saved immediately the
select key is pressed when in the time adjustment menu.
ZONE PROGRAMMING
SELECT ZONE #
SELECT ZONE #
(ALL)
Use the "NEXT" & "PREVIOUS" keys to scroll through "ALL" "1" "2" "3" Up to the maximum number of zones fitted and then wrap around. Once the desired zone number has been highlighted, pressing the "SELECT" button will select it. Pressing "EXIT" at this stage will return to main menu.
ZONE SELECTED
ZONE # ALL
(TYPE) OUTPUT
Use the "NEXT" & "PREVIOUS" keys to scroll through "TYPE" & "OUTPUT". Once the desired option has been highlighted, pressing the "SELECT" button will select it. Pressing "EXIT" at this stage will return "SELECT ZONE #".
ZONE TYPE
ZONE # ALL TYPE
STD LATCHING
Use the "NEXT" & "PREVIOUS" keys to scroll through
P/N 10069 ECN08-0066
STD LATCHING STD LATCHING AVF NON LATCH NON LATCH 20S TIME DELAY 10S TIME DELAY 20S TIME DELAY 30S TIME DELAY 40S TIME DELAY 50S TIME DELAY 60S
Page 32 IFS-2600 Installation & Programming Manual
Once the desired option has been highlighted, pressing the "SELECT" button will select it. Making a selection or pressing "EXIT" will return to zone selected.
Note: The option previously set is displayed in brackets and is the first to be displayed. Previously set options will not be displayed if "ALL" is selected.
A function of “BELL” also operates the WARNING SYSTEM.
ZONE OUTPUT CONFIGURATION
ZONE #ALL OUTPUT
IBGA BRIG 1&2
Use the "NEXT" & "PREVIOUS" keys to scroll through:
INDICATE I BELL IB GENERAL IBG ACF OUT IBGA BRIGADE 1 IBGA BRIGADE 2 IBGA BRIG 1&2
Once the desired option has been highlighted, pressing the "SELECT" button will select it. Pressing "EXIT" at this stage will return to "Zone Selected".
Note: The option previously set is displayed in brackets and is the first to be displayed. Previously set options will not be displayed if "ALL" is selected.
A function of “BELL” also operates the WARNING SYSTEM.
RELAY PROGRAMMING MODE
SELECT RELAY #
SELECT RELAY#
(ALL)
Use the "NEXT" & "PREVIOUS" keys to scroll through "ALL" "1" "2" "3". Up to 64 and then wrap around. Once the desired relay number has been selected, pressing the "SELECT" button will select it. Pressing "EXIT" at this stage will return to main menu.
RELAY SELECTED
RELAY #ALL
(TYPE) MAPPING
Use the "NEXT" & "PREVIOUS" keys to scroll through "TYPE" & "MAPPING". Once the desired option has been highlighted, pressing the "SELECT" button will select it. Pressing "EXIT" at this stage will return to "Select Relay #".
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 33
RELAY TYPE
RELAY #ALL TYPE
(GENERAL)
Use the "NEXT" & "PREVIOUS" keys to scroll through:
ISOLATE ANCILLARY BRIGADE 1 BRIGADE 2 FAULT MAINS FAIL GENERAL BELL DOOR HOLDER MAP -AND­MAP -OR­MAP –FAULT­MAP –ISOLATE­MAP -ISOLATE/FLT­DOOR SWITCH RESET
Once the desired option has been highlighted, pressing the "SELECT" button will select it. Making a selection or pressing "EXIT" will return to "Relay Selected".
Note: The option previously set is displayed in brackets and is the first to be displayed. Previously
set options will not be displayed if "ALL" is selected.
RELAY MAPPING
RELAY #1 MAP
(00) 00 00 00 00
** Relay mapping can only be selected if the relay is set as a MAP type. These 5 entry fields represent the zone numbers that the relay is to be mapped to and will be activated from. Use the "NEXT" and "PREVIOUS" keys to increment/decrement the zone number within the brackets. Use the "ENTER" key to move to the next field. Fields may be changed as required and set by pressing
"SELECT". Any fields left as (00) will be ignored. Pressing "EXIT" at this stage will return to "RELAY # ".
Note: The option previously set is displayed in brackets and is the first to be displayed. Previously set options will not be displayed if "ALL" is selected.
GLOBAL PROGRAMMING
(ACF) AVF
RELAY TIME
Use the "NEXT","PREVIOUS" & "SELECT" keys to select. Pressing "EXIT" will return to "Main Menu".
P/N 10069 ECN08-0066
Page 34 IFS-2600 Installation & Programming Manual
ACF OUTPUT
ACF OUTPUT
(NON-LATCH ND)
Use the "NEXT" & "PREVIOUS" keys to scroll through:
LATCHING ND
NON-LATCH NE
LATCHING NE
Note: The option previously set is displayed in brackets and is the first to be displayed.
ND = Normally De-energised i.e.: Output is not energised until an alarm occurs. NE = Normally energised i.e.: Output is energised and then is de-energised once an alarm occurs.
AVF
AVF TIMEOUT
(3 MINUTES)
Use the "NEXT" & "PREVIOUS" keys to scroll through:
DISABLED 2 MINUTES 3 MINUTES 4 MINUTES 5 MINUTES
Note: The option previously set is displayed in brackets and
is the first to be displayed.
RELAY (GLOBAL RELAY UNITY MAP)
MAP RELAY (XX) >> FROM ZONE (XX)
Use the "NEXT" & "PREVIOUS" keys to change the first relay to start from, together with the matching zone. Use the “ENTER” key to toggle between the two and press “SELECT” once finalised. “Exit” will abort unity map.
This function will start programming relays starting from the relay number specified in a 1 to 1 configuration with zones starting from the first zone number specified.
Example 1: if the above table was to look like this:
MAP RELAY (10) >> FROM ZONE (01)
Then relay #10 would be set as MAP OR with its mapping as (01) 00 00 00 00, relay #11 would be set as MAP OR with it’s mapping set as (02) 00 00 00 00 and so on all the way up to relay #64. Relays number 1-through 9 remains unaffected by this function.
Example 2: if the above table was to look like this:
MAP RELAY (01) >> FROM ZONE (09)
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 35
Then relay #1 would be set as MAP OR with its mapping as (09) 00 00 00 00, relay #2 would be set as MAP OR with it’s mapping set as (10) 00 00 00 00 and so on all the way up to relay #64.
Note: In example 2, zone number 64 is reached and there are still more relays to go. (I.e. we are only at
relay #56) the programming stops at this point and any relays not yet programmed will be left in their previous programmed mode and are unaffected by this function.
PRINT PROGRAMMING DATA
Prints the programming data currently stored in RAM, including all changes made (they may have not yet been written to the E2ROM).
Output is printed directly onto the serial printer if fitted.
TIME (DATE & TIME)
The current DATE & TIME will be displayed as DD/MM/YY (in 24h format) Use the PREVIOUS” & NEXT” keys to increment or decrement the number highlighted by brackets. The ENTER key will move to the next field. When finished, the SELECT key must be pushed to store the date/time.
Note:
The Date/Time data is saved when the Select key is pushed. DO NOT select “Save Changes “Y” as this will restart (and drop any door holders / air­conditioning if connected).
P/N 10069 ECN08-0066
Page 36 IFS-2600 Installation & Programming Manual
APPENDIX A
DESCRIPTION OF ALARM ZONE TYPES
Different zone types can be selected using the programming mode. Each zone can be selected as any one of the following:
Type Description Input Delay
1 Standard Latching 2 seconds 2 Standard Latching 2 seconds with AVF 3 Non Latching 2seconds 4 Non Latching 20 seconds 5 Time Delay 10 seconds 6 Time Delay 20 seconds 7 Time Delay 30 seconds 8 Time Delay 40 seconds 9 Time Delay 50 seconds 10 Time Delay 60 seconds
LATCHING TYPE
Once an alarm condition is received from the detector, the alarm zone will start a timer, if after 2 seconds the detector is still activated the alarm zone will register an alarm condition. Indicators will illuminate and alarm functions are initiated immediately, unless zone is set as AVF - refer Appendix C. The alarm zone will remain in alarm until manually reset.
A reset is performed by interrupting the power to the detector for 0.5 seconds and returning the alarm zone back to its quiescent state. If an alarm is still present in the detector area, the detector will re-activate and the 2-second timer will be re-initiated.
NON LATCHING TYPE
A temporary actuation device (e.g. Flow Switch) is usually connected to this type of alarm zone. Once a signal has been received CONTINUOUSLY for 2 seconds or 20 seconds (dependant on programming) an alarm will be registered causing the alarm LED to flash and alarm functions will be performed as programmed.
The alarm group will remain in alarm until the actuating device no longer reports a signal. When actuating device signal is clear, the alarm is cleared, causing the zone to power down for 0.5 seconds and return back to normal state.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 37
TIME DELAY AZF
The time delay AZF zone can be preset to any one of 6 time delays in the initial setup. This type of zone is used for AS1668 smoke detection zones. Zone timing etc is as per AS1668-1991.
Example: Timer #1 = 60 seconds Once the first alarm is received, the alarm LED is turned on steady; this indicates "PARTIAL ALARM"
condition. The detector is then reset (by removing its power for 0.5 seconds) and a timer is also started for 60 seconds
(TIMER#1). Another timer of 10 seconds (TIMER#2) is also started. The zone must respond again within this 10 seconds (TIMER#2) to register another alarm.
Failure to receive another alarm within this 10-second period will return the zone back to its normal state immediately and extinguish the alarm LED.
If an alarm is received, the detector is reset again and TIMER#2 is also reset. This monitoring continues until the 60-second timer (TIMER#1) has elapsed and then the NEXT alarm signal
will trip the zone into "FULL ALARM". This is the stage at which all mapped relays, bells etc. will operate. When "FULL ALARM" condition is reached, a third timer (TIMER#3) of 70 seconds is started. This timer is
used to prevent "hunting" of air conditioning fans as specified in AS1668
TIMER#2 is kept operating and alarm signals are still to be received as per previous. Alarm signals are required continually to keep the zone in "FULL ALARM". Each time another alarm is received Timer#3 is restarted (i.e. 70 seconds)
Failure to comply with TIMER#2 will result in the zone being returned back to its NORMAL state once TIMER#3 has elapsed.
P/N 10069 ECN08-0066
Page 38 IFS-2600 Installation & Programming Manual
APPENDIX B
ZONE OUTPUT CONFIGURATIONS
Once a zone has alarmed, its output functions as programmed to one of the following output types.
Type Output Description 1 Indicate Only 2 Indicate, Bell 3 Indicate, Bell, General Alarm 4 Indicate, Bell, General Alarm, Ancillary 5 Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1 6 Indicate, Bell, General Alarm, Ancillary, Brigade Relay #2 7 Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1, & Brigade Relay #2
NOTE: A function of “BELL” also operated the WARNING SYSTEM. Refer to technical specification for descriptions of output types. The zone can also be programmed to operate one (1) or more relay contacts through the use of the relay
mapping output feature.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 39
APPENDIX C
ALARM VERIFICATION FACILITY (AVF)
Alarm verification (AVF) is a facility used to minimise false alarms. AVF only applies to the zones programmed for the AVF function.
GLOBAL PROGRAMMABLE OPTIONS
AVF TIMEOUT
Disabled 2 Minutes 3 Minutes 4 Minutes 5 Minutes
Operation is as follows: If a zone is programmed as AVF and it registers an alarm, no alarm functions are performed, if it is the first
AVF zone in alarm. This zone and all other zones programmed as AVF zones are reset by shutting down power to their detectors
for 12 seconds, the power is then restored and the zones are re- enabled. The alarm verification zones are now in "alert" mode. Any AVF zone going into alarm within the pre-selected
timeout period (2,3,4,5 minutes) will then cause an immediate alarm condition with all the programmed output functions being initiated.
If no alarm is received within this period, the AVF zones are removed from the "alert" mode and returned to normal. A further alarm will re-initiate the reset sequence etc.
Other zones are unaffected by the actions of AVF zones. They will all function as normal, regardless of AVF zone status.
If the timeout period is disabled, the alarm will transmit instantly thus making the AVF non-functional.
P/N 10069 ECN08-0066
Page 40 IFS-2600 Installation & Programming Manual
APPENDIX D
ANCILLARY TRIP (ACF)
The ancillary trip is used for the shutting down of air conditioning systems etc. in the event of a fire.
GLOBAL PROGRAMMABLE OPTIONS
ANCILLARY TRIP (ACF)
NON-LATCHING ND
LATCHING ND
NON-LATCHING NE
LATCHING NE The ancillary trip can be programmed as latching or non- latching depending on the application. It call also be programmed as normally energised or normally de-energised. If a zone is programmed to operate the ancillary trip, an alarm condition will energise the ancillary trip until the
alarm is removed (if non-latching), or until the alarm is removed and the ACF is manually reset via the keypad (latching).
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 41
APPENDIX E
RELAY OUTPUT MAPPING
A total of 64 expansion relays can be fitted to the IFS-2600. Each relay can be individually programmed to mimic any of the following;
STANDARD OUTPUTS WHICH MAY BE MIMICED
ANCILLARY OUTPUT (ACF) BRIGADE ALARM RELAY #1 BRIGADE ALARM RELAY #2
*
FAULT RELAY (NORMALLY ENERGISED)
*
MAINS FAIL RELAY (NV) (NORMALLY ENERGISED) ISOLATE RELAY GENERAL ALARM RELAYS BELL OUTPUT DOOR SWITCH RESET DOOR HOLDER RELAY FAULT/ISOLATE
When mapping to a normally energised relay, take care to ensure that connections take into account the normally energised state of the relay.
Alternatively, the expansion relay(s) can be mapped to provide customised logic to suit specific installations:
AND MAPPING
AND MAPPING allows the relay output to be programmed for a combination of up to 5 zones, and only after they all go into alarm, will the relay operate.
AND MAPPING is useful for applications which have special shutdowns, multiple risk Gas Facilities etc.
OR MAPPING
OR MAPPING works similarly. This function will cause the relay to operate if any one of up to five (5) zones go into alarm, the relay will operate.
If the relay map options are set as "01" "02" "03" "00" "00", zones 1 or 2 or 3 in alarm will cause the relay to operate.
OR MAPPING is useful for applications which have special shutdowns, zoned mimic outputs etc.
FAULT MAPPING
FAULT MAPPING works the same as OR mapping of alarm except it relates to the fault flag on each zone instead of the alarm flag. This function will cause the relay to operate if any one of up to five (5) zones go into fault.
If the relay map options are set as "01" "02" "03" "00" "00", then zones 1 or 2 or 3 going into fault, will cause the relay to operate.
P/N 10069 ECN08-0066
Page 42 IFS-2600 Installation & Programming Manual
FAULT/ISOLATE MAPPING
FAULT/ISOLATE MAPPING works the same as OR mapping of alarm except it relates to the fault/isolate flag on each zone instead of the alarm flag. This function will cause the relay to operate if any one of up to five (5) zones go into fault/put in isolate.
If the relay map options are set as "01" "02" "03" "00" "00", then zones 1 or 2 or 3 going into fault/(or are manually put in isolate) will cause the relay to operate.
ISOLATE MAPPING
ISOLATE MAPPING works the same as or mapping of alarm except it relates to the isolate flag on each zone instead of the alarm flag. This function will cause the relay to operate if any one of up to five zones is put in isolate.
If the relay map options are set as "01" "02" "03" "00" "00", then zones 1 or 2 or 3, if put in isolate will cause the relay to operate.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 43
APPENDIX F
GLOSSARY OF TERMS
AS-4428.1 Australian standard for; -
Automatic Fire Detection and Alarm Systems Control and Indicating Equipment.
AS-4428.1 Australian standard for; -
Automatic Fire Detection and Alarm Systems Power Supply Units.
AS-1670 Australian standard for; -
Automatic Fire Detection and Alarm Systems System Design Installation and Commissioning.
AS-1668.1 Australian standard for; -
SAA Mechanical Ventilation and Air Conditioning Fire Precautions in Buildings with Air­handling Systems.
AZF Alarm Zone Facility (zone) MAF Master Alarm Facility ACF Ancillary Control Facility AVF Alarm Verification Facility ISOL Isolate FLT Fault ZONE Alarm Zone Facility DET Detector LED Light Emitting Diode LCD Liquid Crystal Display A/C Air Conditioning AC Alternating Current DC Direct Current V Voltage A Amps FIP Fire Indicator Panel N/L Non Latching TD Time Delay STD Standard SBY Standby BR1 Brigade Relay 1 BR2 Brigade Relay 2 NV AC Fail Relay IS Isolate GEN General Alarm Contacts D/H Door Holder RLY Relay
P/N 10069 ECN08-0066
Page 44 IFS-2600 Installation & Programming Manual
APPENDIX G
SUMMARY OF TERMINATIONS AND CAUTIONS
MCP LOOP
Used for the looping of the manual call point to a particular zone chosen for indication. This is achieved by wiring from the zone, to the MCP, to the MCP loop then out to the field with the EOL across the last detector. The MCP is the first device on the circuit and both fault and alarm conditions will be indicated.
DETECTION ZONES
Refer to list of compatible actuation devices for detectors which may be used. Any other hard contact device may be used on these detection zones. An end of line resistor (E.O.L) of 4K7 ohms is required.
RELAY OUTPUTS
Relay outputs are voltage free change over contacts rated at 24VDC 1Amp (resistive). DO NOT attempt to switch 240VAC with these relay contacts.
Note: RelayContacts Shown At Terminals (NC, C, NO) Are For The Relay In a De-energised State.
BELL OUTPUTS
This output is fused at 1 Amp and can drive up to 10 NIFS bells as specified. Output is also monitored and if no bells are connected an EOL resistor (4K7 ohms) is required across the output terminals.
ACF OUTPUTS
This output is fused at 1 Amp. Output is also monitored and if no ancillary devices are connected, an EOL resistor (4K7 ohms) is required across the output terminals.
WARNING SYSTEM
Connection for warning systems such as Occupant Warning System or electronic sounders.
DOOR HOLDER OUTPUTS
When a door holder transformer is fitted to the panel, this output becomes functional. Output is rated at 3 Amps maximum and can power up to 30 NIFS style door holders continuously. (Nom. 80mA each). Output is separately fused at 3A (FS-1). Jumper JP3 if fitted will disable this output, i.e. 24V DC output all the time. The Door Holder Output can be isolated using the ACF Isolate function.
AUXILIARY POWER & MIMIC POWER
A total auxiliary power draw of 500mA is available from the auxiliary power and mimic power terminals. This output is fused at 1 Amp (FS-3) and is battery backed.
MAF ISOL & TRANSPONDER 0V
A 0V signal is switched back from the transponder test switch and is used for indication purposes at the FIP. This will indicate as MAF ISOLATED and initiate a common fault. It can also used for an external device to indicate a fault.
MIMIC DATA & CLOCK
These outputs together with the mimic power terminals are used to serially communicate with the mimic panels when fitted. EOL resistor is not required on these lines.
NOTE: Firmware must be Version 6 or above for mimic operation
AC INPUT
Mains step down transformer output (30VAC) is connected at these terminals. DO NOT connect 240VAC to these terminals.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 45
BATTERY
The 24V batteries are connected at these terminals. Reverse polarity will cause serious and permanent damage to the equipment.
DOOR HOLDER AC INPUT
Terminate the door holder AC transformer at these terminals. 24 VAC is the only acceptable power source at this point. DO NOT connect 240VAC at this point.
OUTPUT RELAYS
STANDBY (N) Normally energised, drops out when power supply (or battery supply) is below specified
voltage.
BRIGADE1 Brigade 1, defaults as energising on any alarm zone, programmable. BRIGADE2 Brigade 2, defaults as energising on any alarm zone, programmable. FAULT (N) Normally energised, drops out on any fault unless that function is isolated. AC-FAIL (N) Normallyenergised, drops out if the mains power is lost. ISOLATE Energised if any zone is isolated. GENERAL1 Energised if any zone goes into alarm GENERAL2 Energised if any zone goes into alarm
P/N 10069 ECN08-0066
Page 46 IFS-2600 Installation & Programming Manual
APPENDIX H
IFS-2600 PROGRAMMED OPTIONS
Global System Parameters Date: / /
Latch ND Non-Latch ND Latch NE Non-Latch NE
ACF Output
Disabled 2 min 3 min 4 min 5 min Alarm Verification (AVF)
Notes:
Programmed by
Place an "X" in the appropriate box = Default
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 47
ZONE TYPE PROGRAMMING Date: / /
1 2 3 4 5 6 7 8 9 10
AZF No. STD STD N/L N/L T/D T/D T/D T/D T/D T/D
2S AVF 2S 20S 10S 20S 30S 40S 50S 60S
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Place an "X" in the appropriate box = Default
P/N 10069 ECN08-0066
Page 48 IFS-2600 Installation & Programming Manual
1 2 3 4 5 6 7 8 9 10
AZF No. STD STD N/L N/L T/D T/D T/D T/D T/D T/D
2S AVF 2S 20S 10S 20S 30S 40S 50S 60S
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
Place an "X" in the appropriate box = Default
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 49
ZONE OUTPUT PROGRAMMING Date: / / AZF No.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
INDICATE I-
BELL
IB-
GENERAL
IBG­ACF
IBGA-
BR1
IBGA- BR2 IBGA-
BR1&BR2
Place an "X" in the appropriate box = Default
P/N 10069 ECN08-0066
Page 50 IFS-2600 Installation & Programming Manual
AZF No. 33
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
INDICATE I-
BELL
IB-
GENERAL
IBG­ACF
IBGA-
BR1
IBGA-
BR2
IBGA-
BR1&BR2
Place an "X" in the appropriate box = Default
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 51
RELAY OUTPUT MAPPING Date: / /
MAPPING
RLY ISO ACF BR1 BR2 FLT MAINS
FAIL
GEN BELL D/H AND OR FLT ISO ISO/
FLT
DO-ORRE-
1 2 3 4 5 6 7 8 9 10
SET
11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Place an "X" in the appropriate box = Default
P/N 10069 ECN08-0066
Page 52 IFS-2600 Installation & Programming Manual
MAPPING
RLY ISO ACF BR1 BR2 FLT MAINS
FAIL
GEN BELL D/H AND OR FLT ISO ISO/
FLT
DO-ORRE-
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
SET
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 53
APPENDIX I
TECHNICAL DRAWINGS
MAIN KEYPAD AND DISPLAY
EXPANSION DISPLAY
P/N 10069 ECN08-0066
Page 54 IFS-2600 Installation & Programming Manual
Block Connection Diagram
1
A A
MAIN PROCESSORBOARD
IFS PCB2004
ZONE DISPLAYS1-8
CABLE C3
16 ZONE
DISP
PCB816
B B
CABLE C32
INPUTS
CABLE C5
INPUTS
CABLE C8
ZONE
1-8
ZONE
9-16
2
DB-9 FEMALE
MAIN TERMINATIONBOARD
IFS PCB2005
POWER SUPPLY BOARD
PCB2006
ZONE
EXP
PCB804
OUT
IN
RELAY BOARD
IFS803
OUT
OUTPUTS
CABLE C1
P/N 130
PCB1125
MAX 120M
8 RELAY
OUTPUTS
1-8
BELL/ACF
3
4 CORE CABLE
TX, CTS, GND
4 CORE CABLE
3 CORE CABLE RX, TX, GND
MIMIC PANEL
4
SERIAL PRINTER
LAPTOP
ZONE
MAINS SUPPLY
240 V AC
240V ISOL
S/W
C C
D D
D Removed Part Numbers IP IP 21/12/05 C Revised Printer Connection IP IP 18/8/05
B REVISEDPART NUMBERS G.W. G.W. 9/3/04
Revision- reviseon CAD. Do not amendby hand Eng. App. Date
No.
1
8 ZONE
DISP
PCB816
LAST DISPLAYCAN BE 8/16 OTHERS MUST BE 16 ZONE
Copyright
Thisdocument is & shall remainthe property of
NotifierInertia Fire Systems
Unauthorised use of this document in anyway is prohibited.
=DocumentFullPathAndName
+ +
12V BATTERY 12V BATTERY
INPUTS
32-40
240V/30VAC
100 VA
TRANSFORMER
2600/DHTX
100 VA
TRANSFORMER
OPTION
-
C
O
DrawingFile No.
ZONE
EXP
PCB804
2
PANEL POWER
D/HOLDER POWER
-
IN
IN OUT
MAX 8 PCB803
RELAY BOARD
IFS803
RELAY BOARD
IFS803
OUT
CABLE C3
8 RELAY OUTPUTS
9-16
CABLE C3
8 RELAY OUTPUTS
32-40
CABLE C9
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153
AUSTRALIA Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
IFS 810 MIMIC DRV IFS 811B IND BRD
IFS 812 DISPLAY BRD
(1 FOR EACH 8 ZONES)
1 1
Sheet:
Of:
Drawn/ Traced
Approved ThisDrawingmust not be used for Construction
3
unlesssigned as approved
Engineer
14/08/03 I.P.
Design
Title
IFS2600
BLOCK CONNECTION DIAGRAM
Size
Drg. No.
L2600-1
4
A4
P/N 10069 ECN08-0066
Rev
D
IFS-2600 Installation & Programming Manual Page 55
System Sensor Conventional Detector Connection Diagram
1
2
3
4
A A
+
TO PANEL
-
DET A DET B
4
5
1
3
2
RIP
+R +D
-D
1
BASE B401
5
2
BASE B401
4
3
DET B
5
1
4
3
2
+R +D
-D
RIP
4K7 EOL
CONVENTIONAL DETECTOR CONNECTION DIAGRAM
B B
+
TO PANEL
-
C C
BASE A
5
1
BASE B401R
PROBE A
4
3
2
SEALED PROBE
SEALED DETECTOR CONNECTION DIAGRAM ( NORMAL HEAD NOT CONNECTED )
BASE B
4
5
1
3
2
BASE B401R
Current limited 10 mA Not current limited (3-24 V)
Common Return
PROBE B
SEALED PROBE
4K7 EOL
470R
+R
+D
-D
+R
+D
-D
REMOTE INDICATOR
D D
Revision- reviseon CAD. Do not amendby hand Eng. App. Date
No.
1
Copyright
Thisdocument is & shall
remainthe property of
NotifierInertia Fire Systems
Unauthoriseduse of this documentin any way is prohibited.
=DocumentFullPathAndName
C
O
Drawing File No.
2
7 Columbia Court, Norwest Business Park BaulkhamHills NSW 2153
AUSTRALIA Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
1 1
Sheet:
Of:
Drawn/ Traced
Approved ThisDrawingmustnot be used for Construction
unlesssigned as approved
Engineer
I PERRY I PERRY
Design
I PERRY
Title
SYSTEM SENSOR CONVENTIONAL DETECTOR CONNECTION DIAGRAM
Size
Drg. No.
SS-DET
4
A4
P/N 10069 ECN08-0066
Rev
A
Page 56 IFS-2600 Installation & Programming Manual
Hochiki Conventional Detector Connection Diagram
1
2
3
4
DET A
A A
+
TO PANEL
3
2
1
4
5
67
+R +D
RIP
-D
DET B
1
DET C
3
2
4
5
67
3
2
1
4
5
67
+R +D
-D
RIP
4K7 EOL
­CONNECTION FOR STANDARD DETECTORS AND BASES
B B
DET A
DET B
DET C
+
BLUE
WHITE
TO PANEL
L CS
RED
-
C C
+R +D
-D
L CS
L CS
CONNECTION FOR DFG-60BLKJ SEALED DETECTOR
RIP
+R +D
-D
RIP
4K7 EOL
470R
Current limited 10 mA Not current limited (3-24 V)
Common Return
+R
+D
-D
+R
+D
-D
REMOTE INDICATOR
D D
Revision- reviseon CAD. Do not amendby hand Eng. App. Date
No.
1
Copyright
Thisdocument is & shall remainthe property of
NotifierInertia Fire Systems
Unauthorised use of this document in anyway is prohibited.
=DocumentFullPathAndName
C
O
DrawingFile No.
2
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153
AUSTRALIA Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
1 1
Sheet:
Of:
Drawn/ Traced
Approved ThisDrawingmust not be used for Construction
unlesssigned as approved
Engineer
I PERRY I PERRY
Design
I PERRY
Title
HOCHIKI CONVENTIONAL DETECTOR CONNECTION DIAGRAM
Size
Drg. No.
HOC-DET
4
A4
P/N 10069 ECN08-0066
Rev
A
IFS-2600 Installation & Programming Manual Page 57
NOTE:
Ancillary Connection Diagram
1
PCB1125maybe omittedif the
ancillarydevice is high impedance or contains an inbuilt
A A
IFS2600
TERMINATION
PCB2004
B B
C C
A
N
240 V AC
E
N/C
COM
GEN2
N/O +24
0V
WARN
+24
0V
BELL
+24
0V
ACF
+24
AUX
0V
TP 0V
MAF ISO
CLK
DATA
MIMIC
­+
HOLD
DOOR
DOOR
INPUT
HOLD
DOOR HOLDER TRANSFORMER2600/DHTX
240V/24V
TRANSFORMER
reverseprotectiondiode.
In this case a 4K7 EOL must be
fittedto the last device on the circuit.
1.5 OHM 5W
FITTED WHEN STROBEUSED
2
DOOR HOLDERS
3
+
IN
-
+
OUT
-
PCB1125C REMOVERESISTOR R1
EXCEPT ON LAST PCB
+
IN
-
+
OUT
-
PCB1125C R1 TO BE FITTED ON
LAST PCB ONLY
+
IN
-
+
OUT
-
PCB1125C REMOVERESISTOR R1
EXCEPT ON LAST PCB
+
IN
-
+
OUT
-
PCB1125C
R1 TO BE FITTED ON LAST PCB ONLY
+
IN
-
+
OUT
-
PCB1125C
+
LOAD
-
+
LOAD
-
+
LOAD
-
+
LOAD
-
+
LOAD
-
4
1 2 3
D2 D1 R1
4
1ST SOUNDER
2220
SOUNDER
1 2 3
D2 D1 R1
4
+
LAST SOUNDER
2220
SOUNDER
24VDC
D2 D1 R1
D2 D1 R1
BELL
STROBE
+
-
D2 D1 R1
RELAY
FAN
D D
Revision- revise on CAD. Do not amend by hand Eng. App. Date
No.
1
Copyright
Thisdocument is & shall remainthe propertyof
NotifierInertia Fire Systems
Unauthoriseduse of this document in any way is prohibited.
=DocumentFullPathAndName
C
O
Drawing File No.
2
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153 AUSTRALIA Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
1 1
Sheet:
Of:
Drawn/ Traced
Approved ThisDrawingmustnot be used for Construction
unlesssignedas approved
23/8/05
I PERRY
Engineer Design
I PERRY
Title
IFS2600 TYPICAL
ANCILLARY CONNECTION
Size
Drg.
A4
26-ANC-CON
No.
4
P/N 10069 ECN08-0066
Rev
A
Page 58 IFS-2600 Installation & Programming Manual
ASE Connection Diagram
1
A A
B B
IFS2600
TERMINATION
PCB2004
2
N/C
COM
N
N/O
STANDBY
N/C
COM
N/O
BRIGADE 1
N/C
COM
N/O
BRIGADE 2
N/C
COM
N
FAULT
N/O N/C
N
COM
AC-FAIL
N/O N/C
COM
ISOLATE
N/O
BR1
AC FAIL
FAULT
ISOLATE
N
N
POWER
ASE
3
4
ASE BRACKET
CODE RED #10115 ROMTEK 10117 TYCO #10116
+24
0V
C C
D D
Revision- revise on CAD. Do not amend by hand Eng. App. Date
No.
1
Copyright
Thisdocumentis & shall
remainthe property of
NotifierInertia Fire Systems
Unauthoriseduse of this document in any wayis prohibited.
=DocumentFullPathAndName
AUX
C
O
Drawing File No.
2
7 Columbia Court, Norwest Business Park BaulkhamHills NSW 2153
AUSTRALIA Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
1 1
Sheet:
Of:
Drawn/
22/8/05 I.P.
Traced
Approved ThisDrawingmustnot be used for Construction
unlesssigned as approved
Engineer Design
Title
2600
ASE CONNECTION
Size
Drg.
A4
No.
26-ASE
4
P/N 10069 ECN08-0066
Rev
A
IFS-2600 Installation & Programming Manual Page 59
NOTE:
Maximum capacity is 10 sounders
Auto Changeover Dual Sounder Connection Diagram
1
A A
B B
C C
PCB2004
N/O +24
0V
+24
BELL
0V
+24
ACF
0V
+24
AUX WARN
0V
IFS2600
TERMINATION
IFS958 RELAYBOARD
+24V
0V
2
NOTE: INSTALL LINK JP1 FOR AUTO
CHANGEOVERFROM ALERT TO EVAC
MONITOREDDRIVER BOARD
IFS 993
AL
0V
EVAC
FAULT COM
NO
COM
NC
NO
COM
NC
WARNSYS EOL
4K7
FAULT N/O
+24
TERM A
3
or 4 strobes
ALERT STROBE
TERM B
(AMBER)
RED REDBLACK BLACK
0V 0V+24V+24V
EVAC STROBE
(RED)
1234
4
1K8
EOL
1234
D D
No.
P/N 10069 ECN08-0066
Revision- revise on CAD. Do not amendby hand Eng. App. Date
1
23/1/04B ADDED RELAY G.W. G.W.
Copyright
This documentis & shall
remainthe property of
NotifierInertia Fire Systems
Unauthoriseduse of this document in any wayis prohibited.
=DocumentFullPathAndName
C
O
Drawing File No.
2
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153
AUSTRALIA Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
DUAL TONE AS2220
SOUNDER
1 1
Sheet:
Of:
Drawn/ Traced
Approved This Drawingmustnot be used forConstruction
unlesssigned as approved
23/8/05
I PERRY
Engineer Design
I PERRY
DUAL TONE AS2220
SOUNDER
Title
IFS2600 MONITORED DUAL SOUNDER AUTO CHANGEOVER
Size
Drg.
No.
2600-DUAL AUTO-SNDR
4
A4
Rev
A
Page 60 IFS-2600 Installation & Programming Manual
NOTE:
Maximumcapacity is 10 sounders
Auto Change Over Dual Sounder Connection Diagram
1
A A
IFS2600
TERMINATION
PCB2004
N/O
B B
+24
0V
+24
BELL
0V
+24
ACF
0V
+24
AUX WARN
0V
ALERT ACTIVATION
IFS958 RELAY BOARD
+24V
0V
NO
2
NOTE: REMOVE LINK JP1 FOR MANUAL
CHANGEOVERFROM ALERT TO EVAC
MONITOREDDRIVER BOARD
IFS 993
AL
0V
EVAC
FAULT COM
COM
NC
NO
COM
NC
WARNSYS EOL
4K7
FAULT N/O
+24
TERM A
3
or 4 strobes
ALERT STROBE
TERM B
(AMBER)
RED REDBLACK BLACK
0V 0V+24V+24V
EVAC STROBE
(RED)
4
1K8
EOL
C C
D D
No.
P/N 10069 ECN08-0066
NC
IFS803 RELAY BOARD
Revision- revise on CAD. Do not amend by hand Eng. App. Date
COM
NO
EVAC ACTIVATION
1
Copyright
Thisdocument is & shall remainthe propertyof
NotifierInertia Fire Systems
Unauthoriseduse of this document in any way is prohibited.
=DocumentFullPathAndName
C
O
Drawing File No.
2
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153 AUSTRALIA Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
1234
1234
DUAL TONE AS2220 DUAL TONE AS2220
SOUNDER
1 1
Sheet:
Of:
Drawn/ Traced
Approved ThisDrawingmustnot be used for Construction
unlesssignedas approved
23/8/05
I PERRY
Engineer Design
I PERRY
SOUNDER
Title
IFS2600 MONITORED DUAL SOUNDER MANUAL CHANGEOVER
Size
Drg. No.
2600-DUAL MANUAL-SNDR
4
A4
Rev
A
IFS-2600 Installation & Programming Manual Page 61
MIMIC Connection Diagram
1
2
3
4
PCB812 PCB812
A A
ZONES 1-8 ZONES 9-16
IFS2600 TERMINATION BOARD
PCB810 FITTED WITH
PCB812
ZONES 17-24
IFS2600 MIMIC DRIVER
N/O +24
B B
C C
TP 0V
MAF ISO
MIMIC
DOOR
0V
WARN
+24
BELL
0V +24
ACF
0V +24
AUX
0V
Max 120 Meters
4/0.75mm cable
POWER AND SIGNAL RETURN
SERIAL BUS
HOLD
CLK
DATA
­+
33-40 41-48 49-56 57-64
DATA
CLK
+24
0V
1-8 9-16 17-24 25-32
MIM/EXT/26 MIM/EXT/26
DOOR
INPUT
HOLD
MIM/26/KIT
FOR 8 ZONES
STANDARD SIZES 8, 24 AND 64 ZONES
FOR EXTRA ZONES
PCB811
D D
Revision- revise on CAD. Do not amend by hand Eng. App. Date
No.
1
Copyright
Thisdocumentis & shall
remainthe propertyof
NotifierInertia Fire Systems
Unauthoriseduse of this document in any way is prohibited.
=DocumentFullPathAndName
C
O
Drawing File No.
2
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153
AUSTRALIA Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
1 1
Sheet:
Of:
Drawn/ Traced
Approved ThisDrawingmust not be used for Construction
unlesssigned as approved
Engineer
2/2/04 G.W.
Design
Title
Size
MIM/26/KIT
Drg.
A4
No.
26-MIM-CON
4
P/N 10069 ECN08-0066
Rev
A
Page 62 IFS-2600 Installation & Programming Manual
Single Fan Connection Diagram
1
2
3
4
FIREPANEL
A A
FIELDWIRING
FAN TERMINATION BOARD
AUX POWER
AUX +24 AUX 0V
FAN START RELAY
B B
FAN STOP RELAY
C C
+24 0V START1 STOP1
PCB1128
RIBBON CABLE
+24
START
STOP
RUN
STOP
FLT
FAN 1
OFF
AUTO
COMMON+VE
CONTROL
INDICATION
RUN
STOP
FAULT
ON
START STOP
FAN RUNNING FAN STOPPED AND POWER AVAILABLE FAN FAULT OR NO POWER AVAILABLE
* NOTE
THE MECHANICAL SERVICES BOARD MUST BE CONFIGURED TO HAVE
FRONT PANEL CONTROL
THE STOP RELAY TO TAKE PRECEDENCE OVER THE START RELAY
D D
Revision- revise on CAD. Do not amendby hand Eng. App. Date
No.
1
Copyright
This documentis & shall
remainthe propertyof
NotifierInertia Fire Systems
Unauthorised use of this document in anyway is prohibited.
=DocumentFullPathAndName
C
O
DrawingFile No.
2
7 Columbia Court, Norwest Business Park BaulkhamHills NSW 2153
AUSTRALIA Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
1 1
Sheet:
Of:
Drawn/ Traced
Approved ThisDrawingmustnot be used forConstruction
unlesssigned as approved
Engineer
19/8/05 I PERRY
Design
Title
Size
SINGLE FAN (GENERAL) CONTROL
Drg.
A4
2600-DUAL FAN
No.
4
P/N 10069 ECN08-0066
Rev
A
IFS-2600 Installation & Programming Manual Page 63
Dual Fan Connection Diagram
1
2
3
4
FIREPANEL
A A
FIELDWIRING
FAN TERMINATION BOARD
AUX POWER
AUX +24 AUX 0V
FAN 1 START RELAY
B B
FAN 1 STOP RELAY
FAN 2 START RELAY
FAN 2 STOP RELAY
C C
+24 0V START1 STOP1 START2 STOP2
PCB1102
*NOTE
FOR SINGLE CONTROL REMOVE SW2 LINK SW1 A & B TO SW2 A, B
+24
START
STOP
RUN
STOP
FLT +24
START
STOP
RUN
STOP
FLT
RIBBON CABLE
FAN 1
OFF
AUTO
COMMON+VE
CONTROL
INDICATION
COMMON+VE
CONTROL
INDICATION
FAN 2
RUN
STOP
FAULT
ON
OFF
AUTO
RUN
STOP
FAULT
START STOP
FAN RUNNING FAN STOPPED AND POWER AVAILABLE FAN FAULT OR NO POWER AVAILABLE
START STOP
FAN RUNNING FAN STOPPED AND POWER AVAILABLE FAN FAULT OR NO POWER AVAILABLE
ON
* NOTE
THE MECHANICAL SERVICES BOARD
FAN 1
FAN 2
MUST BE CONFIGURED TO HAVE
FRONT PANEL CONTROL
THE STOP RELAY TO TAKE PRECEDENCE OVER THE START RELAY
D D
Revision- revise on CAD. Do not amend by hand Eng. App. Date
No.
1
Copyright
Thisdocumentis & shall
remainthe property of
NotifierInertia Fire Systems
Unauthoriseduse of this document in any wayis prohibited.
=DocumentFullPathAndName
C
O
Drawing File No.
2
7 Columbia Court, Norwest Business Park BaulkhamHills NSW 2153
AUSTRALIA Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
1 1
Sheet:
Of:
Drawn/ Traced
Approved ThisDrawingmustnot be used for Construction
unlesssigned as approved
Engineer
19/8/05 I PERRY
Design
Title
Size
DUAL FAN (GENERAL) CONTROL
Drg.
A4
2600-DUAL FAN
No.
4
P/N 10069 ECN08-0066
Rev
A
Page 64 IFS-2600 Installation & Programming Manual
Exhaust Fan Connection Diagram
1
2
3
4
FIRE PANEL
A A
B B
AUX POWER
AUX +24 AUX 0V
FAN STOP RELAY
(MAPPED TO ACF FOR
GENERALOR ZONED)
FAN TERMINATION BOARD
+24 0V START1 STOP1
PCB1128
+24
START
STOP
RUN
STOP
FLT
COMMON+VE
CONTROL
INDICATION
START STOP
FIELDWIRING
FAN RUNNING FAN STOPPED AND POWER AVAILABLE FAN FAULT OR NO POWER AVAILABLE
* NOTE
EITHER THE MAPPING ABOVE MAY BE USED TO STOP THE EXHAUST FAN OR THE GENERAL ACF TRIP BELOW, BUT NOT BOTH.
USE OF THE FIRE TRIP RELAY BELOW REQUIRES THAT THE MSSB
RIBBON CABLE
STOPS THE FAN.
C C
FAN 1
OFF
AUTO
RUN
STOP
FAULT
ON
* NOTE
THE MECHANICAL SERVICES BOARD MUST BE CONFIGURED TO HAVE THE STOP RELAY TO TAKE PRECEDENCE OVER THE START RELAY
FROM FIP
+24
ACF
0v
D D
Revision- reviseon CAD. Do not amend by hand Eng. App. Date
No.
1
Copyright
Thisdocumentis & shall
remainthe propertyof
NotifierInertiaFire Systems
Unauthorised use of this document in anyway is prohibited.
=DocumentFullPathAndName
C
O
Drawing File No.
2
FRONT PANEL CONTROL
PCB1125
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153
AUSTRALIA Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
+
IN
-
+
OUT
-
1 1
Sheet:
Of:
Drawn/
19/8/05 I PERRY
Traced
Approved ThisDrawingmust not be used for Construction
unlesssigned as approved
Engineer Design
+
LOAD
-
D1 R1
FIRE TRIP
RELAY
Title
EXHAUST FAN (TYPICAL)
CONTROL
Size
Drg.
No.
2600-EXH
4
A4
P/N 10069 ECN08-0066
Rev
A
IFS-2600 Installation & Programming Manual Page 65
Supply Fan Connection Diagram
1
2
3
4
FIREPANEL
A A
B B
AUX POWER
AUX +24 AUX 0V
FAN START RELAY
(MAPPEDTO ACF FOR
GENERAL OR ZONED)
FAN STOP RELAY (MAPPEDTO AIR INTAKE SMOKE DETECTOR)
FAN TERMINATION BOARD
+24 0V START1 STOP1
PCB1128
+24
START
STOP
RUN
STOP
FLT
COMMON+VE
CONTROL
INDICATION
START STOP
FIELDWIRING
FAN RUNNING FAN STOPPEDAND POWER AVAILABLE FAN FAULT OR NO POWER AVAILABLE
* NOTE
EITHER THE MAPPING ABOVE MAY BE USED TO START THE SAF OR THE GENERAL ACF TRIP BELOW, BUT NOT BOTH.
USE OF THE FIRE TRIP RELAY BELOW REQUIRES THAT THE MSSB
RIBBON CABLE
STARTS THE FAN.
C C
FAN 1
OFF
AUTO
RUN
STOP
FAULT
ON
* NOTE
THE MECHANICAL SERVICES BOARD MUST BE CONFIGURED TO HAVE THE STOP RELAY TO TAKE PRECEDENCE OVER THE START RELAY
FROM FIP
+24
ACF
0v
D D
Revision- reviseon CAD. Do not amendby hand Eng. App. Date
No.
1
Copyright
Thisdocument is & shall
remainthe propertyof
NotifierInertia Fire Systems
Unauthoriseduse of this document in anyway is prohibited.
=DocumentFullPathAndName
C
O
Drawing File No.
2
FRONT PANEL CONTROL
PCB1125
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153 AUSTRALIA Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
+
IN
-
+
OUT
-
1 1
Sheet:
Of:
Drawn/
19/8/05 I PERRY
Traced
Approved ThisDrawingmustnot be used for Construction
unlesssigned as approved
Engineer Design
+
LOAD
-
D1 R1
FIRE TRIP
RELAY
Title
SUPPLY AIR FAN (TYPICAL)
CONTROL
Size
Drg. No.
2600-SAF
4
A4
P/N 10069 ECN08-0066
Rev
A
Page 66 IFS-2600 Installation & Programming Manual
Smoke Spill Fan Connection Diagram
1
2
3
4
FIREPANEL
A A
B B
AUX POWER
AUX +24 AUX 0V
FAN START RELAY
(MAPPEDTO ACF FOR
GENERAL OR ZONED)
* NOTE
EITHER THE MAPPING ABOVE MAY
FAN TERMINATION BOARD
+24 0V START1 STOP1
PCB1128
+24
START
STOP
RUN
STOP
FLT
COMMON+VE
CONTROL
INDICATION
START STOP
FIELDWIRING
FAN RUNNING FAN STOPPED AND POWER AVAILABLE FAN FAULT OR NO POWER AVAILABLE
BE USED TO START THE SSF OR THE GENERAL ACF TRIP BELOW, BUT NOT BOTH.
USE OF THE FIRE TRIP RELAY BELOW REQUIRES THAT THE MSSB STARTS THE FAN.
RIBBON CABLE
C C
FAN 1
OFF
AUTO
RUN
STOP
FAULT
ON
* NOTE
THE MECHANICAL SERVICES BOARD MUST BE CONFIGURED TO HAVE THE STOP RELAY TO TAKE PRECEDENCE OVER THE START RELAY
FROM FIP
+24
ACF
0v
D D
Revision- reviseon CAD. Do not amend by hand Eng. App. Date
No.
1
Copyright
Thisdocumentis & shall
remainthe property of
NotifierInertia Fire Systems
Unauthoriseduse of this document in anyway is prohibited.
=DocumentFullPathAndName
C
O
Drawing File No.
2
FRONT PANEL CONTROL
PCB1125
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153
AUSTRALIA Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
+
IN
-
+
OUT
-
1 1
Sheet:
Of:
Drawn/
19/8/05 I PERRY
Traced
Approved ThisDrawingmustnot be used forConstruction
unlesssigned as approved
Engineer Design
+
LOAD
-
D1 R1
FIRE TRIP
RELAY
Title
SMOKE SPILL FAN (TYPICAL)
CONTROL
Size
Drg.
No.
2600-SSF
4
A4
P/N 10069 ECN08-0066
Rev
A
IFS-2600 Installation & Programming Manual Page 67
NOTE:
10W EVAC Connection Diagram
1
FRONT PANEL EVAC
A A
IFS2600 TERMINATION BOARD
+24
0V
WARN
+24
AUX
0V
CONTROL
2
3
10W EVAC
VOLPA
JP2JP1
PCB 908
4
SOUND
0V
PTT
PA+
FAULT
+24V COM
ALERT OUT
ALERT IN
EVAC IN
BGM EN
ALARM
EVAC OUT
BGM +
PA -
BGM -
GND
+24
COM
LINE +
B B
EXTERNAL
POWER
MONITORJP1
REMOTE
REMOTE
OUTPUT
AC INPUT
+24V
C C
D D
Revision- revise on CAD. Do not amendby hand Eng. App. Date
No.
INPUT
BATT
0V
+24V
0V
+24V
0V
1
LINK JP1
Copyright
Thisdocumentis & shall
remainthe propertyof
NotifierInertia FireSystems
Unauthorised use of this document in anyway is prohibited.
=DocumentFullPathAndName
C
O
Drawing File No.
2
4K7 5%
BGM ENABLE
( ENABLED ON
CLOSURE)
SHIELDED
SHIELDED
BGM INPUT
1V P-P
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153 AUSTRALIA Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
WHITE RED
BLACK/SHIELD BLUE
1 1
Sheet:
Of:
Drawn/ Traced
I PERRY
Approved ThisDrawingmust not be used for Construction
unlesssigned as approved
Engineer Design
MICROPHONE
WITHPTT
I PERRYI PERRY
SPEAKERSWITH 100VLINE TRANSFORMERS AND ISOLATIONCAPACITORS
TO SLAVE TWO AMPLIFIERS
TOGETHER, REMOVETHE IFS903 BOARDFROM THE SLAVE AMPLIFIERAND CONNECTJP1 ON THE MASTER TO JP2 ON THE SLAVE.
THE MICROPHONE AND BGM
MUSTONLY BE CONNECTED TO THE MASTER AMPLIFIER.
CONNECTPIN 4, P12 ON MASTER
TO PIN4 P12 ON SLAVE.
Title
IFS-2600 10 WATT CONNECTION DIAGRAM
Size
A4
Drg. No.
2600-10W
4
EOL
47K 5%
Rev
A
P/N 10069 ECN08-0066
Page 68 IFS-2600 Installation & Programming Manual
NOTE:
10W EVAC Slave Connection Diagram
1
FRONT PANEL EVAC
A A
IFS2600 TERMINATION BOARD
+24
0V
WARN
+24
AUX
0V
CONTROL
2
3
10W EVAC
VOLPA
JP2JP1
PCB 908
4
SOUND
0V
PTT
PA+
FAULT
+24V COM
ALERT OUT
ALERT IN
EVAC IN
BGM EN
ALARM
EVAC OUT
BGM +
PA -
BGM -
GND
+24
COM
LINE +
B B
EXTERNAL
POWER
MONITORJP1
REMOTE
REMOTE
OUTPUT
AC INPUT
+24V
C C
D D
Revision- reviseon CAD. Do not amend by hand Eng. App. Date
No.
INPUT
BATT
0V
+24V
0V
+24V
0V
1
LINK JP1
Copyright
Thisdocumentis & shall
remainthe propertyof
NotifierInertiaFireSystems
Unauthoriseduse of this document in anyway is prohibited.
=DocumentFullPathAndName
C
O
Drawing File No.
2
4K7 5%
CONNECTTO FAULT OUT FROM SLAVE
BGM ENABLE
( ENABLED ON
CLOSURE)
SHIELDED
SHIELDED
BGM INPUT
1V P-P
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153 AUSTRALIA Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
WHITE RED
BLACK/SHIELD BLUE
1 1
Sheet:
Of:
Drawn/ Traced
I PERRY
Approved ThisDrawingmustnot be used for Construction
unlesssignedas approved
Engineer Design
MICROPHONE
WITHPTT
I PERRYIPERRY
SPEAKERSWITH 100V LINE TRANSFORMERS AND ISOLATIONCAPACITORS
TO SLAVE TWOAMPLIFIERS
TOGETHER,REMOVETHE IFS903 BOARDFROM THE SLAVE AMPLIFIERAND CONNECTJP1 ON THE MASTER TO JP2 ON THE SLAVE.
THE MICROPHONEAND BGM
MUSTONLY BE CONNECTEDTO THE MASTER AMPLIFIER.
CONNECTFAULTOUTPUTS
TOGETHERAND MOVE THE LASTWRE ON I/O PCB TO THE FAULTTERMINALON THE MASTERAMPLIFIER.
CONNECTPIN 4, P12 ON MASTER
TO PIN4 P12 ON SLAVE.
Title
IFS-2600 10 WATT SLAVE CONNECTIONDIAGRAM
Size
A4
Drg. No.
2600-10WSLAVE
4
EOL
47K5%
Rev
A
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 69
NOTE:
30W EVAC Connection Diagram
1
FRONT PANEL EVAC
A A
CONTROL
2
3
30W EVAC
VOLPA
PCB 908
4
IFS2600 TERMINATION BOARD
B B
REMOTE
REMOTE
OUTPUT
AC INPUT
+24V
C C
A
N
E
INPUT
0V
+24V
240V/20V
TRANSFORMER
0V
+24V
EXTERNAL
BATT
0V
AC1
AC2
+24
0V
WARN
+24
AUX
0V
POWER
MONITORJP1
LINK JP1
IFS1100
POWERSUPPLY
+24V
0V
PTT
BGM EN
ALARM
EVAC OUT
FAULT
+24V COM
ALERT OUT
4K75%
0V
BGMENABLE
( ENABLED ON
CLOSURE)
ALERT IN
EVAC IN
PA+
PA -
BGMINPUT
BGM +
1V P-P
BGM -
SHIELDED
SHIELDED
JP2JP1
SOUND
GND
+24
WHITE RED
BLACK/SHIELD BLUE
COM
LINE +
MICROPHONE
WITHPTT
SPEAKERS WITH 100V LINE TRANSFORMERS AND ISOLATIONCAPACITORS
TO SLAVE TWO AMPLIFIERS
TOGETHER, REMOVETHE IFS903 BOARDFROM THE SLAVE AMPLIFIERAND CONNECTJP1 ON THE MASTER TO JP2 ON THE SLAVE.
THE MICROPHONEAND BGM
MUSTONLY BE CONNECTED TO THE MASTER AMPLIFIER.
CONNECTPIN 4, P12 ON MASTER
TO PIN4 P12 ON SLAVE.
EOL
47K5%
D D
Revision- revise on CAD. Do not amend by hand Eng. App. Date
No.
1
Copyright
Thisdocumentis & shall remainthe property of
NotifierInertia Fire Systems
Unauthoriseduse of this document in any wayis prohibited.
=DocumentFullPathAndName
C
O
Drawing File No.
2
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153
AUSTRALIA Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
1 1
Sheet:
Of:
Drawn/ Traced
Approved This Drawingmust not be used for Construction
unlesssigned as approved
I PERRY
Engineer Design
Title
IFS-2600
I PERRY25/8/05
30 WATT CONNECTIONDIAGRAM
Size
A4
Drg.
No.
2600-30W
4
P/N 10069 ECN08-0066
Rev
A
Page 70 IFS-2600 Installation & Programming Manual
NOTE:
30W EVAC Slave Connection Diagram
1
FRONT PANEL EVAC
A A
CONTROL
2
3
30W EVAC
VOLPA
PCB 908
4
IFS2600 TERMINATION BOARD
B B
REMOTE
REMOTE
OUTPUT
AC INPUT
+24V
C C
A
N
E
INPUT
0V
+24V
0V
240V/20V
TRANSFORMER
+24V
EXTERNAL
BATT
0V
AC1
AC2
+24
0V
WARN
+24
AUX
0V
POWER
MONITORJP1
LINK JP1
IFS1100
POWERSUPPLY
+24V
0V
PTT
FAULT
+24V COM
ALERT OUT
4K7 5%
CONNECT TO FAULT OUT FROM SLAVE
0V
BGM ENABLE
( ENABLED ON
CLOSURE )
EVAC IN
BGM EN
ALARM
EVAC OUT
PA+
ALERT IN
PA -
BGM INPUT
BGM +
1V P-P
BGM -
SHIELDED
SHIELDED
JP2JP1
SOUND
GND
+24
WHITE RED
BLACK/SHIELD BLUE
COM
LINE +
MICROPHONE
WITHPTT
SPEAKERS WITH 100V LINE TRANSFORMERS AND ISOLATIONCAPACITORS
TO SLAVE TWOAMPLIFIERS
TOGETHER, REMOVETHE IFS903 BOARDFROM THE SLAVE AMPLIFIERAND CONNECTJP1 ON THE MASTERTO JP2 ON THE SLAVE.
THE MICROPHONEAND BGM
MUSTONLY BE CONNECTEDTO THE MASTER AMPLIFIER.
CONNECTFAULTOUTPUTS
TOGETHERAND MOVE THE LASTWRE ON I/O PCB TO THE FAULTTERMINALON THE MASTERAMPLIFIER.
CONNECTPIN 4, P12 ON MASTER
TO PIN4 P12 ON SLAVE.
47K 5%
EOL
D D
Revision- reviseon CAD. Do not amend by hand Eng. App. Date
No.
1
Copyright
Thisdocumentis & shall
remainthe property of
NotifierInertia Fire Systems
Unauthoriseduse of this document in any wayis prohibited.
=DocumentFullPathAndName
C
O
DrawingFile No.
2
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153
AUSTRALIA Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
1 1
Sheet:
Of:
Drawn/ Traced
Approved ThisDrawingmust notbe used for Construction
unlesssigned as approved
I PERRY
Engineer Design
Title
I PERRY25/8/05
IFS-2600 30 WATT SLAVE CONNECTION DIAGRAM
Size
A4
Drg.
No.
2600-30W-SLAVE
4
P/N 10069 ECN08-0066
Rev
A
IFS-2600 Installation & Programming Manual Page 71
NOTE:
50W EVAC Connection Diagram
1
AUDIOTRANSFORMER
A A
POWER
WARN
AUX
MONITORJP1
LINK JP1
+24
0V
+24 0V
IFS2600 TERMINATION BOARD
B B
REMOTE
REMOTE
OUTPUT
AC INPUT
+24V
INPUT
0V
+24V
0V
+24V
EXTERNAL
BATT
0V
2
0 2 4 6 8 0
60 30 20 10
AMP
PRI
GND LINE +
SECOUT
LINE ­LINE + LINE -
3
50W EVAC
PCB 905E
JP4JP3
FAN
PA GAIN
MAIN
JP2JP1
SOUND
+24 COM
FAULT
ALERT OUT
EVAC OUT
ALARM
BGM EN
EVAC
ALERT
PTT
GND
PA+
PA -
BGM +
FRONT PANEL EVAC CONTROL
BGM -
4K75%
+24 BAT
BAT OV
24V AC
24V AC
4
SPEAKERSWITH 100V LINE TRANSFORMERS AND ISOLATIONCAPACITORS
TO SLAVE TWOAMPLIFIERS
TOGETHER, REMOVETHE IFS903 BOARDFROM THE SLAVE AMPLIFIERAND CONNECTJP1 ON THE MASTERTO JP2 ON THE SLAVE.
THE MICROPHONEAND BGM
MUSTONLY BE CONNECTEDTO THE MASTER AMPLIFIER.
CONNECTJP3 MASTERTO JP4
SLAVEFOR FAN CONTROL
CONNECTPIN 4, P12 ON MASTER
TO PIN4 P12 ON SLAVE.
EOL
47K 5%
C C
PCB 974
D D
Revision- reviseon CAD. Do not amend by hand Eng. App. Date
No.
CHGBAT
MAINS_ON
N
LOW_N/C LOW_N/O
N
LOW_COM
+24V
0V
MF_N/C MF_N/O MF_COM
1
Copyright
Thisdocumentis & shall
remainthe property of
NotifierInertia Fire Systems
Unauthoriseduse of this document in any wayis prohibited.
=DocumentFullPathAndName
C
O
DrawingFile No.
2
A
N
E
240V/30V
TRANSFORMER
BGMENABLE
( ENABLED ON
CLOSURE )
BGMINPUT
1V P-P
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153
AUSTRALIA Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
WHITE RED
BLACK/SHIELD BLUE
SHIELDED
SHIELDED
1 1
Sheet:
Of:
Drawn/ Traced
Approved ThisDrawingmust not be used for Construction
unlesssigned as approved
I PERRY
Engineer Design
I PERRY25/8/05
MICROPHONE
WITHPTT
Title
IFS-2600 50 WATT CONNECTION DIAGRAM
Size
A4
Drg.
No.
2600-50W
4
P/N 10069 ECN08-0066
Rev
A
Page 72 IFS-2600 Installation & Programming Manual
NOTE:
50W EVAC Slave Connection Diagram
1
AUDIOTRANSFORMER
A A
POWER
WARN
AUX
MONITORJP1
LINK JP1
+24
0V
+24 0V
IFS2600 TERMINATION BOARD
B B
REMOTE
REMOTE
OUTPUT
AC INPUT
+24V
INPUT
0V
+24V
0V
+24V
EXTERNAL
BATT
0V
2
0 2 4 6 8 0
60 30 20 10
AMP
PRI
GND LINE +
SECOUT
LINE ­LINE + LINE -
3
50W EVAC
PCB 905E
JP4JP3
FAN
PA GAIN
MAIN
JP2JP1
SOUND
+24 COM
FAULT
ALERT OUT
EVAC OUT
ALARM
BGM EN
EVAC
ALERT
PTT
GND
PA+
PA -
BGM +
FRONT PANEL EVAC CONTROL
BGM -
4K75%
+24 BAT
BAT OV
24V AC
24V AC
4
SPEAKERS WITH 100VLINE TRANSFORMERS AND ISOLATIONCAPACITORS
TO SLAVE TWO AMPLIFIERS
TOGETHER, REMOVETHE IFS903 BOARDFROM THE SLAVE AMPLIFIERAND CONNECTJP1 ON THE MASTER TO JP2 ON THE SLAVE.
THE MICROPHONEAND BGM
SHOULDONLYBE CONNECTED TO THE MASTERAMPLIFIER.
CONNECTJP3 MASTERTO JP4
SLAVEFOR FAN CONTROL
CONNECTFAULTOUTPUTS
TOGETHERAND MOVE THE LASTWRE ON I/O PCB TO THE FAULT TERMINAL ON THE MASTERAMPLIFIER.
CONNECTPIN 4, P12 ON MASTER
TO PIN4 P12 ON SLAVE.
47K5%
EOL
C C
PCB 974
D D
Revision- revise on CAD. Do not amendby hand Eng. App. Date
No.
CHGBAT
MAINS_ON
N
N
LOW_COM
+24V
MF_N/C MF_N/O
MF_COM LOW_N/C LOW_N/O
1
0V
240V/30V
TRANSFORMER
Copyright
Thisdocumentis & shall
remainthe propertyof
NotifierInertia Fire Systems
Unauthoriseduse of this document in anyway is prohibited.
=DocumentFullPathAndName
C
O
Drawing File No.
2
A
N
E
CONNECTTO FAULT OUT FROM SLAVE
BGMENABLE
( ENABLED ON
CLOSURE )
BGM INPUT
1V P-P
7 Columbia Court, Norwest Business Park BaulkhamHills NSW 2153
AUSTRALIA Tel
61 2 9894 1444
Fax
61 2 9899 4156
Email: support@inertia.com.au
3
WHITE RED
BLACK/SHIELD BLUE
SHIELDED
SHIELDED
1 1
Sheet:
Of:
Drawn/ Traced
Approved ThisDrawingmust not be used forConstruction
unlesssigned as approved
I PERRY
Engineer Design
I PERRY25/8/05
MICROPHONE
WITHPTT
Title
IFS-2600 50 WATT SLAVE CONNECTION DIAGRAM
Size
Drg.
A4
No.
4
2600-50W-SLAVE
P/N 10069 ECN08-0066
Rev
A
Notes
Notes
New South Wales (Head Office)
7 Columbia Court Baulkham Hills NSW 2153
Queensland
24 Potts Street East Brisbane, QLD 4169
Victoria
32 Lambert Street Richmond, VIC 3121
ph +61 (02 9899-4155 fax +61 (0)2 9899-4156
Western Australia
Unit 4, 283 Camboon Road Malaga WA 6090
ph +61 (0)8 9270 6555 fax +61 (0)8 9270 6556
ph +61 (0)7 3391 5777 fax +61 (0)7 3391 5800
New Zealand
264 Mt Eden Road Auckland
ph +64 (0)9 623 5275 fax +64 (0)9 623 5060
ph +61 (0)3 9421 5552 fax +61 (0)3 9421 5553
Loading...