Adherence to the following will aid in
problem-free installation with long-term
reliability:
WARNING - Several different sources of power
can be connected to the fire alarm control
panel. Disconnect all sources of power before
servicing. Control unit and associated equipment
may be damaged by removing and/or inserting
cards, modules, or interconnecting cables while the
unit is energized. Do not attempt to install, service,
or operate this unit until manuals are read and
understood.
Verify that wire sizes are adequate for all
initiating and indicating device loops. Most devices
cannot tolerate more than a 10% I.R. drop from the
specified device voltage.
Like all solid state electronic devices, this
system may operate erratically or can be damaged
when subjected to lightning induced transients.
Although no system is completely immune from
lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or
outside aerial wiring is not recommended, due to
an increased susceptibility to nearby lightning
strikes. Consult with the Technical Services
Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to
removing or inserting circuit boards. Failure to do
so can damage circuits.
Remove all electronic assemblies prior to any
drilling, filing, reaming, or punching of the
enclosure. When possible, make all cable entries
from the sides or rear. Before making
modifications, verify that they will not interfere with
battery, transformer, or printed circuit board
location.
Do not over tighten screw terminals. Over
tightening may damage threads, resulting in
reduced terminal contact pressure and difficulty
with screw terminal removal.
This system contains static-sensitive
components. Always ground yourself with a
proper wrist strap before handling any circuits so
that static charges are removed from the body.
Use static suppressive packaging to protect
electronic assemblies removed from the unit.
Follow the instructions in the installation,
operating, and programming manuals. These
instructions must be followed to avoid damage to
the control panel and associated equipment.
FACP operation and reliability depend upon proper
installation.
This equipment must be correctly programmed
and installed to suit the specific application.
Please ensure correct operational parameters are
set prior to commissioning. If further details on
programming options are required, please consult
the programming manual or contact our helpful
technical support personnel.
EMC WARNING:
This equipment may radiate radio frequency energy. It may also be affected by radio frequency energy and, if
not installed and operated in accordance with the manufacturers instructions, may cause interference to radio
communications. It has been tested and found to comply with the Class A radiated and conducted EMI
requirements of AS/NZ 3548:1995 (including Amendments 1 & 2) as well as the EMI susceptibility
requirements of Clause C3.5 in AS4428.0:1997.
Radio communication devices should not be used in the vicinity of fire panels or associated ancillary devices
and systems.
Documentation Feedback
Your feedback helps us keep our documentation up to date and accurate. If you have any comments or suggestions about
our printed manuals you can email us.
Please include the following information:
Product name and version number (if applicable)
Manual part number and revision (found on the front cover)
Page number
Brief description of the content you think should be improved or corrected
Your suggestion for how to correct/improve documentation
Send email messages to:
techpubs@notifier.com.au
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
you nearest branch for technical support.
POWER SUPPLY RATINGS AND SETTINGS ............................................................................................................. 9
INTERNAL 24 VDC (nom) 3.0A MAIN POWER SUPPLY .......................................................................................... 9
INTERNAL 27.3V DC 1.5A BATTERY CHARGER..................................................................................................... 9
Internal 5VDC 2A Power Supply ..................................................................................................................................... 9
EXTERNAL 27VDC POWER SUPPLY ....................................................................................................................... 10
BATTERY TYPE AND CAPACITIES .......................................................................................................................... 10
GENERAL ........................................................................................................................................................................ 11
CURRENT CONSUMPTION ......................................................................................................................................... 11
AZF SUPERVISORY CURRENT .................................................................................................................................. 12
PROGRAMMING BY COMPUTER............................................................................................................................. 13
ALIGNMENT AND ADJUSTMENT.....................................................................................14
PCB2006 POWER SUPPLY BOARD ............................................................................................................................ 14
INTERNAL 24VDC (nom) POWER SUPPLY.............................................................................................................. 14
INTERNAL 5VDC POWER SUPPLY TP8...................................................................................................................14
POWER SUPPLY COMPARATOR REFERENCE VOLTAGE TP10 ......................................................................... 14
NON ADJUSTABLE TEST POINTS..............................................................................................................................14
IFS2004 - JP4 PROGRAM DISABLE ..........................................................................................................................16
IFS2004 - JP5 CPU RESET...........................................................................................................................................16
IFS2005 – JP2 DOOR HOLDER BYPASS...................................................................................................................16
IFS804 - JP1-7 ZONE BOARD ADDRESSING...........................................................................................................16
PLACING INTO OPERATION............................................................................................ 17
EQUIPMENT AS FITTED..............................................................................................................................................17
POWER UP CHECKLIST...............................................................................................................................................18
GLOBAL FUNCTIONS.................................................................................................................................................22
ZONE FUNCTIONS.......................................................................................................................................................24
GLOBAL OPTIONS.........................................................................................................................................................27
ZONE OPTIONS ..............................................................................................................................................................27
PROGRAM MODE..........................................................................................................................................................29
GLOBAL ........................................................................................................................................................................ 30
MAIN MENU.................................................................................................................................................................... 30
ZONE PROGRAMMING................................................................................................................................................ 31
SELECT ZONE #........................................................................................................................................................... 31
ZONE SELECTED......................................................................................................................................................... 31
ZONE TYPE .................................................................................................................................................................. 31
ZONE OUTPUT CONFIGURATION ........................................................................................................................... 32
GLOBAL PROGRAMMING.......................................................................................................................................... 33
TIME (DATE & TIME)................................................................................................................................................... 35
APPENDIX A ......................................................................................................................36
DESCRIPTION OF ALARM ZONE TYPES................................................................................................................ 36
NON LATCHING TYPE ............................................................................................................................................... 36
TIME DELAY AZF........................................................................................................................................................ 37
APPENDIX B ......................................................................................................................38
ZONE OUTPUT CONFIGURATIONS.......................................................................................................................... 38
APPENDIX C ......................................................................................................................39
AND MAPPING ............................................................................................................................................................... 41
OR MAPPING.................................................................................................................................................................. 41
APPENDIX F ......................................................................................................................43
GLOSSARY OF TERMS.................................................................................................................................................43
DETECTION ZONES ....................................................................................................................................................44
BELL OUTPUTS ...........................................................................................................................................................44
DOOR HOLDER OUTPUTS.........................................................................................................................................44
AUXILIARY POWER & MIMIC POWER ................................................................................................................... 44
MIMIC DATA & CLOCK..............................................................................................................................................44
AC INPUT......................................................................................................................................................................44
DOOR HOLDER AC INPUT.........................................................................................................................................45
MAIN KEYPAD AND DISPLAY..................................................................................................................................53
ASE Connection Diagram...............................................................................................................................................58
Auto Changeover Dual Sounder Connection Diagram....................................................................................................59
Auto Change Over Dual Sounder Connection Diagram.................................................................................................. 60
Single Fan Connection Diagram .....................................................................................................................................62
Dual Fan Connection Diagram........................................................................................................................................63
Exhaust Fan Connection Diagram...................................................................................................................................64
Supply Fan Connection Diagram ....................................................................................................................................65
Smoke Spill Fan Connection Diagram............................................................................................................................66
System SensorThermalType A5451 AUS
System SensorThermalType A51A51
System SensorThermalType B4451 AUS
System SensorThermalType B51B51
System SensorThermalType B Sealed51B51S
System SensorThermalType C51C51
System SensorThermalType D51D51
System SensorSmokePhoto-Optical2151 AUS
System SensorSmokePhoto-Optical2151B AUS
System SensorSmokeIonisation1151 AUS
System SensorThermalType D51D51
System SensorSmokeBeamBEAM1224
System SensorSmokeDuctDHP-100
IEIVESDA E700, E70DCONTACT DEVICE
Please contact NOTIFIER INERTIA for any additional detectors.
P/N 10069 ECN08-0066
Page 6IFS-2600 Installation & Programming Manual
OVERVIEW
IFS-2600 Fire Indicator Panel (FIP) is designed to provide simplicity to the end user. The FIP uses both a liquid crystal
display and conventional LED displays for fast and accurate display of system status and changing events.
A custom designed membrane keypad is used together with the liquid crystal display and LED indicators to provide fast,
efficient and simple modes of operation. The keypad also provides the required flexibility for the programming of the
many user configurable options of this FIP.The FIP can be configured on-site without the need of expensive
programmers or components.
A serial printer can also be connected if required. The printer can be used to output programming information for ease of
modification, for safekeeping and to assist in the commissioning of the installation.
IFS-2600 uses serial chain mimic outputs which significantly saves time and costs of cabling to mimic panels.
A door holder power supply (using optional transformer) is incorporated into the system for the release of smoke and fire
doors on alarm.
IFS-2600 is available in a standard 8-zone configuration and can be expandable to its fully expanded state as required.
The IFS-2600 in its fully expanded state can;
•Monitor 64 detection zones
•Control 64 optional "mapped" relay outputs
•Output to a serial printer
•Output serially to a mimic panel
•Control to door holders
•Interface as required to any Australian Fire Brigade
IFS-2600 has been designed to be functional, flexible and reliable whilst maintaining a user-friendly interface.
CAUTION
IFS-2600 FIP has been tested and approved to AS4428.1 and meets the requirements of AS1670 and AS1668 Parts 1 &
2.
However, the equipment must be correctly programmed and installed to suit the specific application. Please ensure
correct operational parameters are set prior to commissioning. If further details on programming options are required,
please consult the programming manual or contact our helpful technical support personnel.
WARNING:
This equipment may radiate radio frequency energy. It may also be affected by radio frequency energy and, if
not installed and operated in accordance with the manufacturers instructions, may cause interference to radio
communications. It has been tested and found to comply with the Class A radiated and conducted EMI
requirements of AS/NZ 3548:1995 (including Amendments 1 & 2) as well as the EMI susceptibility
requirements of Clause C3.5 in AS4428.0:1997
CAUTION:Radio communication devices should not be used in the vicinity of fire panels or associated
ancillary devices and systems
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming ManualPage 7
SPECIFICATION
CabinetZinc Sealed Steel 1.6mm
Powder Coated
Hinged Inner Door
Hinged Outer Door
Outside Dimensions2608 (8 zones)394mm H x 390mm W x 180mm D*
2624 (24 zones)750mm H x 390mm W x 180mm D*
2600 (32 to 64 zones)18U, 28U & 40U Cabinets
Battery Box
*Note: the depth quoted is including the door and break glass.
The internal cabinet depth not including he door and break glass
is 140mm.
AC Operational Voltage240 VAC 50Hz+ 10%
Internal Power SuppliesBattery Charger27.3 VDC1.5AMP
Panel Supply24 VDC(nom) 3.0AMP
Logic Supply5 VDC2.0AMP
Microprocessor80C52
Memory TypeNon-volatile E2ROM
Liquid Crystal Display2 Lines x 16 Characters LED Backlit
FusesF1: Panel SupplyM205 5A
F2: Battery ChargerM205 3A
F3: Battery ProtectionPolyfuse 3A
F4: External SupplyM205 7A
F5: Door HolderM205 3A
F6: Aux Power OutputM205 1A Slow Blow
F7: BellM205 1A
F8: Warning SystemM205 1A
F9: ACFM205 1A
E.O.L Resistor On AZFs, monitored
outputs, Bells, Warning system, ACF
4K7 Ohms
APPROVALS
Australian Standard AS4428.1 1998
SSL Approval No AFP-1553
C-Tick Approval No. N1336
ENVIRONMENTAL LIMITS
-10 Deg. C to +55 Deg. C Dry heat.
+40 Deg. C @ 93% Relative Humidity.
P/N 10069 ECN08-0066
Page 8IFS-2600 Installation & Programming Manual
SYSTEM EXPANSION
ZonesQtyHardware RequiredProduct Code
81Main Control BoardPCB-2004
This supply's primary function is to power panel logic and all external operations of the FIP, i.e.: detection
circuits, ancillary circuits, etc. This supply meets the requirements of AS4428.5.
AC Input30 VAC +10% - 15%
Output Current3.0 AMPS
Output Voltage26.5 VDC
Current Limit3.0 AMPS
Output Ripple50 mV
INTERNAL 27.3V DC 1.5A BATTERY CHARGER
Its primary function is to charge the batteries. This supply meets the requirements of AS4428.5.
AC Input30 VAC +10% -15%
Output Current1.5 AMPS
Output Voltage27.3 VDC
Current Limit1.5 AMPS
Output Ripple200 mV
Important Note:
After a power failure, the battery will only reconnect to the charger if the battery voltage is above approximately
20V +/- 2V.
A battery fault will be generated in the event that the battery does not automatically reconnect. This is to ensure
that a faulty or dead flat battery (due to an extended power failure) does not bring the entire system down.
In order to reconnect a flat battery, it is necessary to disconnect the battery from the panel and charge it
externally. The battery should be thoroughly tested before returning it to service.
In the event that an external charger is not available, the battery may be trickle charged above 22V via a 30
ohm, 5W resistor connected between the 24v Aux Output and the battery positive terminal. A 1N4004 Diode
(Notifier part number #286) or similar should also be fitted in series with the resistor to stop the battery from
pulling down the main panel voltage. Trickle charging the battery by this method may take several hours to
bring it up to the minimum level.
The battery can then be reconnected to the panel for charging via the internal battery charger. It is important
that the voltage on the battery be monitored to ensure that it is charging. The battery should then be left for 24
hours and then fully tested to ensure that no damage has occurred due to the deep discharge.
Internal 5VDC 2A Power Supply
This supply's primary function is to power all internal operations of the FIP, i.e.: Microprocessor, liquid crystal
display, LED's keypad etc.
AC Input30 VAC +15% or 27.6VDC+15%
Output Current2.0 AMPS
Output Voltage5.0 VDC
Current Limit2.0 AMPS
Output Ripple150 mV
P/N 10069 ECN08-0066
Page 10IFS-2600 Installation & Programming Manual
INPUT
INPUT
24V0V
IFS-2600 TERMINATION BOARD
EXTERNAL 27VDC POWER SUPPLY
This supply is used in addition to the internal power supply for large systems. Its primary function is to power
any additional ancillary loads of the FIP up to 7 amps. This supply meets the requirements of AS4428.5
Important Notes:
When using external power supply, JP1 link on IFS2006E must be fitted to enable external PSU monitoring.
If this supply is used to power a NI-2008 gas module, the following additional components are required to
ensure a break free change over from the mains supply to the panel battery in case of mains fail condition.
1. A 6A4 or P600G rectifier diode (Notifier part number #266) is to be installed in series with the
external +27V output of the IFS-2600 termination board.
2. A 3300µF 50V Electrolytic Capacitor (Notifier part number #1248) should be installed across the
+27V and 0V of the ancillary device.
AC
REMOTE
REMOTE
OUTPUT
24V 0V-+24V 0V
BATT
INPUT
EXTERNAL
POWER
SUPPLY
OUTPUT
0V
24V
6A4
+
3300uF
POWER IN
NI-2008 GAS
SUPPRESSION
MODULE
BATTERY TYPE AND CAPACITIES
In general, any Sealed Lead Acid Battery, or Wet Lead Acid Battery designed for stationary use is compatible
with the IFS-2600 Fire Indicator Panel. Automotive batteries must not be used. The use of Nickel Cadmium
batteries is not recommended.
Best and BestSealed LABP17-1212172
Best and BestSealed LABP24-1212242
Best and BestSealed LABP40-1212402
Olympic BatteriesSealed LACJ12-71272
Olympic BatteriesSealed LACJ12-1212122
Olympic BatteriesSealed LACJ12-1812182
Olympic BatteriesSealed LACJ12-2612262
Olympic BatteriesSealed LACJ12-3312332
Olympic BatteriesSealed LACJ12-4012402
Olympic BatteriesSealed LACJ12-8812882
Olympic BatteriesSealed LACJ12-100121002
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming ManualPage 11
TECHNICAL DESCRIPTION
GENERAL
The IFS-2600 in its most basic form comprises of three boards, the main control board, the main termination
board and the power supply board.
The main control board contains the Microprocessor, EPROM, RAM and E2ROM. The main control board also
has the liquid crystal display and keypad attached. All of the "delicate" electronics have been placed on this
board. The main control board complete with the inner door is easily removed during installation to avoid
damage and allow greater access to the field terminals.
The main termination board contains the one power supply for 5V logic, and connectors for a Power Supply
and Battery Charger daughter board, the first eight zones, all common outputs and the printer interface. All
charger settings, fuses etc are located on this board. The Power Supply and Battery Charger board contains
two switch mode regulators, 26.5V for the panel power, 27.3V for the battery charger.
Up to seven (7) zone expansion boards can be added to the system to increase its detection capability. These
boards contain the same electronics as on the main termination board for zone scanning. Addressing is by a
jumper that selects which group of eight zones the board refers to.
Up to four (4) zone indicator boards can also be added. These boards will display the status of the zone
expansion boards fitted.
Up to eight (8) relay boards can be added. These boards contain 8 change-over relay contacts, each rated at
1 amp. These boards require no addressing, as they work on a serial data chain. Output 1 is the closest
output to the main board.
NOTE This product utilises state of the art components and materials and therefore boards must be returned
to our factory for proper troubleshooting, repair and retesting. Field component level repairs are not
recommended and would void all warranties on the product.
TRANSIENT SUPPRESSION
The IFS-2600's superior transient protection comprises of Dual Transorb input traps, inductive paths on
incoming PCB tracks, circuit board planes and metal oxide varistors on outputs. These devices are all selfresetting.
CURRENT CONSUMPTION
Zones FittedQuiescent CurrentQuiescent + 2 AZF'S in alarm +1A of Bell +1 Amp ACF
Note:
1:Each installation would require individual battery calculations to be performed for load capacity and
power supply capacity.
2:Each IFS-717 relay board, can add 370 mA (in alarm and quiescent) current per board.
P/N 10069 ECN08-0066
Page 12IFS-2600 Installation & Programming Manual
AZF DESCRIPTION
The AZF's on the IFS-2600 are monitored and scanned by custom thick film hybrids. These hybrid IC's
significantly reduce the possibility of false alarms and improve product efficiency and reliability.
The total Alarm Zone loop resistance is the sum of the end of line resistor (EOLR 4K7) plus all the parallel
connected detector loads.
AZF SUPERVISORY CURRENT
The supervisory current flows through the external terminal AZF+, through the field cable and to the end of line
resistor (EOLR), returning to the panel at AZF- terminal. Parallel connected, across the 2-wire pair field cable,
are a number of the previously listed detectors. During the quiescent state there is essentially an open circuit
across the + and - terminals of the detector base. The maximum number of detectors that can be installed on
each AZF is dependant on the type of detector and is listed in the IFS-2600 ActivFire®listing.
In an alarm state, a 560-ohm resistor is connected across the detector base causing additional loop current to
flow. This is sensed by the AZF to produce an alarm output. Removal of the E.O.L. resistor (in a non alarm
state) or the interruption of the supervisory current will produce a fault signal in the AZF.
As described above, the level of current is used to define the status of the alarm zone: -
I = 3.5 mA and belowFAULT
I = 4.0 - 5.0mA at 24VQUIESCENT
I = 16 mA to 40 mA (current limited)ALARM
The zone current is used by the hybrid IC to determine the condition of the zone as above. This information is
then transferred to the microprocessor for processing.
If a zone is overloaded by an accidental short to earth on an AZF circuit, the zone will automatically shut down
and produce a fault. Once this happens the panel will automatically recheck the zone every 60 seconds and
once the overload is removed, restore power and the fault will clear.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming ManualPage 13
PRINTER OUTPUT
The printer port is designed to be used during testing and commissioning of the panel. The serial printer will
report alarms and faults together with the date and time of the event.The printer can also be used during
“walk test” mode to produce a history of the test and can also be used to print current programming
configuration.
A DB9 plug male is provided at the top of the main termination board.This communication port will
communicate with an IBM compatible serial printer (ASCII printer) with the following settings.
Baud Rate1200 bps
Data Bits8
Stop Bits1
ParityNone
HandshakingDTR
CABLE CONNECTION
Cabling to the printer requires a 4-core telephone style cable with a maximum length of 10 metres. A DB9
socket is required at the panel end. The printer end is dependent on the type of printer used but is usually a
male DB25. Connection is as follows. A 5-core cable can be used for both comms and printer functions
IFS-2600 ENDPRINTER END
DB9 FEMALEDB25 MALEDB9 MALE
2RX (only for programming)23
3TX32
5GND75
7RTS ( do not use)(5)(8)
8CTS ( only for printer)47
PROGRAMMING BY COMPUTER
Programming of the zones, relays, global functions and time can by set with the DOS based program
“2600/SW” using the printer port. (Cannot be used with Windows XP)
After the cable is installed, the program can be run and the menu will prompt for the available functions.
2600
P/N 10069 ECN08-0066
Page 14IFS-2600 Installation & Programming Manual
ALIGNMENT AND ADJUSTMENT
PCB2006 POWER SUPPLY BOARD
INTERNAL 24VDC (nom) POWER SUPPLY
With batteries disconnected and no alarms present, measure voltage across the 0V and MAIN test
points on the 2006 power supply board and, if necessary, adjust the multi-turn potentiometer VR2 until
voltage is 26.5V 0.05V (26.45V – 26.55V).
Current limiting is fixed and field adjustment is not possible.
INTERNAL 27.3 VDC BATTERY CHARGER
With batteries disconnected and no alarms present, measure voltage across the 0V and CHARG test
points on the 2006 power supply board and, if necessary, adjust the multi-turn potentiometer VR1 until
voltage is 27.3V 0.05V (27.25V – 27.35V).
Current limiting is factory preset and field adjustment is not required.
EXTERNAL 24VDC (nom) POWER SUPPLY (if fitted)
With batteries disconnected and no alarms present, measure voltage across Remote Input terminals
on PCB2005 and adjust the voltage on the external power supply until the voltage is 26.5V 0.5V
(26.0V – 27.0V).Note: This voltage is not critical for the operation of the IFS-2600 panel, but the
voltage must not go outside the limits as specified for the field ancillaries that it powers.
PCB2005 TERMINATION BOARD
INTERNAL 5VDC POWER SUPPLY TP8
All parameters are fixed and field adjustment is not possible.
POWER SUPPLY COMPARATOR REFERENCE VOLTAGE TP10
With the panel in the quiescent mode, measure voltage between system 0V and TP10. Adjust multiturn potentiometer VR3 until voltage is 7.0V 1% (6.93V – 7.07V)
NON ADJUSTABLE TEST POINTS
TP8 = 5.0 VDC 5%5VDC POWER SUPPLY
TP5 = 12.0 VDC 5%12VDC POWER SUPPLY
(If these test point voltages are not correct, please return the main termination board to the factory for
repair.)
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming ManualPage 15
ALARM THRESHOLD COMPARATOR TP7
With the panel in the quiescent mode, measure and take note of the INTERNAL 24V DC POWER
SUPPLY as above.
Measure voltage between system 0V and TP7. Adjust multi-turn potentiometer VR4, and adjust until
the voltage is as per the following table.
Rail Voltage3.3V SettingRange
20.62.8332.80 to 2.86
21.02.8882.86 to 2.92
21.52.9562.93 to 2.99
22.03.0252.99 to 3.06
22.53.0943.06 to 3.12
23.03.1633.13 to 3.19
23.53.2313.20 to 3.26
24.03.3003.27 to 3.33
24.53.3693.34 to 3.40
25.03.4383.40 to 3.47
25.53.5063.47 to 3.54
26.03.5753.54 to 3.61
26.53.6443.61 to 3.68
27.03.7133.68 to 3.75
27.53.7813.74 to 3.82
27.63.7953.76 to 3.83
28.03.8503.81 to 3.89
FAULT THRESHOLD COMPARATOR TP6
With the panel in the quiescent mode, measure and take note of the INTERNAL 24V DC POWER
SUPPLY as above.
Measure the voltage between system 0V and TP6. Adjust multi-turn potentiometer VR1, and adjust
until the voltage is as per the following table.
Rail Voltage0.6V SettingRange
20.60.6000.59 to 0.61
21.00.6120.61 to 0.62
21.50.6260.62 to 0.63
22.00.6410.63 to 0.65
22.50.6550.65 to 0.66
23.00.6700.66 to 0.68
23.50.6840.68 to 0.69
24.00.6990.69 to 0.71
24.50.7140.71 to 0.72
25.00.7280.72 to 0.74
25.50.7430.74 to 0.75
26.00.7570.75 to 0.76
26.50.7720.76 to 0.78
27.00.7860.78 to 0.79
27.50.8010.79 to 0.81
27.60.8040.80 to 0.81
28.00.8160.81 to 0.82
P/N 10069 ECN08-0066
Page 16IFS-2600 Installation & Programming Manual
CONFIGURATION JUMPERS
IFS2004 - JP3 DEFAULT
Holding a short across these pins for 5 seconds during start-up causes the panel to reset to standard
factory defaults. The panel will give 4 beeps after reset, to acknowledge default on start-up.
IFS2004 - JP4 PROGRAM DISABLE
When fitted, jumper between these pins to inhibit program changes.
IFS2004 - JP5 CPU RESET
With panel operating, a momentary short across these pins will cause a CPU restart.
IFS2005 – JP2 DOOR HOLDER BYPASS
If zoned door holder outputs are required and is to be done external to the main termination board,
then the main door holder release needs to be disabled. Fitting a link across JP2 on IFS2005 PCB
does this.
Note: Door holder output is only enabled if optional door holder transformer is fitted. SW1 must be
linked on PCB2004 CPU board prior to Version 6 Firmware.
IFS2006 – JP1 EXTERNAL PS MONITORING
When using external power supply, JP1 link on IFS2006E must be fitted to enable external PSU
monitoring.
IFS804 - JP1-7 ZONE BOARD ADDRESSING
Jumper JP1 to JP7 on zone expansion board IFS-804 selects the addressing for the zones.
Place jumper in link position for the appropriate 8 zones to which the expansion board applies.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming ManualPage 17
PLACING INTO OPERATION
Suitably qualified technicians must install the panel. The following check procedures are recommended after
every installation and prior to initial power-up.
A thorough visual inspection should be made to every aspect of the fire panel. This includes loose wire, metal
filings, loose circuit boards, loose cabling, damage in transit etc.
All problems must be rectified immediately as they could cause incorrect operation or permanent damage to
the equipment.
EQUIPMENT AS FITTED
QTYDescriptionCode
1MAIN CONTROL BOARDIFS -2004
1MAIN TERMINATION BOARDIFS -2005
1MAIN POWER SUPPLYIFS -2006
8 ZONE EXPANSION BOARDIFS -804
16 ZONE INDICATOR BOARDIFS -816
ADD ON, 8 WAY RELAY BOARDIFS-717
EXTERNAL POWER SUPPLY BOOSTERPS244, PS249, NPS-3,
3A DOOR HOLDER P/SUPPLY TRANSFORMER2600/DHTX
INITIAL CHECKLIST
System general appearance good
Cabinet colour and condition good
Cabinet keyed 003
All circuit boards firmly fastened
Manual call point fitted & functional
Viewing window clear and firmly secured
Cable entries adequately sealed
240VAC mains cabling is correctly terminated
All earthing secured
Transformer securely mounted
Transformer correctly wired
All ribbon cables firmly secured
All operational zones adequately identified
All fuses correct value and fitted properly
All other modules securely fitted
Manufacturing label affixed
NPS-5, NPS-11
You are now ready to power up the IFS-2600 Fire Indicator Panel.
P/N 10069 ECN08-0066
Page 18IFS-2600 Installation & Programming Manual
POWER UP CHECKLIST
Ensure batteries are disconnected.
Turn mains switch to "on"
The "mains on" led should light.
Allow 15 seconds for the panel to perform its start up tests.
Connect batteries
FUNCTIONAL TESTING
Primary ac supply voltage: 200 or 220 or 240vac +10% as required
Charger output voltage without batteries: 27.3v dc
Keypad functional
Perform auto test
Internal sounder operating
MCP loop wired to zone number ______ (if applicable)
Test auxiliary power output
Test bell output
Test warning system output
Test ACF output
Test door holder output (optional)
Test bell output supervision
Test warning system output supervision
Test ACF output supervision
Test brigade alarm relay #1
Test brigade alarm relay #2
Test standby relay (normally energised)
Test fault relay (normally energised)
Test mains fail relay
Test isolate relay
Test general alarm relays (2)
Test relay boards (if fitted)
Test open collector output boards (if fitted)
Press "battery test" once
If batteries are flat, allow 24hrs to charge and then re-test.
P/N 10069 ECN08-0066
IFS-2600 Installation & Programming ManualPage 19
FAULT RECORD
FAULTCORRECTIONDATE
TESTS SATISFACTORILY COMPLETED.
TESTED BY _______________________________
SIGNATURE _______________________________
DATE OF TEST ____________________________
If all faults have been rectified and all tests are completed satisfactorily, the 2600 fire indicator panel is now
ready for operation.
P/N 10069 ECN08-0066
Page 20IFS-2600 Installation & Programming Manual
INSTRUCTIONS TO OPERATORS
INDICATORS
QtyDescriptorColourFunctionBuzzer
1MAINS ONGreenIlluminates when there is 200/220/240 VAC supply to
the panel.
1BATTERY
FAULT
1PSU FAULTYellowIlluminates if the power supply is outside the
1CHARGER
LOW
1COMMON
FAULT
1ACF ACTRedIlluminates if the ACF output has been activated.
1ACF FLTYellowIlluminates if the ancillary circuit is open or short
1ACF ISOYellowIlluminates if the ancillary output has been manually
1Bell ACTRedIlluminates when the bell output has been energised.
1Bell FLTYellowIlluminates if the bell circuit is open or short circuit.
1Bell ISOYellowIlluminates if the bell output has been manually
1Warning
System ACT
1Warning
System FLT
1Warning
System ISO
8ALARM LEDSRedThis LED will flash if it's corresponding zone goes
8FAULT LEDSYellowThis LED illuminates if it's corresponding zone goes
8ISOLATE LEDSYellowThis LED illuminates if its corresponding zone is
YellowIlluminates if the battery fails a battery test.
Illuminates if batteries are disconnected >30
seconds.
Illuminates if batteries are short circuit >30 seconds.
manufacturers range.
YellowIlluminates if the battery charger is outside the
recommended float charge voltage.
YellowIlluminates if;
Any un-isolated zone goes into fault.
ACF output is open or short circuit
Bell output is open or short circuit
Warning System output is open or short circuit
Battery Fault
Charger Fault
Power Supply Fault
MAF Isolate Input is Open Circuit
Configuration Fault
circuit. The LED will extinguish when the load is
restored.
isolated.
The LED will extinguish when the load is restored.
isolated.
RedIlluminates if the Warning System output has been
energised.
YellowIlluminates if the Warning System circuit is open or
short circuit. The LED will extinguish if the load is
restored.
YellowIlluminates if the Warning System has been manually
isolated.
into alarm. It will remain flashing until it is
Acknowledged at which time it will go steady and
remain on until the alarm is reset. If the zone is
programmed as a time delay type, a steady LED
indicates the “pre-alarm” condition. If the zone is
isolated and in alarm it will also be steady.
into fault. It will remain on until the fault is removed.
isolated. It will remain on until the zone is deisolated.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
P/N 10069 ECN08-0066
Loading...
+ 56 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.