Ultraviolet Band (0.18 – 0.26 µ)√
Visible Band (0.4 – 0.7 µ)√√√√
NearBand IR (0.7 µ – 1.1 µ)√√√√
WideBand IR1 (1.1 – 3 µ)√√√√
SPECTRAL
SENSITIVITY
WideBand IR1 (1.1 – 3.5 µ)√
SENSITIVITY
WideBand IR2 (3.0 – 5.0 µ)√√
Very High200+200+200+
High15015015045
(feet)*
Medium10010010030
Low50505015
Fireball / Quick Response Option (< 500 mS)√
Acetylene Long Range Option√
RESPONSEOTHERENCLOSURES
Field of View (conical)110°90°90°90°
TEST
HART Option√√√
Modbus Built-In√√√
Aluminum Class I, Div. 1√√√√
316 Stainless Steel Class I, Div. 1√√√√
FM√√√√
cFM√√√√
ATEX√√√√
IECEx√√√√
INMETRO√√√
APPROVALS
GOST-R√√√
SIL 2 Compliant√√
TL-2055√√√
TL-1055√√√
LAMPS
FS-846-B√
SM4√√√√
MOUNT
*Detection distance for a one sq. ft.
reference heptane pan fire
Recommended Suitable Not Recommended
2.
FSX Detectors
4
Applications Chart
Aerosol Filling Facilities
Automotive Paint Lines
Curing Ovens
General Finishing
Liquid Paint Spray Line
FINISHINGGENERALOIL, GAS and PETROCHEMICALSGENERAL
Paint and Solvent Storage
Powder Coating Booths
Aircraft Hangars
Airport Terminals
Cold Storage Warehouses
Engine Test Cells
General Warehouse
Lumber Storage
Marine Engine Rooms
Marine Terminals
PowerPlants
Acetylene Processing and Storage
Chemical Storage
Cogeneration Plants
Crude and Product Tank Farms
Ethanol Production and Storage
Gas Collection Facilities
Gas Compressor Buildings
Gas Processing Plants
Gas Turbine Enclosures
Gasoline Loading Terminals
Isopropanol (IPA) Production and Storage
LNG Storage/Distribution
LPG Storage/Distribution
Methanol Production and Storage
Natural Gas and CNG Plants
Offshore Drilling Platforms
Offshore Production Platforms
Petrochemical Plants
Triple IR Fire and Flame Detector (IR/IR/IR/Visible)
The FS24X is the latest generation high technology Multi-Spectrum Triple IR
(IR/IR/IR/Visible) Fire and Flame Detector, which is part of our FSX family of
advanced technology Electro-Optical fire detectors. Using our patented*
WideBand IR™, WideBand 4.3 micron IR™, and Visible detection technology,
the FS24X is a quantum leap in flame and fire detection. Sophisticated
software algorithms and dual microprocessors ensure that the FS24X has the
highest fire detection performance combined with optimal false alarm
rejection.
110° field of view with a detection range greater than 200 ft.
Features
• Patented* WideBand IR™ Technology
• Patented* Electronic Frequency Analysis™
• Visible Sensor for optimum false alarm
rejection
• Selectable detection sensitivities
• Field-of-View: 110° cone-of-vision
(90° cone-of-vision model also available)
• Dual microprocessors for reliable
performance
• Real-time clock for accurate time dating of
events
• FirePic™ — pre-fire event data storage
• Event log with date and time stamp
• RS-485 Modbus communication
• Non-Isolated 4-20 mA Analog output (sink or
source)
• Alarm, Fault and Fire Verification relays
• Automatic optical path and electronic selftest
• Widest operating temperature range
• Patented* Electronics Module for
components protection with easy plug-in
terminations and field installation
• Two 3/4 in. NPT OR 25 mm conduit entries
• Low Power Consumption
• High RFI and EMI immunity
Benefits
• Detects hydrocarbon and non-hydrocarbon
fires in all environmental conditions
• User selectable outputs
• Optimal false alarm rejection for all
environmental conditions
• Minimal maintenance for trouble-free
operation
• PC software and Interface Module (FSIM) for
fault diagnostics, real-time graphics (RTGs),
and downloading of FirePics™ and event log
• Suitable for a wide variety of applications
• Easy electronics module replacement
• Test lamps for manual testing
Certifications
• FM:
Class I, Div. 1 & 2, Groups B, C, & D
Class II, Div. 1 & 2, Groups E, F, & G
Class III
• ATEX: II 2 G D
Ex d IIC T4 (Ta: -60 to +110ºC), T5 (Ta: -60
to +90ºC), T6 (Ta: -60 to +75ºC)
• CE:
Complies with EN6000-6-4, EN50130-4, & EN54-10:2002 + A1:2005
• SIL Rating:
FMEDA meets IEC 61508 safety
requirements
Universal charger for Fire Sentry Test Lamps and Interface Kits. For 110-240 VAC with
international plugs
IR Test lamp for testing FSX detectors, explosion proof version. Incl universal charger
IR Test lamp for testing FSX detectors, non-explosion proof version. Incl universal charger
Sunshield for SS2, SS4 & FS24X Detectors, 316 Stainless Steel
Optional Registered HART Module for FS24X Detectors
3.
Part Number
Description
FSX-A009
FSX-A010
FSX-A006
PW-3123-0005
9
Model F24X QuadBand™
Triple IR Fire and Flame Detector (IR/IR/IR/Visible)
20.7 Spare Parts FS24X
Spare Parts
Stainless Steel Grill Kit for FS24X-2 Detectors, for -5 version only
Stainless Steel Grill Kit for FS24X-9 Detectors, for -5 version only
Replacement IR Bulb TL1055/TL2055
Battery Pack for FT-2145/TL-1055/TL-2055 Test Lamp
4.
Model FS20X
Multi-Spectrum Fire and Flame Detector UV/Dual IR/VIS
10
The FS20X is the latest generation high technology Multi-Spectrum (UV/Dual IR/VIS) Fire and
Flame Detector, which is part of the FSX family of advanced technology Electro-Optical Flame
Detectors. Based on the foundation of the highly successful and reliable SS4 detector, the
FS20X detector represents a quantum leap in integrating Infrared and Ultraviolet sensing
technologies. The FS20X is a fire and flame detector with a proven UV solar-blind Sensor.
The FS20X exhibits faster false-alarm free response to fires over a wider temperature range
and with a much longer detection range compared to conventional UV/IR detectors.
Solar blind 90° field of view and detection range greater than 200 ft.
Features
• Patented* WideBand IR™ Infrared combined
with Ultraviolet
• Detection range greater than 200 ft. to
1 sq. ft. heptane fire
• Patented* Electronic Frequency Analysis
• Visible Sensor for optimum false alarm
rejection
• Selectable detection sensitivities
• Solar blind 90° cone‑of-vision
• Dual Microprocessors for reliable
performance
• Real-time clock for accurate time dating of
events
• FirePic™ — Up to 6 pre-fire event data
storage
• Event log — Up to 200 events with date and
time stamp
• Built-in RS-485 Modbus Communication
• Built-in non-isolated 4-20 mA analog output
(sink or source)
• Alarm, Fault and Fire Verification relays
• Automatic Optical Path and Electronic
Self-Test
• Widest operating temperature range
• Patented* Electronics Module for
components protection with plug-in
terminations for easy field installation
• Two 3/4 in. NPT or 25 mm conduit entries
• Low Power Consumption
• High RFI and EMI immunity
• FM, ATEX, CE mark approvals
• Meets SIL 2 requirements
Benefits
• Detects hydrocarbon and non‑hydrocarbon
fuel fires in all environmental conditions
• Arc welding immunity
• False alarm rejection for all environmental
conditions
• Minimal maintenance for trouble-free
operation
• PC software and Interface Module (FSIM)
for fault diagnostics real-time graphs (RTGs), and
downloading of FirePics™ and event log
• Suitable for a wide variety of applications
Certifications
• FM: Class I, Div. 1 & 2, Groups B, C, & D;
Class II, Div. 1 & 2, Groups E, F, & G;
Class III
• ATEX: II 2 G D; Ex d IIC T4 (Ta: -40 to
+110ºC), T5 (Ta: -40 to +75ºC), T6
(Ta: -40 to +60ºC)
• CE: Complies with EN6100-6-4 &
EN50130-4, EN54-10:2002 + A1:2005
4.
Model FS20X
Multi-Spectrum Fire and Flame Detector UV/Dual IR/VIS
FS20X-211-21-4
FS20X-211-22-4
FS20X-211-23-4
FS20X-211-24-4
Part Number
Description
FSX-A014
FVR-01
PSU-12
SH-001
SM4
TL-1055
TL-2055
11
4.1 FS20X-211 Series, standard temp range -40° to 85°C
FS20X-211 Series, standard temp range -40° to 85°C
Part Number Description
FS20X-211-21-2
FS20X-211-22-2
FS20X-211-23-3
FS20X-211-24-3
4.2 FS20X-212 Series w/HART, standard temp range -40° to 85°C
FS20X-212 Series, standard temp range -40° to 85°C
Part Number Description
FS20X-212-21-2
FS20X-212-22-2
FS20X-212-23-3
FS20X-212-24-3
FS20X-212-21-4
FS20X-212-22-4
FS20X-212-23-4
FS20X-212-24-4
DUAL IR/UV Detector Copper-Free Aluminum Encl. with (2) ¾” NPT entries, FM, cFM for Class I,
Division 1, Groups A, B, C, D; Class II, Division 1, Groups E, F, G; Class III
DUAL IR/UV Detector 316 Stainless Steel Encl. with (2) ¾”NPT entries, FM, cFM for Class I,
Division 1, Groups A, B, C, D; Class II, Division 1, Groups E, F, G; Class III
DUAL IR/UV Detector Copper-Free Aluminum Encl. with (2) M25 entries, FM, cFM, ATEX, IECEx
for Class I, Zone 1
DUAL IR/UV Detector 316 Stainless Steel Encl. with (2) M25 entries, FM, cFM, ATEX, IECEx for
Class I, Zone 1
Dual IR/UV Detector Copper-Free Aluminum Encl. with (2) 3/4 in. NPT entries, INMETRO
Dual IR/UV Detector 316 Stainless Steel Encl. with (2) 3/4 in. NPT entries, INMETRO
DUAL IR/UV Detector Copper-Free Aluminum Encl. with (2) M25 entries, INMETRO
DUAL IR/UV Detector 316 Stainless Steel Encl. with (2) M25 entries, INMETRO
Optional HART Module for FS20X Detectors
Field of View Restrictor
Universal charger for Fire Sentry Test Lamps and Interface Kits. For 110-240 VAC with international plugs
Sunshield for SS2, SS4 & FS24X Detectors, 316 Stainless Steel
Stainless Steel Swivel mounting assembly for FS24X, FS20X, SS4, SS2 detectors
IR Test lamp for testing FSX detectors, non-explosion proof version. Incl universal charger
IR Test lamp for testing FSX detectors, explosion proof version. Incl universal charger
4.
Model FS20X
Multi-Spectrum Fire and Flame Detector UV/Dual IR/VIS
FS20X-211-10
FS20X-212-10
Part Number
Description
FSX-A006
FSX-A011
PW-3123-0005
12
4.4 Replacement Detector Module for FS20X
Replacement Detector Module for FS20X
Part Number Description
Replacement IR Bulb for TL1055 and TL2055
Grill Kit for the FS20X
Battery Pack for FT-2145/TL-1055/TL-2055 Test Lamp
- Explosion-Proof; Class I, Div. 1 & 2, Groups B, C, & D Class II, Div. 1 & 2,
FS10 Fire Detection Systems
For Liquid Paint Spray and Electrostatic Powder Coating
A high-speed microprocessor based fire detection and process control system specially
13
5.
designed for liquid and powder coating applications, the FS System 10 quickly detects
the presence of a flame, reacts by initiating a shutdown of the electrostatic finishing
process in a matter of milliseconds; and effectively interrupts the fire before residues
and wet paint films can ignite.
‑
The FS System 10 is the only system that provides a two
for spray gun "fireball" type fires and if the fire continues, a FIRE ALARM is declared in
4-5 seconds.
90° field of view and detection range of 15 ft.
Features
- Multi-Spectral digital electro-optical infrared fire Detector
- Meets requirements of NFPA 33
- Unique two-stage ALERT and FIRE ALARM response
- Immune to false alarms caused by arcs or corona discharges
- Built-in automatic “through the lens” self-test
- Not sensitive to background radiant energy sources such as paint heaters
- Not affected by absorbing smoke or paint solvent mist in liquid pant spray booths
- Sees through paint, powder or oil residue on Detector’s lens
- Digital communications with RS-485 interface
stage response: an ALERT
Certifications
Groups E, F, & G, Class III
- FM, CE
5.1 Card Controller with FS10 Electro-Optical Fire Detector
FS10 fire Detector with card controller. Incl PC software and manual.
Note: Requires backplane card and 24 Vdc.
Card Controller with FS10 Electro-Optical Fire Detector
Part NumberDescription
-2FL
Option
Option-2GF
Option-2WE
Option-2WL
Option-2GE
BP-1Backplane for 1 card controller
BP-2Backplane for 2 card controllers
BP-4-L9Backplane for 4 card controllers
2FL system: liquid paint spray line applications with two (2) fire signal relay levels
2GF system: general finishing applications with process control and fire alarm signal relays
2WE system: powder coating and paint spray line applications with two (2) fire signal relay levels
2WL system: paint spray line applications with three (3) fire signal relay levels
2GE system: powder coating and paint spray line applications with two (2) fire signal relay levels
FS10 Fire Detection Systems
For Liquid Paint Spray and Electrostatic Powder Coating
14
5.
5.2 Spare Parts - FS10 Wall Mount Controller and Card Controller
Spare Parts - FS10 Wall Mount Controller and Card Controller
Part NumberDescription
SW-5143-001
FS10-CARD-2FL
FS10-CARD-2GE
FS10-CARD-2GF
FS10-CARD-2WL
FS10-Detector
FS10-DET-MODULE
Replacement keypad for FS10 wallmount
Liquid paint spray line applications with two (2) fire signal relay levels
Powder coating and paint spray line applications with two (2) fire signal relay levels
General finishing applications with process control and fire alarm signal relays
Paint spray line applications with three (3) fire signal relay levels
Model FS10 fire Detector for use with wall mount controller or card controller
Replacement electronics module for fire detector for the above systems
5.3 Detector Cables
Card Controller with FS10 Electro-Optical Fire Detector
Part Number Description
CAB-50
CAB-100
50 ft. card controller cable. Connects fire detector to controller
100 ft. card controller cable. Connects fire detector to controller
5.4 FS10 Stand Alone (Unitized) Electro-Optical Fire Detectors
Includes ALARM and FAULT relays. 24 Vdc input. Temperature range (-40°C to +85°C). Approvals: FM, cFM, CSFM for Class I, Div. 2,
Groups B, C, & D.
FS10 Stand Alone (Unitized) Electro-Optical Fire Detectors
Part NumberDescription
FS10-R30
FS10-R30-SS
FS10-R30-EC
FS10-R45
FS10-R45-SS
FS10-RN30
FS10-RN30-SS
FS10-RN45
FS10-RN45-SS
Copper-free aluminum housing incl ALERT / FIRE EARLY WARNING relay, 30 ft. sensitivity (latching alert and alarm
relays)
316 stainless steel housing incl ALERT / FIRE EARLY WARNING relay, 30 ft. sensitivity (latching alert and alarm
relays)
Copper-free aluminum housing incl ALERT / FIRE EARLY WARNING relay, 30 ft. sensitivity (latching alert and alarm
relays), Normally Energized with Normally Closed Contacts
Copper-free aluminum housing 45 ft. sensitivity (latching alarm relays)
316 stainless steel housing 45 ft. sensitivity (latching alarm relays)
Copper-free aluminum housing incl ALERT / FIRE EARLY WARNING relay, 30 ft. sensitivity (non-latching alert and
alarm relays)
‑
316 stainless steel housing incl ALERT / FIRE EARLY WARNING relay, 30 ft. sensitivity (non
relays)
Copper-free aluminum hsg 45 ft. sensitivity (non-latching alarm relays)
316 Stainless steel housing 45 ft. sensitivity (non-latching alarm relays)
latching alert and alarm
FS10 Fire Detection Systems
For Liquid Paint Spray and Electrostatic Powder Coating
15
5.
5.5 Spare Parts - FS10 Stand Alone (Unitized) Electro-Optical Fire Detectors
Spare Parts - FS10 Stand Alone (Unitized) Electro-Optical Fire Detectors
Part NumberDescription
FS10-R30-MOD
FS10-R30-EC-MOD
FS10-R45-MOD
FS10-RN30-MOD
FS10-RN45-MOD
Replacement electronics module for Model FS10-R30 stand alone fire Detector (latching alert and alarm relays)
Replacement electronics module for Model FS10-R30 stand alone fire Detector (latching alert and alarm relays),
Normally Energized with Normally Closed Contacts
Replacement electronics module for Model FS10-R45 stand alone fire Detector (latching alarm relay)
Replacement electronics module for Model FS10-RN30 stand alone fire Detector (non-latching alert and alarm relays)
Replacement electronics module for Model FS10-RN45 stand alone fire Detector (non-latching alarm relay)
5.6 Spare Parts - FS10 Stand Alone (Unitized) Electro-Optical Fire Detectors
Card Controller with FS10 Electro-Optical Fire Detector
Part NumberDescription
FS10R-GR-Kit
RS-232 Cable
PSU-12
Stainless steel grill Kit for FS10-R and FS10-CS Detectors (Killark housing) Kit includes: (1) SS grill, (2) SS brackets,
and (2) SS screws
RS232 computer Cable for connection from FS7-130-SX, S7-2175, option-1 or option-2 controllers or interface box to
PC
110/220 Vac, 50-60 HZ input /15 Vdc output : universal Charger for interface box or DD Series, FT Series and TL
Series test lamps
5.7 Accessories - FS10 Stand Alone (Unitized) and Controller Based Electro-Optical
Fire Detectors
FS10 Stand Alone (Unitized) Electro-Optical Fire Detectors
Part Number Description
SM4
FS-846-B
EXPL-1
DPC-12
DASA1-P
DASA6-N
Stainless steel swivel mount allows Detector to be pointed in any direction
Test lamp Battery operated for testing FS10 fire Detectors up to 10 ft.
EXTENSION POLE FOR DPC-12 Extension Pole for placing and removing Disposable Protective Covers on FS10
Detectors
Disposable protective covers keeps powder or paint off the window lens of the FS10 fire Detector (12 per bag) (for use
with FS10 only)
Air shield for powder applications protects FS10 fire Detector window lens from powder build-up. Supplied with fitting
for 1/4 in. tubing (can also be used with FS24X, FS20X, SS4, and SS2)
Air shield for powder applications protects FS10 Fire Detector window lens from powder build-up. Supplied with fitting
for 6 mm tubing
Description
FS7-2173
FS7-2173-2RP
FS7-2173-2RP-K
FS7-2173-KALO
6.
FS7
Multi-Spectrum Fire and Flame Detector
16
The Fire Sentry FS7 Flame Detector provides and intelligent two-stage response to
semiconductor wet bench fires:
Stage 1: Alert. This is the first-stage response to a small fire with a heat energy output of 3
kW (the equivalent of a 4-inch diameter polypropylene pool fire). This fire may selfextinguish.
Stage 2: Alarm. If the fire does not self-extinguish, and grows to the Factory Mutual
specified heat energy threshold of 13 kW (the equivalent of an 8-inch diameter
polypropylene pool fire), the second stage response is activated.
The Fire Sentry FS7-2173 is used with Fire Sentry FS7-130-SX Controller. Controller supplies
power to detectors monitors the status of all detectors and communicates with the
detectors via the digital RS-485 communication channel. Fire Sentry FS7-2173 is supplied
with a standard 20 ft. cable connector. Detectors are connected to the controller using the
self-locking connectors and Fire Sentry junction boxes. This allows for fast and easy
connections eliminating wiring problems. Each detector can store up to six time and date
stamped FirePics™ (pre-event multi-spectral sensor array data) in non-volatile memory.
Controller can also store event history table in the non-volatile memory, which contains
the time and date stamped alert, alarm and fault histories. FirePics™ and event histories
can be retrieved from the controller.
6.1 Detectors
FS7 - Detectors Part
Number
Additional Features and Benefits
• Multi-Spectral digital electro-optical radiant
energy infrared fire detector
• Unique two-stage fire detection response
• Immune to false alarm sources
• NOT affected by absorbing smoke, gasses or
chemical vapors
• NOT sensitive to background radiant energy
from electric heaters and ovens
• Detects hydrocarbon and non-hydrocarbon
fires
Viton O-ring. For use with FS7-130-SX Controller
Non-Latching Alert and Alarm relays. Viton O-ring.
Non-Latching Alert and Alarm relays. Kal-rez O-ring.
Kal-rez O-ring. For use with FS7-130-SX Controller
• FirePic™; time and date-stamped digital
fire signatures
• Built-in detector automatic self test
• Unitized model design for stand-alone
operation
Description
FS-746-B
FT-S7
CBMM-5
CBMM-10
Description
PW-3123-0002
6.2 Controller Systems
17
Controller Systems FS7
Part NumberDescription
FS7-130-SX
Multi-Zone Compact Controller, designed to be installed in Fire Panels, which
monitors up to 12 Model FS7-2173 Fire Detectors. Programmable for up to 4 zones
with relay outputs for ALERT and ALARM. Requires 24 VDC. Approvals: FM & CSFM
6.3 Accessories
FS7 - Accessories Part
Number
Test Lamp. Battery operated for testing FS7 Fire Detectors up to 10 ft. distance.
Test Lamp. Battery operated for testing FS7 Fire Detectors up to 2 ft. distance.
FS7-2179
Junction Box for connecting Model FS7-2173 Fire Detectors in a daisy chain or star
configuration. Complete with (4) Lemo female connectors. Required for Model FS7130-SX applications.
6.4 Interconnection Cables
FS7 - Interconnection Cables
Part Number Description
5 ft. cable with Male/Male Lemo connectors, (Junction Box to Junction Box).
10 ft. cable with Male/Male Lemo connectors, (Junction Box to Junction Box).
CBMO-20
CBMO-50
20 ft. cable with Male Lemo connector/open pigtail, (Junction Box to Model FS7-130SX Controller or Model S7-2175 Control Panel).
50 ft. cable with Male Lemo connector/open pigtail, (Junction Box to Model FS7-130SX Controller or Model S7-2175 Control Panel).
6.5 Spare Parts
Spare Parts
Part Number
PSU-12
110/220 VAC, 50-60 HZ Input /15 VDC Output : Universal Charger for Interface Box or
DD Series, FT Series and TL Series Test Lamps
Replacement Battery for FT-S7 Tester (1 required)
7.
SS Series of UV and UV/IR Fire and Flame Detectors
18
Quick Reference Chart
Ultraviolet Band (0.18 - 0.26 µ)√√√√
Visible Band (0.4 - 0.7 µ)√√√
SPECTRAL
SENSITIVITY
WideBand IR (0.7 - 3.5 µ)√√√
Very High60606060
High454545
(feet)*
Medium303030
SENSITIVITY
Low151515
Ultra High-Speed Response (Munitions)√
Optimized Response (H4Si, H2, Alcohols, CH4)√
RESPONSEOTHERENCLOSURES
Standard Response√√
Field of View120°120°120°120°
SS4-A SS4-AS SS4-AUV SS2-AM
HART Option√√√
Modbus Option
4-20 mA Option√√√
Aluminum Class I, Div. 1√√√√
316 Stainless Steel Class I, Div. 1√√√√
FM√√√√
cFM√√√√
ATEX√√√
IECEx√√√
INMETRO√
APPROVALS
GOST-R√
SIL 2 Compliant√√√
FT-2145 (Explosion Proof)√√√√
Multi-Spectrum™ Electro-Optical Digital Fire & Flame Detector (UV/IR & UV)
The SS4 is a hazardous area certified flame detector for the detection of hydrocarbon (SS4A2) and non‑hydrocarbon fires (SS4-AS2). This multispectrum detector senses radiant
energy in the ultraviolet (UV), visible and wideband infrared (IR) spectrum. The radiant
energy from all types of flaming fires will alert the detector to their presence. The field of
view is the widest in the industry with 120° field of view with a range of 60 ft. This means
more hazard can be covered by each detector.
Features
• Multi-Spectrum™: senses ultraviolet, visible and Wide Band Infrared™
• Built-in test for optical “through the lens” testing
• False alarm immunity
• Detects hydrocarbon and non‑hydrocarbon based fires
• Wide field-of-view and solar-blind
• Adjustable detector sensitivity
• Microprocessor based algorithms: FirePic™, Snapshot™ and Tri-Mode Plot™
• Wide temperature range of operation
• Compatible with standard approved fire alarm panels
• Explosion-proof housing
• Time programmable alarm verification
While retaining all the features of the standard SS4-A2, the SS4-AS2 is optimized for the
detection of ethanol, methanol, hydrogen and natural gas with a range up to 60 ft. range
and a field of view of 120°, the UV only Version, SS4-AUV2, is for indoor applications
where UV sources such as welding are not present.
Features
• Senses solar-blind ultraviolet band
• Built-in test for optical “through the lens” testing
• Utilizes long-life, ruggedized UV Sensors
• Detects hydrocarbon and non‑hydrocarbon based fires
• Wide field-of-view and solar-blind
• Adjustable Detector sensitivity
• Microcomputer based algorithms: FirePic™, Snapshot™ and UV Plot
• Wide temperature range of operation
• Compatible with standard approved fire alarm panels
• Explosion-proof housing
• Time programmable alarm verification
• FM, ATEX mark approvals
Certifications
• Explosion-proof
• Class I, Div. 1 & 2, Groups B, C and D
• Class II, Div. 1 & 2, Groups E, F and G
8.
20
SS4 Series
Multi-Spectrum™ Electro-Optical Digital Fire & Flame Detector (UV/IR & UV)
8.1 SS4 Series
SS4-A2, SS4-AS2, & SS4-AUV2 FM Certification
Part Number Description
SS4-A2
SS4-A2-SS
SS4-AS2
SS4-AS2-SS
SS4-AUV2
SS4-AUV2-SS
SS4-A2-M
SS4-A2-SS-M
SS4-AS2-M
SS4-AS2-SS-M
Aluminum UV/IR, FM, Hydrocarbon Fires, Non Latching Alarm LED, FM, cFM, CSFM for
Class I, Div.1 groups B,C & D (2) 3/4 NPT
Stainless Steel UV/IR, FM, Hydrocarbon Fires, Non Latching Alarm LED, FM, cFM, CSFM for
Class I, Div.1 groups B,C & D (2) 3/4 NPT
Aluminum UV/IR, FM, optimised for Non-Hydrocarbons and Silane, Ethanol, Methanol,
Hydrogen & Natural Gas Fires, Non-latching Alarm LED, FM, cFM, CSFM for Class I, Div.1
groups B,C & D (2) 3/4 NPT
Stainless Steel UV/IR, FM, optimised for Non-Hydrocarbons and Silane, Ethanol, Methanol,
Hydrogen & Natural Gas Fires, Non-latching Alarm LED, FM, cFM, CSFM for Class I, Div.1
groups B,C & D (2) 3/4 NPT
Aluminum UV, FM, Hydrocarbon & Non-Hydrocarbon Fires, indoor applications, Nonlatching Alarm LED, FM, cFM, CSFM for C1, D1, Groups B,C,D (2) 3/4 NPT
Stainless Steel UV, FM Hydrocarbon & Non-Hydrocarbon Fires, indoor applications, Nonlatching Alarm LED, FM, cFM, CSFM for C1, D1, Groups B,C,D (2) 3/4 NPT
SS4-A2 Aluminum UV/IR, FM, Hydrocarbon Fires, Non Latching Alarm LED, FM, cFM, CSFM
for Class I, Div.1 groups B,C & D (2) 3/4 NPT with MA420-4 4-20 mA Module for SS4
Detectors New version Factory installed.
SS4-A2-SS Stainless Steel UV/IR, FM, Hydrocarbon Fires, Non Latching Alarm LED, FM,
cFM, CSFM for Class I, Div.1 groups B,C & D (2) 3/4 NPT with MA420-4 4-20 mA Module
for SS4 Detectors New version Factory installed.
SS4-AS2 Aluminum UV/IR, FM, optimised for Non-Hydrocarbons and Silane, Ethanol,
Methanol, Hydrogen & Natural Gas Fires, Non-latching Alarm LED, FM, cFM, CSFM for
Class I, Div.1 groups B,C & D (2) 3/4 NPT with MA420-4 4-20 mA Module for SS4 Detectors
New version Factory installed.
SS4-AS2-SS Stainless Steel UV/IR, FM, optimised for Non-Hydrocarbons and Silane,
Ethanol, Methanol, Hydrogen & Natural Gas Fires, Non-latching Alarm LED, FM, cFM,
CSFM for Class I, Div.1 groups B,C & D (2) 3/4 NPT with MA420-4 4-20 mA Module for SS4
Detectors New version Factory installed.
8.
21
SS4 Series
Multi-Spectrum™ Electro-Optical Digital Fire & Flame Detector (UV/IR & UV)
SS4-AUV2-M
SS4-AUV2-SS-M
SS4-A2-H
SS4-A2-SS-H
SS4-AS2-H
SS4-AUV2-H
SS4-AUV2-SS-H
SS4-A2, SS4-AS2, & SS4-AUV2 ATEX Certification
SS4-A2-C-E
SS4-A2-CSS-E
SS4-AS2-C-E
SS4-AS2-CSS-E
SS4-A2-C-E-M
SS4-A2-CSS-E-M
SS4-AUV2 Aluminum UV, FM, Hydrocarbon & Non-Hydrocarbon Fires, indoor applications,
Non-latching Alarm LED, FM, cFM, CSFM for C1, D1, Groups B,C,D (2) 3/4 NPT with MA4204 4-20 mA Module for SS4 Detectors New version Factory installed.
SS4-AUV2-SS Stainless Steel UV, FM Hydrocarbon & Non-Hydrocarbon Fires, indoor
applications, Non-latching Alarm LED, FM, cFM, CSFM for C1, D1, Groups B,C,D (2) 3/4 NPT
with MA420-4 4-20 mA Module for SS4 Detectors New version Factory installed.
SS4-A2 Aluminum UV/IR, FM, Hydrocarbon Fires, Non Latching Alarm LED, FM, cFM, CSFM
for Class I, Div.1 groups B,C & D (2) 3/4 NPT with SS4-FSCHCOM SS4 Module HART Factory
installed.
SS4-A2-SS Stainless Steel UV/IR, FM, Hydrocarbon Fires, Non Latching Alarm LED, FM,
cFM, CSFM for Class I, Div.1 groups B,C & D (2) 3/4 NPT with SS4-FSCHCOM SS4 Module
HART Factory installed.
SS4-AS2 Aluminum UV/IR, FM, optimised for Non-Hydrocarbons and Silane, Ethanol,
Methanol, Hydrogen & Natural Gas Fires, Non-latching Alarm LED, FM, cFM, CSFM for
Class I, Div.1 groups B,C & D (2) 3/4 NPT with SS4-FSCHCOM SS4 Module HART Factory
installed.
SS4-AUV2 Aluminum UV, FM, Hydrocarbon & Non-Hydrocarbon Fires, indoor applications,
Non-latching Alarm LED, FM, cFM, CSFM for C1, D1, Groups B,C,D (2) 3/4 NPT with SS4FSCHCOM SS4 Module HART Factory installed.
SS4-AUV2-SS Stainless Steel UV, FM Hydrocarbon & Non-Hydrocarbon Fires, indoor
applications, Non-latching Alarm LED, FM, cFM, CSFM for C1, D1, Groups B,C,D (2) 3/4 NPT
with SS4-FSCHCOM SS4 Module HART Factory installed.
Aluminum UV/IR, ATEX, Hydrocarbon Fires, Non Latching Alarm LED, FM, cFM, ATEX, IECEx
FOR Zone 1 (2) M25
Stainless Steel UV/IR, ATEX, Hydrocarbon Fires, Non Latching Alarm LED, FM, cFM, ATEX,
IECEx FOR Zone 1 (2) M25
Aluminum UV/IR, ATEX, optimised for Non-Hydrocarbons and Silane, Ethanol, Methanol,
Hydrogen & Natural Gas Fires, Non Latching Alarm LED, FM, cFM, CSFM for Class I, Div.1
groups B,C & D (2) M25
Stainless Steel UV/IR, ATEX, optimised for Non-Hydrocarbons and Silane, Ethanol,
Methanol, Hydrogen & Natural Gas Fires, Non Latching Alarm LED, FM, cFM, ATEX, IECEx
for Zone 1 (2) M25
SS4-A2-C-E Aluminum UV/IR, ATEX, Hydrocarbon Fires, Non Latching Alarm LED, FM, cFM,
ATEX, IECEx FOR Zone 1 (2) M25 with MA420-4 4-20 mA Module for SS4 Detectors New
version Factory installed.
SS4-A2-CSS-E Stainless Steel UV/IR, ATEX, Hydrocarbon Fires, Non Latching Alarm LED, FM,
cFM, ATEX, IECEx FOR Zone 1 (2) M25 with MA420-4 4-20 mA Module for SS4 Detectors
New version Factory installed.
8.
FT-2145
FVR-01
MA420-4
SH-001
SM4
SS4-FSCHCOM
22
SS4 Series
Multi-Spectrum™ Electro-Optical Digital Fire & Flame Detector (UV/IR & UV)
SS4-AS2-C-E-M
SS4-AS2-CSS-E-M
SS4-AUV2-C-E-M
SS4-AUV2-CSS-E-M
SS4-A2-C-E-H
SS4-A2-CSS-E-H
SS4-AS2-C-E-H
SS4-AS2-CSS-E-H
SS4-AUV2-C-E-H
SS4-AUV2-CSS-E-H
SS4-AS2-C-E Aluminum UV/IR, ATEX, optimised for Non-Hydrocarbons and Silane, Ethanol,
Methanol, Hydrogen & Natural Gas Fires, Non Latching Alarm LED, FM, cFM, CSFM for
Class I, Div.1 groups B,C & D (2) M25 with MA420-4 4-20 mA Module for SS4 Detectors
New version Factory installed.
SS4-AS2-CSS-E Stainless Steel UV/IR, ATEX, optimised for Non-Hydrocarbons and Silane,
Ethanol, Methanol, Hydrogen & Natural Gas Fires, Non Latching Alarm LED, FM, cFM,
ATEX, IECEx for Zone 1 (2) M25 with MA420-4 4-20 mA Module for SS4 Detectors New
version Factory installed.
SS4-AUV2-C-E Aluminum UV, FM, ATEX, Hydrocarbon & Non-Hydrocarbon Fires, indoor
applications, Non-latching Alarm LED, FM, cFM, ATEX, IECEx Zone 1 (2) M25 with MA4204 4-20 mA Module for SS4 Detectors New version Factory installed.
SS4-AUV2-CSS-E Stainless Steel UV, FM, ATEX, Hydrocarbon & Non-Hydrocarbon Fires,
indoor applications, Non-latching Alarm LED FM, cFM, ATEX, IECEx Zone 1 (2) M25 with
MA420-4 4-20 mA Module for SS4 Detectors New version Factory installed.
SS4-A2-C-E Aluminum UV/IR, ATEX, Hydrocarbon Fires, Non Latching Alarm LED, FM, cFM,
ATEX, IECEx FOR Zone 1 (2) M25 with SS4-FSCHCOM SS4 Module HART Factory installed.
SS4-A2-CSS-E Stainless Steel UV/IR, ATEX, Hydrocarbon Fires, Non Latching Alarm LED, FM,
cFM, ATEX, IECEx FOR Zone 1 (2) M25 with SS4-FSCHCOM SS4 Module HART Factory
installed.
SS4-AS2-C-E Aluminum UV/IR, ATEX, optimised for Non-Hydrocarbons and Silane, Ethanol,
Methanol, Hydrogen & Natural Gas Fires, Non Latching Alarm LED, FM, cFM, CSFM for
Class I, Div.1 groups B,C & D (2) M25 with SS4-FSCHCOM SS4 Module HART Factory
installed.
SS4-AS2-CSS-E Stainless Steel UV/IR, ATEX, optimised for Non-Hydrocarbons and Silane,
Ethanol, Methanol, Hydrogen & Natural Gas Fires, Non Latching Alarm LED, FM, cFM,
ATEX, IECEx for Zone 1 (2) M25 with SS4-FSCHCOM SS4 Module HART Factory installed.
SS4-AUV2-C-E Aluminum UV, FM, ATEX, Hydrocarbon & Non-Hydrocarbon Fires, indoor
applications, Non-latching Alarm LED, FM, cFM, ATEX, IECEx Zone 1 (2) M25 with SS4FSCHCOM SS4 Module HART Factory installed.
SS4-AUV2-CSS-E Stainless Steel UV, FM, ATEX, Hydrocarbon & Non-Hydrocarbon Fires,
indoor applications, Non-latching Alarm LED FM, cFM, ATEX, IECEx Zone 1 (2) M25 with
SS4-FSCHCOM SS4 Module HART Factory installed.
8.2 Accessories SS4-AS, SS4-AS2, & SS4-AUV2
Accessories SS4-AS, SS4-AS2, & SS4-AUV2
Part Number Description
UV/IR Test Lamp with universal charger (FM & ATEX approval)
Field of view restrictor
4-20 mA Module for SS4 Detectors New version
Sunshield for SS2, SS4 & FS24X Detectors, 316 Stainless Steel
Stainless Steel Swivel mounting assembly for FS24X, FS20X and SS4 detectors
SS4 Module HART
8.
SS4-MOD-A2
SS4-MOD-AS2
SS4-MOD-AUV2
SS4-MOD-A2-M
SS4-MOD-AS2-M
SS4-MOD-A2-H
SS4-MOD-AS2-H
SS4-MOD-AUV2-H
H200
LAMP-3135-0002
LAMP-3125-0002
TN2-MOD-PIL
PW-3123-0005
interface Kits. For 110-240 Vac with international plugs
23
SS4 Series
Multi-Spectrum™ Electro-Optical Digital Fire & Flame Detector (UV/IR & UV)
8.3 Spares SS4-A, SS4-A, & SS4-AUV2
SS2-A and SS4-AS
Part Number Description
Replacement Electronics Module for SS4-A2 (UV/IR) Detectors. Module only, non-latching LED
Replacement Electronics Module for SS4-AS2 (UV/IR) Detectors. Module only, non-latching LED
Replacement Electronics Module for SS4-AUV2 (UV) Detectors. Module only, non-latching LED
Replacement Electronics Module for SS4-A2 (UV/IR) Detectors. Module only, non-latching LED with 4-20mA Output
Replacement Electronics Module for SS4-AS2 (UV/IR) Detectors. Module only, non-latching LED with 4-20mA Output
SS4-MOD-AUV2-M
PSU-12Power supply for use with FT-2145 and FT-2145-2; PSU-12 is a Universal Charger for Fire Sentry test lamps and
Replacement Electronics Module for SS4-AUV2 (UV) Detectors. Module only, non-latching LED with
4-20mA Output
Replacement Electronics Module for SS4-A2 (UV/IR) Detectors. Module only, non-latching LED with HART Output
Replacement Electronics Module for SS4-AS2 (UV/IR) Detectors. Module only, non-latching LED with HART Output
Replacement Electronics Module for SS4-AUV2 (UV) Detectors. Module only, non-latching LED with HART Output
UV Test Source Module for SS4 Detectors
IR Test Lamp Bulb (FT-2145)
Replacement lamp for FT-2145
UV Test Lamp Bulb (FT-2145) + Fixture
Battery Pack for Model FT-2145/TL-1055/Tl-2055 Test Lamps
Description
Part Number
Description
SM4
FT-2145
SH-001
FVR-01
Description
SS2-MOD-AM
SS2-MOD-AML
LAMP-3135-0002
TN2-MOD-PIL
PW-3123-0005
9.
120° field of view with range up to 60 ft.
24
SS2-AM Series
Ultra-High Speed Digital Fire and Flame Detector (UV/IR)
The Model SS2-AM, (non-latching Fire Alarm relay), and SS2-AML (latching Fire Alarm
relay), represent the world´s pre-eminent Ultra-High Speed UV/IR technology for ElectroOptical Fire and Flame Detectors, with thousands successfully operating in a multitude of
installations worldwide.
This detector senses radiant energy in the Ultraviolet (UV), Visible and WideBand
Infrared™ (IR) spectrum. The radiant energy from all types of flaming fires will alert the
detector to their presence. 120° field of view with range up to 60 ft.
Features
• Multi-Spectrum senses energy in the UV, Vis and WideBand IR™
• False alarm immunity
• Detects hydrocarbon and non‑hydrocarbon fires
• Microprocessor based algorithms: FirePic™ and Tri-Mode Plot™
• Wide field of view and solar blind
• Wide temperature range of operation
• Explosion-proof housing
• FS2000™ System compatible or stand-alone operation
Stainless Steel Swivel mounting assembly for FS24X, FS20X, SS4, SS2 detectors
UV/IR Test Lamp with universal charger, (FM & ATEX approval)
Sunshield for SS2, SS4 & FS24X Detectors, 316 Stainless Steel
Field of View Restrictor
9.3 Spares SS2-AM
Spares SS2-AM
Part Number
SS2-AM Replacement Electronics Module
SS2-AML Replacement Electronics Module
IR Test Lamp Bulb (FT-2145)
UV Test Lamp Bulb (FT-2145) + Fixture
Battery Pack for Model FT-2145/Tl-1055/TL-2055 Test Lamps
Description
FSL100-SM21
FSL100-TL
FSL100-TLX
* Please contact Honeywell representative
Description
FSL100-TLBT
FSL100-TLBU
FSL100–TLCH
10.
25
Series FSL100 Flame Detectors
10.1 UV (Ultraviolet) Flame Detector
UV (Ultraviolet) Flame Detector
Part Number Description
FSL100-UV
FSL100-UV-W
UV flame detector. Suitable for ATEX zone 2/22; FM 3611 Class 1,2&3 Div2
EN54-10 (HIGH sensitivity) certificate. FM3260 approval. Red Housing
UV flame detector. Suitable for ATEX zone 2/22; FM 3611 Class 1,2&3 Div2
EN54-10 (HIGH sensitivity) certificate FM3260 approval. White Housing.
10.2 UVIR (Ultraviolet & Infrared) Flame Detector
UVIR (Ultraviolet & Infrared) Flame Detector
Part Number Description
FSL100-UVIR
FSL100-UVIR-W
UV/IR flame detector. Suitable for ATEX zone 2/22; FM 3611 Class 1,2&3 Div2
EN54-10 (HIGH sensitivity) certificate. FM3260 approval. Red Housing.
UV/IR flame detector. Suitable for ATEX zone 2/22; FM 3611 Class 1,2&3 Div2
EN54-10 (HIGH sensitivity) certificate FM3260 approval. White Housing.
The new FSL100 series is the latest generation range of Mid market Flame
Detectors from Honeywell Analytics. The range consists of UV, UVIR and IR3
flame detectors. All utilize sophisticated sensing and signal analysis to detect
fires quickly while also rejecting false alarms. The FSL100 may be small and
lightweight for easy installation but they are designed to work in tough
environments both in and out of doors as well as potentially explosive
atmospheres. With a large field of view they can detect a range of different
types of fire including hydrocarbon and non hydrocarbon sources.
Note: A swivel mount should be ordered with each Flame Detector.
10.3 IR3 (3 Infrared bands) Flame Detector
IR3 (3 Infrared bands) Flame Detector
Part Number Description
FSL100-IR3
FSL100-IR3-W
Triple IR flame detector. Suitable for ATEX zone 2/22; FM 3611 Class 1,2&3 Div2
EN54-10 (HIGH sensitivity) certificate. FM3260 approval. Red Housing.
Triple IR flame detector. Suitable for ATEX zone 2/22; FM 3611 Class 1,2&3 Div2
EN54-10 (HIGH sensitivity) certificate. FM3260 approval. White Housing.
10.4 Accessories
Accessories
Part Number
FSL100 Optional swivel mount
FSL100 test lamp, incl. universal charger and carrying case; non EX
FSL100 test lamp, incl. carrying case; intrinsically safe (Pending *)
10.5 Spare Parts
Accessories
Part Number
12 Vdc battery for FSL-TL test lamp
H3 light bulb for FSL-TL test lamp
Universal charger kit for FSL-TL test lamp
- Instrument calibration equipment certified to national/regional standards
- Site surveys
- Stock surveys
11.
Honeywell Analytics Service
Lincolnshire, IL 60069
26
Honeywell Analytics Service contact information:
USA Service Workshop
Honeywell Analytics
405 Barclay Blvd.
USA
Tel: 800-538-0363 (option #5)
E-mail: ha.us.service@honeywell.com
Calgary Service Department
Honeywell Analytics
Suite 110, 4411 – 6 Street SE
Calgary AB T2G 4E8
Canada
Tel: 1-800-563-2967
Email: haservice.canada@honeywell.com
Honeywell Analytics’ global standing for portable, fixed and low level toxic gas detection is backed up with a dedicated team of
professionals that takes service and support to a whole new level.
It’s your choice...
Whatever industry you’re in, we have the levels of support that are right for your business.
It’s your business. It’s your industry.
And no matter whether you’re managing personnel for confined space entry, or securing your plant against gas risks, the
process has to keep moving.
The alternative is downtime, or even total shutdown, and then the risks to your business are far greater.
Honeywell provides service levels that make it easy to choose the right kind of support to keep your plant and people safe;
to keep your business up and running - because that’s our job!
Choose from:
Installation and CommissioningCon
- Installation, configuration and commissioning
- Functional tests - On-site/workshop repair and calibration
- Start-up
- Staff training
- Bump testing
tract Maintenance
Service and Repair
- Modification and conVersion
Calibration and Surveys
11.
Honeywell Analytics Service
27
Field Service:
We have a global network of fully qualified and highly skilled Technical Support Resources and Field Service Specialists ready to
support your business. Honeywell Analytics is ready to support you 24 hours a day / 7 days a week in the United States & Canada.
For Monday thru Friday Daytime support please contact Honeywell Analytics and follow the voice prompts. In the US please dial 1800-538-0363. Technical Support is currently Option 4 then Option 3. In Canada please dial 1-800-563-2967 Option 1 English,
Option 2 French. Tech Support is currently Option 2.
For Afterhours and weekend support please contact Honeywell Analytics at 1-847-634-2842. Phone support rates will apply.
www.honeywell.com
Contact Honeywell Analytics
Find out more - www.honeywellanalytics.com
USA
Honeywell Analytics, Inc.
405 Barclay Blvd.
Lincolnshire, IL 60069
USA
analytics.industrial.sales@Honeywell.com
Honeywell Analytics, Asia Pacific
#701 Kolon Science Valley (1)
43 Digital-Ro 34-Gil, Guro-Gu
Seoul 152-729
Korea
Tel: +82 2 6909 0300
Fax:+82 2 2025 0388
analytics.ap@honeywell.com
Please Note:
While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for
errors or omissions. Data may change, as well as legislation, and you are strongly advised to obtain copies of the
most recently issued regulations, standards, and guidelines. This publication is not intended to form the basis of a
contract.