Honeywell H808C User Manual

H808C
Convertible Dehumidifier Controller
Application
The H808C Dehumidifier Controller provides automatic low voltage control of dehumidifiers in central heating systems. The humidity controller has an spst, snap-acting, dust-proof switch and is designed for wall or surface duct mounting.
MODELS:
H808C1029: Premier White™.
H808C1037: Beige.
ELECTRICAL RATING: 50 VA at 24 Vac.
MAXIMUM AMBIENT TEMPERATURE: 125° F [52° C].
SWITCH DIFFERENTIAL: 5 percent RH, nonadjustable.
SET POINT ADJUSTMENT RANGE: 20 to 80 percent
RH; positive ON and OFF positions.
Installation
CAUTION
1. Installer must be a trained, experienced service technician.
2. Disconnect power supply before beginning installation.
3. Conduct a thorough checkout before leaving installation.
WALL MOUNTING
1. Locate the humidity controller about 5 ft [1.5m]
above the floor on an inside wall.
NOTES:
a. Be sure the humidity controller is subject to average
room temperature and average relative humidity. The maximum temperature at the location selected must not exceed 125° F [52° C].
b. The humidity controller can be mounted directly on
the wall.
2. Drill a small hole in the wall.
3. Run low voltage wiring to the location and pull about
6 in. [152 mm] of wire through the hole.
NOTE: Plug the opening to prevent drafts from affecting
humidity controller operation.
4. Remove the humidity controller assembly by prying with a screwdriver in the notch on the bottom of the case (Fig. 1).
5. Position the case horizontally over the wires with the arrows on the tabs pointing up and secure the case to the wall using the two screws provided.
6. Connect the wires to the humidity controller assem­bly using leadwires and wire nuts provided (see Wiring section and Fig. 2).
7. Tuck the wires into the bottom of the case.
8. Snap the cover assembly into the case (Fig. 2).
Fig. 1—Removing humidity controller assembly from case.
M9262
Fig. 2—Wiring connections on humidity controller.
QUICK-CONNECT WIRE LEAD
UP
MOUNTING HOLE (2)
COVER
CASE
UP
UP
M9263
WIRE NUT
HUMIDIFIER LEADWIRE
1 69-0821
J.F. • 3-94 • ©Honeywell Inc. 1994 • Form Number 69-0821
DUCT MOUNTING
1. Locate the humidity controller at least 8 in. [203 mm]
upstream of the humidifier in the return air duct.
NOTE: If mounting near an elbow area, keep the humidity
controller 6 in. [152 mm] upstream of the elbow so the element will be affected by the normal airflow (Fig. 3)
.
2. Using Fig. 4 and the instructions on the template, drill two mounting holes (3/32 in. [2.4 mm]) and 12 sensing holes (1/4 in. [6.4 mm] in diameter) in the duct. (The sensing holes allow return air to reach the nylon sensing element and operate the humidity controller.)
NOTE: If desired, cut a square hole in the duct as indicated
on the template in place of the sensing holes.
Fig. 3—Selecting a duct location for the humid­ity controller.
ALTERNATE
RETURN AIR
6 in. [152 mm] MINIMUM
BEST LOCATION
RETURN AIR DUCT
LOCATIONS
15 in. [381 mm] MINIMUM
RETURN AIR
M9277
7. While holding wire in place, mount the case on the
duct using the two mounting screws provided.
NOTE: Tighten the screws firmly so the gasket seals the
space between the case and the duct (Fig. 4).
8. Connect the wires to the humidity controller assem­bly using leadwires and wire nuts supplied (see Wiring section and Fig. 2).
9. Snap cover assembly into the case.
Fig. 4—Mounting humidity controller on return air duct.
LOCATE TEMPLATE.
1
2
PEEL BACKING FROM TEMPLATE AND APPLY TO DUCT.
3
PUNCH AND DRILL TWO 3/32 IN. [3 mm] MOUNTING HOLES.
DRILL MINIMUM
4
OF TWELVE 1/4 IN. [7 mm] HOLES. OR DRILL OR PUNCH CORNER HOLES AND CUT OUT SQUARE ON SOLID LINE.
3. Remove the protective backing from the foam gasket included with each control and apply the foam gasket to the template in the location indicated.
4. Remove the cover and humidity controller assembly from the case by prying with a screwdriver in the notch in the bottom of the case (Fig. 1).
5. Run low voltage wire from the humidity controller to the template (Figs. 5 and 6).
6. Lay wire over one side of the foam gasket allowing about 6 in. [152 mm] for connection to the humidity con­troller. Wire can enter the humidity controller case from any direction.
NOTE: Do not position wire directly under the two stand-
off projections at the back of the case. If wire is under these projections, the case will not seat tightly against the gasket, causing air leakage and possible improper operation.
CASE
TEMPLATE
GASKET
UP
M9264
69-0821 2
Fig. 5—Typical parallel wiring diagram of H808C with T87F/Q539A combination for dehumidification and mildew control.
H808C
T87F/Q539A INTERNALSCHEMATIC
FILTER LIGHT
HEAT OFF FANAUTO ONCOOL
3 2
BX O
PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS
1
AS REQUIRED.
HEATING DAMPER MOTOR, IF USED.
2
3
CLOGGED FILTER SWITCH OR COOLING PANEL CONNECTION.
Fig. 6—Typical series wiring diagram of H808C with T87F/Q539A combination for dehumidification and mildew control.
H808C
FILTER LIGHT
R1
T87F/Q539A INTERNALSCHEMATIC
R1
T87F
TEMPERATURE FALL
W1 Y1
HEAT OFF COOL
W Y
HEATING RELAY OR VALVE COIL
COOLING CONTACTOR COIL
T87F
TEMPERATURE FALL
W1 Y1
FIXED COOL ANTICIPATOR
G RHR
FAN RELAY COIL
FIXED COOL ANTICIPATOR
ADJUSTABLE HEAT ANTICIPATOR
ADJUSTABLE HEAT ANTICIPATOR
1
M18627
HEAT OFF FANAUTO ONCOOL
3 2
BX O
PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS
1
AS REQUIRED.
HEATING DAMPER MOTOR, IF USED.
2
3
CLOGGED FILTER SWITCH OR COOLING PANEL CONNECTION.
HEAT OFF COOL
W Y
HEATING RELAY OR VALVE COIL
COOLING CONTACTOR COIL
G RHR
FAN RELAY COIL
1
M18626
3 69-0821
Fig. 7—Typical wiring diagram for H46C,E.
1
L1 (HOT)
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS
1
AND OVERLOAD PROTECTION AS REQUIRED.
HUMIDITY RISE
H46C, E CONTROLLER
DEHUMIDIFIER EXHAUST FAN OR AIR CONDITIONER
M9297
WIRING
All wiring must comply with local codes and ordi­nances. Make wiring connections according to to dehu­midifier instructions if available; otherwise, see typical wiring diagrams in Figs. 5 and 6.
Settings
HUMIDITY CONTROLLER ADJUSTMENT
The humidity comfort range of a living space is gener­ally between 25 and 50 percent RH. However, as the outdoor temperature changes, the humidity level on the humidity controller may need to be reset to assure maxi­mum comfort.
To reduce the relative humidity, reduce the set point ap­proximately three percent RH every 24 hours. To increase the relative humidity, increase the set point approximately three percent RH every 24 hours.
WALL MOUNT HUMIDITY CONTROLLER
Set the humidity set point according to the prevailing outdoor temperature to provide optimum relative humidity control for most installations. Adjust the humidity level to a particular structure using the procedure above.
DUCT MOUNT HUMIDITY CONTROLLER
If the temperature at the humidity controller location
on the return air duct is less than 80° F [27° C] ,use the procedure for wall mounted humidity controllers.
If the air surrounding the humidity controller is greater
than 80° F [27° C], reset the recommended settings to compensate for the higher ambient temperature. High ambi­ent temperatures will cause the humidity controller to control at an increased setting. To determine the compensated set point for surface mounted humidity controllers with high ambient temperatures, use the following procedure:
1. With a bulb type thermometer, accurately determine the surrounding duct temperature at the humidity controller location.
2. Decrease the recommended setting about five percent for each 5° F [3° C] above 80° F [27° C] at the humidity controller.
For example, if the humidity controller is set at 25 per-
cent and the temperature at the humidity controller is 90° F [32° C], the compensated set point should be 15 percent. (This is the 25 percent setting less 10 percent for the 10° F [6° C] above ambient temperature.)
Checkout
Place the system in operation and observe through at least one complete cycle to make certain that all compo­nents are functioning properly.
Home and Building Control Home and Building Control Helping You Control Your World
Honeywell Inc. Honeywell Limited—Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley, MN 55422 Scarborough, Ontario
69-0821 4
Printed in U.S.A.
M1P 2V9
QUALITY IS KEY
Loading...