Honeywell F300a2025 Owner's Manual

F300 Electronic Air Cleaner
PRODUCT DATA

APPLICATION

The F300 Electronic Air Cleaner is mounted in the return air duct of a forced air heating, cooling, or ventilating system. It captures a significant amount of the airborne particles 0.3 micron and larger from air circulated through it.
• Media postfilters (optional) provide enhanced filtration.
• Available in five sizes to fit most ducts; adapts to airflow from either side.
3
• Capacity varies from 1000 cfm (2040 m (3400 m
• Solid state power supply is self-regulating and maintains peak efficiency during a wide range of cell dirt loading conditions.
• Low pressure drop.
• Optional W8600F Air Cleaner Monitor indicates air cleaner performance, reminds homeowner when filter and cell maintenance are due and when to check the system.
• Optional wireless W8600A AIRWATCH™ LCD indicator provides reminder when air cleaner electronic cells need washing, when media postfilters need replacing, when UV lamps need replacing and when humidifier pad needs replacing.
3
/hr), depending on size.
/hr) to 2000 cfm
Contents
Application/Features.......................................................... 1
Specifications/Ordering Information .................................. 2
Installation ........................................................................ 8
Operation .......................................................................... 11
Checkout .......................................................................... 11
Service ............................................................................. 12
Replacement Parts/Exploded View ................................... 17
68-0240EF—06
F300 ELECTRONIC AIR CLEANER

SPECIFICATIONS

IMPORTANT
The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed specifica­tions. This product is tested and calibrated under closely controlled conditions, and some minor differ­ences in performance can be expected if those con­ditions are changed.
Model:
F300E Electronic Air Cleaner: Includes cabinet, access door,
solid state power supply, two electronic cells, two metal mesh prefilters, and two media postfilters.
F300A,B Electronic Air Cleaner: Includes cabinet, access
door, solid state power supply, two electronic cells and two metal mesh prefilters.
Electrical Ratings:
Voltage and Frequency: Models available for 120V, 60 Hz.,
240V, 60Hz. 120V models can be converted in the field to 240V, 60 Hz or 220/240V, 50 Hz with the 203365A Conversion Kit.
Power Consumption:
One cell models: 22 W maximum
Two cell models: 36 W maximum. Current Draw: See Table 1. Ionizer Voltage: 8150 Vdc. Collector Voltage: 4075 Vdc.
Table 1. Current Draw.
Size
in. mm 120V 220/240V
16 x 25 406 x 635 2 0.4 0.2
20 x 25 508 x 635 2 0.4 0.2
16 x 20 406 x 508 2 0.4 0.2
20 x 20 508 x 508 2 0.4 0.2
20 x
12-1/2 508 x 318 1 0.4 0.2
No.
Cells
Max Current (A)
Fractional Efficiency:
Efficiency ratings are based on American Society of Heating, Refrigerating and Air-Conditioning Engineers Standard
52.2-1999. Efficiency ranges are defined for small particles, E
=.3 to 1.0 micron; medium particles, E2 = 1.0 to 3.0
1
microns; and large particles, E
Table 2. Fractional Efficiency With and Without Postfilter.
With postfilter Without postfilter
= 3.0 to 10.0 microns.
3
E
= Up to 81% at 492 fpm. E1 = Up to 73% at 492 fpm.
1
E
= Up to 93% at 492 fpm. E2 = Up to 88% at 492 fpm.
2
E
= Up to 99% at 492 fpm. E3 = Up to 95% at 492 fpm.
3
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
68-0240EF—06 2
F300 ELECTRONIC AIR CLEANER
AIR CLEANER EFFICIENCY AND PRESSURE DROP AT VARIOUS AIRFLOW RATES.
WITHOUT POST FILTERS
20 x 12-1/2 in. (508 x 318 mm)
4
1
2
400
500
(850)
600
(1020)
(680)
WITH POST FILTERS
700
(1190)
20 x 12-1/2 in. (508 x 318 mm)
3
800
(1360)
20 x 20 in. (508 x 508 mm)
900
(1530)
16 x 25 in. (406 x 635 mm)
1000
(1700)
110 0
(1870)
16 x 20 in. (406 x 508 mm)
16 x 25 in. (406 x 635 mm)
16 x 20 in. (406 x 508 mm)
1200
1300
(2040)
(2210)
CAPACITY IN cfm (m
20 x 20 in. (508 x 508 mm)
1400
(2380)
3
/hr)
20 x 25 in. (508 x 635 mm)
1500
(2550)
20 x 25 in. (508 x 635 mm)
1600
(2720)
1700
(2890)
1800
(3060)
1900
(3230)
2000
(3400)
.25 (62.2)
.20 (49.7)
.15 (37.3)
.10 (24.9)
.05 (12.4)
0
.35 (87.2)
.30 (74.7)
.25 (62.2)
.20 (49.7)
.15 (37.3)
PRESSURE DROP IN in. wc (Pa)
400
500
(680)
(850)
1 MINIMUM RECOMMENDED cfm FOR 20 x 12-1/2 in. (508 x 318 mm) MODEL.
2 MINIMUM RECOMMENDED cfm FOR 16 x 25 in. (406 x 635 mm), 20 x 20 in. (508 x 508 mm), 16 x 20 in. (406 x 508 mm) MODELS.
600
(1020)
700
(1190)
800
(1360)
900
(1530)
1000
(1700)
110 0
1200
(1870)
(2040)
CAPACITY IN cfm (m3 /hr)
Fig. 1. Pressure Drop Vs. Airflow.
Temperature Ratings:
Operating Ambient: 40° to 125°F (4° to 52°C). Temperature of Airflow Through Cells: 40° to 125°F
(4° to 52°C). Maximum Cell Washing Temperature: 220°F (140°C). Storage and Shipping Ambient: Minus 40°F to plus 140°F
(minus 40°C to plus 60°C).
Mounting:
Mounts in the return air duct of a forced air heating, cooling, or ventilating system. Mount upstream from an atomizing humidifier. See Planning the Installation section.
1400
1300
(2210)
3 MINIMUM RECOMMENDED cfm FOR 20 x 25 in. (508 x 635 mm) MODEL.
4 SELECT SIZE THAT MOST CLOSELY FITS DIMENSIONS OF FURNACE/AIR HANDLER RETURN AIR OPENING
(2380)
1500
(2550)
1600
(2720)
1700
(2890)
1800
(3060)
1900
(3230)
2000
(3400)
M13654
Weight:
See Table 3.
Dimensions:
See Fig. 2.
Approvals:
Underwriters Laboratories Inc. Listed: File E30954.
.10 (24.9)
.05 (12.4)
0
PRESSURE DROP IN in. wc (Pa)
3 68-0240EF—06
F300 ELECTRONIC AIR CLEANER
Accessories:
203365A Conversion Kit for changing 120V, 60 Hz power
supply to 240V, 60 Hz or 220/240V, 50 Hz. W8600F Air Cleaner Monitor. W8600A AIRWATCH™ Indicator.
Table 3. Shipping and Installed Weight.
16 x 20 in.
(406 x 508 mm)
Item
Electronic Cell (each)
Shipping Weight 30 13.6 33 15.0 25 11.3 33 15.0 38 17.2
Installed Weight (Cells included)
lb kg lb kg lb kg lb kg lb kg
5 2.25 6 2.7 7-1/2 3.4 6-3/16 2.8 7-1/2 3.4
26 11.6 28 12.7 21 9.5 29 13.2 33 15.0
16 x 25 in.
(406 x 635 mm)
Repair Parts:
See Replacement Parts/Exploded View section.
Weight
20 x 12-1/2 in.
(508 x 318 mm)
20x 20 in.
(508x 508 mm)
(508 x 635 mm)
20 x 25 in.
68-0240EF—06 4
F300 ELECTRONIC AIR CLEANER
3
6
8
(162)
ELECTRONIC AIR CLEANER
6
(172)
DIM. E
(SEE TABLE)
DIM. A
(SEE TABLE)
7
3 4
(22)
5
8
8
(16)
DIM. C (SEE TABLE)
DIM. D (SEE TABLE)
DIM. B
(SEE TABLE)
7 8
(22)
F50F SIZE
IN.
16 X 25 16 X 20 20 X 25 20 X 20 20 X 12 1/2
MM 406 X 635 406 X 508 508 X 635 508 X 508 508 X 318
DIM. A
IN. MM IN. MM
14 7/16 14 7/16 18 7/16 18 7/16 18 7/16
367 367 468 468 468
16 3/16 16 3/16 20 3/16 20 3/16 20 3/16
DIM. B
411 411 513 513 513
Fig. 2. Electronic air cleaner installation dimensions in in. (mm).

PLANNING THE INSTALLATION

Application

The F300 Electronic Air Cleaner is used in a forced air heating, cooling, or ventilating system. It removes airborne particles from the air circulated through it. All models have an internal air flow switch that automatically energizes the air cleaner cells when the system blower is on.

Review Installation Requirements

The air cleaner should be installed where all the air passing through the system circulates through it. The best location is in the return air duct next to the blower compartment so the air cleaner can help keep the blower motor and evaporator coils clean.
DIM. C
IN. MM IN. MM
23 1/4
591
18 1/4
457
23 1/4
591
18 1/4
457
10 7/8
276
DIM. D
25 1/2 20 1/2 25 1/2 20 1/2 13 1/8
648 521 648 521 333
DIM. E
IN. MM 2 3/4 2 3/4 2 3/4 2 3/4 3 5/8
70 70 70 70 92
M2872A
IMPORTANT
Do not mount in the discharge air duct.
For most efficient air cleaning, airflow must be spread evenly across the face of the air cleaner. If the duct is a different size than the air cleaner cabinet, gradual transitions are recommended. If the duct turns sharply just before the air cleaner, turning vanes are recommended.

Applications with Air Conditioning

The air cleaner should be installed upstream from the evaporator coil. The air cleaner will help keep the coil clean, reducing maintenance.
5 68-0240EF—06
F300 ELECTRONIC AIR CLEANER
WARNING

Applications with a Humidifier

An evaporative humidifier can be mounted upstream from the air cleaner. An atomizing humidifier should be mounted downstream from the air cleaner, even though hard water salts will be blown into the living space and deposited as dust. If an atomizing humidifier must be mounted upstream from the air cleaner:
1. Mount it as far as possible upstream from the air cleaner.
2. Install a standard disposable furnace filter between the
humidifier and the air cleaner to trap water droplets and hard water salts.
3. Frequently clean the air cleaner to prevent a hard water
salt buildup.
NOTE: The volume of water that is discharged from an atom-
izing humidifier can overload the air cleaner, resulting in hard water salts being deposited as dust in the liv­ing space.

Applications with Outdoor Air Intake

Return air temperature must be at least 40°F (4°C). Lower temperatures can cause ionizer wire failure. If outdoor air is used, warm it upstream from the air cleaner by:
• Making sure the outdoor intake is far enough upstream from the air cleaner so the return and outdoor air is thoroughly mixed. Stratified air can dump a stream of very cold air into one section of the air cleaner.
• Adding baffles upstream from the air cleaner to force thorough air mixing.
• Installing a Honeywell Perfect Window™ Fresh Air Ventilation System that transfers up to 80 percent of the heat from the exhaust air to the incoming outside air. This keeps the incoming air above 40°F (4°C) and reduces energy usage.
• Installing a preheater if large amounts of outdoor air are used. The preheater, which could be an electric strip heater or hot water coil, should be controlled by a thermostat. Hot water or steam coils should be protected by a freeze-up control.

Optional W8600F Air Cleaner Monitor

The W8600F Air Cleaner Monitor can be mounted in the living area or in the furnace room. It should be located in a convenient location to observe the display.
The W8600F Air Cleaner Monitor is furnished with all the connectors needed for easy installation. Follow the installation instructions provided with the W8600F.

Optional W8600A AIRWATCH™ Indicator

The W8600A can be mounted next to the thermostat or in any other location in the living area of the home where the display can be conveniently observed. No wiring is necessary.

Choose Location

Choose a location that is readily accessible for regular inspection and cleaning. Allow at least 13 in. (330 mm) in front of the access door for removing the metal mesh prefilter, media postfilter and electronic cell. Allow enough room above the power supply so it can be serviced without removing pipes, ducts, or other heating system components.
The air cleaner must be installed where the temperature is between 40° to 125°F (4° to 52°C).
IMPORTANT
UV light can damage media postfilters. Avoid installing UV lamp downstream of F300 in location where UV light illuminates postfilter.

Choose Mounting Position

Heavy Equipment Hazard. Can cause injury or equipment damage.
Do not mount air cleaner with access door facing down because the latch may not hold and the cell, postfilter and prefilter can fall unexpectedly.
NOTE: Nothing holds the cell, postfilter, and prefilter in place
when the access door is opened.
The air cleaner can be mounted in any position except with the access door facing down. A list of air cleaner mounting positions for a variety of furnace installations follows.
NOTE: At least 13 in. (330 mm) clearance is required
between the access door and any obstructions for cell, postfilter and prefilter maintenance.
— Upflow Highboy furnace: Side installation; air cleaner is
mounted vertically where return enters side inlet of furnace. See Fig. 3A.
— Upflow Highboy furnace: Installation beneath furnace (air
cleaner cabinet can easily support weight of furnace and air conditioner coil). Air cleaner is mounted horizontally where return enters from below. See Fig. 3B.
— Upflow Highboy furnace: Closet installation. Air cleaner is
mounted vertically on furnace between furnace and louvered return air opening in closet door. See Fig. 3C.
— Lowboy furnace: Air cleaner is mounted horizontally in
return plenum just above furnace, opposite of supply plenum. See Fig. 3D.
— Downflow Counterflow furnace: Air cleaner is mounted
horizontally in return duct or plenum just above furnace. See Fig. 3E.
— High capacity system: Two or more air cleaners can be
used together. See Fig. 3F.
— Horizontal furnace: Air cleaner is mounted vertically where
return enters. See Fig. 3G.
68-0240EF—06 6
F300 ELECTRONIC AIR CLEANER
A
B
C
E
D
F
Fig. 3. Mounting positions with variety of furnace installations.

Determine Duct Design Requirements

The air cleaner is adaptable to all new or existing forced air heating, cooling and ventilating systems used in residential applications. Transitions, turning vanes, or offsets may be needed in some applications for effective operation.
Transitions
Transitions are needed when the duct is a different size than the air cleaner cabinet. Gradual transitions reduce air turbulence and increase efficiency. Limit expansion to no more than 20 degrees or about 4 in. per running foot (100 mm per 300 linear mm) on each side of a transition fitting. See Fig. 4.
G
M19777
CHANGE DUCT SIZE GRADUALLY TO MINIMIZE TURBULENCE.
20 DEGREE EXPANSION PER SIDE PER FITTING (4 in. PER LINEAR FOOT [100 mm PER 300 LINEAR mm]).
RETURN AIR DUCT
TRANSITION FITTING
ELECTRONIC AIR CLEANER CABINET
M5626A
Fig. 4. Change duct size gradually to minimize turbulence.
Turning Vanes
If the air cleaner is installed close to an elbow or angle fitting, install turning vanes inside the angle to distribute airflow more evenly across the face of the cell. See Fig. 5.
7 68-0240EF—06
F300 ELECTRONIC AIR CLEANER
WARNING
M5627A
LESS THAN 7 in. [178 mm]
OFFSET
AT LEAST 7 in. [178 mm]
1
1 TURNING VANES HELP DISTRIBUTE AIRFLOW EVENLY.
E L
E CT
R O NI
C AI R
C LE
A N E
R
TYPICAL USE OF DUCT OFFSET TO ALLOW SPACE FOR ELECTRONIC AIR CLEANER.
M20804
Offsets
If the duct connection to the furnace in a side installation allows less than 7 in. (178 mm) for mounting the air cleaner cabinet, add an offset to the elbow. See Fig. 5.
Fig. 5. Typical use of duct offset to allow space for
electronic air cleaner.

INSTALLATION

Clean Blower Compartment

Remove and discard the existing furnace filter.Thoroughly clean the blower compartment.If possible, power vacuum the ductwork to remove
accumulated dust in an existing home, or construction dirt in a new home. The electronic air cleaner cannot remove dust that has settled in the blower compartment and distribution ducts.
Check the edges of the furnace fan blades for dirt buildup
and clean as necessary. The fan will not deliver the rated cfm if the blades are dirty.

Fasten Cabinet To Furnace

NOTE: This procedure shows a side installation on a typical
highboy furnace. You may need to alter the procedure to fit your application.
Remove and set aside the access door, electronic cells
metal mesh prefilters and media postfilters.
Align the cabinet with the return air opening.Create opening in furnace to match air cleaner cabinet
opening.
Install a transition when the furnace and air cleaner
openings are different sizes. See Fig. 4.
Place blocks under the cabinet so the unit is firmly
supported and level. The 5/8 in. (16 mm) mounting foot on the cabinet hinge plate provides the minimum clearance required for the access door hinge.
Attach the cabinet securely to the furnace. The unit can be attached directly, as shown, or a starting collar can first be fitted in the furnace opening. Either drill holes and fasten with sheet metal screws or rivets, or use slip joints. See Fig. 6.

When Installing this Product...

1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
Electric Shock Hazard. Can cause electrical shock or equipment damage.
Do not connect to power before installation is complete.

Unpack Electronic Air Cleaner

Check that all components are included. The electronic air
cleaner is shipped assembled. The unit consists of a galvanized steel cabinet, power supply with On-Off switch and neon light, two electronic cells, two metal mesh prefilters, two media postfilters (on select models), access door and product data literature.
Order W8600F (optional) including mounting hardware and
Order W8600A (optional) including mounting hardware,
installation literature separately.
batteries, and literature separately.
Fig. 6. Fasten cabinet to furnace.
68-0240EF—06 8

Install Turning Vanes

M20815
LOCKING PLIERS
TURNING VAN ES
Mount turning vanes inside the elbow or angle fitting that is
directly against the air cleaner cabinet. See Fig. 7.
F300 ELECTRONIC AIR CLEANER

Fasten Cabinet To Ductwork

Install a transition when the opening in the air cleaner
cabinet and the duct are different sizes. See Fig. 4.
Fasten the other side of the cabinet to the elbow using
sheet metal screws, rivets, or slip joints as appropriate. If drilling holes, use locking pliers to help hold the unit in place during drilling. See Fig. 7.
Fig. 7. Connect ductwork to air cleaner. (Note turning vanes. Locking pliers hold duct to air cleaner cabinet
during installation.)
CELL KEY
PREFILTER GUIDES
M5639
DOWNSTREAM
CELL KEY
AIRFLOW
CELL KEY SCREW
ALTERNATE HOLES FOR KEY
Fig. 8. Position of cell key determines orientation of cell
(arrow on key must point downstream).
3. Turn the key around and place it over the opposite holes.
The tab on the bottom fits into the larger hole, and the screw fits into the smaller hole. Make sure the arrow on the key points in the direction of the air flow (down­stream).
4. Tighten the screw into the new hole.
5. Insert the electronic cell. The ionizer section will now be
on the air-entering (upstream) side of the cabinet.

Attach Cell Handles

Cell handles included with the air cleaner must be installed on the end of the cell closest to the access door. To install:
1. Orient the cell as it will be when installed. The gray
contact board must be up and the airflow arrow stamped into the cell must point downstream.
2. Hold the handle sideways and insert the solid tab on the
back of the handle into the slot in the cell. Turn the handle 90 degrees clockwise to align the divided tab with the square hole. See Fig. 9.

Seal Joints

Seal all joints in the return air system between the air
cleaner and the furnace to prevent dust from entering the clean airstream. Use optional air cleaner cabinet gasket kit (part no. 32002109-001), mastic or foil tape.

Position Cell Key

The electronic cell must always be installed so the ionizer section is on the upstream side. A factory-installed cell key on the bottom of the cabinet allows the cell to be inserted in only one direction. If the arrow molded into the plastic key points in the same direction as the airflow, the ionizer is always on the upstream side.
If position of the key must be reversed, proceed as follows:
1. Remove the electronic cell.
2.
Remove the screw holding the cell key in place. See Fig. 8.
9 68-0240EF—06
INSTALL HANDLE ON END OF CELL CLOSEST TO ACCESS DOOR
ROTATE 90 DEGREES
FOLD TAB TO LOCK HANDLE IN PLACE
M6047A
Fig. 9. Install the handle on the end of the cell closest to
the access door.
3. Insert the divided tab into the square hole.
4. Fold up the wedge and insert it into the divided tab to
lock the handle in place. If necessary, press with a blunt instrument like the end of a pliers.
F300 ELECTRONIC AIR CLEANER
WARNING
P3
P4
P1
P2
J3
BLACK
W4 W2 W1 W3
AIRFLOW SWITCH BOARD
ORANGE
GRAY
VIOLET
BLACK
1 INTERLOCK SWITCH.
2 SHORTING BAR FOR OZONE REDUCTION.
3 AIRFLOW SWITCH DISABLE JUMPER, J8. AIRFLOW SWITCH PLUG, J3.
4 NEON LIGHT.
5 OPTIONAL W8600F AIR CLEANER MONITOR.
M23413
POWER SUPPLY
2
4
BLACK
BLACK
BLACK
BROWN
BLACK
BLACK
WHITE
GREEN
1
3
J4
J5
J1
BLACK
RED
TEST BUTTON
CONTACT BOARD
RED IONIZER
BLACK COLLECTOR
5
J8

Reassemble Air Cleaner

Insert the electronic cells with the gray contact board toward
the power supply and the airflow arrow pointing downstream. If the cell does not slide easily into the cabinet, check the orientation of the cell key.
Insert the metal mesh prefilters on the upstream side of the
cabinet in the guide provided.
Insert the media postfilters (on select models) on the
downstream side of the cabinet in the guide provided.
Replace the access door. Insert the tab on the bottom of the
door into the slot in the cabinet, then swing it closed and press into place. The door must be firmly in place or the air cleaner will not operate.

Complete Wiring

Electric Shock Hazard. Can cause personal injury.
Do not use an extension cord.
• Assure all wiring complies with local codes and ordinances.
• The line voltage power source must match the voltage and frequency printed on the label inside the access door.
• When the System fan comes on, the Air Flow Switch (AFS) senses the negative pressure in the duct and turns on the power supply. If power to the air cleaner is controlled by another switch, the AFS can be disabled by disconnecting the AFS plug J3 and cutting the J8 jumper on the power supply. See Fig. 10.
Plug the electronic air cleaner directly into the correct
voltage and frequency outlet. See Fig. 10 for internal schematic. The air cleaner operates correctly with any fan when wired with conduit or plugged in.
NOTE: To reduce the risk of electric shock, this product has a
grounding type plug that has a third (grounding) pin. This plug only fits into a grounding type power outlet. If the plug does not fit into the outlet, contact a quali­fied electrician to install the proper outlet. Do not
change the plug in any way.
Alternatively, the electronic air cleaner can be wired with
conduit.
68-0240EF—06 10
Fig. 10. Internal schematic for electronic air cleaner.
F300 ELECTRONIC AIR CLEANER
3
1
2
REMOVING COVER FROM POWER BOX.
ELECTRONIC AIR CLEANER
WIRING COMPARTMENT
BLACK
BROWN
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
THE AIR CLEANER CAN BE COMPLETELY ISOLATED FROM THE ELECTRICAL CIRCUIT OF THE HVAC SYSTEM UNLESS REQUIRED BY LOCAL CODE TO USE SAME CIRCUIT. ANY CONVENIENT HOUSE CIRCUIT CAN POWER AIR CLEANER, REGARDLESS OF ELECTRICAL RATING OF HVAC SYSTEM.
M5707
2
1
2
L1 (HOT)
L2
1
1. Open access door.
2. Remove and retain the two screws from the front of the
power box and the two screws from the sides of the power box. See Fig. 11.
3. In the power box, remove and retain two wire nuts that
connect the line cord leads to the power box wiring.
4. Remove the power cord green lead from the green
grounding screw on the wiring compartment barrier.
5. Remove the power cord and the strain relief.
6. Install the plug (provided with the literature pack) in the
hole left by the power cord.
7. Attach conduit through a power box side knockout.
8. Wire the air cleaner directly to line voltage using wire
nuts. See Fig. 12. Secure ground connection to the green ground screw on the wiring compartment barrier.
9. Replace power supply cover and access door.
Fig. 11. Removing cover from power box.

OPERATION

Large particles (lint, hair) are caught by the prefilter. As the dirty air passes through the intense high voltage electric field surrounding the ionizer wires, all particles are given an electrical charge.
The air then moves through the collector part of the cell where alternate parallel plates are charged positively and negatively, creating a uniform electrostatic field. The charged particles are attracted to and collect on the plates that have the opposite electrical charge.
The air then passes through media postfilters, removing additional particles from the air stream. The air leaving the air cleaner has fewer particles. Each time the air circulates through the electronic air cleaner, more particles are removed.

CHECKOUT

Inspect the Installation

Make sure:
• Turning vanes and transitions, as needed, are correctly installed.
• Sheet metal joints between air cleaner and furnace are sealed.
• All sheet metal connections are complete.
• Original furnace filter has been removed and the blower compartment cleaned.
• If atomizing humidifier is installed upstream from the air cleaner, a disposable furnace filter is installed between the humidifier and the air cleaner.
• Outside air, if used, is mixed with return air or heated, as necessary, before it can reach the air cleaner.
• Airflow arrows on the electronic cell point downstream.
• Metal mesh prefilter is on the upstream side and media postfilter is on downstream side of the cell.
• Cell handle faces outward.
• Electronic cell and prefilter are clean and dry.
• W8600F wiring connections are correctly made.
Fig. 12. Conduit connection for electronic air cleaner.
11 68-0240EF—06
F300 ELECTRONIC AIR CLEANER
CAUTION
CAUTION

Check Air Cleaner Operation

With all components in place, turn on air cleaner switch and energize system blower. Check following points of operation:
1. The neon light next to the On-Off switch is on. The neon
light shows that the air cleaner is energized and the high voltage power supply is working correctly. If a W8600F is part of the installation, also check the wall panel and make sure the On indicator is lit. The W8600F Fault indi­cator comes on if there is a problem with the high voltage power supply.
2. Turn off the system blower. The neon light should go off
after a few seconds.
3. Turn on the system blower. With the air cleaner ener-
gized, push the test button. A snapping sound indicates that the collector voltage is present on the cell.
4. With a multispeed blower, repeat steps 1 through 3 for
each fan speed.

SERVICE

Sharp Edges. Can cause personal injury.
Carefully handle the cell(s) or wear protective gloves to avoid cuts from the sharp metal edges.

Cleaning the Cells and Prefilters

To assure optimum performance from the air cleaner, the cells and prefilters must be cleaned regularly and the postfilters replaced regularly—twice a year with normal use or more frequently with heavy use. Washing frequency varies, depending on the number of family members, pets, activities (such as cooking or woodworking) and smoking habits. Use the Service Reminder Schedule at the end of this document to help establish and maintain a regular cleaning schedule. Keep your Service Reminder Schedule in a convenient location.
If the air cleaner has a W8600F Air Cleaner Monitor, the SERVICE indicator activates to indicate filter and cell maintenance are due. The time between activation of the SERVICE indicator is based on air cleaner run time that is selected by the installer at installation.
If the air cleaner has a W8600A AIRWATCH Indicator, the Air Cleaner LCD arrow blinks to indicate it is time to service the cells and prefilters. The time between activations of the Air Cleaner LCD is based on calendar time that is selected at installation.
NOTE: To let the heating or air conditioning system operate
normally while the cells are being washed, simply turn off the air cleaner switch.
Cleaning your Prefilter
1. The quickest and easiest way to clean your prefilter is to
use the brush attachment of your vacuum cleaner to vac­uum the lint off the dirty side of the prefilter. Greasy dirt
may require soaking the prefilter in a tub or rinsing with the garden hose. Do not wash the prefilter in the dish­washer or car wash.
2. The prefilter should be cleaned every 6 months or more
frequently with heavy use. This will keep the prefilter clean of air choking lint that can make your system work harder.
Cleaning your Cells
1. A quick cleaning of the cells can be done by simply wip-
ing down the ionizer wires with a damp cloth. This will help boost the efficiency of the air cleaner between full cleaning cycles. This quick clean can be done every time the prefilters are cleaned.
2. A full cleaning of the cells will return the air cleaner to its
peak efficiency. An easy way to wash the cells is in a tub of hot, soapy water. Just soak the cells until the water cools, agitate and rinse. For details see below instruc­tions on Cleaning in a Container, Automatic Dishwasher or Washing Cells at the Car Wash.
3. A full cleaning of the cells can be put off for yearly main-
tenance because the efficiency of the air cleaner remains high even as it loads up with dirt. A quick clean­ing can be done more often. Those wishing to renew to peak effeciency or with heavier use may want to wash more frequently.
Replacing your Postfilter
1. The postfilter is an optional filter that boosts the effi-
ciency of the air cleaner. Do not wash the postfilter because that will neutralize the factory applied charge.
2. The postfilter should be replaced every six months to
ensure peak performance.
Automatic Dishwasher
Burn Hazard. Can cause personal injury.
Allow cells to cool completely in dishwasher at end of wash cycle or wear protective gloves to avoid burns. Hot water can accumulate in the tubes supporting collector plates; tip cells so tubes drain.
IMPORTANT
• Check the dishwasher owner's manual. Some manufacturers do not recommend washing electronic cells in their dishwashers.
• If the dishwasher has upper and lower arms, position the cells carefully to allow good water circulation.
• Be careful to avoid damaging the cells when placing them in the dishwasher. Broken ionizer wires or bent collector plates are not included in the warranty.
• Very dirty cells, especially from tobacco or cooking smoke, can discolor the plastic parts and the lining of some dishwashers. This discoloration is not harmful. To minimize it, wash the cells more frequently or try a different brand of detergent.
Do not allow the dishwasher to run through the dry cycle. This bakes on any contaminants not removed during the wash cycle and reduces air cleaner efficiency.
68-0240EF—06 12
F300 ELECTRONIC AIR CLEANER
CAUTION
1. Put the cells on the lower rack of the dishwasher with the
airflow arrow pointing up. It may be necessary to remove the upper rack. Do not block water flow to the upper arm.
NOTE: Lay a few large water glasses between the spikes on
the lower rack and rest the cell(s) on them so the spikes do not damage the aluminum collector blades.
2. Using regular dishwasher detergent, allow the dish-
washer to run through the complete wash and rinse cycle. Do not use the dry cycle. To avoid burns, let the cells cool completely before removing, or wear protective gloves when removing the cells. Remember that water may be trapped inside the cells. Tip the cells so the tubes can drain.
3. Wipe ionizer wires and contact board on the end of the
cell using thumb and forefinger with a small, damp cloth.
4. Inspect the dishwasher. Rerun wash and/or rinse cycle
with the dishwasher empty if there is dirt or residue from washing the cells. If dirt or residue seems excessive, wash cells more often or try a different detergent.
Washing Cells in a Container
Hazardous Chemical. Can cause personal injury.
Do not splash detergent solution in eyes. Wear rubber gloves to avoid prolonged detergent contact with skin. Keep detergent and solution out of reach of children.
NOTE: Always wash the cells first, then the prefilters, to keep
heavy prefilter lint from getting caught in the cells.
1. Use a large enough container, such as a laundry tub or
trash container, to hold one or both cells.
NOTE: Sharp corners on cells can scratch surface of
bathtub.
2. Dissolve about 3/4 cup of automatic dishwasher deter-
gent per cell in enough hot water to cover the cells. If detergent does not dissolve readily, or forms a scum on the water, try another brand, or use softened water
3. After detergent has completely dissolved, place cells in
the container and let soak for 15 to 20 minutes. Agitate up and down a few times and remove. See Fig. 13.
WEAR GLOVES TO PROTECT HANDS FROM DETERGENT SOLUTION.
M922A
Fig. 13. Washing cells in container.
4. Next, wash the prefilters the same way. Empty and rinse
the wash container.
5. Rinse the cells and prefilters with a hard spray of very
hot water; rinse the tub clean, then fill the tub with clean hot water and soak for 5 to 15 minutes. Rinse until the water draining from the cells and prefilters no longer feels slippery.
6. Soak cells and prefilters in a final clear water rinse for
ten minutes.
7. Wipe ionizer wires and contact board on end of cell using
your thumb and forefinger with a small, damp cloth.
13 68-0240EF—06
F300 ELECTRONIC AIR CLEANER
HIGH VELOCITY DETERGENT SPRAY
STEAM
M20831
M1540B
IONIZER WIRE
IONIZER WIRE
NEEDLENOSE PLIERS
SPRING CONNECTORS
PRESS DOWN
EYELETS
REPLACING AN IONIZER WIRE.
TWO EYELETS HOLD IONIZER WIRE TO CELL.
1
1
Washing Cells at the Car Wash
Use the hand sprayer at a coin-operated do-it-yourself car wash to clean the cells. Hold the nozzle at least two feet away from the unit to avoid damage (such as broken ionizer wires or bent collector plates) from the high pressure stream of water. See Fig. 14. Follow the same sequence of wash and rinse as recommended for cars. However, do not wax the cells. Be sure to rinse until the water draining from the cells no longer feels slippery.
Replacing Ionizer Wires
Broken or bent ionizer wires can cause an electrical short to ground, often resulting in visible arcing or sparking. Do not use cells until broken wires are removed. Cells can be used temporarily with one wire missing, but replace the wire as soon as possible.
Replacement wires are supplied cut to length with eyelets on both ends for easy installation. See Parts and Accessories Not Illustrated section. To install:
1. Hook the eyelet on one end of the wire over the spring
connector on one end of the cell. See Fig. 15. Be careful to avoid damaging spring connectors or other parts of the cells.
2. Hold the opposite eyelet with a needle nose pliers and
stretch the wire the length of the cell. Depress the opposite spring connector and hook the eyelet over it.
3. Check the cell for short circuits using an ohmmeter; see
Fig. 16. Check the resistance between the frame of the cell and both the ionizer and the collector contacts. In each case, the resistance should be infinite.
Fig. 14. Washing cells at car wash.
Reinstall the Cells and Prefilters
1. Inspect the cells for broken ionizer wires and bent collec-
tor plates. Repair as necessary or take to a Honeywell Authorized Air Cleaner Repair Station.
2. Slide the prefilters into the upstream prefilter guides.
3. Slide in the air cleaner cells so the airflow arrow points
downstream and the handles faces outward.
4. Firmly close the access door.
5. Turn on the air cleaner. If the cells and prefilters are wet,
the neon light may not come on and you may hear arcing. If the arcing is annoying, simply turn off the air cleaner for two to three hours or until the cells are dry.
Replacing Media Postfilters
To maximize the filtration efficiency of the media postfilters, replace them every six months. Replacement filters are available in the same size and configuration as the original unit. Contact your local Honeywell distributor to purchase replacement filters. Install the replacement filters exactly as the filters provided with the equipment. Use the Service Reminder Schedule at the end of this document to help you establish and maintain a regular replacement schedule. Keep your Service Reminder Schedule in a convenient location.
Fig. 15. Replacing an ionizer wire.
68-0240EF—06 14
Loading...
+ 30 hidden pages