HONEYWELL EXCEL 5000 OPEN SYSTEM
Features
• Reduced the total installed cost:
• Universal operation:
• Reduced cost for service, operation and maintenance:
• Vendor independence:
General
Excel Web® is Honeywell’s new Ethernet-based, freelyprogrammable Building Automation controller.
It demonstrates Honeywell’s full commitment to reducing total
installed cost and total building lifecycle cost for building
investors and building operators.
Excel Web® incorporates the two major open standards in
today’s building industry: BACnet® and L
As a native BACnet® Building Controller (B-BC), Excel Web®
integrates into any 3
predictable effort.
Furthermore, Excel Web® is a full L
This gives the benefit of making use of Honeywell’s complete
L
ONWORKS® product portfolio, which is unique in the Building
Industry.
Excel Web® can host a huge variety of Building Management
applications, be it traditional heating, ventilation, and air
conditioning (HVAC) applications, energy management
functions, including optimum start/stop, night purge, and
maximum load demand, supervisory functions for lighting,
sun-blind, heat and energy metering and many other
applications.
By virtue of its "peer-to-peer" concept, Excel Web® is not
dependent upon the availability of superordinant centrals or
application network controllers.
Excel Web® seamlessly integrates into Honeywell’s
Enterprise Buildings Integrator™ (EBI) and SymmetrE® frontends.
rd
-party BACnet® system with low and
ONWORKS®.
ONWORKS® controller.
• Expandable trend buffer:
• Fast application control:
• Reliable control performance:
• Embedded e-mail/SMS alarming:
• Honeywell CARE tool:
• Network security:
• Flexible mounting options:
Excel Web®
Control System
PRODUCT DATA
Existing standard Ethernet/LAN infrastructure is used for
communication between Excel Web® controllers, 3
BACnet® controllers, and BACnet® front-ends.
Operate Excel Web® from any place, from any integrated
PC! An integrated web-server allows local and remote
operation by standard browsers.
Maintenance or upgrade of Operator Interface Software is
superfluous because it resides in Excel Web®, itself
(single-source principle).
Communication is based on the international ISO 16484-5
BACnet® standard and L
3rd-party BACnet® controllers (peer-to-peer) and front-ends
is based on the BACnet® Building Controller (B-BC) profile
of Excel Web®. Interoperability with room and zone
controls, field equipment, and field I/Os is based on
L
ONWORKS®.
The onboard trend buffer can store 64,000 trend entries,
and can be expanded using standard Compact Flash
Cards (type 1 or 2).
Four selectable control loop priorities (multitasking),
selectable control loop cycle times, and event-driven
switching tables allow for tailored and highly effective
applications control.
Embedded LINUX ensures reliable, independent, and
secure operation, especially for systems with Internet
access.
Configurable e-mail alarming options allow alarms to be
sent (via network, Internet-DSL connection, or Internetmodem connection) to e-mail accounts and thus also to
mobile phones.
Allows re-use of existing applications and application
macros, enables highly effective application generation,
and supports online and offline debugging and application
simulation.
Based on its design as an IP device, Excel Web® can be
easily integrated into any existing network security
mechanism.
DIN-rail, wall, or panel front door mounting.
ONWORKS®. Interoperability with
rd
-party
® U.S. Registered Trademark
Copyright © 2009 Honeywell Inc. • All Rights Reserved EN0B-0443GE51 R0409
EXCEL WEB CONTROL SYSTEM
Operator Interface
Excel Web is operated via a standard browser.
By default, an integrated web-server provides all operation
pages for a full browser-based operation.
Through the consequent use of software standards, any PC
platform can be used as an operator interface (client),
including laptops, desktops PCs, or touch screen PCs for
direct flush mounting into electrical panel doors (IP65).
Alternatively, the 5.7" touch-panel operator unit (order
number: XI882) can be used. In this case, 320x240 pixel webpages will be displayed.
Fig. 1. Excel Web "Homepage" Example
Specifications
Communication Protocols
BACnet/IP - ISO 16484-5 – ENV 13321-1
Communication with other Excel Web controllers, with 3
party BACnet devices, with Honeywell Enterprise Buildings
Integrator™ and SymmetrE front-ends, and with 3
BACnet front-ends is based on the international BACnet
Protocol.
Excel Web conforms to the BACnet Building Controller (B-BC)
profile.
For details on the BACnet Interoperability, see the Excel Web
Protocol Implementation Conformance Statement (PICS).
LonTalk®
Communication with physical I/O modules, with room and
zone controllers, and with Excel 50/500/800 controllers is
based on LonTalk.
A Free Topology Transceiver (FTT-10A or FT-X1) allows a
communication speed of 78 Kbaud.
In typical cases, field devices are controlled via Honeywell
Distributed I/O (XFL52xB, XFL82x) or Smart I/O (XFCxxx or
XFCLxxx) modules. Max. cable lengths: 320 m to 2,200 m.
By default, the Excel Web XIF comprises the LonMark® node
object, plus application-specific L
ONWORKS objects.
rd
-party
rd
-
HTTP
Excel Web provides two operating options:
Internet browsers having a resolution of 800x600 pixels or
higher. Operation has been optimized for I.E. 5.5 or
higher, but Netscape (6.2.1 or higher) and Mozilla
Firefox® are likewise suitable.
Internet Explorer for WIN CE with resolution of 320x240
pixels.
For Internet Browser settings, please consult the Software
Release Bulletin.
FTP
The firmware and application are downloaded using CARE via
the standard FTP (File Transfer Protocol). Via FTP, product or
plant-related literature can be downloaded (without special
tools) into Excel Web for later use.
SMTP
Simple Mail Transfer Protocol is used for e-mail alarming via
network, Internet-DSL connection, and Internet-modem
connection.
Hardware Interfaces
Ethernet
• 10/100 Mbit/s, RJ45
• 1 LED “link”, 1 LED “activity”
LONWORKS®
• 78 Kbit/s
• FTT10A, FT-X1
• 2x screw terminal, removable
• 1x RJ45
ONWORKS® Service button
• L
• 1 service LED
RS232C Port 1
• Service interface (root terminal = LINUX console)
• data transmission rate: 9.6, 19.2, 76.8, or 115.2 Kbaud
(depending upon configuration)
• 9-pin Sub-D
RS232C Port 2
• Browser interface
• data transmission rate: 9.6, 19.2, 76.8, or 115.2 Kbaud
(depending upon configuration)
• 9-pin sub-D
RS232C Port 3
• Modem Interface for analog modems, ISDN Adapters, or
GSM Adapters
• data transmission rate: 9.6, 19.2, 76.8, or 115.2 Kbaud
(depending upon configuration)
• 9-pin sub-D
Compact Flash Type 1 or Type 2
• Standard Compact Flash card (not included)
• 1 "active" LED