FEATURES
• High Efficiency Particulate Air (HEPA) filter models are
99.97% efficient and the hospital grade particle filter models are 95% efficient at 0.3 micron particles. Both models are more efficient on particles smaller and larger. There is also a 95% ASHRAE model.
• Circulates up to 1230 cfm.
• Designed to overcome the increase in air flow resistance normally caused by filter loading.
• White or black color cover to complement the ceiling.
• CPZ™ module removes up to 95% of the space odors for up to 24 months.
The F111 (Series 1,2) Ceiling Media Air Cleaner is a media air cleaner that uses a single-speed direct drive forward curve blower motor with particle filter. When equipped with CPZ™ modules (2), gases and odors are absorbed from the air passing through the unit. The air cleaner removes airborne particles such as dust, soot, mold spores, pollen and some cooking smoke from the air circulated through the filter.
• READ AND SAVE THESE INSTRUCTIONS
Contents
Application.........................................................................1
Features............................................................................1
Specifications....................................................................2
Ordering Information .........................................................2
Planning the Installation ....................................................3
Installation.........................................................................4
Operation...........................................................................6
Service ..............................................................................6
Parts List .......................................................... ... ... ...........8
Limited Two-Year Warranty...............................................10
The Honeywell Trademark is used under license from Honeywell Intellectual Properties, inc. by Air-Pure Systems. Honeywell International Inc. makes no representations or warranties with respect to this product
68-0198EF-4
F111 (SERIES 1,2) IN CEILING MEDIA AIR CLEANER
SPECIFICATIONS
IMPORTANT
Models: Refer to Table 1 for model descriptions.
The specifications given in this publication do not include normal manufacturing tolerances. Therefore,
Color: White or black cabinet and cover.
this unit may not exactly match the listed specifica­tions. Also, this product is tested and calibrated
Blower/Motor: Single speed direct drive forward curve.
under closely controlled conditions, and some minor differences in performance can be expected if those
Dimensions: See Fig. 1 for dimensions.
conditions are changed.
Table 1. F111 (Series 1,2) Description.
Efficiency
V.O.C./Odor
Air Volume
in cfm
3
(m
/hr)
Model Voltage
Particulates at
0.3 Micron (DOP Test)
(Most Gases/
Odors First Pass
Average)
Gas, V .O.C. and
Odor Control
Modules (2)
F111A1063 (11006) 120 Vac, 60 Hz, 1PHS, 6.5A 99.97% HEPA N/A N/A 1000 (1700) F111A1253(11025) 120 Vac, 60 Hz, 1PHS, 6.5A
95% ASHRAE
a
CPZ™ available
ab
1230/1125 F111A2007 208/230 Vac, 50/60 Hz, 3.7A 99.97% HEPA N/A N/A 1000 (1700) F111C1012 (11001) 120 Vac, 60 Hz, 6.5A 95% 85% CPZ™ modules 1000 (1700) F111C1038 (11003) 277 Vac, 60 Hz, 2.8A 95% 85% CPZ™ modules 1000 (1700) F111C1053 (11005) 208/230 Vac, 50/60 Hz, 3.7A 95% 85% CPZ™ modules 1000 (1700) N/A = not applicable.
a
Purchase filters separately.
b
Depends on filters used.
c
1230 or 1125 when used with CPZ modules.
c
TOP VIEW
Installation Weight:
3/8 X 16 INTERNAL THREAD (4)
Approximately 115 lb to 155 lb (kg) depending on the filter con-
figuration. Refer to Table 2.
Table 2. Sorbent Module Weight.
48 (1219)
46-3/4 (1187)
POWER CONNECTION POINT
24 (610)
22-1/2 (572)
CPZ™ module 43 (20)
Sound Level at 3.3 ft (1m):
Media Weight in lb (kg)
Low speed: 53 dBA (when using optional variable speed
17-1/4
(438)
4-1/2 (114)
CEILING
LINE
switch).
High speed: 61 dBA.
Grille Type: Perforated metal. Mounting: Recesses into opening on the ceiling.
Fig. 1. Approximate Dimensions of F111 in in. (mm)
Ordering Information
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Commercial Air Products Distributor.
2. Air-Pure Systems.
16873 Fish Point Rd. SE
Prior Lake, MN 55372
www.cleanairfacility.com Phone: (800) 998-1919 Fax: (800) 221-3248
68-0198EF-4 2
F111 (SERIES 1,2) IN CEILING MEDIA AIR CLEANER
Approvals:
Underwriters Laboratories Inc.: Listed. Canadian Standards Association: Listed.
Accessory: 32000234 Variable Speed Switch. Replacement Parts See Parts List, Table 4.
PLANNING THE INSTALLATION
The number of F11 1 (series 1,2) air cleaners that are needed is determined by taking into account the number of occupants and the volume of the space. Type of contamination, outdoor air quality and use of the area are also factors. Refer to Table 3 for general guidelines when determining how many air cleaners are needed.
EXAMPLE: One air cleaner can provide 2.5 air changes per
hour in a 24,000 cubic feet (720 cubic meters) no smoking area. Table 3 suggests two air cleaners for a 24,000 cubic feet area because most areas have contaminants that require more units to provide quality air.
If any questions should arise concerning determining the number of air cleaners needed for an area, consult your distributor or local Honeywell Commercial Air Cleaner Distributor.
Table 3. Determining the Minimum Number of
Air Cleaners Needed for a Space.
Space Volume
(L x W x H) in Cubic
Feet (Cubic Meter)
12000 to 18000
(360 to 540)
18001 to 35000
(540 to 1050)
35001 to 51000
(1050 to 1530)
51001 to 65000
(1530 to 1950)
65001 to 80000
(1950 to 2400)
80001 to 95000
(2400 to 2850)
Number of
Persons Present
30 to 60 1
61 to 90 2
91 to 120 3
121 to 180 4
181 to 240 5
241 to 300 6
Minimum
Number of Air
Cleaners
2. When Cutting Or Drilling Into The Wall Or Ceiling, Do
Not Damage Electrical Wiring And Other Hidden Utili­ties.
3. Never Place A Switch Where It Can Be Reached From A Tub Or Shower.
4. Use This Unit Only In The Manner Intended By The Manufacturer. If You have Questions, Contact The Man­ufacturer.
5. Before Servicing Or Cleaning Unit, Switch Power Off At Service Panel And Lock Service Panel To Prevent Power From Being Switched on Accidentally.
6. If This Unit Is To Be Installed Over A Tub Or Shower, It Must Be Marked As appropriate For The Application.
Choose Location
Choosing the correct location for the air cleaner affects the overall performance of the unit. The bidirectional airflow pattern must flow into the longest reaches of the zone being cleaned. See Fig. 2.
CLEANING FOOTPRINT
F111
(SERIES
11000)
2
CORRECT
1
INCORRECT
Fig. 2. Correct positioning of the air cleaner
for optimum cleaning.
NOTE: The F111 Has Not Been Investigated For Use In Fire Resistance Rated Construction.
The air cleaner is designed to be suspended centrally in a space and mounted into or on a ceiling. The cleaning footprint of the air cleaner is rectangular with air patterns that move clean air to the corners of the area while drawing contaminated air up from the center of the area. See Fig. 2.
CEILING
FLOOR
M12652A
WARNING
TO REDUCE THE RISK OF FIRE,ELECTRICAL SHOCK, OR INJURY TO PERSONS,OBSERVE THE FOLLOWING:
1. Installation Work And Electrical Wiring Must Be Done
By Qualified Person(s) In Accordance With All Applica­ble Codes And Standard, Including Fire Rated Con­structions.
When multiple air cleaners are installed, the allotted areas to be cleaned should be equal. The air throw in one direction is approximately 55 ft (17m). Air velocity at 90 ft per minute (27m per minute) is considered end of throw.
IMPORTANT
Never hang the air cleaner higher than 16 ft (5m) above the floor.