Honeywell EXCEL SMART I-O INSTALLATION INSTRUCTIONS

XFC1Axx, XFC1Dxx, XFC2Axx, XFC2Dxx, XFC3Axx,
HONEYWELL EXCEL 5000 OPEN SYSTEM
GENERAL INFORMATION
In addition to the four fast digital inputs and four relays (two normally open, two changeover) present in every Excel Smart I/O, specific models are equipped as follows:
Removable Terminals (XFC1Dxx), 110 Vac (long housing)
XFC1D06001: four universal inputs (NTC20k), two
0...10 V analog outputs, built-in transformer, six manual overrides, ten status LEDs
Removable Terminals (XFC2Dxx), 230 Vac (long housing)
XFC2D05001: two universal inputs (PT1000, Ni1000, or Ni1000TK5000), two 0...10 V analog outputs, built-in transformer, six manual overrides, ten status LEDs
XFC2D06001: four NTC20k universal inputs, two 0...10 V analog outputs, built-in transformer, six manual overrides, ten status LEDs
Removable Terminals (XFC3Dxx), 24 Vac (short housing)
XFC3D04001: two universal inputs for three-wire PT100 sensors, two 0...20 mA analog outputs, six manual overrides, ten status LEDs
XFC3D05001: two universal inputs (PT1000, Ni1000, or Ni1000TK5000), two 0...10 V analog outputs, six manual overrides, ten status LEDs
XFC3D06001: four NTC20k universal inputs, two 0...10 V analog outputs, six manual overrides, ten status LEDs
Fixed Terminals (XFC1Axx), 110 Vac (long housing)
XFC1A06001: four universal inputs (NTC20k), two
0...10 V analog outputs, built-in transformer
Fixed Terminals (XFC2Axx), 230 Vac (long housing)
XFC2A05001: two universal inputs (PT1000, Ni1000, or Ni1000TK5000), two 0...10 V analog outputs, built-in transformer
XFC2A06001: four NTC20k universal inputs, two 0...10 V analog outputs, built-in transformer
Fixed Terminals (XFC3Axx), 24 Vac (short housing)
XFC3A04001: two universal inputs for three-wire PT100 sensors, two 0...20 mA analog outputs, short housing
XFC3A05001: two universal inputs (PT1000, Ni1000, or Ni1000TK5000), two 0...10 V analog outputs
XFC3A06001: four NTC20k universal inputs, two 0...10 V analog outputs
The term "universal inputs" refers to analog inputs for tem­perature-sensor signals which can be configured as voltage­variable or slow digital inputs (e.g. for dry-contact / open­collector signals). In the case of the XFC3A04001 and XFC3D04001, reconfiguration of the two 3-wire PT100 uni­versal inputs yields four voltage-variable or slow digital inputs.
Further, the universal inputs and the analog outputs each feature an extra 24 Vac power output terminal capable of powering field devices.
BEFORE INSTALLATION
IMPORTANT
INSTALLATION
Mounting
The Excel Smart I/O is available with either
short (W x L x H = 126 x 76 x 110 mm) or
long (W x L x H = 180 x 76 x 110 mm)
housings (see Fig. 1) conforming to IP20/30. The mounting procedures are similar for both sizes.
The Excel Smart I/O is suitable for mounting on both a standard rail (DIN EN 50022-35 x 7,5) for installation in wiring cabinets or fuse boxes, and on walls/ceilings.
Excel Smart I/O
AND XFC3Dxx MODULES
It is recommended that the Excel Smart I/O be kept at room temperature for at least 24 h before applying power to allow the evaporation of any condensation resulting from low shipping / storage temperatures.
CAUTION
To avoid electrical shock or equipment damage, you must turn OFF the power supply before attaching / removing connections to/from any terminals.
Fig. 1. Excel Smart I/O housing (side view)
® U.S. Registered Trademark Copyright © 2004 Honeywell Inc. EN1B-0180GE51 R1004B / 95-7666-5 All Rights Reserved
EXCEL SMART I/O MODULES
DIN Rail Mounting/Dismounting
The unit can be mounted onto the DIN rail simply by snapping it into place. It is dismounted by gently pulling the stirrup located in the base of the housing (see Fig. 2).
screwing nose
(round hole)
eyelets for
cable binders
screwing nose
(oval hole)
eyelets for
cable binders
eyelet for
cable binders
stirrup;
pull to dismount
from rail
Fig. 2. Housing base (view from below)
When mounted on a DIN rail, the unit must be secured in place with a stopper to prevent sliding.
Wall/Ceiling Mounting/Dismounting
The unit can be mounted on walls or ceilings in any orien­tation desired. In the case of ceiling mounting, however, it should not be operated at ambient temperatures exceeding 45 °C. The unit is mounted by inserting 3.5-mm dowel screws through the corresponding screwing noses.
short housing: 100 mm; long housing: 154 mm
round hole
(diameter: 4 mm)
oval hole
(4x7 mm)
short housing: 100 mm
Fig. 3. Drilling template (view from above)
After mounting the Excel Smart I/O, provide for cable access by snipping out the terminal protection covers' cut-out tabs and snap (by hand) the covers (available in packs of 8) into place onto the housing. To remove a cover, place a screw­driver in the leverage slot (see Fig. 10) and pry it loose.
Power Supply
General Information
All module inputs and outputs are protected against overvoltages of max. 40 Vdc and 24 Vac.
NOTE: Local wiring guidelines (e.g. VDE 0100) may take
precedence over recommendations provided in these installation instructions.
NOTE: To comply with CE requirements, devices with a
voltage in the range of 50 to 1000 Vac or 75 to 1500 Vdc lacking a supply cord, a plug, or other means for disconnection from the power supply having a contact separation of at least 3 mm at all poles must have the means for disconnection incorporated in the fixed wiring.
Models equipped with a built-in transformer are powered with either:
230 Vac (-15%/+10%), 50 or 60 Hz (XFC2xx) or
110 Vac (-15%/+10%), 50 or 60 Hz (XFC1xx)
When not supplying external devices with 24 Vac, these models have a power consumption of under 17.5 VA.
Models with a short housing are powered with 24 Vac (±20%), 50 or 60 Hz from an external transformer (which can power more than a single Excel Smart I/O; in this case, it is essential that the different Excel Smart I/O's not be connected with each other in any additional fashion, e.g. by being grounded, or by being connected to the same field devices). The 24 V models have a power consumption of under 6.5 VA.
Each universal input and each analog output features a 24 Vac power output terminal capable of supplying power to field devices. If the module is supplied with direct current, these power output terminals will deliver only direct current.
NOTE: The max. combined current draw of all of the field
devices supplied by the power output terminals of a single Excel Smart I/O equipped with a built-in trans­former must not exceed 300 mA (cos φ = 1) for pro­longed periods of time. In the case of an Excel Smart I/O powered by an external transformer, the max. combined current draw is 500 mA (cos φ = 1). Disregarding these limits can result in the destruction of the built-in / external transformer.
Connecting to the Power Supply
The Excel Smart I/O is connected to the power supply as shown in Fig. 4 or Fig. 5, as the case may be.
All wiring must comply with applicable electrical codes and ordinances. Refer to job or manufacturers’ drawings for details. Use a min. of 18 AWG (1.0 mm
long housing: 100 mm
AWG (2.5 mm
2
) for all power wiring.
Do not reverse the polarity of the power connection cables. Also, avoid ground loops (i.e. do not connect one field device to several Excel Smart I/O modules): Failure to observe these instructions may result in short circuits, damaging your devices.
In the case of models with removable terminals, an orange­colored T terminal plug may be used. In this case, the T terminal plug is plugged into pins 1 and 2 (24 Vac models) or pins 43 and 44 (110 Vac and 230 Vac models).
If power is supplied via T terminal plugs, it is possible to disconnect individual Excel Smart I/O modules from the power supply without disturbing the operation of other devices powered by the same source.
2
) and a max. of 14
EN1B-0180GE51 R1004B / 95-7666-5
2
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
24V
A
A
A
A
A
A
A
A
A
A
A
A
A
A
24V
0
24 Vac
+/- 20%
230 Vac 120 Vac
~
22
24V
~ 1
24V
~
22
24V
~ 1 2
23
24V
0 2
24V
0
23
24V
0
fuses dependent
24V
AI1
out
109
24
V
0...10 Vdc
active sensor 1
24V
AI1
out
109
24
V
0...10 Vdc
active sensor 1
upon your
transformer
AI1
0
Y
11
0
AI1
0
Y
11
0
24V out
12
24
V
0...10 Vdc
24V out
12
24
V
0...10 Vdc
AI2
0
13
0
AI2
0
13
0
Excel Smart I/O
AI2Y24V
I3
I3
24V
I4
out
18
24
V
0...10 Vdc
I4
0
Y
19
20
0
out
0
Y
16
1514
17
24
0
V
0...10 Vdc
active sensor 3 actuator 1
Excel Smart I/O
AI2Y24V
I3
I3
24V
I4
out
18
24
V
0...10 Vdc
I4
0
Y
19
20
0
out
1514
24
V
0...10 Vdc
active sensor 3
0
Y
16
17
0
24V out
30
24
V
0...10 V
24V out
30
24
V
0...10 V actuator 1
O1
O1
24V
0
31
0
O1 0
31
0
O2
out
0
Y
34
32
33
M
24
0
V
M
0...10 V actuator 2active sensor 4active sensor 2
O1
24V
O2
out
Y
0
32
33
34
M
24
0
V
M
0...10 V actuator 2active sensor 4active sensor 2
Fig. 4. Connection to power supply (24 Vac models)
Excel Smart I/O
~
0
24V
power
power
out
43
44
24
V
active sensor 1 active sensor 3 actuator 1
AI1
0
109
0
0...10 Vdc
24V
AI1
AI2
AI2Y24V
AI3
I3
24V
I4
I4
24V
O1
O1
24V
O2
out
Y
0
out
0
Y
out
0
Y
out
0
13
12
11
24
V
0...10 Vdc
16
1514
24
V
0...10 Vdc
0
19
17
18
20
0
24
0
V
0...10 Vdc
30
24
V
0...10 V
Y
31
32
0
M
out
33
24
V
0...10 V actuator 2active sensor 4active sensor 2
O2
0
Y
34
35
0
M
Excel Smart I/O
~
0
power
power
43
44
N
230 Vac
(110 Vac)
+10%/-15%
24V out
24
V
active sensor 1 active sensor 3 actuator 1
AI1
0
109
0
0...10 Vdc
24V
AI1
AI2
AI2Y24V
AI3
I3
24V
I4
I4
24V
O1
O1
24V
O2
out
Y
0
out
0
Y
out
0
Y
out
0
12
11
13
1514
16
17
18
19
20
24
24
0
V
0...10 Vdc
0
V
0...10 Vdc
24
V
0...10 Vdc
0
30
24
V
0...10 V
Y
31
32
0
M
out
33
24
V
0...10 V actuator 2active sensor 4active sensor 2
O2
0
Y
34
35
0
M
Fig. 5. Connection to power supply (110 Vac and 230 Vac
models)
LonWorks Communications
General Information
The Excel Smart I/O is equipped with a free topology trans­ceiver (FTT10A) for communicating on L works. The L
ONWORKS network is insensitive to polarity,
eliminating installation errors due to miswiring. Different network configurations (daisy-chain, loop, and star configurations, or any combination thereof) are possible (see also: Excel 50/500 L
ONWORKS Mechanisms Interface
Description, EN0B-0270GE51).
Connecting to the LONWORKS Network
IMPORTANT REMARKS:
— Do not bundle wires carrying field device signals or
L
ONWORKS communications together with high-voltage
power supply or relay cables. Specifically, maintain a min. separation of 3 inches (76 mm) between such cables. Local wiring codes may take precedence over this recommendation.
ONWORKS® net-
EXCEL SMART I/O MODULES
— Try to avoid installing in areas of high electromagnetic
noise (EMI).
The unit must be wired to the L
O2 Y
IV 22 AWG (Belden part number 9D220150) or plenum-rated
35
ONWORKS network using level
level IV 22 AWG (Belden part number 9H2201504) non­shielded, twisted-pair, solid-conductor wire. When possible, use Honeywell AK3781, AK3782, AK3791, or AK3792 cable (US part numbers). See E-Bus (L
ONWORKS Network) Wiring
Practices, form number 74-2865, for more information, including max. lengths.
Use wire with a min. size of 20 AWG (0.5 mm size of 14 AWG (2.5 mm
O2 Y
35
Connection to the L
2
).
ONWORKS network is as shown in Fig. 6
2
) and a max.
and Fig. 7 via terminal pins 3 and 4 (black screw-type T ter­minal plug) underneath the terminal protection cover (if present) located on the low-voltage side.
In the case of terminals connected to the L
ONWORKS network
via a removable terminal plug, it is possible to disconnect individual modules from the network without disturbing the operation of other devices in the same network.
Depending upon the chosen configuration, one or two ter­mination modules (either part no. 209541B or XAL-Term) may be required (see also: Excel 10 FTT/LPT 209541B Ter­mination Module Installation Instructions, form 95-7554).
24V
24V
LON
~
22
24V
~ 1
24V
~
22
24V
~ 1
LON
1
2
0
23
24
25
24V
LON
LON
0
1
2
3
24V
LON
LON
0
1
23
24
24V
LON
LON
0
1 3
2
Excel Smart I/O with fixed terminals
2 4
2
25
Excel Smart I/O with fixed terminals
2 4
Fig. 6. Connection to L
ONWORKS (fixed terminals)
Excel Smart I/O
24V
24V
0
~ 1
2
removable
T plug
LON
1 3
LON
2 4
Excel Smart I/O
24V
24V
0
~ 1
2
removable
T plug
LON
Excel Smart I/O
LON
24V
24V
LON
1
2
3
4
~ 1
removable
T plug
0
1
2
3
Fig. 7. Connection to LonWorks (removable plugs)
Inputs/Outputs
General Information
Depending upon the model, the units are equipped with removable or fixed screw-type terminal blocks. Removable screw-type terminal blocks allow the terminal assignments to
LON
2 4
3
EN1B-0180GE51 R1004B / 95-7666-5
EXCEL SMART I/O MODULES
be made before plugging them into the unit, and to be preserved after unplugging them from a unit requiring repair or replacement. The terminal blocks are arranged on two sides: the relay side and the low-voltage side.
The relay side consists of a single row of terminal blocks for the connection of cables to the relays. In the case of models with a long housing, the high-voltage power supply, too, is connected on this side.
The low-voltage side consists of two rows of terminal blocks for the connection of cables to all other input / outputs. In the case of models with a short housing, the low-voltage power supply, too, is connected on this side.
NOTE: VDE guidelines prohibit mixing low-voltage and high-
voltage signals on the relay side.
Wiring the Inputs/Outputs
Use a min. size of 20 AWG (0.5 mm2) and a max. of 14 AWG (2.5 mm all input/output cables is 1300 ft (400 m).
Two wires with a total thickness of 14 AWG can be twisted together and connected using a wire nut (include a pigtail with this wire group and attach the pigtail to the individual terminal block). Deviations from this rule can result in improper electrical contact. Local wiring codes may take precedence over this recommendation. If cable binders are used, pass them through the corresponding eyelets.
2
) for all input/output connections. The max. length of
Terminal Assignment
Fig. 8 depicts the terminal assignments of a typical Excel Smart I/O. Refer to job drawings for specific wiring diagrams.
Fig. 8. Example terminal assignment
In the case of models not equipped with manual override switches, a terminal assignment label (see Fig. 9) is fixed to the top of the housing. In the case of modules equipped with manual override switches, this label is included in the delivery. Attach this label to the terminal protection cover or swivel label holder, as appropriate. Unused terminals are marked with an "x" on the device type label. In the case of models powered with 110 Vac or 230 Vac, hook up the external power supply to terminals 1, 2, 22, and 23, which are connected to the 24 Vac internal transformer; these terminals must not be used for connecting an external 24 Vac power supply.
Fig. 9. Example terminal assignment label
After completing terminal assignment, perform a wiring check using the XILON Handheld MMI. See XILON Handheld Tool for Wiring Checks User Guide (EN2B-0214GE51) for details.
Hardware Features
Fast Digital Inputs
Every Excel Smart I/O is equipped with four fast digital inputs, each with its own ground terminal pin. The fast digital inputs are not electrically insulated from the CPU core.
In order for the software to detect that a fast digital input is closed, the resistance of the dry contact must be less than 200 , the incoming current must not exceed 3 mA, and the voltage must be less than 0.8 Vdc.
In order for the software to detect that a fast digital input is open, the resistance of the dry contact must exceed 50 k, and the voltage must be greater than 10 Vdc.
In order to totalize signals (max. frequency = 20 Hz), the driving signal must be stable for a min. of 22 ms.
Relays
Every Excel Smart I/O is equipped with four relays, including two normally-open relays and two changeover relays. During power-off and after a reset (before the software begins working), the hardware default position of a normally-open relay is open.
In order to switch reliably, the relays require a min. current of 50 mA.
The normally-open contacts are designed for a max. continuous current of 6 A (at max. 230 Vac / max. 24 Vdc).
The normally-closed contacts are designed for a max. continuous current of 1 A (at max. 230 Vac / max. 24 Vdc).
The max. combined allowable current flowing through all relays simultaneously is 24 A (continuous) (at max. 230 Vac / max. 24 Vdc).
The max. peak current (10 ms) at the normally-open contact is 50 A at cos φ = 1 and 30 A at cos φ = 0.6.
After these relays have been configured using Honeywell's LonMaker for Windows™ plug-in, floating actuators can be directly connected to them (max. two relays per floating drive).
NOTE: If inductive components are to be connected to the
relays and if these relays switch more often than once every two minutes, these components must be prevented from causing harmful interference to radio or television reception (conformance with EN
45014).
Accuracy and Resolution of Universal Inputs
The Excel Smart I/O is equipped with universal inputs for reading analog signals from different types of temperature
EN1B-0180GE51 R1004B / 95-7666-5
4
EXCEL SMART I/O MODULES
sensors. Each universal input features an extra terminal capable of supplying 24 Vac power to sensors.
At 25 °C, NTC sensors (e.g. Siemens type B57111-J2203-A3) display a resistance of 20 k. Table 1 lists the typical accuracy and resolution of inputs reading signals from such sensors.
Table 1. Accuracy, resolution of inputs (NTC20k sensors)
temperature range accuracy resolution
-50 to -40 °C (-58 to -40 °F)
-40 to -30 °C (-40 to -22 °F)
-30 to -20 °C (-22 to -4 °F)
-20 to -10 °C (-4 to 14 °F)
-10 to 0 °C (14 to 32 °F) 0 to 10 °C (32 to 50 °F) 10 to 50 °C (50 to 122 °F)
5.5 K 3.0 K 1.8 K 1.1 K 0.8 K 0.6 K 0.4 K
1.0 K
0.4 K
0.32 K
0.2 K
0.14 K
0.1 K
0.1 K
50 to 70 °C (122 to 158 °F) 0.6 K 0.14 K 70 to 90 °C (158 to 194 °F) 1.0 K 0.36 K 90 to 100 °C (194 to 212 °F) 1.5 K 0.4 K 100 to 120 °C (212 to 248 °F) 2.4 K 0.8 K 120 to 150 °C (248 to 302 °F) 5.3 K 2.0 K
At 0 °C, Pt100 sensors (DIN EN 60751) display a resistance of 100 . Table 2 lists the typical accuracy of inputs reading signals from such sensors; the resolution amounts to 0.01 K throughout the entire temperature range.
Table 2. Accuracy of inputs (Pt100 sensors)
temperature range accuracy
-50 to -20 °C (-58 to -4 °F)
-20 to 0 °C (-4 to 32 °F) 0 to 30 °C (32 to 86 °F) 30 to 70 °C (86 to 158 °F) 70 to 100 °C (158 to 212 °F)
1.7 K 1.2 K 0.9 K 1.1 K 1.7 K
100 to 130 °C (212 to 266 °F) 1.7 K 130 to 150 °C (266 to 302 °F) 1.8 K
At 0 °C, Pt1000, Ni1000, and Ni1000TK5000 sensors (DIN EN 60751) display a resistance of 1000 . Table 3 lists the typical accuracy of inputs reading signals from such sensors; the resolution amounts to 0.01 K throughout the entire temperature range.
Table 3. Accuracy of inputs (Pt1000, Ni1000, and
Ni1000TK5000 sensors)
temperature range accuracy
-50 to -20 °C (-58 to -4 °F); Ni1000: -40 to -20 °C (-40 to -4 °F)
-20 to 0 °C (-4 to 32 °F) 0 to 30 °C (32 to 86 °F) 30 to 70 °C (86 to 158 °F) 70 to 100 °C (158 to 212 °F) 100 to 130 °C (212 to 266 °F); not Ni1000;
Ni1000TK5000: 100 to 120 °C (212 to 248 °F)
1.2 K 0.7 K
0.5 K 0.7 K 1.2 K
1.2 K
130 to 150 °C (266 to 302 °F); Pt1000, only 1.2 K The universal inputs can be configured as voltage-variable or
slow digital inputs (in the case of the XFC3A04001 and the XFC3D04001, reconfiguration of the two 3-wire PT100 universal inputs yields four voltage-variable or slow digital inputs).
Analog Outputs
The Excel Smart I/O is equipped with two analog outputs (0...10 V or 0...20 mA, depending upon the specific model). Each analog output features a 24 Vac power output terminal capable of supplying power to actuators.
Status LEDs and Manual Override Switches
The XFC1D06001, XFC2D05001, XFC2D06001, XFC3D04001, XFC3D05001, and XFC3D06001 are equipped with six manual override switches and ten status LEDs (see Fig. 10).
The status LEDs can be freely programmed to indicate the current state of any digital input or relay. By default, status LEDs 1 through 4 are assigned to digital inputs 1 through 4, respectively, with "red = ON" and "green = OFF." Status LEDs 5 through 8 are assigned to relays 1 through 4, respectively, with "yellow = ON" and "unlit = OFF." LEDs 9 and 10 are permanently assigned to analog outputs. In the case of normally-open contacts, "lit = CLOSED CONTACT."
The manual override switches can be freely assigned to any relay or analog output (including hardware). By default, manual overrides 1 through 4 are assigned to relays 1 through 4, respectively, with "0 Position = OFF" and "1 Position = ON." Manual overrides 5 and 6 are assigned to analog outputs 1 and 2, respectively, with "0 Position = 0%" and "1 Position = 100%."
red LEDs
(specific modules)
manual overrides
(specific modules)
leverage slot
LonWorks
service button
long housing (with built-in transformer): 180 m (7-7/8 in.)
Short housing (without transformer): 126 mm (4-15/16 in.)
Fig. 10. Housing (top view, with covers and label holder)
yellow LEDs
(specific modules)
3-color LEDs
(specific modules)
power LED
LonWorks
service LED
ventilation slits
5
EN1B-0180GE51 R1004B / 95-7666-5
Troubleshooting
All models feature a LONWORKS service LED and cor­responding service button (accessible from the outside on top of the module) for use in troubleshooting. When the service button is pressed, the following actions take place:
The service pin message (containing the Neuron ID and the Standard Program ID) is broadcast on the L
ONWORKS
network (the service pin message is broadcast whenever the service button is pressed, after each reset due to power-up, after every software reset, and whenever the mode is changed from offline to online).
When the service button has been pressed longer than 30 sec, the node reverts to normal mode (provided it has been in the manual override mode via nviAoManOvrd or nviDoManOvrd).
For more information on standard service LED behavior, refer to Motorola L
ONWORKS Technology Device Data Manual,
page AL-190.
Table 4. Service LED Behaviors and Meanings
LED Blinking Pattern Meaning
1 LED remains OFF after power-up. Defective device hardware. Suspect power supply problems, clock 2 LED is ON continuously, even before first power-up. Defective hardware.
3 LED flashes at power-up, goes OFF, then comes ON solid. Node is applicationless. 4 LED flashes briefly once every second. This device is probably experiencing continuous watchdog resets,
5 LED blinks ON and OFF at 0.5 Hz. Node is unconfigured but has an application. 6a
OFF duration 10 sec. Afterwards, the service LED turns ON and stays ON, indicating completion of the blanking process.
6b
OFF duration 1 sec. Afterwards, the service LED turns ON and stays ON.
6c OFF duration is 1...15 sec, depending on the application size
and the system clock. Afterwards, the service LED begins blinking ON and OFF at 0.5 Hz.
6d OFF duration is indefinite (1-15 sec to load internal EEPROM;
stays OFF). 7 LED remains OFF after a short ON duration. Node is configured and running normally. 8 LED blinks ON for 1 sec and OFF for 1 sec five times in
succession and then stays OFF for 5 sec, after which the
pattern is repeated. 9 LED blinks ON for 1 sec and OFF for 1 sec four times in
succession and then stays OFF for 5 sec, after which the
pattern is repeated.
10 LED blinks ON for 1 sec and OFF for 1 sec three times in
succession and then stays OFF for 5 sec, after which the
pattern is repeated.
Possible problem causes and the corresponding recommended actions are as follows:
Power LED is not lit check the power supply
CPU not working contact your Honeywell dealer
Incorrect wiring → contact your Honeywell dealer
Defective hardware → contact your Honeywell dealer
Check if the behavior is changed if you:
1. Push the L Excel Smart I/O module. The L
ONWORKS service button to reconfigure the
ONWORKS service LED will
remain lit as long as the service button is pushed. If this is not the case, the hardware is defective.
2. Switch the power OFF / ON.
Please contact Honeywell if the above actions do not solve the problem. Further, more information is available under the following URL:
http://web.ge51.honeywell.de/dep/mc/Building_Automation/TAC/Overview_
TAC_Tips/Tac_Tip_files
problems, or a defective Neuron Chip.
or the external memory or EEPROM is corrupt. Using EEBLANK on a Neuron 3150 Chip-based custom node. First power-up with a new PROM on a Neuron 3150 Chip-based
custom node. Applicationless firmware state exported. First power-up with a new PROM on a Neuron 3150 Chip-based
custom node. Unconfigured firmware state exported. First power-up with a new PROM on a Neuron 3150 Chip-based
custom node. Configured firmware state exported. Module has received a WINK command from the network. Other
physical outputs are unaffected. Coprocessor identification. After reset (power-up), the Neuron Chip
waits for the coprocessor's ID message (sent periodically until acknowledged). While waiting, the application remains OFF. This wait status will remain if the hardware identification fails e.g. because the Neuron application does not match the hardware. The module has been switched to the manual override mode. Pressing the service button for more than 30 sec will disable the manual override mode.
Optional Features
Optional features include the terminal protection covers (available in packs of 8) required for wall/ceiling mounting and
the swivel label holders (available in packs of 8) necessary for modules equipped with manual overrides.
Automation and Control Solutions
Honeywell GmbH Böblinger Straβe 17 D-71101 Schönaich Phone: (49) 7031 63701 Fax: (49) 7031 637493 http://europe.hbc.honeywell.com
Subject to change without notice. Printed in Germany Manufacturing location certified to EN1B-0180GE51 R1004B / 95-7666-5
Loading...