H7012A,B Room Humidity / Temperature Sensor
Honeywell Regelsysteme GmbH
Honeywellstr. 2-6
D-63477 Maintal
Tel. (0 61 81) 401-1 
Fax (0 61 81) 4 54 56
Subject to change without notice. Printed in Germany.
EN0C-0610 0398R3-MA
DIN
 EN ISO 9001
Manufacturi ng location is certified according to
Wiring run Maximum length
Sensor to controller 200m (660ft)
Offset due to wire resistance per 10m distance from sensor 
to controller:
Type of wire Temperature offset
Pt 1000 BALCO 500 NTC
0.5mm
2
(AWG20)
0.18°C (0.324°F) 0.3°C (0.54°F)
1.0mm
2
(AWG17)
0.09°C (0.162°F) 0.15°C (0.27°F) negligible
1.5mm
2
(AWG15)
0.06°C (0.108°F) 0.1°C (0.1°F)
CAUTION
NOTE
Use shielded wiring in areas with high EMI. 
Keep 15cm (5.9’’) minimum distance between 
sensor lines and 230Vac power lines.
Use two transformers: one for sensors and 
actuators and one for the controller (see Fig. 3).
Mounting and Installation Advice:
• 
Mount these units at the inside wall of the room to be 
heated or air conditioned, away from doors, windows 
and heat sources.
• 
Do not mount in niches, book shelves, behind cabinets 
or curtains or where it could be exposed to solar 
radiation.
• 
Seal the conduit opening to avoid false measurement 
due to draught from the conduit.
• 
Provide sufficient air circulation.
Wiring connection
1 
2 
3 
4 
5 
6
TEMPERATURE SENSOR
POWER SUPPLY
REL. HUMIDITY SENSOR
8 
9
10
7
24V
Pt 1000/NTC/ 
BALCO 500
0...1V
0...10V
24V
COM = 24V
Fig. 4 Installation