Honeywell H7625B, H7635C, H7655B, H7635B User Manual

H7625B; H7635B,C; H7655B Duct-Mount and Outdoor-Mount Humidity/Temperature Sensors
INSTALLATION INSTRUCTIONS
APPLICATION
The H7625B, H7635B, H7655B Duct-Mount and H7635C Outdoor-Mount Humidity/Temperature Sensors are universal Relative Humidity transmitters that can be powered with either a +18 to 36 Vdc or 24 Vac supply. The sensors use a half-wave bridge rectifier to convert AC power to a usable DC voltage. The device also includes a 20K ohm temperature sensor for optional use.
The humidity sensors are designed with a field­selectable 4to20 mA, 0to5Vdc, or 0to10Vdc output signal equivalent to 0 to 100% RH. All units are shipped from the factory with a default setting to accept AC power with three-wire, 0 to 10 Vdc loop-powered output.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check ratings given in instructions and on the product to ensure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
Mounting
The method of mounting depends on the particular sensor application. The following procedures include outdoor and duct applications. Also refer to the instructions for the electronic control.
Duct Mounting
The H7625B, H7635B and H7655B can be mounted in a duct to sense humidity and temperature.
IMPORTANT
Select a location to expose sensor to average duct humidity and temperature. Avoid locations where stratification can cause sensing errors.
NOTES:
H7635C is weatherproof for outdoor use.
Knockouts allow 1/2 in. conduit connection.
To avoid damaging board during installation,
the cover can be detached completely:
1.Carefully remove wire plug from board.
1. Cut a hole in the duct just large enough to accept
2. Open case by rotating the cover counterclockwise.
3. Mount standard 1/2 in. conduit to the case.
4. Use case to mark mounting screw pilot hole
5. Drill the pilot holes and fasten the sensor to the
6. Wire the sensor. See Wiring section.
7. Reattach the wire plug and cover being careful not
2.Set the cover aside.
the sensing element.
locations.
duct.
NOTE: The two free wires are thermistor wiring
connections. When connecting these, use two wire nuts.
to pinch wires between the cover and case.
CAUTION
Equipment Damage Hazard. Improper wiring can damage the sensor beyond repair.
Follow the wiring instructions carefully.
63-2579—3
H7625B; H7635B,C; H7655B DUCT-MOUNT AND OUTDOOR-MOUNT HUMIDITY/TEMPERATURE SENSORS
Outdoor Mounting
The H7635C senses outdoor air humidity and temperature. Mount this control where it can sense average outdoor air humidity and temperature. Normally, the north side of a building provides a suitable location.
NOTES:
H7635C is weatherproof for outdoor use.
Knockouts allow 1/2 in. conduit connection.
To avoid damaging board during installation,
the cover can be detached completely:
1.Carefully remove wire plug from board.
2.Set the cover aside.
1. Open case by rotating the cover counterclockwise.
NOTE: Orient case so the element points down.
2. Mount standard 1/2 in. conduit to the case.
3. Use case to mark mounting screw pilot hole
locations.
4. Drill pilot holes.
5. Fasten the case to the wall.
6. Wire the sensor. See Wiring section.
NOTE: The two free wires are thermistor wiring
connections. When connecting these, use two wire nuts.
7. Reattach the wire plug and cover being careful not to pinch wires between the cover and case.
Output Settings (Table 1)
The board has three switch blocks: — A six DIP switch block. — A four DIP switch block. — A white gang switch on a blue block.
1. Adjust the 4-switch block according to Table 1.
NOTE: The 6-switch block normally requires no
adjustment. (See the Appendix.)
2. Set the gang switch (white switch in blue block) to correspond with the output (mA or Vdc).
NOTE: See Fig. 1 for DIP switch locations.
Table 1. Controller Compatibility
and Output Settings.
Required
4-Switch Block
Controller
W7750, W7760, W7761
W7750B,C W7760C, W7753, W7760
T7350, XL50, XL100, XL500 XF Modules, XFL
Sensor Output Setting
4-20 mA — On — — 4-20 mA C7600C
0-10 Vdc (default)
0-10 Vdc (default)
Settings
On — — On Vout H7621/31
On — — On Vout n/a
Non-Honeywell 0-5 Vdc On — On — Vout n/a
Blue and
White Output Switch
ONSPEC
L
Setting4321
NORMAL OPERATION
OFF
ON
Fig. 1. DIP switch locations and settings.
63-2579—3 2
OFF
ON
OFF
ON
OFF
ON
0-10 VDC
4-20 MA
0-5 VDC
M22705
H7625B; H7635B,C; H7655B DUCT-MOUNT AND OUTDOOR-MOUNT HUMIDITY/TEMPERATURE SENSORS
WIRING
For voltage output, shielded cable (16-22 AWG) should be used.
For current output, either shielded cable or twisted pair (16-22 AWG) can be used.
NOTE: When using shielded cable, ground the shield
only at the controller end (see Fig. 2). Grounding both ends can cause a ground loop.
The 20K ohm NTC temperature output is accessed through the separate blue and green wires (located inside the enclosure).
OUTDOOR
5
Gnd Vin
(Vac)
AIR SENSOR
123456789
T3
OSOS ASAS
M
MHC HP
MOTION SENSOR
T7770 REMOTE SENSOR
T7350 SUBBASE
T5 T6 T7 T4
HS
Vo
(0-10 Vdc)
HUMIDITY SENSOR
L2
2
1
L1 (HOT)
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
ENSURE TRANSFORMER IS SIZED TO HANDLE THE LOAD.
2
3
HEAT/COOL SYSTEMS WITH ONE TRANSFORMER REQUIRE THE FACTORY-INSTALLED JUMPER.
4
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
5
HC AND HP PROVIDE 24 VAC TO THE HUMIDITY SENSOR.
Fig. 3. Humidity sensor (0-10 Vdc output) wiring with T7350
(use with RH/Temperature combination T7350 units only).
mA OUTPUT TRANSDUCER ONLY
18 TO 36 Vdc POWER SUPPLY
Vin +
Io
CONTROLLER, METER OR RECORDER
INPUT SIGNAL
+
COMMON
GROUND
Fig. 2. Typical wiring diagram for transducer with two-
wire mA output and external DC power supply.
HEAT RELAY 2
DISCHARGE AIR SENSOR
COMPRESSOR CONTACTOR 4
W3/Y4 Y3 W2
RCX
AUXRH
3
4
ECONOMIZER
W1 G
HEAT RELAY 1
COMPRESSOR CONTACTOR 1
COMPRESSOR CONTACTOR 2
Y2
Y1
FAN RELAY
COMPRESSOR CONTACTOR 3
M22529
M22528
3 63-2579—3
Loading...
+ 5 hidden pages