Honeywell EXCEL ADT-HRSI User Manual

S Y S T E M
74- 3346
ADT-HRSI
Intelligent Heat Detector
SPECIFICATION DATA
FEATURES
70ft (21.3 meter) spacing
9°C (15°F) per minute rate-of-rise and 57°C (135°F)
fixed temperature alarm threshold
Intelligent detector with integral microprocessor
Non-volatile memory
Automatic device mapping
Electronic addressing
Identification of defective detectors
Twin status LEDs
Standard, relay, and fault isolator mounting bases
Designed and manufactured to ISO 9001 standards
DESCRIPTION
Honeywell's Signature Series Model ADT-HRSI Intelligent Heat Detectors gather analog information from their fixed temperature and/or rate-of-rise heat sensing elements and converts it into digital signals. The detector's on-board microprocessor measures and analyzes these signals. It compares the information to historical readings and time patterns to make an alarm decision. Digital filters remove signal patterns that are not typical of fires. Unwanted alarms are nearly eliminated.
The microprocessor in each detector provides four additional benefits; self-diagnostics and history log, automatic device mapping, stand-alone operation and fast, stable communication.
Self-diagnostics and History Log:
Each Signature Series detector constantly runs self-checks to provide important maintenance information. The results of the self-check are automatically updated and permanently stored in the detector's non-volatile memory. This information is accessible for review any time at the control panel, PC, or by using the SIGA-PRO Signature Program/Service Tool. The information stored in the detector's memory includes:
- Detector serial number, address, and type
- Date of manufacture, hours of operation, and last maintenance date
- Current detector sensitivity values and the extent of environmental compensation
- Original detector sensitivity values upon manufacturing
- Number of recorded alarms and troubles
- Time and date of last alarm
- Analog signal patterns just before the last alarm
- Up to 32 possible trouble codes which may be used to diagnose faults.
In the unlikely event that an unwanted alarm does take place, the history file can be called up to help isolate the problem and prevent it from happening again.
Automatic Device Mapping:
The loop controller learns where each device's serial number address is installed relative to other devices on the circuit. This "mapping" feature provides supervision of each device's installed location to prevent a detector from being reinstalled (after cleaning etc.) in a different location from where it was originally. The history log for the detector at its original location remains relevant and intact.
The Signature Series Data Entry Program also uses the mapping feature. With interactive menus and graphic support, the wired circuits between each device can be examined. Layout or "as-built" drawing information showing wire branches (T-taps), device types and their address are stored on disk for printing hard copy. This takes the "mystery" out of the installation. The preparation of "as-built" drawings is fast and efficient.
EN0C-0746E 0599R0-OB
ADT-HRSI INTELLIGENT HEAT DETECTOR
Device mapping allows the Signature loop controller to discover:
- Unexpected additional device addresses
- Missing device addresses
- Changes to the wiring in the circuit.
Stand-alone Operation:
A decentralized alarm decision by the detector is guaranteed. On-board intelligence permits the detector to operate in stand-alone mode. If loop controller CPU communications fail for more than 4 seconds, all devices on that circuit go into stand-alone mode. The circuit acts like a conventional alarm receiving circuit. Each detector on the circuit continues to collect and analyze information from its surroundings. The ADT-HRSI detectors alarm if the ambient temperature increases 57°C (135°F) or if the temperature increases at a rate exceeding 9°C (15°F) per minute. If the detector is mounted to a relay base, the relay operates.
Fast Stable Communication:
On-board intelligence means less information needs to be sent between the detector and the loop controller. Other than regular supervisory polling response, the detector only needs to communicate with the loop controller when it has something new to report. This provides very fast control panel response time and allows a lower baud rate (speed) to be used for communication on the circuit.
The lower baud rate offers several advantages including:
- Less sensitivity to circuit wire characteristics
- Less sensitivity to noise glitches on the cable
- Less emitted noise from the analog wiring
- Twisted or shielded wiring is not required.
Installation Spacing:
The ADT-HRSI detector is rated for installation at up to 70ft (21.3m) spacing. These detectors may be installed in rooms with an ambient temperature of up to 100°F (38°C).
Status LEDs:
Twin LEDs are visible from any direction. A flashing GREEN LED shows normal system polling from the loop controller. A flashing RED LED means the detector is in alarm state. Both LEDs on steady shows alarm state - stand- alone mode.
Electronic Addressing:
The loop controller electronically addresses each detector, saving valuable time during system commissioning. Setting complicated switches or dials is not required. Each detector has its own unique serial number stored in its "on-board memory". The loop controller identifies each device on the circuit and assigns a "soft" address to that device's serial number. If desired, detectors can be addressed using the SIGA-PRO Signature Program/ Service Tool.
Installation:
Signature series detectors mount to North American 1-gang boxes, 3-1/2 in or 4 in octagonal boxes and to 4 in square electrical boxes 1-1/2 in (38 mm) deep. They also mount to European BESA and 1-gang boxes with 60.3 mm fixing centers.
Honeywell recommends that this detector be installed according to local fire alarm codes.
NOTE:
- This detector will not operate without electrical power. As fires frequently cause power interruption, we suggest you discuss further safeguards with your fire protection specialist.
- This detector will NOT sense fires that start in areas where heat cannot reach the detector. Heat from fires in walls, roofs, or on the opposite side of closed doors may not reach the detector to alarm it.
- The heat sensor in this device only provides a source of information to supplement the information provided by the ionization and photoelectric smoke sensors. The heat sensor by itself does NOT provide life safety protection. Under no circumstances should heat detectors be relied upon as the sole means of fire protection.
Testing and Maintenance:
Each detector automatically identifies when it is defective and the user friendly maintenance program shows the current state of each detector and other pertinent messages. Single detectors may be turned off temporarily, from the control panel. Availability of maintenance features is dependent on the fire alarm system used.
Scheduled maintenance should be planned to meet local codes.
Normal green LED activity is not distracting to building occupants, but can be quickly spotted by a maintenance technician.
Quality and Reliability:
Honeywell detectors are manufactured to strict international ISO 9001 standards. All electronics utilize surface mount technology (SMT) for smaller size and greater immunity to RF noise. A conformal coating is used for humidity and corrosion resistance. All critical contacts are gold plated.
74-3346 2
Loading...
+ 2 hidden pages