Honeywell H7625B, H7635B, H7636B, H7626B, H7656B Installation Instructions Manual

...
62-0330-01
H7625B, H7626B, H7635B,C
CAUTION
CAUTION
H7636B, H7655B, H7656B
DUCT-MOUNT AND OUTDOOR-MOUNT HUMIDITY/ TEMPERATURE SENSORS
INSTALLATION INSTRUCTIONS

APPLICATION

The humidity sensors are designed with a field selectable 4 to 20 mA, 0 to 5 Vdc, or 0 to 10 Vdc output signal equivalent to 0 to 100% RH. All units are shipped from the factory with a default setting to accept AC power with three-wire, 0 to 10 Vdc output.

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check ratings given in instructions and on the product to ensure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
Equipment Damage Hazard. Improper wiring can damage the sensor beyond repair.
Follow the wiring instructions carefully.

Mounting

The method of mounting depends on the particular sensor application. The following procedures include outdoor and duct applications. Also refer to the instructions for the electronic control.
Duct mounting Configuration
The H7625B, H7626B, H7635B, H7636B, H7655B and H7656B can be mounted in a duct to sense humidity and temperature.
IMPORTANT
Select a location to expose sensor to average duct humidity and temperature. Avoid locations where stratification can cause sensing errors.
NOTES:
• Knockouts allow 1/2 in. conduit connection. To avoid damaging board during installation, the cover can be detached completely:
• Carefully remove wire plug from board.
• Set the cover aside.
1. Drill a 3/4” diameter hole in the duct where the transmitter is to be mounted.
2. Insert the stainless steel probe into the hole until the foam is in direct contact with the duct.
3. Attach the transmitter to the duct using the sup­plied #8 X 3/4” self-tapping screws.
4. Remove the cover and install your conduit connec­tor or watertight fitting. The outer ring is used when using a 1/2” NPT conduit fitting.
5. After wiring the unit, place the cover back on and gently turn it until it is tight.
Outdoor Mounting Configuration
The H7635C senses outdoor air humidity and temperature. Mount this control where it can sense average outdoor air humidity and temperature. Normally, the north side of a building provides a suitable location.
NOTES:
• H7635C is weatherproof for outdoor use. Knockouts allow 1/2 in. conduit connection.
• To avoid damaging board during installation, the cover can be detached completely:
• Carefully remove wire plug from board.
• Set the cover aside.
H7625B, H7626B, H7635B,C H7636B, H7655B, H7656B
The transmitter should be mounted under an eave, shield, or in an area out of the elements or direct sunlight. The aluminum tube should point down when mounting the outside transmitter. Refer to Figure 1 for proper mounting position.
1. Place the unit where it is to be mounted with the cover facing out.
2. Attach the unit with the supplied #8 X 3/4” self-tap­ping screws.
3. Remove the cover and install your conduit connec­tor, watertight fitting or 1/2” vent plug. The outer ring is used when using a 1/2” NPT conduit fitting.
4. After wiring the unit, place the cover back on and turn it until it is tight.
INCORRECT CORRECT
M31319
Fig. 1. Typical sensor location.
PUSH TAB IN AND PULL ON THE SENSOR
RED
FACTO RY USE ONLY
CABLE TO REMOVE FROM J13 CONNECTOR
GREEN
BLUE
SW1
1ON2345678
J13
J14
P1P2
ZEROSPAN
4-20mA VIN VOUTCOM

Output Settings

The humidity output signal can be adjusted for 0-5Vdc, 0­10 Vdc or 4-20 mA using the switch block. Switches 6, 7, and 8 are used to set the output.
NOTE: Refer Fig. 2 for switch settings.
Table 1. Controller Compatibility
and Output Settings.
Controller
W7750, W7760, W7761
W7750B,C W7760C, W7753, W7760
T7350, XL50, XL100, XL500 XF Modules, XFL
Required Sensor Output
Setting
4-20 mA C7600C
0-10 Vdc (default) H7621/31
0-10 Vdc (default) n/a
Non-Honeywell 0-5 Vdc n/a
0-10 VDC OUTPUT
ON OFF
ON OFF
ON OFF
SW1
SW1
SW1
(DEFAULT)
1ON2345678
0-5VDC OUTPUT
1ON2345678
4-20mA OUTPUT
1ON2345678
FACTO RY USE ONLY
J2
TB1
ONSPEC
L
Setting
WIRE CONNECTIONS
Fig. 2. DIP switch and Wire Connection locations.
62-0330—01 2
M31320
REVERSE ACTING OUTPUT
CAUTION
CAUTION
The output can be changed to reverse acting mode. The output range stays the same but the corresponding RH value is opposite. Example: Direct Acting (DA) (Default)
To change the transmitter to reverse acting or back to direct acting, set switch 4 ON to put the unit in setup mode. After switch 4 is on, switch 2 will put the unit in direct/reverse acting mode. When switch 2 is set to ON, the output can be used to show if the unit is in direct or reverse acting mode. For direct acting the output will be 1V for 0-5V, 2V for 0-10V, and 7.2mA for 4-20mA. For reverse acting the output will be 4V for 0-5V, 8V for 0-10V, and 16.8mA for 4-20mA.
With switches 2 and 4 ON, each time switch 5 is set to ON the output will change to reverse acting or direct acting.
To reset the unit to the default setting, toggle both switches 5 and 6 ON then OFF while both switches 2 and 4 are ON.
When all calibration is completed, remember to place the switches back into the positions that correspond to the output needed as shown in Figure 3.
0-10V output mode 0V = 0% RH and 10V = 100% RH
Reverse Acting (RA)
0-10V output mode, 0V = 100% and 10V = 0%

WIRING

A 16 to 22 AWG shielded cable is recommended for all transmitters. Twisted pair may be used for 2-wire current output transmitters. the connections to the temperature sensor should be made with wire nuts or crimp-style connectors.Refer to Figure 3 for wiring diagrams.
H7625B, H7626B, H7635B,C H7636B, H7655B, H7656B
Never connect or disconnect wiring with power applied.
TEMPERATURE SENSOR-
TEMPERATURE SENSOR+
SUPPLY VOLTAGE
4-20mA OUTPUT
TEMPERATURE SENSOR­TEMPERATURE SENSOR+
SUPPLY GROUND/SIGNAL COMMON
0-10 OR 0-5 VDC OUTPUT SIGNAL
SUPPLY GROUND/SIGNAL COMMON
SUPPLY VOLTAGE
4-20mA OUTPUT
TEMPERATURE SENSOR­TEMPERATURE SENSOR+
SUPPLY VOLTAGE
2 WIRE CURRENT OUTPUT SIGNAL
3 WIRE CURRENT OUTPUT SIGNAL
VOLTAGE OUTPUT SIGNAL
CONNECT TO THE 2 22 AWG 24” FLYING LEADS
4-20mA VIN VOUTCOM
CONNECT TO THE 2 22 AWG 24” FLYING LEADS
4-20mA VIN VOUTCOM
CONNECT TO THE 2 22 AWG 24” FLYING LEADS
4-20mA VIN VOUTCOM
TB1
TB1
TB1
M31321
Fig. 3. Wiring Diagrams
It is recommended that you use an isolated UL-listed class 2 transformer when powering the unit with 24 VAC. Failure to wire the devices with the correct polarity when sharing transformers may result in damage to any device powered by the shared transformer.
IMPORTANT
When using shielded cable, ground the shield only at the controller end (see Fig. 4). Grounding both ends can cause a ground loop.
mA OUTPUT TRANSDUCER ONLY
18 TO 36 Vdc POWER SUPPLY
Vin +
4-20mA
CONTROLLER, METER OR RECORDER
INPUT SIGNAL
+
COMMON
GROUND
M22528A
Fig. 4. Typical wiring diagram for transducer with two-
wire mA output with external DC power supply.
3 62-0330—01
Loading...
+ 5 hidden pages