Honeywell IFS-2600 User Manual

IFS-2600
8/05/08
3.01
Fire Indicator Panel
TECHNICAL, PROGRAMMING
& INSTALLATION MANUAL
P/N 10069 ECN08-0066
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before
servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location.
Do not over tighten screw terminals. Over tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These
instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
This equipment must be correctly programmed and installed to suit the specific application.
Please ensure correct operational parameters are set prior to commissioning. If further details on programming options are required, please consult the programming manual or contact our helpful technical support personnel.
EMC WARNING:
This equipment may radiate radio frequency energy. It may also be affected by radio frequency energy and, if not installed and operated in accordance with the manufacturers instructions, may cause interference to radio communications. It has been tested and found to comply with the Class A radiated and conducted EMI requirements of AS/NZ 3548:1995 (including Amendments 1 & 2) as well as the EMI susceptibility requirements of Clause C3.5 in AS4428.0:1997.
Radio communication devices should not be used in the vicinity of fire panels or associated ancillary devices and systems.
Documentation Feedback
Your feedback helps us keep our documentation up to date and accurate. If you have any comments or suggestions about our printed manuals you can email us.
Please include the following information:
Product name and version number (if applicable)Manual part number and revision (found on the front cover)Page numberBrief description of the content you think should be improved or correctedYour suggestion for how to correct/improve documentation
Send email messages to:
techpubs@notifier.com.au
Please note this email address is for documentation feedback only. If you have any technical issues, please contact you nearest branch for technical support.
IFS-2600 Installation & Programming Manual Page 1
TABLE OF CONTENTS
COMPATIBLE DETECTORS................................................................................................5
OVERVIEW...........................................................................................................................6
CAUTION ........................................................................................................................................................................... 6
SPECIFICATION...................................................................................................................7
APPROVALS...................................................................................................................................................................... 7
ENVIRONMENTAL LIMITS........................................................................................................................................... 7
POWER SUPPLY RATINGS AND SETTINGS ............................................................................................................. 9
INTERNAL 24 VDC (nom) 3.0A MAIN POWER SUPPLY .......................................................................................... 9
INTERNAL 27.3V DC 1.5A BATTERY CHARGER..................................................................................................... 9
Internal 5VDC 2A Power Supply ..................................................................................................................................... 9
EXTERNAL 27VDC POWER SUPPLY ....................................................................................................................... 10
BATTERY TYPE AND CAPACITIES .......................................................................................................................... 10
TECHNICAL DESCRIPTION..............................................................................................11
GENERAL ........................................................................................................................................................................ 11
TRANSIENT SUPPRESSION......................................................................................................................................... 11
CURRENT CONSUMPTION ......................................................................................................................................... 11
AZF DESCRIPTION........................................................................................................................................................ 12
AZF SUPERVISORY CURRENT .................................................................................................................................. 12
OVERLOAD PROTECTION.......................................................................................................................................... 12
ZONE OVERLOAD SELF RESET ................................................................................................................................ 12
PRINTER OUTPUT......................................................................................................................................................... 13
CABLE CONNECTION.................................................................................................................................................. 13
PROGRAMMING BY COMPUTER............................................................................................................................. 13
ALIGNMENT AND ADJUSTMENT.....................................................................................14
PCB2006 POWER SUPPLY BOARD ............................................................................................................................ 14
INTERNAL 24VDC (nom) POWER SUPPLY.............................................................................................................. 14
INTERNAL 27.3 VDC BATTERY CHARGER............................................................................................................ 14
EXTERNAL 24VDC (nom) POWER SUPPLY (if fitted)............................................................................................. 14
P/N 10069 ECN08-0066
Page 2 IFS-2600 Installation & Programming Manual
PCB2005 TERMINATION BOARD...............................................................................................................................14
INTERNAL 5VDC POWER SUPPLY TP8...................................................................................................................14
POWER SUPPLY COMPARATOR REFERENCE VOLTAGE TP10 ......................................................................... 14
NON ADJUSTABLE TEST POINTS..............................................................................................................................14
ALARM THRESHOLD COMPARATOR TP7.............................................................................................................15
FAULT THRESHOLD COMPARATOR TP6 ..............................................................................................................15
CONFIGURATION JUMPERS......................................................................................................................................16
IFS2004 - JP3 DEFAULT .............................................................................................................................................16
IFS2004 - JP4 PROGRAM DISABLE ..........................................................................................................................16
IFS2004 - JP5 CPU RESET...........................................................................................................................................16
IFS2005 – JP2 DOOR HOLDER BYPASS...................................................................................................................16
IFS2006 – JP1 EXTERNAL PS MONITORING..........................................................................................................16
IFS804 - JP1-7 ZONE BOARD ADDRESSING...........................................................................................................16
PLACING INTO OPERATION............................................................................................ 17
EQUIPMENT AS FITTED..............................................................................................................................................17
INITIAL CHECKLIST....................................................................................................................................................17
POWER UP CHECKLIST...............................................................................................................................................18
FUNCTIONAL TESTING...............................................................................................................................................18
FAULT RECORD.............................................................................................................................................................19
INSTRUCTIONS TO OPERATORS....................................................................................20
INDICATORS...................................................................................................................................................................20
SUGGESTED ALARM PROCEDURE.......................................................................................................................... 21
OPERATOR INSTRUCTIONS.......................................................................................................................................21
FIREFIGHTER FUNCTIONS........................................................................................................................................21
GLOBAL FUNCTIONS.................................................................................................................................................22
ZONE FUNCTIONS.......................................................................................................................................................24
PROGRAMMING................................................................................................................27
GLOBAL OPTIONS.........................................................................................................................................................27
ZONE OPTIONS ..............................................................................................................................................................27
OUTPUT RELAY OPTIONS ..........................................................................................................................................28
DEFAULT SETTINGS.....................................................................................................................................................28
PROGRAM MODE..........................................................................................................................................................29
PROGRAMMING MODE..............................................................................................................................................29
PROGRAMMING HIERARCHY..................................................................................................................................29
ZONES............................................................................................................................................................................29
RELAYS.........................................................................................................................................................................30
GLOBAL ........................................................................................................................................................................ 30
PRINT.............................................................................................................................................................................30
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 3
MAIN MENU.................................................................................................................................................................... 30
EXIT PROGRAMMING MODE................................................................................................................................... 31
ZONE PROGRAMMING................................................................................................................................................ 31
SELECT ZONE #........................................................................................................................................................... 31
ZONE SELECTED......................................................................................................................................................... 31
ZONE TYPE .................................................................................................................................................................. 31
ZONE OUTPUT CONFIGURATION ........................................................................................................................... 32
RELAY PROGRAMMING MODE................................................................................................................................ 32
SELECT RELAY # ........................................................................................................................................................ 32
RELAY SELECTED...................................................................................................................................................... 32
RELAY TYPE................................................................................................................................................................ 33
RELAY MAPPING........................................................................................................................................................ 33
GLOBAL PROGRAMMING.......................................................................................................................................... 33
ACF OUTPUT................................................................................................................................................................ 34
AVF................................................................................................................................................................................ 34
RELAY (GLOBAL RELAY UNITY MAP) .................................................................................................................. 34
PRINT PROGRAMMING DATA.................................................................................................................................. 35
TIME (DATE & TIME)................................................................................................................................................... 35
APPENDIX A ......................................................................................................................36
DESCRIPTION OF ALARM ZONE TYPES................................................................................................................ 36
LATCHING TYPE......................................................................................................................................................... 36
NON LATCHING TYPE ............................................................................................................................................... 36
TIME DELAY AZF........................................................................................................................................................ 37
APPENDIX B ......................................................................................................................38
ZONE OUTPUT CONFIGURATIONS.......................................................................................................................... 38
APPENDIX C ......................................................................................................................39
ALARM VERIFICATION FACILITY (AVF).............................................................................................................. 39
GLOBAL PROGRAMMABLE OPTIONS.................................................................................................................... 39
APPENDIX D ......................................................................................................................40
ANCILLARY TRIP (ACF).............................................................................................................................................. 40
GLOBAL PROGRAMMABLE OPTIONS.................................................................................................................... 40
APPENDIX E.......................................................................................................................41
RELAY OUTPUT MAPPING......................................................................................................................................... 41
AND MAPPING ............................................................................................................................................................... 41
OR MAPPING.................................................................................................................................................................. 41
FAULT MAPPING........................................................................................................................................................... 41
FAULT/ISOLATE MAPPING........................................................................................................................................ 42
ISOLATE MAPPING ...................................................................................................................................................... 42
P/N 10069 ECN08-0066
Page 4 IFS-2600 Installation & Programming Manual
APPENDIX F ......................................................................................................................43
GLOSSARY OF TERMS.................................................................................................................................................43
APPENDIX G...................................................................................................................... 44
SUMMARY OF TERMINATIONS AND CAUTIONS.................................................................................................44
MCP LOOP..................................................................................................................................................................... 44
DETECTION ZONES ....................................................................................................................................................44
RELAY OUTPUTS ........................................................................................................................................................44
BELL OUTPUTS ...........................................................................................................................................................44
ACF OUTPUTS..............................................................................................................................................................44
WARNING SYSTEM.....................................................................................................................................................44
DOOR HOLDER OUTPUTS.........................................................................................................................................44
AUXILIARY POWER & MIMIC POWER ................................................................................................................... 44
MAF ISOL & TRANSPONDER 0V ..............................................................................................................................44
MIMIC DATA & CLOCK..............................................................................................................................................44
AC INPUT......................................................................................................................................................................44
BATTERY......................................................................................................................................................................45
DOOR HOLDER AC INPUT.........................................................................................................................................45
OUTPUT RELAYS ........................................................................................................................................................45
APPENDIX H...................................................................................................................... 46
IFS-2600 PROGRAMMED OPTIONS...........................................................................................................................46
APPENDIX I........................................................................................................................ 53
TECHNICAL DRAWINGS.............................................................................................................................................53
MAIN KEYPAD AND DISPLAY..................................................................................................................................53
EXPANSION DISPLAY ................................................................................................................................................ 53
Block Connection Diagram.............................................................................................................................................54
System Sensor Conventional Detector Connection Diagram.......................................................................................... 54
System Sensor Conventional Detector Connection Diagram.......................................................................................... 55
Hochiki Conventional Detector Connection Diagram.....................................................................................................55
Hochiki Conventional Detector Connection Diagram.....................................................................................................56
Ancillary Connection Diagram........................................................................................................................................57
ASE Connection Diagram...............................................................................................................................................58
Auto Changeover Dual Sounder Connection Diagram....................................................................................................59
Auto Change Over Dual Sounder Connection Diagram.................................................................................................. 60
MIMIC Connection Diagram..........................................................................................................................................61
Single Fan Connection Diagram .....................................................................................................................................62
Dual Fan Connection Diagram........................................................................................................................................63
Exhaust Fan Connection Diagram...................................................................................................................................64
Supply Fan Connection Diagram ....................................................................................................................................65
Smoke Spill Fan Connection Diagram............................................................................................................................66
10W EVAC Connection Diagram...................................................................................................................................67
10W EVAC Slave Connection Diagram.........................................................................................................................68
30W EVAC Connection Diagram...................................................................................................................................69
30W EVAC Slave Connection Diagram.........................................................................................................................70
50W EVAC Connection Diagram...................................................................................................................................71
50W EVAC Slave Connection Diagram.........................................................................................................................72
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 5
COMPATIBLE DETECTORS
Make Model Type Model Number
System Sensor Thermal Type A 5451 AUS System Sensor Thermal Type A 51A51 System Sensor Thermal Type B 4451 AUS System Sensor Thermal Type B 51B51 System Sensor Thermal Type B Sealed 51B51S System Sensor Thermal Type C 51C51 System Sensor Thermal Type D 51D51 System Sensor Smoke Photo-Optical 2151 AUS System Sensor Smoke Photo-Optical 2151B AUS System Sensor Smoke Ionisation 1151 AUS System Sensor Thermal Type D 51D51 System Sensor Smoke Beam BEAM1224 System Sensor Smoke Duct DHP-100
Apollo Thermal Type A Series 60 Apollo Thermal Type B Series 60 Apollo Thermal Type C Series 60 Apollo Thermal Type D Series 60 Apollo Smoke Ionisation Series 60 Apollo Smoke Photo Optical Series 60
Hochiki Thermal Type A DCA-B-60R MkV Hochiki Thermal Type A DCC-A Hochiki Thermal Type A DCD-A Hochiki Thermal Type B DFE-60B Hochiki Thermal Type B DFJ-60B Hochiki Thermal Type C DCA-B-90R Mk1 Hochiki Thermal Type C DCC-C Hochiki Thermal Type C DCD-C Hochiki Thermal Type D DFE-90D Hochiki Thermal Type D FDJ-90D Hochiki Thermal Cool Room Type B sealed DFG-60BLKJ Hochiki Smoke Ionisation SIH-AM Hochiki Smoke Ionisation SIJ-ASN Hochiki Smoke Photo Optical SLK-A Hochiki Smoke Photo Optical SLR-AS
Olsen Thermal Type A T56B-T6A Olsen Thermal Type B T56B-T6B Olsen Thermal Type C T56B-T6C Olsen Thermal Type D T56B-T6D Olsen Smoke Ionisation C24B Olsen Smoke Photo Optical P24B
Panelect Thermal Type A PFS-A Panelect Thermal Type B PFS-B Panelect Thermal Type C PFS-C Panelect Thermal Type D PFS-D Panelect Smoke Ionisation PFS-I Panelect Smoke Ionisation PFS-I , MkII Panelect Smoke Photo Optical PFS-P Panelect Smoke Photo Optical PFS-P, MkII
IEI VESDA E700, E70D CONTACT DEVICE Please contact NOTIFIER INERTIA for any additional detectors.
P/N 10069 ECN08-0066
Page 6 IFS-2600 Installation & Programming Manual
OVERVIEW
IFS-2600 Fire Indicator Panel (FIP) is designed to provide simplicity to the end user. The FIP uses both a liquid crystal display and conventional LED displays for fast and accurate display of system status and changing events.
A custom designed membrane keypad is used together with the liquid crystal display and LED indicators to provide fast, efficient and simple modes of operation. The keypad also provides the required flexibility for the programming of the many user configurable options of this FIP. The FIP can be configured on-site without the need of expensive programmers or components.
A serial printer can also be connected if required. The printer can be used to output programming information for ease of modification, for safekeeping and to assist in the commissioning of the installation.
IFS-2600 uses serial chain mimic outputs which significantly saves time and costs of cabling to mimic panels.
A door holder power supply (using optional transformer) is incorporated into the system for the release of smoke and fire doors on alarm.
IFS-2600 is available in a standard 8-zone configuration and can be expandable to its fully expanded state as required. The IFS-2600 in its fully expanded state can;
Monitor 64 detection zones
Control 64 optional "mapped" relay outputs
Output to a serial printer
Output serially to a mimic panel
Control to door holders
Interface as required to any Australian Fire Brigade
IFS-2600 has been designed to be functional, flexible and reliable whilst maintaining a user-friendly interface.
CAUTION
IFS-2600 FIP has been tested and approved to AS4428.1 and meets the requirements of AS1670 and AS1668 Parts 1 &
2.
However, the equipment must be correctly programmed and installed to suit the specific application. Please ensure correct operational parameters are set prior to commissioning. If further details on programming options are required, please consult the programming manual or contact our helpful technical support personnel.
WARNING:
This equipment may radiate radio frequency energy. It may also be affected by radio frequency energy and, if not installed and operated in accordance with the manufacturers instructions, may cause interference to radio communications. It has been tested and found to comply with the Class A radiated and conducted EMI requirements of AS/NZ 3548:1995 (including Amendments 1 & 2) as well as the EMI susceptibility requirements of Clause C3.5 in AS4428.0:1997
CAUTION: Radio communication devices should not be used in the vicinity of fire panels or associated ancillary devices and systems
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 7
SPECIFICATION
Cabinet Zinc Sealed Steel 1.6mm
Powder Coated Hinged Inner Door Hinged Outer Door
Outside Dimensions 2608 (8 zones) 394mm H x 390mm W x 180mm D*
2624 (24 zones) 750mm H x 390mm W x 180mm D* 2600 (32 to 64 zones) 18U, 28U & 40U Cabinets Battery Box
*Note: the depth quoted is including the door and break glass. The internal cabinet depth not including he door and break glass
is 140mm. AC Operational Voltage 240 VAC 50Hz + 10% Internal Power Supplies Battery Charger 27.3 VDC 1.5AMP
Panel Supply 24 VDC(nom) 3.0AMP
Logic Supply 5 VDC 2.0AMP Microprocessor 80C52
Memory Type Non-volatile E2ROM Liquid Crystal Display 2 Lines x 16 Characters LED Backlit Fuses F1: Panel Supply M205 5A
F2: Battery Charger M205 3A
F3: Battery Protection Polyfuse 3A
F4: External Supply M205 7A
F5: Door Holder M205 3A
F6: Aux Power Output M205 1A Slow Blow
F7: Bell M205 1A
F8: Warning System M205 1A
F9: ACF M205 1A E.O.L Resistor On AZFs, monitored
outputs, Bells, Warning system, ACF
4K7 Ohms
APPROVALS
Australian Standard AS4428.1 1998 SSL Approval No AFP-1553 C-Tick Approval No. N1336
ENVIRONMENTAL LIMITS
-10 Deg. C to +55 Deg. C Dry heat. +40 Deg. C @ 93% Relative Humidity.
P/N 10069 ECN08-0066
Page 8 IFS-2600 Installation & Programming Manual
SYSTEM EXPANSION
Zones Qty Hardware Required Product Code 8 1 Main Control Board PCB-2004
1 Main Termination board PCB-2005 1 Power Supply board PCB-2006
16 1 Main Control board PCB-2004
1 Main Termination board PCB-2005 1 Power Supply board PCB-2006 1 8 Zone Expansion board PCB-804G3 1 16 Zone Indicator board PCB-816
24 1 Main Control board PCB-2004
1 Main Termination board PCB-2005 1 Power Supply board PCB-2006 2 8 Zone Expansion board PCB-804G3 1 16 Zone Indicator board PCB-816
32 1 Main Control board PCB-2004
1 Main Termination board PCB-2005 1 Power Supply board PCB-2006 3 8 Zone Expansion board PCB-804G3 2 16 Zone Indicator board PCB-816
40 1 Main Control board PCB-2004
1 Main Termination board PCB-2005 1 Power Supply board PCB-2006 4 8 Zone Expansion board PCB-804G3 2 16 Zone Indicator board PCB-816
48 1 Main Control board PCB-2004
1 Main Termination board PCB-2005 1 Power Supply board PCB-2006 5 8 Zone Expansion board PCB-804G3 3 16 Zone Indicator board PCB-816
56 1 Main Control board PCB-2004
1 Main Termination board PCB-2005 1 Power Supply board PCB-2006 6 8 Zone Expansion board PCB-804G3 3 16 Zone Indicator board PCB-816
64 1 Main Control board PCB-2004
1 Main Termination board PCB-2005 1 Power Supply board PCB-2006 7 8 Zone Expansion board PCB-804G3 4 16 Zone Indicator board PCB-816
Additional relay outputs:
Relays Qty Hardware Required Product Code 8 1 Relay board containing 8 relays 24VDC 1A IFS-717 16 2 Relay board containing 8 relays 24VDC 1A IFS-717 24 3 Relay board containing 8 relays 24VDC 1A IFS-717 32 4 Relay board containing 8 relays 24VDC 1A IFS-717 40 5 Relay board containing 8 relays 24VDC 1A IFS-717 48 6 Relay board containing 8 relays 24VDC 1A IFS-717 56 7 Relay board containing 8 relays 24VDC 1A IFS-717 64 8 Relay board containing 8 relays 24VDC 1A IFS-717
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 9
POWER SUPPLY RATINGS AND SETTINGS
INTERNAL 24 VDC (nom) 3.0A MAIN POWER SUPPLY
This supply's primary function is to power panel logic and all external operations of the FIP, i.e.: detection circuits, ancillary circuits, etc. This supply meets the requirements of AS4428.5.
AC Input 30 VAC +10% - 15% Output Current 3.0 AMPS Output Voltage 26.5 VDC Current Limit 3.0 AMPS Output Ripple 50 mV
INTERNAL 27.3V DC 1.5A BATTERY CHARGER
Its primary function is to charge the batteries. This supply meets the requirements of AS4428.5.
AC Input 30 VAC +10% -15% Output Current 1.5 AMPS Output Voltage 27.3 VDC Current Limit 1.5 AMPS Output Ripple 200 mV
Important Note:
After a power failure, the battery will only reconnect to the charger if the battery voltage is above approximately 20V +/- 2V.
A battery fault will be generated in the event that the battery does not automatically reconnect. This is to ensure that a faulty or dead flat battery (due to an extended power failure) does not bring the entire system down.
In order to reconnect a flat battery, it is necessary to disconnect the battery from the panel and charge it externally. The battery should be thoroughly tested before returning it to service.
In the event that an external charger is not available, the battery may be trickle charged above 22V via a 30 ohm, 5W resistor connected between the 24v Aux Output and the battery positive terminal. A 1N4004 Diode (Notifier part number #286) or similar should also be fitted in series with the resistor to stop the battery from pulling down the main panel voltage. Trickle charging the battery by this method may take several hours to bring it up to the minimum level.
The battery can then be reconnected to the panel for charging via the internal battery charger. It is important that the voltage on the battery be monitored to ensure that it is charging. The battery should then be left for 24 hours and then fully tested to ensure that no damage has occurred due to the deep discharge.
Internal 5VDC 2A Power Supply
This supply's primary function is to power all internal operations of the FIP, i.e.: Microprocessor, liquid crystal display, LED's keypad etc.
AC Input 30 VAC +15% or 27.6VDC+15% Output Current 2.0 AMPS Output Voltage 5.0 VDC Current Limit 2.0 AMPS Output Ripple 150 mV
P/N 10069 ECN08-0066
Page 10 IFS-2600 Installation & Programming Manual
INPUT
INPUT
24V0V
IFS-2600 TERMINATION BOARD
EXTERNAL 27VDC POWER SUPPLY
This supply is used in addition to the internal power supply for large systems. Its primary function is to power any additional ancillary loads of the FIP up to 7 amps. This supply meets the requirements of AS4428.5
Important Notes:
When using external power supply, JP1 link on IFS2006E must be fitted to enable external PSU monitoring. If this supply is used to power a NI-2008 gas module, the following additional components are required to
ensure a break free change over from the mains supply to the panel battery in case of mains fail condition.
1. A 6A4 or P600G rectifier diode (Notifier part number #266) is to be installed in series with the
external +27V output of the IFS-2600 termination board.
2. A 3300µF 50V Electrolytic Capacitor (Notifier part number #1248) should be installed across the
+27V and 0V of the ancillary device.
AC
REMOTE
REMOTE
OUTPUT
24V 0V-+24V 0V
BATT INPUT
EXTERNAL
POWER SUPPLY
OUTPUT
0V
24V
6A4
+
3300uF
POWER IN
NI-2008 GAS
SUPPRESSION
MODULE
BATTERY TYPE AND CAPACITIES
In general, any Sealed Lead Acid Battery, or Wet Lead Acid Battery designed for stationary use is compatible with the IFS-2600 Fire Indicator Panel. Automotive batteries must not be used. The use of Nickel Cadmium batteries is not recommended.
Manufacturer Type Number Voltage Capacity (Ah) Qty Required
Best and Best Sealed LA BP17-12 12 17 2 Best and Best Sealed LA BP24-12 12 24 2 Best and Best Sealed LA BP40-12 12 40 2 Olympic Batteries Sealed LA CJ12-7 12 7 2 Olympic Batteries Sealed LA CJ12-12 12 12 2 Olympic Batteries Sealed LA CJ12-18 12 18 2 Olympic Batteries Sealed LA CJ12-26 12 26 2 Olympic Batteries Sealed LA CJ12-33 12 33 2 Olympic Batteries Sealed LA CJ12-40 12 40 2 Olympic Batteries Sealed LA CJ12-88 12 88 2 Olympic Batteries Sealed LA CJ12-100 12 100 2
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 11
TECHNICAL DESCRIPTION
GENERAL
The IFS-2600 in its most basic form comprises of three boards, the main control board, the main termination board and the power supply board.
The main control board contains the Microprocessor, EPROM, RAM and E2ROM. The main control board also has the liquid crystal display and keypad attached. All of the "delicate" electronics have been placed on this board. The main control board complete with the inner door is easily removed during installation to avoid damage and allow greater access to the field terminals.
The main termination board contains the one power supply for 5V logic, and connectors for a Power Supply and Battery Charger daughter board, the first eight zones, all common outputs and the printer interface. All charger settings, fuses etc are located on this board. The Power Supply and Battery Charger board contains two switch mode regulators, 26.5V for the panel power, 27.3V for the battery charger.
Up to seven (7) zone expansion boards can be added to the system to increase its detection capability. These boards contain the same electronics as on the main termination board for zone scanning. Addressing is by a jumper that selects which group of eight zones the board refers to.
Up to four (4) zone indicator boards can also be added. These boards will display the status of the zone expansion boards fitted.
Up to eight (8) relay boards can be added. These boards contain 8 change-over relay contacts, each rated at 1 amp. These boards require no addressing, as they work on a serial data chain. Output 1 is the closest output to the main board.
NOTE This product utilises state of the art components and materials and therefore boards must be returned
to our factory for proper troubleshooting, repair and retesting. Field component level repairs are not recommended and would void all warranties on the product.
TRANSIENT SUPPRESSION
The IFS-2600's superior transient protection comprises of Dual Transorb input traps, inductive paths on incoming PCB tracks, circuit board planes and metal oxide varistors on outputs. These devices are all self­resetting.
CURRENT CONSUMPTION
Zones Fitted Quiescent Current Quiescent + 2 AZF'S in alarm +1A of Bell +1 Amp ACF
8 150 mA 2.23 AMPS 16 250 mA 2.33 AMPS 24 350 mA 2.43 AMPS 32 450 mA 2.53 AMPS 40 550 mA 2.63 AMPS 48 650 mA 2.73 AMPS 56 750 mA 2.83 AMPS 64 850 mA 2.93 AMPS
Note: 1: Each installation would require individual battery calculations to be performed for load capacity and power supply capacity. 2: Each IFS-717 relay board, can add 370 mA (in alarm and quiescent) current per board.
P/N 10069 ECN08-0066
Page 12 IFS-2600 Installation & Programming Manual
AZF DESCRIPTION
The AZF's on the IFS-2600 are monitored and scanned by custom thick film hybrids. These hybrid IC's significantly reduce the possibility of false alarms and improve product efficiency and reliability.
The total Alarm Zone loop resistance is the sum of the end of line resistor (EOLR 4K7) plus all the parallel connected detector loads.
AZF SUPERVISORY CURRENT
The supervisory current flows through the external terminal AZF+, through the field cable and to the end of line resistor (EOLR), returning to the panel at AZF- terminal. Parallel connected, across the 2-wire pair field cable, are a number of the previously listed detectors. During the quiescent state there is essentially an open circuit across the + and - terminals of the detector base. The maximum number of detectors that can be installed on each AZF is dependant on the type of detector and is listed in the IFS-2600 ActivFire®listing.
In an alarm state, a 560-ohm resistor is connected across the detector base causing additional loop current to flow. This is sensed by the AZF to produce an alarm output. Removal of the E.O.L. resistor (in a non alarm state) or the interruption of the supervisory current will produce a fault signal in the AZF.
As described above, the level of current is used to define the status of the alarm zone: -
I = 3.5 mA and below FAULT I = 4.0 - 5.0mA at 24V QUIESCENT I = 16 mA to 40 mA (current limited) ALARM
The zone current is used by the hybrid IC to determine the condition of the zone as above. This information is then transferred to the microprocessor for processing.
OVERLOAD PROTECTION
Panel Supply Fuse F1 M205 5A Battery Charger Fuse F2 M205 3A Battery Protection Fuse F3 Polyfuse 3A External Supply Fuse F4 M205 7A Door Holder Fuse F5 M205 3A Aux Power Output Fuse F6 M205 1A Slow Blow Bell Fuse F7 M205 1A Warning System Fuse F8 M205 1A ACF Fuse F9 M205 1A AZF Circuits Current Limited 40mA
ZONE OVERLOAD SELF RESET
If a zone is overloaded by an accidental short to earth on an AZF circuit, the zone will automatically shut down and produce a fault. Once this happens the panel will automatically recheck the zone every 60 seconds and once the overload is removed, restore power and the fault will clear.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 13
PRINTER OUTPUT
The printer port is designed to be used during testing and commissioning of the panel. The serial printer will report alarms and faults together with the date and time of the event. The printer can also be used during “walk test” mode to produce a history of the test and can also be used to print current programming configuration.
A DB9 plug male is provided at the top of the main termination board. This communication port will communicate with an IBM compatible serial printer (ASCII printer) with the following settings.
Baud Rate 1200 bps Data Bits 8 Stop Bits 1 Parity None Handshaking DTR
CABLE CONNECTION
Cabling to the printer requires a 4-core telephone style cable with a maximum length of 10 metres. A DB9 socket is required at the panel end. The printer end is dependent on the type of printer used but is usually a male DB25. Connection is as follows. A 5-core cable can be used for both comms and printer functions
IFS-2600 END PRINTER END
DB9 FEMALE DB25 MALE DB9 MALE
2 RX (only for programming) 2 3 3 TX 3 2 5 GND 7 5 7 RTS ( do not use) (5) (8) 8 CTS ( only for printer) 4 7
PROGRAMMING BY COMPUTER
Programming of the zones, relays, global functions and time can by set with the DOS based program “2600/SW” using the printer port. (Cannot be used with Windows XP) After the cable is installed, the program can be run and the menu will prompt for the available functions.
2600
P/N 10069 ECN08-0066
Page 14 IFS-2600 Installation & Programming Manual
ALIGNMENT AND ADJUSTMENT
PCB2006 POWER SUPPLY BOARD
INTERNAL 24VDC (nom) POWER SUPPLY
With batteries disconnected and no alarms present, measure voltage across the 0V and MAIN test points on the 2006 power supply board and, if necessary, adjust the multi-turn potentiometer VR2 until voltage is 26.5V 0.05V (26.45V – 26.55V).
Current limiting is fixed and field adjustment is not possible.
INTERNAL 27.3 VDC BATTERY CHARGER
With batteries disconnected and no alarms present, measure voltage across the 0V and CHARG test points on the 2006 power supply board and, if necessary, adjust the multi-turn potentiometer VR1 until voltage is 27.3V 0.05V (27.25V – 27.35V).
Current limiting is factory preset and field adjustment is not required.
EXTERNAL 24VDC (nom) POWER SUPPLY (if fitted)
With batteries disconnected and no alarms present, measure voltage across Remote Input terminals on PCB2005 and adjust the voltage on the external power supply until the voltage is 26.5V 0.5V (26.0V – 27.0V). Note: This voltage is not critical for the operation of the IFS-2600 panel, but the voltage must not go outside the limits as specified for the field ancillaries that it powers.
PCB2005 TERMINATION BOARD
INTERNAL 5VDC POWER SUPPLY TP8
All parameters are fixed and field adjustment is not possible.
POWER SUPPLY COMPARATOR REFERENCE VOLTAGE TP10
With the panel in the quiescent mode, measure voltage between system 0V and TP10. Adjust multi­turn potentiometer VR3 until voltage is 7.0V 1% (6.93V – 7.07V)
NON ADJUSTABLE TEST POINTS
TP8 = 5.0 VDC 5% 5VDC POWER SUPPLY TP5 = 12.0 VDC 5% 12VDC POWER SUPPLY
(If these test point voltages are not correct, please return the main termination board to the factory for repair.)
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 15
ALARM THRESHOLD COMPARATOR TP7
With the panel in the quiescent mode, measure and take note of the INTERNAL 24V DC POWER SUPPLY as above.
Measure voltage between system 0V and TP7. Adjust multi-turn potentiometer VR4, and adjust until the voltage is as per the following table.
Rail Voltage 3.3V Setting Range
20.6 2.833 2.80 to 2.86
21.0 2.888 2.86 to 2.92
21.5 2.956 2.93 to 2.99
22.0 3.025 2.99 to 3.06
22.5 3.094 3.06 to 3.12
23.0 3.163 3.13 to 3.19
23.5 3.231 3.20 to 3.26
24.0 3.300 3.27 to 3.33
24.5 3.369 3.34 to 3.40
25.0 3.438 3.40 to 3.47
25.5 3.506 3.47 to 3.54
26.0 3.575 3.54 to 3.61
26.5 3.644 3.61 to 3.68
27.0 3.713 3.68 to 3.75
27.5 3.781 3.74 to 3.82
27.6 3.795 3.76 to 3.83
28.0 3.850 3.81 to 3.89
FAULT THRESHOLD COMPARATOR TP6
With the panel in the quiescent mode, measure and take note of the INTERNAL 24V DC POWER SUPPLY as above.
Measure the voltage between system 0V and TP6. Adjust multi-turn potentiometer VR1, and adjust until the voltage is as per the following table.
Rail Voltage 0.6V Setting Range
20.6 0.600 0.59 to 0.61
21.0 0.612 0.61 to 0.62
21.5 0.626 0.62 to 0.63
22.0 0.641 0.63 to 0.65
22.5 0.655 0.65 to 0.66
23.0 0.670 0.66 to 0.68
23.5 0.684 0.68 to 0.69
24.0 0.699 0.69 to 0.71
24.5 0.714 0.71 to 0.72
25.0 0.728 0.72 to 0.74
25.5 0.743 0.74 to 0.75
26.0 0.757 0.75 to 0.76
26.5 0.772 0.76 to 0.78
27.0 0.786 0.78 to 0.79
27.5 0.801 0.79 to 0.81
27.6 0.804 0.80 to 0.81
28.0 0.816 0.81 to 0.82
P/N 10069 ECN08-0066
Page 16 IFS-2600 Installation & Programming Manual
CONFIGURATION JUMPERS
IFS2004 - JP3 DEFAULT
Holding a short across these pins for 5 seconds during start-up causes the panel to reset to standard factory defaults. The panel will give 4 beeps after reset, to acknowledge default on start-up.
IFS2004 - JP4 PROGRAM DISABLE
When fitted, jumper between these pins to inhibit program changes.
IFS2004 - JP5 CPU RESET
With panel operating, a momentary short across these pins will cause a CPU restart.
IFS2005 – JP2 DOOR HOLDER BYPASS
If zoned door holder outputs are required and is to be done external to the main termination board, then the main door holder release needs to be disabled. Fitting a link across JP2 on IFS2005 PCB does this.
Note: Door holder output is only enabled if optional door holder transformer is fitted. SW1 must be linked on PCB2004 CPU board prior to Version 6 Firmware.
IFS2006 – JP1 EXTERNAL PS MONITORING
When using external power supply, JP1 link on IFS2006E must be fitted to enable external PSU monitoring.
IFS804 - JP1-7 ZONE BOARD ADDRESSING
Jumper JP1 to JP7 on zone expansion board IFS-804 selects the addressing for the zones. Place jumper in link position for the appropriate 8 zones to which the expansion board applies.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 17
PLACING INTO OPERATION
Suitably qualified technicians must install the panel. The following check procedures are recommended after every installation and prior to initial power-up.
A thorough visual inspection should be made to every aspect of the fire panel. This includes loose wire, metal filings, loose circuit boards, loose cabling, damage in transit etc.
All problems must be rectified immediately as they could cause incorrect operation or permanent damage to the equipment.
EQUIPMENT AS FITTED
QTY Description Code
1 MAIN CONTROL BOARD IFS -2004
1 MAIN TERMINATION BOARD IFS -2005
1 MAIN POWER SUPPLY IFS -2006
8 ZONE EXPANSION BOARD IFS -804
16 ZONE INDICATOR BOARD IFS -816
ADD ON, 8 WAY RELAY BOARD IFS-717
EXTERNAL POWER SUPPLY BOOSTER PS244, PS249, NPS-3,
3A DOOR HOLDER P/SUPPLY TRANSFORMER 2600/DHTX
INITIAL CHECKLIST
System general appearance good Cabinet colour and condition good Cabinet keyed 003 All circuit boards firmly fastened Manual call point fitted & functional Viewing window clear and firmly secured Cable entries adequately sealed 240VAC mains cabling is correctly terminated All earthing secured Transformer securely mounted Transformer correctly wired All ribbon cables firmly secured All operational zones adequately identified All fuses correct value and fitted properly All other modules securely fitted Manufacturing label affixed
NPS-5, NPS-11
You are now ready to power up the IFS-2600 Fire Indicator Panel.
P/N 10069 ECN08-0066
Page 18 IFS-2600 Installation & Programming Manual
POWER UP CHECKLIST
Ensure batteries are disconnected. Turn mains switch to "on" The "mains on" led should light. Allow 15 seconds for the panel to perform its start up tests. Connect batteries
FUNCTIONAL TESTING
Primary ac supply voltage: 200 or 220 or 240vac +10% as required Charger output voltage without batteries: 27.3v dc Keypad functional Perform auto test
Led’s all functional LCD backlighting functional Liquid crystal display functional Zone fault detection Zone alarm detection
Internal sounder operating MCP loop wired to zone number ______ (if applicable) Test auxiliary power output Test bell output Test warning system output Test ACF output Test door holder output (optional) Test bell output supervision Test warning system output supervision Test ACF output supervision Test brigade alarm relay #1 Test brigade alarm relay #2 Test standby relay (normally energised) Test fault relay (normally energised) Test mains fail relay Test isolate relay Test general alarm relays (2) Test relay boards (if fitted) Test open collector output boards (if fitted) Press "battery test" once If batteries are flat, allow 24hrs to charge and then re-test.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming Manual Page 19
FAULT RECORD
FAULT CORRECTION DATE
TESTS SATISFACTORILY COMPLETED. TESTED BY _______________________________ SIGNATURE _______________________________ DATE OF TEST ____________________________ If all faults have been rectified and all tests are completed satisfactorily, the 2600 fire indicator panel is now
ready for operation.
P/N 10069 ECN08-0066
Page 20 IFS-2600 Installation & Programming Manual
INSTRUCTIONS TO OPERATORS
INDICATORS
Qty Descriptor Colour Function Buzzer
1 MAINS ON Green Illuminates when there is 200/220/240 VAC supply to
the panel.
1 BATTERY
FAULT
1 PSU FAULT Yellow Illuminates if the power supply is outside the
1 CHARGER
LOW
1 COMMON
FAULT
1 ACF ACT Red Illuminates if the ACF output has been activated. 1 ACF FLT Yellow Illuminates if the ancillary circuit is open or short
1 ACF ISO Yellow Illuminates if the ancillary output has been manually
1 Bell ACT Red Illuminates when the bell output has been energised. 1 Bell FLT Yellow Illuminates if the bell circuit is open or short circuit.
1 Bell ISO Yellow Illuminates if the bell output has been manually
1 Warning
System ACT
1 Warning
System FLT
1 Warning
System ISO
8 ALARM LEDS Red This LED will flash if it's corresponding zone goes
8 FAULT LEDS Yellow This LED illuminates if it's corresponding zone goes
8 ISOLATE LEDS Yellow This LED illuminates if its corresponding zone is
Yellow Illuminates if the battery fails a battery test.
Illuminates if batteries are disconnected >30 seconds. Illuminates if batteries are short circuit >30 seconds.
manufacturers range.
Yellow Illuminates if the battery charger is outside the
recommended float charge voltage.
Yellow Illuminates if;
Any un-isolated zone goes into fault. ACF output is open or short circuit Bell output is open or short circuit Warning System output is open or short circuit Battery Fault Charger Fault Power Supply Fault MAF Isolate Input is Open Circuit Configuration Fault
circuit. The LED will extinguish when the load is restored.
isolated.
The LED will extinguish when the load is restored.
isolated.
Red Illuminates if the Warning System output has been
energised.
Yellow Illuminates if the Warning System circuit is open or
short circuit. The LED will extinguish if the load is restored.
Yellow Illuminates if the Warning System has been manually
isolated.
into alarm. It will remain flashing until it is Acknowledged at which time it will go steady and remain on until the alarm is reset. If the zone is programmed as a time delay type, a steady LED indicates the “pre-alarm” condition. If the zone is isolated and in alarm it will also be steady.
into fault. It will remain on until the fault is removed.
isolated. It will remain on until the zone is de­isolated.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
P/N 10069 ECN08-0066
Loading...
+ 56 hidden pages