Echelon, LON, LONM
trademarks of Echelon Corporation registered in the United
States and other countries.
ARK
, LONT
ALK, LONWORKS
, Neuron, are
3 EN1B-0375GE51 R0308
Page 4
Excel 800 LION
Safety Information
General Safety Information
►
When performing any work (installation, mounting, startup), all instructions given by the manufacturer and in
particular the safety instructions provided in these
Installation and Commissioning Instructions are to be
observed.
►
The Excel 800 LION System (including the CLLIONLC01
Controller Module, I/O modules, manual disconnect
modules, and the auxiliary terminal package) may be
installed and mounted only by authorized and trained
personnel.
►
Rules regarding electrostatic discharge should be
followed.
►
If the Excel 800 LION System is modified in any way,
except by the manufacturer, all warranties concerning
operation and safety are invalidated.
►
Make sure that the local standards and regulations are
observed at all times. Examples of such regulations are
VDE 0800 and VDE 0100 or EN 60204-1 for earth
grounding.
►
Use only accessory equipment which comes from or has
been approved by Honeywell.
►
It is recommended that devices are to be kept at room
temperature for at least 24 hours before applying power.
This is to allow any condensation resulting from low
shipping/storage temperatures to evaporate.
►
The Excel 800 LION System must be installed in such a
manner (e.g., in a lockable cabinet) as to ensure that
uncertified persons have no access to the terminals.
Safety Information as per
EN60730-1:2005-12
Purpose
The Excel 800 LION System is an independently mounted
electronic control system with fixed wiring.
It is used for the purpose of building HVAC control and is
suitable for use only in non-safety controls for installation on
or in appliances.
Pollution degree
Overvoltage
category
Rated impulse
voltage
Automatic action
Software class
Ball-pressure test
temperature
Pollution Degree 2,
suitable for use in residential
controls, commercial controls,
in a clean environment.
Category II
for mains-powered (16A) controls
Category I
for 24 V powered controls
2500 VAC
Type 1.C
(micro-interruption for the relay
outputs)
Class A
75 °C for all housing and plastic
parts
125 °C in the case of devices
applied with voltage-carrying parts
and connectors
EN1B-0375GE51 R0308 4
Electromagnetic
interference
System transformer
Table 1 System data as per EN60730-1:2005-12
Tested at 230 VAC,
with the modules in normal
condition.
Europe: safety isolating
transformers according to
IEC61558-2-6
U.S.A. and Canada: NEC Class-2
transformers
Page 5
Excel 800 LION
System Overview
System Architecture
An Excel 800 LION System consists of the CLLIONLC01 Controller and various I/O modules.
The CLLIONLC01 Controller provides interface connections, which allow connection to external systems.
Auxiliary parts enable special features.
Fig. 1 Excel 800 LION System architecture
Fig. 2 CLLIONLC01 Controller and I/O modules
5 EN1B-0375GE51 R0308
Page 6
Excel 800 LION
ANALOGOVÉ
22
25
CLIOL821A
CLIOP822A
CLIOPR822A
CLIOL822A
CLIOLR822A
CLIOP823A
CLIOL823A
CLIOP824A
CLIOPR824A
CLIOL824A
CLIOLR824A
CLIOPR825A
CLLIONLC01
3-BODOVÝ
I/O Modules
Variants of I/O Modules
There are 2 variants of I/O modules:
• Panel Bus I/O modules with communication via Panel
Bus (light gray housings)
Modules are automatically commissioned (with firmware
download) by the CLLIONLC01 Controller
• LONW
Terminal Sockets
I/O modules are mounted on the appropriate terminal
sockets. Panel Bus I/O modules and LONW
modules use the same terminal sockets.
ORKS
Bus I/O modules (dark gray housings) with
communication via LONW
compatible) for easy integration and use with 3rd-party
controllers
ORKS
(FTT10-A, link power
ORKS
Bus I/O
ANALOGOVÉ
VSTUPY
VÝSTUPY
Color Coding
To distinguish modules and components, the following color
coding is used:
Color Part
Red
Light-gray
Dark-gray
Table 2 Color coding of Excel 800 LION Modules
DIGITÁLNÍ
VSTUPY
All of the user-accessible adjustable
mechanical parts (i.e., bridge connectors
and locking mechanism) and operating
controls (manual overrides, etc.)
Panel Bus I/O modules
LONW
ORKS
Bus I/O modules
DIGITÁLNÍ
VÝSTUPY
VÝSTUP
LonWorks
BUS
MODULY
PANEL
BUS
MODULY
CLIOP821A
Fig. 3 Overview of I/O modules and terminal sockets
Table 4 I/O modules and corresponding terminal sockets
7 EN1B-0375GE51 R0308
Page 8
Excel 800 LION
Auxiliary Parts
Module Type Figure
Corresponding
I/O modules CLIO…
Information
XS812
Manual disconnect
modules
XS812RO
Auxiliary terminal
package
Cross connectors,
short (yellow)
Table 5 Auxiliary parts
Spare Parts
Module Type Figure
Cross connectors, long
(red)
XS814
XS817
XS815
…821
…822
…823
…824
…825
All Excel 800 LION I/O
modules
…824
…825
Corresponding
I/O modules CLIO…
…824
…825
Module allows
disconnection of individual
I/O signals
Module allows
disconnection of individual
I/O signals
For 24 V applications only
2 rows of 7 terminals
connected to each other for
redistributing voltage
Connects 3 relay commons,
required in case of line
voltage and low voltage in
the same I/O module
Information
Connects 6 relay commons
Connector bridge XS816
Swivel label holder XAL10
Table 6 Spare parts
All Excel 800 LION I/O
modules
All Excel 800 LION I/O
modules
Connects CLLIONLC01 and
I/O modules
Can be plugged into socket,
for attaching label
generated by CARE
EN1B-0375GE51 R0308 8
Page 9
Excel 800 LION
Interfaces and Bus Connections
The Excel 800 LION System can be connected to the
following devices and systems:
Panel Bus
• For communication with up to 16 Panel Bus I/O modules
• Polarity-insensitive
LONW
ORKS
Bus
• For communication with other LONW
within the building
• FTT10, link power compatible
• Polarity-insensitive
C-Bus
• For communication with other controllers, e.g., existing
Excel 500 Controllers
HMI
• For connecting an operator interface, e.g., XI582 or a
laptop, e.g., for CARE
Modem
• For connecting a modem or an ISDN terminal adapter
ORKS
Bus devices
Technical Data
System Data
Operating voltage 24 VAC, ± 20 %, 21 … 30 VDC
Max. number of C-Bus
participants
Power consumption Max. 3.57 A
30
(1 CLLIONLC01 Controller
+ 16 I/O modules)
Standards
Protection class IP20
Product standard EMC EN 60730-2-9:2005-10
Testing electrical
components
Certification CE
System transformer
Low-Voltage Device
Safety Assessment
Table 8 Standards
IEC68
The system transformer(s) must
be safety isolating transformers
according to IEC 61558-2-6.
In the U.S.A. and Canada, NEC
Class 2 transformers must be
used.
EN 60730-1:2005-12,
EN 60730-2-9:2005-10
Operational Environment
Ambient operating
temperature
Ambient operating
humidity
Ambient storage
temperature
Ambient storage
humidity
Vibration under
operation
Dust, vibration According to EN60730-1:2005-12
RFI, EMI According to EN60730-1:2005-12
Table 9 Operational environment
0 … 50 °C (32 … 122 °F)
5 … 93 % rel. humidity
(non-condensing)
–20 … 70 °C (–4 … +158 °F)
5 … 95 % rel. humidity
(non-condensing)
0.024” double amplitude
(2 … 30 Hz),
0.6 g (30 … 300 Hz)
Push-in terminals 1.5 mm2
Overvoltage protection All inputs and outputs are
protected against 24 VAC and
40 VDC overvoltage as well as
against short-circuiting.
Calculated lifetime of
weakest component
Table 7 System data
9 EN1B-0375GE51 R0308
MTBF ≥ 13.7 years
Page 10
Excel 800 LION
Planning
Overview
Engineering with CARE
During CARE engineering, the type of I/O modules, terminal
assignment and module configuration are defined
depending on the application.
Planning
In this step, the following has to be defined, if applicable:
• Power supply
• Fusing
• Earth grounding
• Lightning protection
• Panel Bus wiring
• Design of a LONW
• Design of a C-Bus network
• Useful accessories
• Cable selection
ORKS
network
Transformer Selection
Note
In Europe the system transformer(s) must be safety isolating
transformers according to IEC61558-2-6.
In the U.S.A. and Canada, NEC Class-2 transformers must
be used.
Power Consumption
When selecting the appropriate transformer, take into
account the number of individual modules, accessories, and
field devices in determining the total power consumption.
Devices powered
CLLIONLC01 with XI582
(backlight ON) and
with watchdog load
(max. 500 mA)
CLLIONLC01 with XI582
(backlight ON)
but without watchdog load
Power consumption
24 VAC 24 VDC
690 mA 640 mA
190 mA 140 mA
…821 130 mA 80mA
…822 160 mA 90 mA
…823 180 mA 130 mA
…824 140 mA 90 mA
…825 140 mA 90 mA
Table 10 Power consumption of Excel 800 LION System
components depending on power supply
Connectable Power Supplies
Honeywell CRT Series (Europe)
Transformer Primary side Secondary side
CRT 2 220/230 VAC 24 VAC, 50 VA, 2 A
CRT 6 220/230 VAC 24 VAC, 150 VA, 6 A
CRT 12 220/230 VAC 24 VAC, 300 VA, 12 A
Table 11 Honeywell CRT series transformers data
EN1B-0375GE51 R0308
10
Page 11
Excel 800 LION
Honeywell 1450 Series (North America)
• 50/60 Hz AC
• Insulated accessory outputs
• Built-in fuses
• Line transient /surge protection
• AC convenience outlet
• NEC Class-2
Part number
1450 7287
-001 120 VAC 24 VAC, 50 VA
-002 120 VAC
-003 120 VAC
-004 240/220 VAC 24 VAC, 50 VA
-005 240/220 VAC
-006 240/220 VAC
Table 12 Honeywell 1450 series transformers data
Standard Transformers (Europe, North America)
Standard commercially available transformers used to
supply power to Excel 800 LION Systems must fulfill the
following specifications:
Output voltage Impedance AC current
24.5 VAC to 25.5 VAC
24.5 VAC to 25.5 VAC
24.5 VAC to 25.5 VAC
Table 13 Requirements for standard transformers
RIN-APU24 Uninterruptable Power Supply
The RIN-APU24 Uninterruptable Power Supply can be wired
to power Excel 800 LION Systems.
See also RIN-APU24 Uninterruptable Power Supply –
Mounting Instructions (MU1B-0258GE51) for detailed wiring
diagrams.
Primary sideSecondary side
2 x 24 VAC, 40 VA,
and 100 VA from separate
transformer
24 VAC, 100 VA,
and 24 VDC; 600 mA
2 x 24 VAC, 40 VA,
and 100 VA from separate
transformer
24 VAC, 100 VA, and
24 VDC, 600 mA
≤ 1.15 Ω
≤ 0.40 Ω
≤ 0.17 Ω
max. 2 A
max. 6 A
max. 12 A
Power Supply of Field Devices
Depending upon the power consumption of the field devices
used, it is possible to use either a single transformer to
power both the CLLIONLC01 Controller and attached field
devices, or it may be necessary to employ an additional
transformer. See also section "Field Device Cables" on
page 14 and connection examples on page 29.
Fusing Specifications
For connection examples see description of the I/O modules
on page 40 and following.
F1 (Fusing for CLLIONLC01 Controller and I/O Modules)
Rating: 4 A, time-lag fuse (slo-blo)
For example:
Manufacturer: Littlefuse
Type: 218004
F2 (Fusing for Active Field Devices)
Depends upon loads in use.
System Protective Earth Grounding
Excel 800 LION Systems comply with SELV (Safety ExtraLow Voltage). Earth grounding is therefore not
recommended.
However, if compliance with EN60204-1 is required, see
Appendix 1.
Lightning Protection
Please contact your local Honeywell representative for
information on lightning protection.
Panel Bus Topologies
• Up to 16 Panel Bus I/O modules can be controlled by a
single CLLIONLC01 Controller.
• Panel Bus I/O modules must be addressed using the
HEX switch on the terminal socket.
• Maximum distance between controller and Panel Bus
I/O module: 40 m.
• No bus termination
• Polarity-insensitive
11 EN1B-0375GE51 R0308
Page 12
Excel 800 LION
XW882
SHIELD
R
x
D
GND
+5V
E
T
xDYELLO
W
G
RAY
(not used)
B
R
OWN
GREEN
WHITE
1
4
3
2
RJ45 plug with clip at front
RS232 plug
sub-D female
XW884
6
7
8
9
1
2
3
4
5
RxD
RTS
TxD
GND
LONW
The LONW
ORKS
Bus Topologies
ORKS
Bus is a 78-kilobit serial link that uses
transformer isolation so that the bus wiring does not have a
polarity. I.e. it is not important which of the two LONW
ORKS
Bus terminals are connected to each wire of the twisted pair.
The LONW
ORKS
Bus does not need to be shielded on the
controller module side.
The LONW
ORKS
Bus can be wired in daisy chain, star, loop
or any combination thereof as long as the maximum wire
length requirements are met.
Configuration
The recommended configuration is a daisy chain with two
bus terminations. This layout allows for max. LONW
ORKS
Bus lengths, and its simple structure presents the least
number of possible problems, particularly when adding on to
an existing bus.
See also “LONW
ORKS
Mechanisms”, Product Literature no.:
EN0B-0270GE51.
C-Bus Topologies
Via the C-Bus up to 30 C-Bus devices (e.g., controllers, etc.)
can communicate with one another and a PC central. The
C-Bus must be connected via the individual controllers
(open ring).
Note
Star connection is not allowed because uncontrollable line
reflections may occur.
Instead of an Excel 800 LION Controllers, other C-Bus
controllers (e.g., the Excel 500, Excel 100, Excel 50) can
also be connected.
Accessories
Besides the auxiliary parts of Table 5 on page 8, the
following accessories are available.
Preconfigured Connection Cables
Type Connecting
CLLIONLC01
Controller with
XW882 XI582 Operator Interface
XW582
+ XW586
XW884
XI582 Operator Interface –
Adapter cable for Excel
500/600 Controllers
XW885 Laptops
XW585
+ XW586
Laptops –
XW586 Modems
Table 14 Preconfigured connection cables
XW882 Cable Details
1236784
5
+5V
Fig. 5 CLLIONLC01/XI582 cable details
Features
5 m, shielded,
RJ45 plug with clip
0.2 m, shielded,
RJ45 – 9 pin sub-D
3 m, shielded,
RJ45 plug with clip
1.8 m, RJ45 – 9 pin
sub-D
XI582
Fig. 4 C-Bus topology Excel 5000
EN1B-0375GE51 R0308
XW884 Cable Details
RJ45 plug with clip at front
1236784
SHIELD
5
+5V
Fig. 6 CLLIONLC01/Excel 500/600 cable details
12
Page 13
Excel 800 LION
1
5
4
3
2
9
8
7
6
XW885
RxD
GND
RTS
TxD
XW582
SHIELD
R
x
D
GND
+5V
E
TxDYELLOW
BROWN
GREEN
WHITE
1
4
3
2
1
5
4
3
2
9
8
7
6
to XL-Online
XW585
SHIELD
RxD
GND
RTS
TxD
1
5
4
3
2
9
8
7
6
RS232 plug
sub-D male
DCD
DSR
RxD
RTS
TxD
CTS
DTR
GND
XW586
XW885 Cable Details
RJ45 plug with clip at front
12
SHIELD
sub-D male of laptop
RS232 plug
3678
4
5
+5V
Fig. 7 CLLIONLC01/laptop cable details
XW582 Cable Details
to XC5010CXI582
1
6
2
7
3
8
4
9
5
Fig. 8 XW582 cable details
LONW
ORKS
Bus Termination Modules
Type Description
209541 LONW
XAL-Term LONW
ORKS
Bus termination module
ORKS
connection and
termination module, which can be
mounted on DIN rails and in fuse
boxes
Table 15 LONW
ORKS
Bus termination modules
Cable Specifications
Power Supply Cables
When checking the length of the power supply cable, the
connection cables to all I/O modules must be taken into
account.
Max. length
Cross section
3 m (per side of the controller),
see Fig. 32 on page 25
min. 0.75 mm
2
(AWG 18)
XW585 Cable Details
to XC5010C
1
6
2
7
+5V
3
8
4
9
5
Fig. 9 XW585 cable details
XW586 Cable Details
RJ45 plug with clip at front
1236784
SHIELD
5
+5V
Table 16 Power supply cables specification
Panel Bus Cables
Max. length
Cable type
Table 17 Panel Bus cables specification
40 m
twisted pair, e.g., J-Y-Y 2 x 2 x 0.8
Fig. 10 XW586 cable details
13 EN1B-0375GE51 R0308
Page 14
Excel 800 LION
to step change
LONW
ORKS
Bus Cables
Cable type Max. bus length
Belden 85102 (plenum) 2700 m (8900 ft)
Belden 8471 (non-plenum) 2700 m (8900 ft)
Level IV, 22 AWG 1400 m (4600 ft)
JY (St) Y 2 x 2 x 0.8 900 m (3000 ft)
TIA568A Cat. 5 24AWG, twisted pair 900 m (3000 ft)
Table 18 Doubly-terminated bus specifications
Notes
• The cable types listed above are as recommended by
Echelon in their FTT-10A User Guide.
• The cable recommended by Honeywell is the level IV,
22 AWG, solid core, non-shielded cable.
• Belden part numbers are 9H2201504 (plenum) and
9D220150 (non-plenum).
FTT Specification
The FTT specification includes two components that must
be met for proper system operation:
• The distance from each transceiver to all other
transceivers and to the termination must not exceed the
max. node-to-node distance.
• If multiple paths exist, the maximum total wire length is
the total amount of wire used.
Cable type
Max. node-tonode distance
Max. total wire
length
Note
In the event that the limit on the total wire length is
exceeded, the FTT physical layer repeaters (FTT 10A) can
be added to interconnect segments. This increases the
overall length by an amount equal to the original
specification for that cable type and bus type for each
repeater used.
For example, adding repeaters for a doubly-terminated bus
using JY (St) Y 2 x 2 x 0.8 cable increases the maximum
length 900 m (3000 ft) for each repeater.
Field Device Cables
Cross-sectional area
Type of signal
24 VAC power
0…10 V signals 0.081 – 2.08 mm2 (28 – 14 AWG)
Table 20 Cable sizing for connection of field devices
For wiring field devices see page 29.
≤≤≤≤ 100 m (300 ft)
(Fig. 39 on p. 29)
one transformer
1.5 mm2
(16 AWG)
≤≤≤≤ 400 m (1300 ft)
(Fig. 40 on p. 29)
separate
transformers
not allowed for
> 100 m (300 ft)
Belden 85102 500 m (1650 ft) 500 m (1650 ft)
Belden 8471 400 m (1300 ft) 500 m (1650 ft)
Level IV, 22AWG 400 m (1300 ft) 500 m (1650 ft)
JY (St) Y 2 x 2 x 0.8 320 m (1050 ft) 500 m (1650 ft)
TIA568A Cat. 5
Unpredictable reflections on the bus due
in line impedance characteristics!
►
Do not use different wire types or gauges on the same
LONW
ORKS
network segment.
EN1B-0375GE51 R0308
14
Page 15
Excel 800 LION
C-Bus Cables
Note
Observe national regulations for C-Bus cables!
• For Europe, only shielded cable is permitted.
• For the U.S., shielded or unshielded cable can be used.
Cable type Description Recommended for
J-Y-(ST)Y
2 x 2 x 0.8
A-Y-(ST)Y
2 x 2 x 0.8
AK 3702
AK 3740A shielded
Belden 9842 twisted pair Europe, US also possible
Belden 9841 shielded US
AK 3702
AK 3740A shielded
Table 21 C-Bus cable types
Maximum Cable Length
The maximum C-Bus cable length is 1200 m (4000 ft).
See section "C-Bus Topologies" on page 12.
shielded,
twisted pair
shielded,
twisted pair
unshielded,
twisted pair
unshielded,
twisted pair
Europe, inside cabinet
Europe, outside cabinet
US
not approved for Europe
US (low-cost)
not approved for Europe
US
not approved for Europe
US (low-cost)
not approved for Europe
15 EN1B-0375GE51 R0308
Page 16
Excel 800 LION
94.1 -/+ 0.
3
2
8
30.
6
4
Dimensions
Controller Module
144 -/+ 0.3
Fig. 11 Controller module, outside dimensions (in mm)
92.75 -/+ 0.3
28
32
I/O Modules
Wiring
channel
69
Wiring
channel
Fig. 12 I/O modules (example shows manual overrides), including terminal socket, outside dimensions (in mm)
XS814 Auxiliary Terminal Sockets
(optional)
89.5 -/+ 0.3
LOCK
1
EN1B-0375GE51 R0308
16
Page 17
Excel 800 LION
1234567
8
0
!
AAAAAAA
A
100
LOC
K
S
2
N
D
I/A
O
252
6
12345
6
--1--
0
--AUT
O
!
LOC
K
S1S
2
2
1
2
2
2
3
1444245434642
5
1
3
1
2
113
1
3
2
3
3
4
1
4
2
4
3
5
1
5
2
5
3
6
1
6
2
6
1
6
2
636
3
5
6
6
LOCKLOC
K
1:ABCDFERTAQWESDERT
1
2:ABCDFERTAQWESDERT
2
3:ABCDFERTAQWESDERT
3
4:ABCDFERTAQWESDERT
4
5:ABCDFERTAQWESDERT
5
6:ABCDFERTAQWESDERT
6
7:ABCDFERTAQWESDERT
7
8:ABCDFERTAQWESDERT
8
1234567
8
!
N
D
I/A
O
252
6
252
6
123456789101112
!
C-Bus
S1S
2
Modem
I/O BusRxTx
Power
/
Alarm
C-Bus
out
C-BUSRESETPC/HM
I
1
2
3
GND
B
I
13141516171819202122232
4
123456789101112
PANEL
PANEL
max. 10
LonWorks
max. 10
LonWorks
Mounting/Dismounting Modules
WARNING
Risk of electric shock or equipment damage!
►
Do not touch any live parts in the cabinet.
►
Disconnect the power supply before you start to install
the Excel 800 LION System.
More than one disconnect switch may be required to deenergize the system.
►
Do not reconnect the power supply until you have
completed the installation.
Note
The terminal socket of each I/O module can be mounted
and wired before inserting and locking the corresponding
electronic module.
• When using both Panel Bus and LONW
modules in an Excel 800 LION System, group both
Panel Bus modules (light gray) and LONW
modules (dark gray), e.g., on different rails.
• Up to 10 Panel Bus I/O modules can be mounted to one
side of the controller. In total, up to 16 Panel Bus
I/O modules can be mounted to one controller.
• The CLLIONLC01 Controller Module is mounted on the
DIN rail in the same way as a terminal socket.
Angle the terminal socket at the upper edge of the DIN
rail until it snaps in.
►
Swing the terminal socket down and apply gentle force
until it snaps into position with an audible "click".
►
Position controller module and terminal sockets flush with
one another along the rail.
►
If desired, mount stoppers at the ends of the rail to
prevent sliding.
Connecting Sockets
Controller and terminal sockets on the same DIN rail can be
connected mechanically and electrically with bridge
connectors.
Controller and terminal sockets on different DIN rails must
be connected using cables, see Fig. 13 and page 24.
NOTICE
Risk of malfunction!
►
Wire Panel Bus I/O modules and LONW
ORKS
Bus
I/O modules separately.
►
When using both Panel Bus and LONW
I/O modules in an Excel 800 LION System, LONW
ORKS
Bus
ORKS
Bus I/O modules must be connected to the controller via
LON terminals 11 … 14.
Position the bridge connector on terminals 71 … 74 of the
right hand terminal socket or controller and on terminals
75 … 78 of the left hand terminal socket or controller. Then
press the bridge connector down.
Fig. 16 Mounting terminal sockets
Note
Take care to not bend the Omega clamp, which serves to
establish the electrical contact with the DIN rail and which
located on the back of the terminal socket.
Fig. 17 Connecting terminal sockets with bridge
connector
Notes
• Bridge connectors transmit both communication signals
and power supply between modules.
• Removing bridge connectors will interrupt the
transmission of both communication signals and power
supply between the modules.
EN1B-0375GE51 R0308
18
Page 19
Excel 800 LION
Dismounting Sockets
Disconnecting Sockets
Release all bridge connectors before removing the controller
module and/or the terminal sockets from the DIN rail.
►
Press down at the same time both the gray side wings
next to the red button and then pull the bridge connector
out of the module.
Fig. 18 Releasing bridge connectors
Mounting/Dismounting Electronic Modules
Mounting Electronic Modules
Note
Electronic modules can be removed from the socket or
inserted into the sockets without switching off the power
supply. The behavior of connected field devices must be
taken into consideration.
►
Make sure that terminal socket und I/O module match,
see Table 4 on page 7.
►
Make sure that the red locking mechanism is in the open,
i.e., left, position.
►
Gently push the electronic module onto the terminal
socket until snug.
Dismounting Controller/Terminal Sockets
►
Insert a screwdriver into the latch on the underside of the
module and lever the red latch 2–3 mm downwards. The
module can then be swung away from the rail.
Fig. 19 Releasing latch
Fig. 20 Inserting the electronic module
►
Lock the red locking mechanism by sliding it to the right.
Fig. 21 Locking the electronic module
Note
The red locking mechanism will not close if the electronic
module is not properly mounted.
19 EN1B-0375GE51 R0308
Page 20
Excel 800 LION
Never use the XS812RO Manual Disconnect Module with
Dismounting Electronic Modules
Note
Electronic modules can be removed from the socket or
inserted into the sockets without switching off the power
supply. The behavior of connected field devices must be
taken into consideration.
►
Open the red locking mechanism by sliding it to the left
and then gently pull the electronic module out of the
terminal socket.
Fig. 22 Dismounting the electronic module
Mounting/Dismounting Manual Disconnect
Modules
XS812 and XS812RO Manual Disconnect Modules are
mounted on the terminal socket appropriate for the
electronic module, see Table 4 on page 7. The electronic
module is mounted onto the manual disconnect module.
WARNING
Risk of electric shock or equipment damage!
The XS812RO Manual Disconnect Module is designed
for 24 V applications only!
►
line voltage.
Mounting Manual Disconnect Modules
►
Make sure that manual disconnect module, electronic
module and terminal socket match, see Table 4 on
page 7.
►
Make sure that the red locking mechanism is in the open,
i.e., left, position.
►
Gently push the manual disconnect module onto the
terminal socket until snug.
►
Lock the red locking mechanism by sliding it to the right.
EN1B-0375GE51 R0308
Fig. 23 Mounting the manual disconnect modules
20
Page 21
Excel 800 LION
Operating the Individual Switches
►
Use a screwdriver to open/close the appropriate
disconnector switches of the manual disconnect
modules.
Fig. 24 Operating the disconnector switches
Dismounting Manual Disconnect Modules
►
Open the red lock mechanism by sliding it to the left and
then gently pull the electronic module out of the terminal
socket.
Mounting/Dismounting Auxiliary Terminal
Packages
Mounting Auxiliary Terminal Packages
►
Push the auxiliary terminal package onto the grooves of
the corresponding terminal socket.
Fig. 25 Mounting the auxiliary terminal package onto the
terminal socket
Dismounting Auxiliary Terminal Packages
►
Push down the catch of the auxiliary terminal package
and pull it out of the grooves of the terminal socket.
Fig. 26 Dismounting the auxiliary terminal package from
the terminal socket
21 EN1B-0375GE51 R0308
Page 22
Excel 800 LION
Mounting/Dismounting Cross Connectors
Note
The long cross connector (incl. in the scope of the delivery)
can be mounted to the XS824-25, as required (see Fig. 28).
It can be dismounted (see Fig. 27) and, if desired, replaced
with one or two short connectors (optional accessory, see
Table 5 on page 8).
►
Insert a screwdriver on one end of the cross connector
and swivel it to the right and to the left.
►
Insert a screwdriver on the other end of the cross
connecter and swivel it to the right and to left until the
cross connector is released.
►
If desired, insert another cross connector.
Mounting/Dismounting Swivel Label
Holders
Note
A swivel label holder is included in the scope of delivery of
each module.
Mounting Swivel Label Holders
►
Snap the swivel label holder onto the terminal socket
hinges.
►
Apply self-adhesive labels to the holders.
Fig. 27 Dismounting the cross connectors (long cross
connector shown here)
Fig. 28 Mounting the cross connectors (short cross
connector shown here)
Fig. 29 Mounting the swivel label holder
Dismounting Swivel Label Holders
►
Press the hinges together and remove the swivel label
holder.
EN1B-0375GE51 R0308
22
Page 23
Excel 800 LION
to or removing connections from terminals of controller or
Wiring and Setting Up the System
General Safety Considerations
• When connecting the CLLIONLC01 Controller Module or
Excel 800 LION I/O modules, both VDE, National Electric
Code (NEC) or equivalent, and any local regulations
concerning grounding and zero voltage must be
observed.
• Electrical work should be carried out by a qualified
electrician.
• The electrical connections must be made at the terminal
blocks. The corresponding connection diagrams are
located on the individual controller module and
I/O modules.
• For Europe only: To comply with CE requirements,
devices with a voltage in the range of 50 ... 1000 VAC or
75 ... 1500 VDC, which are not provided with a supply
cord and plug or with other means for disconnection from
the supply having a contact separation of at least 3 mm
in all poles, must have the means for disconnection
incorporated in the fixed wiring.
WARNING
Risk of electric shock or equipment damage!
►
Do not touch any live parts in the cabinet.
►
Disconnect the power supply before making connections
Wiring Push-in Terminals
The Excel 800 LION System is equipped with push-in
terminals for easy wiring.
For correct wiring, cables must fulfill the following
specifications according to IEC664-1 / VDE 0110 (4.97):
Max. plug gauge
Solid conductor H05/07) V-U
Stranded conductor H05(07) V-K
Stranded conductor with wire end
Do not use spare terminals as wiring support points.
►
Do not reconnect the power supply until you have
completed the installation.
►
Observe precautions for handling electrostatic sensitive
devices.
23 EN1B-0375GE51 R0308
Page 24
Excel 800 LION
C
A
1
2
TRANSFORMER 2
Connecting Power Supply
The Excel 800 LION System can be powered by one or
more external transformers.
Note
The maximum length for the power supply cable from a
transformer is 3 m. This also includes the length of the
modules and the connection cables between the rails.
Referring to Fig. 30 the following conditions must be fulfilled:
A + B ≤ 3 m and A + C ≤ 3 m
Single or the First Transformer
►
Connect the transformer to terminals 1 and 2 of the
CLLIONLC01 Controller.
LION
I/O MODULE
LION
I/O MODULE
B
CLLIONLC01
LION
I/O MODULE
Additional Transformer
►
Connect the additional transformer in a second room or
cabinet to terminals 73 and 74 or 77 and 78 of an
I/O module.
71
LION
72
73
I/O MODULE
74
LION
I/O MODULE
MAX. 3 m
Fig. 31 Wiring the power supply from a second
transformer
NOTICE
Equipment damage!
►
Do not use bridge connectors to connect modules
powered by different transformers.
►
When connecting modules powered by different
transformers using cables, be sure to not connect
terminals 73 and 77.
Fig. 30 Wiring power supply from the (first) transformer to
the controller module
EN1B-0375GE51 R0308
24
Page 25
Excel 800 LION
CLLIONLC01
2
71
LION
I/O MODULE
75
76
77
78
LION
I/O MODULE
75
76
77
78
I/O MODULE
M
A
X
.
4
0
m
24 V0
74
LION PANEL
I/O MODULE
LION PANEL
I/O MODULE
77
78
LION PANEL
I/O MODULE
76
77
78
75
76
Connecting Single Bus Controller Systems
This section describes how to connect a controller system
which uses Panel Bus I/O modules only or LONW
Bus I/O modules only.
Controller and I/O Modules on a Single Rail
►
Connect controller and I/O modules using the bridge
connectors.
This provides power supply and communication connection.
No further wiring is necessary.
Controller and I/O Modules on Several Rails in a
Single Cabinet
The rails of a controller system are connected in series.
►
Connect the rail ends as follows:
– Power supply
via power supply terminals 73, 74 or 77, 78
– Communication
via communication terminals 71, 72 or 75, 76
LION
72
73
I/O MODULE
74
71
LION
72
73
I/O MODULE
74
LION
I/O MODULE
ORKS
Panel Bus I/O Modules in Separate Rooms
In this scenario, communication and reference voltage
(24 V0) must be connected between the rooms.
►
Connect the last module of room 1 to the first module of
room 2:
– Reference voltage
via power supply terminals 74 or 78
terminals 73 and 77 must not be connected
– Communication
via communication terminals 71, 72 or 75, 76
ROOM 1
71
LION PANEL
72
I/O MODULE
7374
CLLIONLC01
1 2
75
ROOM 2
LION PANEL
I/O MODULE
73
71
LION
72
73
I/O MODULE
74
71
LION
72
73
74
1
Fig. 32 Wiring the power supply and the communication
lines to the I/O modules
Maximum Power Cable Length
The maximum length for power supply cable per side is 3 m.
This also includes the connection cables between the rails,
the lengths of the modules, and the cable from the
transformer.
Fig. 33 Wiring the Panel Bus I/O modules in separate
rooms
Maximum Cable Length
The maximum cable length for connecting room 1 and
room 2 is 40 m.
25 EN1B-0375GE51 R0308
Page 26
Excel 800 LION
LION LonWorks
LION LonWorks
74
LION LonWorks
LION LonWorks
LION LonWorks
78
75
76
77
78
76
77
LonWorks Bus I/O Modules in Separate Rooms
In this scenario, only communication lines must be
connected between the rooms.
►
Connect the last module of room 1 to the first module of
room 2:
– via communication terminals 71, 72 or 75, 76
ROOM 1
7172
I/O MODULE
7374
CLLIONLC01
1 2
I/O MODULE
75
ROOM 2
I/O MODULE
73
I/O MODULE
I/O MODULE
Connecting Panel Bus and LONW
ORKS
Bus
Mixed Controller Systems
I/O Modules with Each Other
For connecting the I/O modules with each other, proceed as
described for single bus controller systems on page 24.
I/O Modules to the Controller
Panel Bus I/O Modules
►
Connect communication terminals 71 …74 or 75… 78 of
Panel Bus I/O modules to communication terminals
71 …74 or 75… 78 of the controller module using either
– Bridge connectors
for flush mounting on a single DIN rail or
– Cables
for separate mounting,
e.g., on multiple rails, separate cabinets, etc.
LONW
ORKS
Bus I/O Modules
►
Connect communication terminals 71 … 74 or 75 … 78 of
LONW
ORKS
Bus I/O modules to LONW
11 … 14 of the controller module using cables.
ORKS
terminals
Fig. 34 Wiring the LONW
ORKS
Bus I/O modules in
separate rooms
Maximum Cable Length
For maximum cable lengths and cable specifications of the
communication lines, see Table 18 and Table 19 on
page 14.
EN1B-0375GE51 R0308
26
Page 27
Excel 800 LION
3
1
4
2
77
75
76
78
3
1
4
2
77
75
76
78
Panel Bus I/O modulesPanel Bus I/O modules
71
72
73
74
71
75
72
76
73
77
74
78
71
75
72
76
73
77
74
78
75
76
77
78
XF...
LonWorks Bus I/O modules
71
72
73
74
71
75
72
76
73
77
74
78
71
75
72
76
73
77
74
78
75
76
77
78
Fig. 35 Mixed bus system – correct wiring
Panel Bus I/O modulesLonWorks Bus modules
71
72
73
74
71
75
72
76
73
77
74
78
71
75
72
76
73
77
74
78
75
76
77
78
71
72
73
74
CLLIONLC01
11
12
13
14
71
72
CLLIONLC01
7374
75
76
77
78
71
72
73
74
71
75
72
76
73
77
74
78
71
75
72
76
73
77
74
78
75
767778
71
72
73
74
71
75
72
76
73
77
74
78
71
75
72
76
73
77
74
78
Fig. 36 Mixed bus system – incorrect wiring
1112
13
14
27 EN1B-0375GE51 R0308
Page 28
Excel 800 LION
Setting Address of Panel Bus I/O Modules
During CARE engineering, each Panel Bus I/O module is
assigned its own unique address. For the sake of clarity for
maintenance personnel, it is recommended that you
address the Panel Bus I/O modules in ascending order
0 through F.
Hex switch
Address
Hex switch
Address
Table 23 HEX switch settings and addresses
►
Use the rotary HEX switch to set the address to the one
already defined in CARE.
0 1 2 3 4 5 6 7
01 02 03 04 05 06 07 08
8 9 A B C D E F
09 10 11 12 13 14 15 16
4
LOCK
4
Setting I/O Bus Switch
►
Set the I/O Bus switch S2 of the CLLIONLC01 Controller
Module depending on the modules connected to
terminals 71 … 78 and the desired communication as
follows:
Communication S2 setting Terminals
LONW
ORKS
Bus
only
Panel Bus and
LONW
ORKS
Bus
Table 24 I/O Bus switch settings
LON 71 … 74 LONW
75 … 78 LONW
11 … 14 LONW
ORKS
ORKS
ORKS
Panel 71 … 74 Panel Bus
75 … 78 Panel Bus
11 … 14 LONW
ORKS
Bus
Bus
Bus
Bus
Fig. 37 HEX switch location
Notes
• If the HEX switch is changed, the Panel Bus I/O module
will revert to its default configuration.
• With LONW
ORKS
Bus I/O modules, the HEX switch is
without function.
Fig. 38 S2 I/O Bus switch
EN1B-0375GE51 R0308
28
Page 29
Excel 800 LION
1...8
11...189GND
Y
24V
(0...10 Vdc)
max.
1...8
GND
Y
24V
24 V0
230 V~
11...18
Connecting Field Devices
Connecting Field Devices with Power Supply
Depending on the distance from the controller, field devices
can be supplied by the controller or need a separate
transformer, see Table 20 on page 14.
For fusing see section "Fusing Specifications" on page 11.
Example 1: Power Supply via Controller
• 24 V actuator connected to an analog output module
• Less than 100 m away from the controller
F2
F1
CLLIONLC01822
1
2
Y (0...10 Vdc)
max. 100 m
230 V~
24 V~
24 V0
Fig. 39 Power supply of field devices via I/O module
Example 2: Power Supply via Separate Transformer
• 24 V actuator connected to an analog output module
• 100 … 400 m away from the controller
~
Cabling Field Devices
Cable Routing
Route low-voltage signal and output cables separately from
mains cables.
Cable Minimum distance
Shielded 10 mm (0.4 in.)
Unshielded 100 mm (4 in.)
Table 25 Minimum distances to power mains cables
All low-voltage signal and output cables should be regarded
as communication circuits in accordance with VDE 0100
and VDE 0800 (or NEC or other equivalent).
Cable Shielding
• If the general guidelines for cable routing are observed, it
is not necessary to shield field device signal and power
supply cables.
• If, for whatever reason, the routing guidelines cannot be
observed, the field device signal and power supply
cables must be shielded.
– Shielding of cables leading to field devices must be
grounded only at the cabinet end.
– The shield must not be terminated at the CLLIONLC01
Controller Module.
24 V~
F2
230 V~
24 V~
24 V0
F1
CLLIONLC01
1
2
822
Y
400 m
Fig. 40 Power supply of field devices via a separate
transformer
~
29 EN1B-0375GE51 R0308
Page 30
Excel 800 LION
Commissioning I/O Modules
Commissioning Panel Bus I/O Modules
During CARE engineering, the HEX address of the Panel
I/O modules is defined.
Note
With Panel Bus I/O modules it is essential that the HEX
switch be set to the address assigned by CARE.
The CLLIONLC01 Controller automatically commissions all
Panel Bus I/O modules.
Commissioning LONW
Commissioning is done using CARE.
ORKS
Bus I/O Modules
Updating Software
CARE is used to update the CLLIONLC01 Controller.
Software with Panel Bus I/O Modules
The CLLIONLC01 Controller automatically updates all Panel
Bus I/O modules.
Software with LONW
You can update the LONW
EXCELON.
ORKS
Bus I/O Modules
ORKS
I/O modules using CARE or
EN1B-0375GE51 R0308
30
Page 31
Excel 800 LION
to or removing connections from terminals of controller or
Connecting to External Systems or Interfaces
WARNING
Risk of electric shock or equipment damage!
►
Do not touch any live parts in the cabinet!
►
Disconnect the power supply before making connections
I/O modules.
►
Do not reconnect the power supply until you have
completed installation.
►
Observe the rules regarding electrostatic discharge.
Connecting via LONW
Via a LONW
connected to other controller systems, to additional
LONW
LONW
Depending upon the configuration, either 1 or 2 termination
modules are required for terminating a LONW
FTT devices on it.
The following 2 different LONW
available for this purpose:
• 209541 LONW
• XAL-Term LONW
Module, which can be mounted on DIN rails and in fuse
boxes
ORKS
Bus, an Excel 800 LION System can be
ORKS
Bus I/O modules, or to laptops and HMIs.
ORKS
Bus Termination
ORKS
ORKS
ORKS
Bus
ORKS
bus with
ORKS
termination units are
Bus Termination Module and
Connection and Termination
Termination Examples
Brown
Orange
Yellow
Brown
Orange
Yellow
Fig. 41 Termination Module 209541 connections for a
doubly-terminated FTT network
Fig. 42 Termination Module 209541 connections for a
singly-terminated FTT network
31 EN1B-0375GE51 R0308
Fig. 43 XAL-Term Connection and Termination Module
Page 32
Excel 800 LION
Connecting via C-Bus
Via C-Bus an Excel 800 LION Controller can be connected
to other controller systems to form a network.
Connecting to the Controller
►
Connect the C-Bus to the CLLIONLC01 Controller
Module as follows:
– Input to C-Bus terminals 8 and 9
– Output to C-Bus terminals 5 and 6
– Do not connect the C-Bus to the cabinet earth or any
other earth ground points
Setting the C-Bus Termination Switch
►
Set the C-Bus termination switch S1 appropriately.
Fig. 44 C-Bus termination switch S1
Switch
setting S1
9.6k all
76k mid Up to 76800 baud without bus termination
76k end Up to 76800 baud with bus termination
In principle, data transmitting cables should be shielded in
case of RFI.
►
On the controller side, connect the shield to terminals 7
and 10.
►
On the side of the device, connect the shield to the
respective terminals.
Do not connect it to the cabinet ground or any other
ground points.
Baud rate
Up to 9600 baud (default setting)
Connecting HMIs or Laptops
Laptops or HMIs, e.g., XI582, can either be connected via
the HMI interface of the CLLIONLC01 Controller Module or
via the LONW
ORKS
interface.
Connecting the XI582 Operator Interface
►
Connect the XI582 Operator Interface to the HMI
interface or LONW
Controller Module by means of
– the XW882 cable or
– the XW582 cable connected with an XW586 cable.
For mounting details, refer to the XI582 Installation
Instructions (Product Literature no.: EN2B-0126GE51).
For cable details, refer to section "Preconfigured Connection
Cables" on page 12.
ORKS
interface of the CLLIONLC01
Connecting Laptops (XL-Online/CARE)
►
Connect a laptop (on which e.g., XL-Online or CARE has
been installed) to the HMI interface or LONW
interface of the CLLIONLC01 Controller Module by
means of
– the XW885 cable or
– the XW585 cable connected with an XW586 Cable.
For cable details, refer to section "Preconfigured Connection
Cables" on page 12.
Connecting Modems
An Excel 800 LION System can be connected to a modem
or an ISDN terminal adapter via the Modem Interface of the
CLLIONLC01 Controller Module by means of the XW786
cable.
►
Connect the RJ45 female connector of the XW586 cable
to the modem interface of the CLLIONLC01 Controller.
►
Connect the 9-pin sub-D connector to the modem.
For cable details, refer to section "Preconfigured Connection
Cables" on page 12.
Refer to Appendix 2 for details regarding remote
communication.
ORKS
EN1B-0375GE51 R0308
32
Page 33
Excel 800 LION
Description of the CLLIONLC01
Overview
Controller Module
Fig. 45 Connections to the CLLIONLC01 Controller
Fig. 46 CLLIONLC01 Controller Module front details
Legend
1 Power supply for I/O modules
2 I/O Bus communication terminals
3 LONW
4 LONW
5 LONW
6 C-Bus Tx LED
7 C-Bus Rx LED
8 Reset button
9 HMI interface and LEDs
10 Alarm LED
11 Power LED
12 Power supply terminals
13 Alarm/watchdog outputs
14 Modem interface and LEDs
15 S2 I/O Bus switch
16 S1 C-Bus termination switch
17 C-Bus terminals
18 LONW
ORKS
interface
ORKS
service button
ORKS
service LED
ORKS
terminals
33 EN1B-0375GE51 R0308
Page 34
Excel 800 LION
2
3
4
7
8
1
7
7
7
6
7
5
2
4
V
~
2
4
V
~
-
+
2
4
~
0
2
4
~
0
N
C
ELD
*
Do
g
y
CLLIONLC01 Terminals
COM
71
A
COM
72
B
24
73
V~
24
74
V~0
87 6543 21
LON
11
1
LON
12
2
LON
1396
1
LON
14107
2
85
C+C
C-C
SHIELDSHI
*Watch
Fig. 47 Terminal assignment and internal connections of
the CLLIONLC01 Controller Module
Terminal
71, 75 COM a
72, 76 COM b
Signal Comment
2-wire communication bus
(LON/Panel Bus)
2-wire communication bus
(LON/Panel Bus)
73, 77 24 V~ Power supply for I/O modules
74, 78 24 V~0 Power supply for I/O modules
1 24 V~ Power supply from transformer
2 24 V~0 Power supply from transformer
3 24 V~0 Alarm/watchdog output
• An RJ45 socket serving as an interface
to connect laptops or HMIs to the LONW
• LONW
Fig. 48 LONW
LONW
Pin Signal type
1 Connection to LONW
2 Connection to LONW
3 … 8 Not used
Table 28 Signals of LONW
LONW
The CLLIONLC01 Controller Module is equipped with a
LONW
Service LED (status: yellow/OFF).
ORKS
terminals 11, 12, 13, and 14
to connect LONW
LONW
ORKS
devices to the CLLIONLC01 Controller or
other LONW
ORKS
ORKS
ORKS
ORKS
ORKS
Interface Signals on RJ45 Socket
Service LED and Button
service button and corresponding LONW
ORKS
Bus I/O modules or other
controllers.
interface and LONW
ORKS
ORKS
ORKS
interface
ORKS
ORKS
Bus
Bus
Bus
terminals
ORKS
LON
1
2
Fig. 49 LONW
ORKS
service button (1) and service LED (2)
See also section "Troubleshooting" on page 68.
EN1B-0375GE51 R0308
34
Page 35
Excel 800 LION
C-Bus Tx LED and Rx LED
The CLLIONLC01 Controller Module is equipped with a Tx
LED (status: yellow/OFF) and an Rx LED (status:
yellow/OFF).
C-Bus
1
2
Fig. 50 C-Bus Tx LED (1) and Rx LED (2)
C-Bus LEDs
Tx (1)
flickering
Rx (2)
flickering
The controller is sending data onto the
C-Bus
The controller is receiving data from the
C-Bus
program changes) to FLASH memory.
Table 29 Controller C-Bus LEDs
Reset Button
The CLLIONLC01 Controller Module is equipped with a
reset button.
RESET
1
Fig. 51 Reset button (1)
Pushing the reset button (1), e.g. using a paperclip, will
cause the CLLIONLC01 Controller Module to reset.
Note
In the event of a reset, all non-volatile memory contents are
permanently deleted, though the clock will not be set to
zero.
In order to avoid problems, we therefore recommend that
you always save your application changes (e.g., time
35 EN1B-0375GE51 R0308
Page 36
Excel 800 LION
HMI Interface
The controller module is equipped with an HMI Interface for
the connection of HMIs, e.g., XI582 Operator Interface or a
laptop (with XL-Online/CARE).
Fig. 52 HMI interface, Tx LED (1) and Rx LED (2)
HMI interface LEDs on RJ45 socket
Tx (1)
flickering
Rx (2)
flickering
Table 30 HMI interface LEDs
HMI interface Signals on RJ45 socket
Pin Signal type
1 2 Receive
3 Transmit
4 5 Signal ground
6 7 5 V
8 -
Table 31 Signals of the HMI interface
The controller is transmitting data to the HMI
The controller is receiving data from the HMI
Alarm and Power LEDs
The CLLIONLC01 Controller Module is equipped with an
alarm LED and a power LED.
Fig. 53 Alarm LED (1) and power LED (2)
Alarm LED (1, red)
Off
On
Flashing
Table 32 Controller alarm LED
Normal operation
Watchdog alarm output is powered
• The controller has encountered a
hardware problem
• The application has a fault
• The controller has been powered up
without an application or the operator has
manually stopped the application,
e.g., using XL-Online.
In this case, the LED will light up
13 minutes after power-up without
application
The watchdog alarm output has not yet been
powered, although the controller has
encountered a problem.
The controller performs a warm start.
If problem persists, the LED will become lit
constantly, see above.
See section "Troubleshooting" on page 68.
NOTICE
Equipment damage!
►
Make sure that the controller is not connected to earth
ground.
►
If nonetheless earth grounding is required, make sure
that only terminal 2 is connected to earth ground.
Terminal 1 must not be connected to earth ground. See
also Appendix 1.
EN1B-0375GE51 R0308
36
Page 37
Excel 800 LION
Power LED (2, green)
On
Flashing
Goes out
briefly
Table 33 Controller power LED
Normal operation
One or more of the internal voltage
supplies are outside of the permissible
ranges.
The controller stops operation.
►
Check wiring or see section "Troubleshooting" on page 68.
• The operator has activated the reset
button
• The controller is performing a warm
start
Watchdog
Watchdog status
Status Signal on terminal 4
Failure (= alarm) 24 V
Normal operation 0 V
Table 34 Watchdog status 4
Modem Interface
The controller module is equipped with a modem interface
for the connection of a modem or an ISDN terminal adapter.
Fig. 54 Modem interface, Tx LED (1) and Rx LED (2)
Modem LEDs on RJ45 socket
Tx (1) flickering
Rx (2) flickering
The controller is transmitting data to the
HMI, e.g., XI582
The controller is receiving data from the
HMI
Permissible Load of Normally Closed Contact
(Terminal 4)
Max. load
Per normally
closed
contact
(terminal 4)
Table 35 Permissible load of terminal 4
19…29 VAC
current at cos φ≥ 0.95: 0.5 A,
current at cos φ≥ 0.6: 0.5 A
19…29 VDC
0.5 A resistive or inductive
Min.
current
10 mA
Table 36 HMI interface LEDs
Modem Signals on RJ45 socket
Pin Signal type
1 Carrier detect
2 Receive
3 Transmit
4 Data terminal ready
5 Signal ground
6 7 5 V
8 Clear to send
Table 37 Signals of the modem interface
Communication Speed
Default setting: 9600 baud
The communication speed can be set to as high as
38.4 Kbaud, e.g., using the XI852 HMI or a Laptop with XLOnline, see Appendix 2.
37 EN1B-0375GE51 R0308
Page 38
Excel 800 LION
I/O Bus Switch S2
The CLLIONLC01 Controller Module features a 2-position
I/O Bus switch S2.
I/O Bus switch S2 must be set in accordance with the kind
of I/O modules connected to communication terminals
71, 72 and 75, 76 of the controller module.
Terminals 71, 72 and 75, 76 must be all connected either to
Panel Bus I/O modules or to LONW
The default setting is Panel.
Fig. 55 I/O Bus switch S2
Communication S2 setting
LONW
ORKS
Bus only LON
Panel Bus and LONW
LONW
ORKS BUS
terminals 11 …. 14 of the controller
Panel Bus connected to terminals 71, 72
or 75, 76 of the controller
Table 38 I/O Bus switch settings
ORKS
Bus
modules connected to
ORKS
Bus I/O modules.
Panel
Panel
C-Bus Termination Switch S1
The CLLIONLC01 Controller Module features a 3-position
C-Bus termination switch S1.
This switch must be set in accordance with the given C-Bus
configuration.
Fig. 56 C-Bus termination switch
Switch
setting S1
9.6k all
76k mid Up to 76800 baud without bus termination
76k end
Table 39 CLLIONLC01 C-Bus termination switch S1
Baud rate
Up to 9600 baud (default setting)
Up to 76800 baud with bus termination
controller at the end of the C-Bus
settings
Memory
Memory Size Usage
EN1B-0375GE51 R0308
SRAM 512 KB For controller application,
modem trend and firmware
RACL application: 128 KB
Total application: 192 KB
Flash 2 MB Firmware (1 MB) and
application (1 MB) storage
EPROM 128 KB For bootstrap loader
Table 40 CLLIONLC01 memory
Note
The CLLIONLC01 Controller Module does not contain a
battery. RAM (data and realtime clocktime) is buffered for
3 days by a super capacitor.
38
Page 39
Excel 800 LION
39 EN1B-0375GE51 R0308
Page 40
Excel 800 LION
Description of the I/O Modules
Common Features
Switches located on the Terminal Socket
Feature Function
Service
button S1
Hex switch
S2
LEDs located on the I/O Module
Feature Function
Service LED
(yellow)
Power LED
(green)
For the location of these elements, see figures of the
relative modules.
• LED test, see section "Troubleshooting"
on page 68
• LONW
• Module addressing for Panel Bus
• Service information, see section
• Information on power supply, see
ORKS
service button functionality
for LONW
I/O modules
"Troubleshooting" on page 68
section "Troubleshooting" on page 68
ORKS
Bus I/O modules
Analog Input Modules
Types of Analog Input Modules, Terminal Socket
Type Description Housing
CLIOP821A Panel Bus analog input module Light gray
CLIOL821A LONW
XS821-822 Terminal socket Light gray
Table 41 Excel 800 LION Analog Input Modules
Features
• 8 analog inputs
• Sensor-break and short-circuit detection, see section
"Troubleshooting" on page 68.
ORKS
module
Bus analog input
Dark gray
EN1B-0375GE51 R0308
Fig. 57 CLIOP821A Analog Input Module with terminal
socket
Legend
1 Service button S1
2 Hex switch S2
3 Service LED
4 Power LED
Functionality of service LED and power LED: see Table 74
to Table 76 on page 72 and following.
40
Page 41
Excel 800 LION
Terminals
COM
71
A
COM
7276
B
24
7377
V~
24
74
V~0
AI8
AI7
AI6
AI5
AI4
AI3
AI2
V
AUXVAUX
21
GND9GND
AI1
3
2
22
10
1
GND11GNDGNDGND GNDGNDGND GND
8
7
6
5
4
18171615141312
Fig. 58 Terminal assignment and internal connections of
analog input modules
Terminal
71, 75 COM a
72, 76 COM b
SIGNAL Comment
2-wire communication bus
(LON/Panel Bus)
2-wire communication bus
(LON/Panel Bus)
73, 77 24 V~ Power supply
74, 78 24 V~0 Power supply
1…8 AI1 … AI8 Analog inputs 1…8
9…18 GND
21, 22
10 VDC/
5 mA, ±2 %
25, 26
Ground. All grounds are connected
internally to each other
Auxiliary voltage signal (used e.g. for
supplying setpoint potentiometers)
Shield connection (functional earth),
internally connected to the DIN rail
Table 42 Description of analog input module terminals
Notes
• Shield connection to be used for shielded I/O cables only.
It is not allowed to connect a LONW
LONW
ORKS
requires a resistor and a capacitor.
ORKS
shield, since
• If additional shield terminals are needed, the
XS814 Auxiliary Terminal Package can be installed.
COM
A
COM
B
24
V~
24
V~0
25 26
75
78
Technical Data
Input
Protection
Resolution
Accuracy
Table 43 Analog input modules data
Range
-50...-20 °C
(-58...-4 °F)
-20…0 °C
(-4…+32 °F)
0...30 °C
(32…86 °F)
30...70 °C
(86...158 °F)
70...100 °C
(158...212 °F)
100...130 °C
(212...266 °F)
130...150 °C
(266...302 °F)
150…400 °C
(302…752
°F)
(1
Balco specified for -30 °C … +120 °C, only
(2
NTC10kΩ specified for -30 °C … +100 °C, only
(3
NI1000TK5000 specified for -30 °C … +130 °C, only
• 0(2) ... 10 VDC
• 0(4) ... 20 mA
(via external 499 Ω/0.25 % resistor
• NTC20kΩ (-50…+150 °C; default)
• PT1000-1 (-50…+150 °C)
• PT1000-2 (0…+400 °C)
• PT3000 (-50…+150 °C)
• BALCO500 (-30…+120 °C)
• NTC10kΩ (-30…+100 °C)
• NI1000TK5000 (-30…+130 °C)
• Slow binary input
Protected against failure voltage (24 VAC,
40 VDC)
16-bit resolution
±75 mV (0 ... 10 V), without sensor
PT1000-1
≤
1.2 K – ≤ 1.2 K
≤
0.7 K – ≤ 0.7 K
≤
0.5 K
≤
0.5 K
≤
0.7 K
≤
0.7 K
≤
1.2 K
≤
1.2 K
≤
1.2 K
≤
1.2 K
≤
1.2 K
≤
1.2 K – ≤ 1.2 K
– ≤ 1.2 K – – – – –
(3
(1
PT1000-2
Balco500
PT3000
NTC20kΩ
≤
1.2 K
≤
5.0 K
≤
0.7 K
≤
1.0 K
≤
0.5 K
≤
0.5 K
≤
0.3 K
≤
0.7 K
≤
0.7 K
≤
0.5 K
≤
1.2 K
≤
1.2 K
≤
1.0 K
≤
1.2 K
≤
1.2 K
≤
3.0 K – ≤ 1.2 K
≤
5.5 K – –
(2
(default)
NTC10kΩ
NI1000TK5000
≤
5.0 K
≤
1.2 K
≤
1.0 K
≤
0.7 K
≤
0.5 K
≤
0.5 K
≤
0.5 K
≤
0.7 K
≤
1.0 K
≤
1.2 K
Table 44 Accuracy of analog input sensors
Note
The accuracy of the sensor itself is not included in this table.
41 EN1B-0375GE51 R0308
Page 42
Excel 800 LION
Internal Impedance when Connecting Sensors
Fig. 59 Analog input low impedance (input circuit for
Fig. 60 Analog input high impedance (input circuit for
voltage input for active sensors)
Fig. 61 Analog input impedance setpoint (input circuit for
NTC10kΩ, NTC20kΩ, wall module setpoint)
EN1B-0375GE51 R0308
42
Page 43
Excel 800 LION
7
4
737
7
727
6
717
5
9
1
0
GND
2
4
V
~
2
4
V~0
COM
B
COM
A
GND
123
CLIOP821A Analog Input Module
5
D
1
6
GND
1
7
GND
1
8
GND
678
2AI3AI4AI5AI6AI7AI8
CLIOP821A
Connection Examples
Active Sensor and Potentiometer
COM
71
A
COM
72
B
24
73
V~
24
7478
V~0
AUXVAUX
V
22
21
GND10GND
9
Optional Aux. Terminal Module XS814
A1 A2 A3 A4 A5 A6 A7
1 234
AI1
AI
1
2345
GND12GND13GND14GND
11
5
67
GN
1
COM
A
COM
B
24
V~
24
V~ 0
Shield
internally
connectedto
DINrail
25 26
F1
F2
Active Sensor
1: 24V~ power supply
2: 0...10 VDC signal
3: GND
1 23
Aux. Voltage + Pot.
1: signal
2: GND
3: 10 VDC auxiliary
0...10V
Fig. 62 Analog input module, wiring example 1
For fusing specifications see section "Fusing Specifications" on page 11.
43 EN1B-0375GE51 R0308
Page 44
Excel 800 LION
7
4
737
7
727
6
717
5
9
1
0
GND
2
4
V
~
2
4
V~0
COM
B
COM
A
GND
1
5
GND
1
6
GND
1
7
GND
1
8
GND
567
8
AI2AI3AI4AI5AI6AI7AI8
1
2
0(4)...20mA
Externa
l 499
Ω
resisto
r wit
h
twi
n wire-en
d
ferrule
s require
d
CLIOP821A Analog Input Module
Passive Sensor and 0 (4) … 20 mA Signal
COM
A
COM
B
24
V~
24
V~ 0
75
76
77
78
COM
71
A
COM
72
B
24
73
V~
24
7478
V~0
AUXVAUX
V
22
21
GND10GND
9
Temp. sensor
(NTC20k or PT1000)
AI1
1
234
GND12GND13GND14GND
11
1 2
COM
A
COM
B
24
V~
24
V~ 0
25 26
CLIOP821ACLIOP821A
Fig. 63 Analog input module, wiring example 2
EN1B-0375GE51 R0308
44
Page 45
Excel 800 LION
Analog Output Modules
Types of Analog Output Modules, Terminal Socket
Type Description Housing
CLIOP822A Panel Bus analog
output module
CLIOPR822A Panel Bus analog
output module with
manual overrides
CLIOL822A LONW
CLIOLR822A LONW
XS821-22 Terminal socket Light gray
Table 45 Excel 800 LION analog output modules
ORKS
Bus analog
output module
ORKS
Bus analog
output module with
manual overrides
Features
• 8 analog outputs;
can also be configured per output as binary outputs
(0 … 10 V, 2 … 10 V, ON/OFF, or floating)
• Corresponding output status LEDs (red)
• …R822: 8 manual overrides, see figure below
Fig. 64 CLIOP822A Analog Output Module with terminal
socket
Legend
1 Service button S1
2 Hex switch S2
3 Manual overrides
4 Output LEDs
5 Service LED
6 Power LED
Light gray
Light gray
Dark gray
Dark gray
Functionality of service LED and power LED: see Table 74
to Table 76 on page 72 and following.
In the event of communication problems, the analog outputs
will move to the safety positions you have configured in
CARE, see analog output point description in the CARE –
User Guide, 74-5587/EN2B-0182GE51.
Terminals
Fig. 65 Terminal assignment and internal connections of
the analog output modules
Terminal
71, 75 COM a
72, 76 COM b
73, 77 24 V~ Power supply
74, 78 24 V~0 Power supply
9…18
21, 22
25, 26
Table 46 Description of the analog output module terminals
Notes
• Shield connection to be used for shielded I/O cables only.
• If additional shield terminals are needed, the
Signal COMMENT
2-wire communication bus
(LON/Panel Bus)
2-wire communication bus
(LON/Panel Bus)
1…8 AO1…AO8 Analog outputs 1…8
GND
N.C. Do not use!
It is not allowed to connect a LONW
LONW
ORKS
requires a resistor and a capacitor.
XS814 Auxiliary Terminal Package can be installed.
Ground. All grounds are connected
internally to each other
Shield connection (functional earth),
internally connected to the DIN rail
ORKS
shield, since
45 EN1B-0375GE51 R0308
Page 46
Excel 800 LION
Technical Data
Voltage rating
Current rating
Resolution
Accuracy
Zero output voltage
Protection
Feedback signal
Table 47 Analog output modules data
Output status LEDs behavior
Automatic mode
Override mode
Table 48 Analog output status LED behavior
0(2)…11 V (default)
max. ±1 mA
8 bit
±150 mV
< 200 mV
Short-circuit protected;
protected against failure
voltage (24 VAC, 40 VDC)
Auto/manual mode and output
value
Brightness follows the
commanded output signal
Flashes
Modules with Manual Overrides
The CLIOPR822A/CLIOLR822A Analog Output Modules are
equipped with manual overrides: one rotary knob for each
analog output.
The manual overrides can be set manually to either "auto"
or "0…110 %" (infinitely adjustable).
NOTICE
Damage to the electronic module!
►
Do not use a tool to adjust the rotary knobs.
►
Do not use excessive force. Adjust only by hand.
Analog Outputs Configured as Binary Outputs
Using CARE, the analog outputs can be configured
individually as binary outputs. The voltage output is then 0 V
or 10 V, depending upon the signal from the controller.
EN1B-0375GE51 R0308
46
Page 47
Excel 800 LION
7
4
737
7
727
6
717
5
9
1
0
GND
2
4
V
~
2
4
V~0
COM
B
COM
A
GND
3
1
5
N
D
1
6
GND
1
7
GND
1
8
GND
567
8
X
1
2
A1A
2
X
S814
NCN
C
CLIOP822A Analog Output Module
Connection Example
COM
71
A
COM
72
B
24
73
V~
24
7478
V~0
AO1
AO2 AO3 AO4 AO5 AO6 AO7 AO8
2221
GND10GND
9
Optional Aux. Terminal Module
A1 A2 A3 A4 A5 A6 A7
1 234
1
GND12GND13GND14GND
11
5
67
234
S814
G
COM
A
COM
B
24
V~
24
V~ 0
Shield
internally
connectedto
DINrail
25 26
CLIOP822A
F1
F2
24V~ drive with
0...10V signal
1: 24V~ power supply
2: GND
3: Signal
1 2
M
0...10V
Fig. 66 Analog output connection example
For fusing specifications see section "Fusing Specifications" on page 11.
47 EN1B-0375GE51 R0308
Page 48
Excel 800 LION
Shield
internally
Connected to
123M1
2
M
Synchronization Behavior of Analog Output
Module Configured as Floating Output
In order to regularly update the real actuator position with
the calculated position and thus ensure that the actuator
definitely reaches its end position, a synchronization
process is performed by the analog output module.
During the synchronization process, the analog output
module will continue running for the configured runtime
once it reaches the calculated end position.
This updating (synchronization) is performed:
• If the calculated position of the actuator
< lower synchronization threshold (2 %)
= synchronization towards 0 %
• If the calculated position of the actuator
> upper synchronization threshold (98 %)
= synchronization towards 100 %
• Following any power-up or any reset
DIN RAIL
Fig. 67 Connection example with Relay Module MCD 3
• The relay module facilitates the control of peripheral devices with high load via the analog outputs.
• Relay terminal 18 of MCD3 controls the N.O. contacts (floating outputs) K1, K2.
For fusing specifications, see section "Fusing Specifications" on page 11.
EN1B-0375GE51 R0308
48
Page 49
Excel 800 LION
9
74
73
10
16
17
18
25
26
5
678
GND
24
24
COMBCOM
COMACOM
GND
GND
GND
GND
GND
A6
A7
1
2
A1
A2
XS814
CLIOP822A Analog Output Module
AO5
AO6
AO7
AO8
MCE 3
max. 240 V
1234567
8
11
121314
15
16
17
18
K1K2K3
E
x
t
e
r
n
a
l
g
r
o
u
p
r
e
q
u
i
r
e
d
t
o
p
o
w
e
r
e
x
t
e
r
n
a
l
d
e
v
i
c
e
s
.
Optional Aux. Terminal Module XS814
COM
7171
A
COM
727276
B
24
73
V
~
24
74
V~0
NC NC
21 22
GND
GND
9
10
A1 A2
A3
A4
AO1 AO2 AO3 AO4
1
234
GND GND GND GND
11 12
A5
13
14
15
75
A
B
24
77
V
~
24
78
V~0
Shield
internally
Connected to
DIN RAIL
V
~
V~0
CLIOP822A
5
4
67
1
2
M
0...10V
3
0.2 A2 A
K1
K2
K3
F1
12
F2
24V Drive with
0...10V Signal
1: 24V power supply
2: GND
3: signal
3
~
~
Fig. 68 Connection example with Relay Module MCE 3
The relay module facilitates the control of peripheral devices with high load via the analog outputs.
• Input terminal 16 of MCE3 controls the N.O. contact K3.
• Input terminal 17 of MCE3 controls the changeover contact K2.
• Input terminal 18 of MCE3 controls the changeover contact K1.
For fusing specifications, see section "Fusing Specifications" on page 11.
49 EN1B-0375GE51 R0308
Page 50
Excel 800 LION
Binary Input Modules
Types of Binary Input Modules, Terminal Socket
Type Description Housing
CLIOP823A Panel Bus binary input module Light gray
CLIOL823A LONW
XS823 Terminal socket Light gray
Table 49 Excel 800 LION Binary Input Modules
Features
• 12 binary inputs
• 12 configurable status LEDs (green/red, yellow/OFF)
• Binary inputs can be used as
– Static digital inputs as dry-contacts (default)
– Fast totalizers (up to 20 Hz)
ORKS
module
Bus binary input
Dark gray
Terminals
COM
71
A
COM
7276
B
24
7377
V~
24
74
V~0
BI12
BI11
BI10
BI9
BI8
BI7
BI6
BI5
BI4
BI3
BI2
BI1
12
11
10
9
8
7
6
5
4
3
2
1
GND13GNDGNDGNDGNDGNDGND GNDGNDGNDGND GND
2423222120191817161514
Fig. 70 Terminal assignment and internal connections of
binary input modules
Terminal
71, 75 COM a
72, 76 COM b
Signal COMMENT
2-wire communication bus
(LON/Panel Bus)
2-wire communication bus
(LON/Panel Bus)
73, 77 24 V~ Power supply
74, 78 24 V~0 Power supply
1…12 BI1…BI12 Binary inputs 1…12
13…24 GND
25, 26
Ground. All grounds are connected
internally to each other.
Shield connection (functional earth),
internally connected to the DIN rail.
COM
A
COM
B
24
V~
24
V~0
25 26
75
78
Fig. 69 CLIOP823A Binary Input Module with terminal
socket
Legend
1 Service button S1
2 Hex switch S2
3 Input LEDs
4 Service LED
5 Power LED
Functionality of service LED and power LED: see Table 74
to Table 76 on page 72 and following.
EN1B-0375GE51 R0308
Table 50 Description of binary input module terminals
Notes
• Shield connection to be used for shielded I/O cables only.
It is not allowed to connect a LONW
LONW
ORKS
requires a resistor and capacitor.
ORKS
shield, since
• If additional shield terminals are needed, the
XS814 Auxiliary Terminal Package can be installed.
50
Page 51
Excel 800 LION
Technical Data
Input type
Current rating (closed
input)
Open contact voltage
Protection
Dry-contact or open collector
2 mA
16…22 VDC
Protected against failure
voltage (24 VAC, 40 VDC)
Status LEDs
Using CARE, the status LEDs can be configured individually
for use as either alarm LEDs (red/green) or as status LEDs
(yellow/OFF [default]).
Given a state of "logical ON," the LED will be lit (yellow or
red).
Configuration as Fast Totalizer
Using CARE, the binary inputs can be configured as fast
totalizers for operation in conjunction with devices equipped
with an open collector output.
Frequency
Pulse ON
Pulse OFF
Bounce
Table 51 Binary inputs used as fast totalizers
max. 20 Hz
min. 25 ms
min. 25 ms
max. 5 ms
Fig. 71 Configuration of binary input as fast totalizer
51 EN1B-0375GE51 R0308
Page 52
Excel 800 LION
747
8
737
7
727
6
717
5
22232
4
252
6
10111
2
BI10BI11BI1
2
2
4
V
~
2
4
V
~
2
4
V~0
2
4
V~0
B
B
A
A
Totalizer
1
: signa
l
2
: GND
1
2
Totalizer
min
. 2
5 m
s
Shiel
d
internall
y
connected t
o
DIN rai
l
CLIOP823A Binary Input Module
Connection Example
71
A
72
B
24
73
V~
24
74
V~0
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9
1
2 3 4
13 14 15 16 17
F1
Fig. 72 CLIOP823A connection examples
5
6 7 89
18 19 20 21
Dry contact
1: signal
2: GND
1 2
Dry
contact
CLIOP823A
For fusing specifications, see section "Fusing Specifications" on page 11.
EN1B-0375GE51 R0308
52
Page 53
Excel 800 LION
Relay Output Modules
Types of Relay Output Modules, Terminal Socket
Type Description Housing
CLIOP824A Panel Bus relay output
module
CLIOPR824A Panel Bus relay output
module with manual
overrides
CLIOL824A LONW
CLIOLR824A LONW
XS824-25 Terminal socket; can be fitted
Table 52 Excel 800 LION Relay Output Modules
ORKS
Bus relay output
module
ORKS
Bus relay output
module with manual
overrides
with long (red) cross
connector (incl. in scope of
the delivery)
Features
• 6 relays (changeover contacts), arranged in two blocks
• …R824: 6 manual overrides
• Low and line voltage allowed, see WARNING.
Light gray
Light gray
Dark gray
Dark gray
Light gray
6 Power LED
Functionality of service LED and power LED: see Table 74
to Table 76 on page 72 and following.
In the event of communication problems, the relay outputs
will move to the safety positions you have configured in
CARE, see relay output point description in the CARE –
User Guide, 74-5587/EN2B-0182GE51.
WARNING
Risk of electric shock or equipment damage!
Low voltage and line voltage must not be wired within
the same relay block.
►
Wire low voltage e.g., to relay block 1 and line voltage to
relay block 2 or vice versa. In this case the short cross
connectors must be used, see Table 5 on page 8.
NOTICE
Risk of malfunction!
Cross connectors may only be used if the same voltage
is used on all relays they connect.
►
Do not use a cross connector if different voltages are
used on the relays.
E.g., use a short cross connector for relay block 1 with
line voltage and no cross connector for relay block 2 with
12 V low voltage for relay 4 and 24 V low voltage for
relays 5 and 6.
Fig. 73 CLIOP824A Relay Output Module with terminal
socket
Legend
1 Service button S1
2 Hex switch S2
3 Manual overrides
4 Status LEDs
5 Service LED
53 EN1B-0375GE51 R0308
Page 54
Excel 800 LION
Terminals
COM
7175
A
COM
7276
B
24
7377
V~
24
74
V~0
NO
NC
COM
CON
Relay block 1
11
12
13
14
NO
NC
COM
CON
NO
21
22
23
24
31415161
NC
32
COM
33435363
CON
34445464
Cross connector (can be removed, as desired)
NO
NC
COM
CON
42
Relay block 2
NO
NC
5262
COM
CON
Fig. 74 Terminal assignment and internal connections of
relay output modules
Terminal Signal Comment
71, 75
72, 76
73, 77
74, 78
11
12
13
14
21
22
23
24
RELAY BLOCK 1
31
32
33
34
41
42
43
44
51
52
53
54
RELAY BLOCK 2
61
62
63
64
25
COM a
COM b
24 V~
24 V~0
REL1 N.O.
REL1 N.C.
R1 COM
R1 COM
REL2 N.O.
REL2 N.C.
R2 COM
R2 COM
REL3 N.O.
REL3 N.C.
R3 COM
R3 COM
REL4 N.O.
REL4 N.C.
R4 COM
R4 COM
REL5 N.O.
REL5 N.C.
R5 COM
R5 COM
REL6 N.O.
REL6 N.C.
R6 COM
R6 COM
2-wire communication bus
(LON/Panel Bus)
2-wire communication bus
(LON/Panel Bus)
Power supply
Power supply
Relay 1 N.O. contact
Relay 1 N.C. contact
relay 1 common contact
For connection of relay 1 common via
cross connector*
Relay 2 N.O. contact
Relay 2 N.C. contact
Relay 2 common contact
For connection of relay 2 common via
cross connector*
Relay 3 N.O. contact
Relay 3 N.C. contact
Relay 3 common contact
For connection of relay 3 common via
cross connector*
Relay 4 N.O. contact
Relay 4 N.C. contact
Relay 4 common contact
For connection of relay 4 common via
cross connector*
Relay 5 N.O. contact
Relay 5 N.C. contact
Relay 5 common contact
For connection of relay 5 common via
cross connector*
Relay 6 N.O. contact
Relay 6 N.C. contact
Relay 6 common contact
For connection of relay 6 common via
Table 53 Description of relay output module terminals
NO
NC
COM
CON
COM
COM
24
V~
24
V~0
A
B
78
25
Permissible Loads
Max. load Min. load
Per relay
output
module (total)
19…250 VAC
current at cos φ≥ 0.6: 12 A
1…29 VDC
12 A resistive, 3 A inductive
Per normally
open contact
19…250 VAC
current at cos φ≥ 0.6: 4 A
1…29 VDC
4 A resistive, 1 A inductive
Per normally
closed
contact
19…250 VAC
current at cos φ≥ 0.95: 2 A,
current at cos φ≥ 0.6: 1 A
1…29 VDC
4 A resistive, 1 A inductive
Table 54 Permissible loads of relay output modules
Notes
• In the case of voltages above 30 VAC/DC and if inductive
components are to be connected to relays switching
more often than once every 2 minutes, these components must be prevented from causing harmful
interference to radio or television reception (conformance
with EN 55014).
• Max. voltage for UL 864-compliant applications is 24 V.
Status LEDs with Manual Overrides
Fig. 75 Manual overrides (sliding switches)
The …R824 Relay Output Modules are equipped with
manual overrides: one for each relay output. These sliding
switches can manually be set to either "auto" or "0" or "1".
Output status LEDs behavior and relay output behavior
Mode LED
Automatic mode, state
ON ON OFF
“logical ON”
Automatic mode, state
OFF OFF ON
“logical OFF”
Override mode (setting “0”) Flashes OFF ON
Override mode (setting “1”) Flashes ON OFF
*As configured using CARE.
Table 55 Relay output status LED behavior
N.O.*
(direct)
–
50 mW
50 mW
N.C.*
(reverse)
EN1B-0375GE51 R0308
54
Page 55
Excel 800 LION
74
24
24
COMBCOM
COMACOM
25
A7
Power Supply
Shield internally
connected to DIN RAIL
Cross Connector (Factory mounted)
COM
CON
COM
54
CON
61
62
63
NC
COM
64
CON
Field Device
1: 230 V (L)
2: 230 V (N)
122
M
M
230V
230V
Connection Example
COM
7171
A
COM
727276
B
24
737377
V
~
24
74
V~0
NO
11
NC
12
COM
13
CON
14
Optional Aux. Terminal Module XS514
A1 A2 A3 A4 A5 A6
CLIOP824A Relay Output Module
NO
NC
COM
CON
21
22
23
24
NO
NC
COM
CON
31
32
33
34
NO
NC
41
42
43
44
NO
NC
51
52
53
NO
A
B
24
V
24
V~0
75
~
78
V
V~0
~
12
230 V
F1
3
4
567
1
Field Device
1: 230 V (L)
2: 230 V (N)
NL
230 V~
Fig. 76 CLIOP824A connection example (both relay blocks with line voltage)
For fusing specifications see section "Fusing Specifications" on page 11.
55 EN1B-0375GE51 R0308
Page 56
Excel 800 LION
Fig. 77 CLIOP824A connection example (relay blocks with low and line voltage)
For fusing specifications see section "Fusing Specifications" on page 11.
EN1B-0375GE51 R0308
56
Page 57
Excel 800 LION
Floating Output Module
Features
• Type: CLIOPR825A Floating Output Module
• Housing: light gray
• Floating outputs sufficient for driving up to 3 floating
actuators
• Manual overrides and 3 corresponding pairs of status
LEDs
In the event of communication problems, the 3 floating
outputs will move to the safety positions you have
configured in CARE, see floating output point description in
the CARE – User Guide, 74-5587/EN2B-0182GE51.
WARNING
Risk of electric shock or equipment damage!
Low voltage and line voltage must not be wired within
the same relay block.
►
Wire low voltage e.g., to relay block 1 and line voltage to
relay block 2 or vice versa. In this case the short cross
connectors must be used, see Table 5 on page 8.
NOTICE
Risk of malfunction!
Cross connectors may only be used if the same voltage
is used on all relays they connected.
►
Do not use a cross connector if different voltages are
used on the relays.
E.g., use a short cross connector for relay block 1 with
line voltage and no cross connector for relay block 2 with
12 V low voltage for relay 4 and 24 V low voltage for
relays 5 and 6.
Permissible loads
Max. load Min. load
Fig. 78 CLIOPR825A Floating Output Module with
terminal socket
Legend
1 Service button S1
2 Hex switch S2
3 Manual overrides
4 Status LEDs
4 Service LED
5 Power LED
Functionality of service LED and power LED: see Table 74
to Table 76 on page 72 and following.
Per relay
output
module (total)
Per normally
open contact
Per normally
closed
contact
Table 56 Permissible loads of floating output modules
Notes
• In the case of voltages above 30 VAC/DC and if inductive
components are to be connected to relays switching
more often than once every 2 minutes, these components must be prevented from causing harmful
interference to radio or television reception (conformance
with EN 55014).
• Max. voltage for UL 864-compliant applications is 24 V.
19…250 VAC
current at cos φ≥ 0.6: 12 A
1…29 VDC
12 A resistive, 3 A inductive
19…250 VAC
current at cos φ≥ 0.6: 4 A)
1…29 VDC
4 A resistive, 1 A inductive
19…250 VAC
current at cos φ≥ 0.95: 2 A,
current at cos φ≥ 0.6: 1 A
1…29 VDC
4 A resistive, 1 A inductive
–
50 mW
50 mW
57 EN1B-0375GE51 R0308
Page 58
Excel 800 LION
Terminals
COM
7175
A
COM
7276
B
24
7377
V~
24
74
V~0
Actuator 2Actuator 3
NO
NC
COM
CON
Cross connector (can be removed, as desired)
NO
31415161
NC
32
COM
33435363
CON
34445464
42
NO
NC
5262
COM
CON
NO
NC
COM
CON
Actuator 1
NO
11
NC
12
COM
13
CON
14
21
22
23
24
Fig. 79 Terminal assignment and internal connections of
floating output module
Terminal
71, 75
72, 76
73, 77
74, 78
ACTUATOR 1
ACTUATOR 2
ACTUATOR 3
* Do not connect by wire!
Signal Comment
COM a
COM b
24 V~
24 V~0
REL1 N.O.
11
REL1 N.C.
12
R1 COM
13
R1 COM
14
REL2 N.O.
21
REL2 N.C.
22
R2 COM
23
R2 COM
24
REL3 N.O.
31
REL3 N.C.
32
R3 COM
33
R3 COM
34
REL4 N.O.
41
REL4 N.C.
42
R4 COM
43
R4 COM
44
REL5 N.O.
51
REL5 N.C.
52
R5 COM
53
R5 COM
54
REL6 N.O.
61
REL6 N.C.
62
R6 COM
63
R6 COM
64
25
2-wire communication bus (LON/Panel Bus)
2-wire communication bus (LON/Panel Bus)
Power supply
Power supply
Floating relay 1 N.O. contact
Floating relay 1 N.C. contact
Floating relay 1 common contact
For connection of floating relay 1 common
via cross connector*
Floating relay 2 N.O. contact
Floating relay 2 N.C. contact
Floating relay 2 common contact
For connection of floating relay 2 common
via cross connector*
Floating relay 3 N.O. contact
Floating relay 3 N.C. contact
Floating relay 3 common contact
For connection of floating relay 3 common
via cross connector*
Floating relay 4 N.O. contact
Floating relay 4 N.C. contact
Floating relay 4 common contact
For connection of floating relay 4 common
via cross connector*
Floating relay 5 N.O. contact
Floating relay 5 N.C. contact
Floating relay 5 common contact
For connection of floating relay 5 common
via cross connector*
Floating relay 6 N.O. contact
Floating relay 6 N.C. contact
Floating relay 6 common contact
For connection of floating relay 6 common
via cross connector*
Shield connection (functional earth),
internally connected to the DIN rail
Table 57 Description of floating output module terminals
NO
NC
COM
CON
COM
A
COM
B
24
V~
24
V~0
78
25
Manual Overrides
The floating output module is equipped with manual
overrides: one rotary knob for each floating output.
These manual overrides can manually be set to either
"Auto" or "0 … 100 %" (infinitely adjustable).
123
AAA
Fig. 80 Manual overrides (rotary knobs)
NOTICE
Damage to the electronic module!
►
Do not use a tool to adjust the rotary knobs.
►
Do not use excessive force. Adjust only by hand.
Auto
In this setting, the signal provided by the respective floating
output (R1 + R2 or R3 + R4 or R5 + R6) and the condition
(ON/OFF) of the respective pair of status LEDs both follow
the commanded output signal.
Override (0…100 %)
When a manual override is set to values in the range of
"0…100 %", the respective floating output will drive to the
set position. The runtime depends upon the actuator runtime
configured in CARE an on the actual position.
Status LEDs
The respective pair of status LEDs will display the following:
Actuator 1
Mode LED
Auto
Green LED ON OFF OFF
Red LED OFF ON OFF
Override
Green LED Flashing OFF Flashing
Red LED OFF Flashing Flashing
Table 58 LED behavior (for e.g., floating output 1)
Closing Opening
Honeywell
0
100
AUTO
!
Not
moving
EN1B-0375GE51 R0308
58
Page 59
Excel 800 LION
747
8
737
7
727
6
717
5
2
4
V
~
2
4
V
~
2
4
V~0
2
4
V~0
COMBCOM
B
COMACOM
A
CLIOPR825A Floating Output Module
4
1
4
2
4
3
O
C
O
M
5
1
5
2
5
3
N
O
N
C
COM
6
1
6
2
6
3
N
O
N
C
COM
6
4
CON
123
M
4
4
O
N
5
4
CON
2
5
Connection Example
COM
71
A
COM
72
B
24
73
V~
24
74
V~0
F1
11
12
13
14
3
NO
NC
COM
CON
4
21
22
23
24
814
567
NO
NC
COM
CON
Optional aux. Terminal Module XS
A1 A2 A3 A4 A5 A6 A7
1 2
NO
NC
COM
CON
Cross connector (factory -mounted)
31
32
33
34
N
N
C
C
Shield internally
connected to DIN rail
Floating actuator
with 24~V (requires two relays)
1:
2:
3: N
L
N
Power supply
230 V or other~
Fig. 81 CLIOPR825A Connection example (floating actuator)
For fusing specifications see section "Fusing Specifications" on page 11.
59 EN1B-0375GE51 R0308
Page 60
Excel 800 LION
Description of Extra Parts
Manual Disconnect Modules
Types
Manual disconnect
module
Corresponding I/O modules
CLIO…
XS812
XS812RO
Table 59 Manual disconnect modules
For mounting the manual disconnect modules, see Fig. 23
on page 20.
…821
…822
…823
…824
…825
WARNING
Risk of electric shock or equipment damage due to
improper use of XS812RO manual disconnect module!
►
Do not connect line voltage to the XS812RO.
Features
• Disconnector switches are used to manually disconnect
individual terminals of the corresponding electronic
module.
• Useful for troubleshooting and installation.
Diagrams
Fig. 83 XS812 and binary input modules
Fig. 84 XS812RO and relay modules/floating module
Fig. 82 XS812 and analog input/analog output modules
EN1B-0375GE51 R0308
60
Page 61
Excel 800 LION
XS814 Auxiliary Terminal Package
Features
• Type: XS814 Auxiliary Terminal Package
• For mounting onto already installed I/O modules in order
to equip them with additional terminals.
• Each unit consists of 2 terminal blocks (the "A" block and
the "B" block), each with 7 terminals with a maximum
load of 12 A.
Fig. 85 XS814 Auxiliary Terminal Package
Terminal Assignment
A1 A2A3A4
1 2 3 4
Fig. 86 Terminal assignment and internal connections of
A5 A6
A7
5
6 7
XS814 Auxiliary Terminal Package
B1 B2B3B4
1 2 3 4
B5 B6
5
B7
6 7
Cross Connectors
XS815 Cross Connector Features
• For connecting the common terminals of all 6 relays.
This is permitted when all terminal blocks carry the same
voltage
• Long, red
• Supplied with the terminal socket
Fig. 87 XS815 Cross Connector
XS817 Cross Connector Features
• For connecting the common terminals of only relays 1–3
or of relays 4–6
• Short, yellow
• Must be ordered separately
Fig. 88 XS817 Cross Connector
XAL10 Swivel Label Holders
• Type: XAL10 Swivel Label Holder
• For applying self-adhesive labels with application
information generated using CARE
• For use with standard commercially-available labels,
e.g., AVERY ZWECKFORM 3669
• Supplied with the terminal socket
XS816 Bridge Connectors
• Type: XS816 Bridge Connectors
• Bridge connectors transmit both communication signals
and power supply between modules
• Supplied with the terminal socket
61 EN1B-0375GE51 R0308
Page 62
Excel 800 LION
LON Software Interface Description
Overview
LonTalk Protocol
Excel 800 LION LONW
protocol communication with other nodes on the LONW
network, with commissioning tools und supervisory devices.
Features
• Network variables for communications between nodes,
but no explicit messages
• Configuration network variables
• LONM
Addressing, binding, and commissioning
Excel 800 LION LONW
bound, and commissioned using CARE or any other
standard LONW
and higher, e.g., LonMaker for Windows.
Configuration
Excel 800 LION LONW
using CARE.
ARK
FPT protocol for downloading an Excel 800
LION LONW
loadable apbG file (supported by CARE and EXCELON)
ORKS
ORKS
Bus I/O Modules use a LONT
Bus I/O Module firmware via LON:
ORKS
Bus I/O Modules are addressed,
ORKS
commissioning tool based on LNS 2.0
ORKS
Bus I/O Modules are configured
ALK
ORKS
CLIOL821A Analog Input Module
For the CLIOL821A Analog Input Module the LONM
Profile 520 "Analog Input" has been assigned per input.
Each input object has its own configuration properties,
except for heartbeat configuration, which will be shared
among all objects.
These variables are transmitted immediately when their
value has been changed by a higher rate than the
configured "send on delta" (default: 0.3 K).
These variables are also transmitted as heartbeat output
(default: 60 sec) on a regular basis as dictated by the
maximum send time (nciSndHrtBt) configuration variable.
nvoAiTempP
INVALID
EN1B-0375GE51 R0308
62
Page 63
Excel 800 LION
Default Service Type
The default service type of these variables is
unacknowledged.
Analog Sensor Output – nvoAiValuePct[ ]
This network variable output represents the percentage
level for the appropriate input, if configured for voltage input.
Valid Ranges for 0 … 10 V Input
Value Representation
< 0 V 0 %
0 V … 10 V 0 … 100 %
> 10 V 100 %
Table 61 Analog input values: 0 … 10 V
Valid Ranges for 2 … 10 V Input
Value Representation
< 1.5 V Sensor break/short circuit
1.5 V … 2 V 0 %
Temperature Sensor Output – nvoAiTempP[ ]
This network variable output represents the temperature for
the appropriate input, if configured for temperature sensor,
except PT1000-2.
Range: see Table 43 and Table 44 on page 41.
Default Value
The default value is set after power-up or reset and remains
until the module has measured a valid value.
nvoAiTempP = INVALID = 0x7FFF (= 327.67 °C)
Slow Digital Input – nvoAiSwitch[ ]
This network variable output represents a slow digital input
connected to the universal input terminals.
The default value is set after power-up or reset and remains
until the module has measured a valid value.
nvoAiValuePct = INVALID = 0x7FFF (=163.835 %)
The sensor failure behavior can be configured for 2 … 10 V.
Temperature#2 Sensor Output – nvoAiTemp[ ]
This network variable output represents the temperature for
the appropriate input, if configured for temperature sensor if
configured for PT1000-2 sensor.
Range: see Table 43 and Table 44 on page 41.
Default Value
The default value is set after power-up or reset and remains
until the module has measured a valid value.
nvoAiTemp = INVALID = 0xFFFF (= 6279.5 °C)
63 EN1B-0375GE51 R0308
Page 64
Excel 800 LION
CLIOL(R)822A Analog Output Module
For the CLIOL822A/CLIOLR822A Analog Output Module
the LONM
per output.
Each analog output object has its own configuration
properties, except for heartbeat configuration and
nciAoConfig, which will be shared among all objects.
Fig. 90 LONM
ARK
open-loop actuator object has been assigned
ARK
analog output object
Analog Output Control Level – nviAoValuePct[ ]
This network variable is used to drive the analog output to
0 … 100 %.
If both nviAoSwitch[ ] and nviAoValuePct[ ] receive valid
values, nviAoValuePct[ ] will have priority.
Valid Ranges
Fig. 91 Analog output control levels – direct actuator
Receive Heartbeat
The default configuration for “Receive Heartbeat” is 300 sec.
If no nvi update is received during this time, the actuators
will go to their configured safety positions.
Start-up Behavior
At start-up, i.e., power-up or reset, all nvi's will be initialized
with INVALID, and after 1 minute, the actuators will go to
their configured safety positions.
Fig. 92 Analog output control levels – reverse actuator
Default Value
nvoAoValuePct = INVALID = 0x7FFF (=163.835 %)
This will cause the actuator to adopt a predefined position
defined for failure behavior.
EN1B-0375GE51 R0308
64
Page 65
Excel 800 LION
Analog Output Feedback – nvoAoPosnFb[ ]
This value represents the current status of the analog output
including feedback related to manual override initiated from
the manual override.
This is typically used for monitoring purposes at a
supervisory station or for diagnostic purposes.
Valid Range
Value State Current analog output position
0.5 … 100 % 1
0 % (OFF) 0
0 … 100 % -1
0xFF -1
Table 64 Analog output feedback range
Transmission
This variable is transmitted immediately when the
corresponding network input variable has changed more
than 1 % or immediately as an answer to an
nviAoValuePct[ ] or nviAoSwitch[ ] update.
Default Service Type
The default service type is unacknowledged.
Analog output position due to
normal control by nviAoSwitch or
nviAoValuePct
Manual override position via the
manual override panel
Current position unknown or
synchronization active,
analog output not configured
Analog Output Command – nviAoSwitch[ ]
This network variable is used to drive the analog output to
0 … 100 %.
It is typically bound to a LONW
output level 0 … 100 %.
If both nviAoSwitch[ ] and nviAoValuePct[ ] receive valid
values, nviAoValuePct[ ] will have priority.
Default Value
Value = 0
State = –1
ORKS
control device issuing an
65 EN1B-0375GE51 R0308
Page 66
Excel 800 LION
CLIOL823A Binary Input Module
One instance of the LONM
been assigned per input of the CLIOL823A Binary Input
Module.
Each digital input object has its own configuration
properties, except for heartbeat configuration, which will be
shared among all objects.
nciDiConfig[x]
UCPT_DIConfig
nciSndHrtBt
SCPTmaxSendTime
Fig. 93 LONM
ARK
Transmission
These variables are transmitted immediately when its value
has been changed by a higher rate than the configured
"send on delta" (in the case of the totalizer, “send on delta”
has a default value of 5 counts).
These variables are also transmitted as a heartbeat output
on a regular basis as dictated by the maximum send time
(nciSndHrtBt) (default = 0 = disabled) configuration variable.
Default Service Type
The default service type of these variables is
unacknowledged.
ARK
open-loop sensor object has
Open Loop Sensor Object
(LonMark Object Type 1)
Configuration
Parameter
Value File
digital input object
nvoDiSwitch[x]
SNVT_switch
nvoDiCount[x]
SNVT_count
|1
#1
Fast Binary Input – nvoDiSwitch[ ]
This network variable output represents the logical state of a
fast binary input connected to the binary input terminals.
Valid Range
Logical input state Value State
ON 100 % 1
OFF 0 % 0
Not configured 0 % -1
Table 65 Slow digital input values
Default Value
The default value is set after power-up or reset and remains
until the module has measured a valid value.
Value = 0
State = -1
Totalizer Count – nvoDiCount[ ]
This network variable output indicates the total number of
transitions from 0 to 1 since the last reset due to power-up
or network reset.
Valid Range
Fig. 94 Totalizer
State Value
EN1B-0375GE51 R0308
For totalizer counts 0 … 65534
For power-up/reset 65535
Table 66 Totalizer counts
Power-up/Reset
After power-up and reset, the value 0xFFFF = 65535 will be
sent to the network to indicate that previous count values
have been lost due to a reset.
66
Page 67
Excel 800 LION
CLIOL(R)824A Relay Output Module
One instance of the LONM
been assigned per input of the CLIOL824A/CLIOLR824A
Relay Output Module.
Each output object has its own configuration properties,
except for heartbeat configuration, which will be shared
among all objects.
nviDoSwitch[x]
SNVT_switch
nciDoConfig[x]
UCPT_DOConfig
nciRcvHrtBt[x]
SCPTmaxRcvTime
Fig. 95 LONM
ARK
ARK
open-loop sensor object has
Open Loop Actuator Object
(LonMark Object Type 3)
|1
Configuration
Parameter
Value File
output object
nvoDoActPosnFb[x]
SNVT_switch
#1
Relay Output Command – nviDoSwitch[ ]
This network variable is used to drive the relay output.
It is typically bound to a LONW
output level ON/OFF, respectively 0 … 100 %.
Valid Range
Value State Action
N/a 0 OFF
0 1 OFF
0.5 … 100 %
1
N/a
-1
Table 67 Relay output command values
Default Value
Value = 0
State = -1
Start-up Behavior
At start-up, i.e., power-up or reset, all nvi's will be initialized
with INVALID, leading the actuator to drive to the configured
safety position after 1 minute.
Receive Heartbeat
The default configuration for “Receive Heartbeat” is 300 sec.
If no nvi update is received during this time, the field devices
will go to their configured safety positions.
ORKS
control device issuing an
Outputs are switched
according to actual output
type configuration
INVALID:
as defined for failure behavior
67 EN1B-0375GE51 R0308
Page 68
Excel 800 LION
Troubleshooting
Testing Wiring Connections
The push-in terminals feature small holes (1 mm in
diameter) which can be used to measure the signals.
►
Insert a probe (1) as shown on the right.
Fig. 96 Testing wiring connections
Troubleshooting on the CLLIONLC01 Controller
The following LEDs of the CLLIONLC01 Controller can be used for troubleshooting purposes:
• Power LED (green)
• Alarm LED (red)
• LONW
• C-Bus Tx and Rx LEDs
• HMI Tx and Rx LEDs
• Modem Interface Tx and Rx LEDs
Power LED (green)
case Power LED Meaning Remedy
ORKS
service LED
1 ON
2 Flashing
3 Goes out briefly
Table 68 CLLIONLC01 power LED
Normal operation No action necessary
One or more of the internal voltage supplies
are outside of the permissible ranges. The
controller stops operation.
• The operator has activated the reset button
• The controller is performing a warm start
►
Check power
►
Check wiring
►
If problem persists, replace hardware
No action necessary
EN1B-0375GE51 R0308
68
Page 69
Excel 800 LION
Alarm LED (red)
Case Alarm LED Meaning Remedy
1 OFF
2 ON
3 Flashing
Table 69 CLLIONLC01 alarm LED
Normal operation No action necessary
Watchdog alarm output is powered
– The controller has encountered a
hardware problem
- or -
– The application has a fault
- or -
►
Try powering down and then
powering up the CLLIONLC01.
►
If problem persists, check and – if
necessary – reload the application.
►
If problem still persists, replace
hardware
– The controller has been powered up
without an application or the operator
has manually stopped the application,
e.g., using XL-Online.
In this case, the LED will light up
13 minutes after power-up without
application
Although the controller has encountered a
problem, the watchdog alarm output has not
yet been powered.
If problem persists, the LED will become lit
constantly, see case #2.
If it happens only once, the controller
has performed a restart
If, however, it happens multiple times,
then there is an application or hardware
problem (see case #2)
The controller performs a warm start.
69 EN1B-0375GE51 R0308
Page 70
Excel 800 LION
LONW
ORKS
Service LED
Fig. 97 Flashing pattern of the LONW
ORKS
service LED
The LONW
ORKS
service LED of the controller module displays the following flashing patterns indicating possible failure modes:
case When can it occur? Meaning Remedy
1
2
3
4
Anytime
Power up of controller
Power up of controller
Power up / reset
Node is configured and running normally
Bad node hardware
Bad node hardware
Node lacks application.
May be caused by neuron chip firmware when
a mismatch occurs on application checksum
No action necessary
►
Replace hardware
►
Replace hardware
►
Using EXCELON, set module to
“configured online”
►
If problem persists, the MIP software
on LW interface has been erased due
to wrong setting performed using
ECHELON tool:
Replace hardware
5
Anytime
Watchdog timer resets occurring.
►
Download firmware
Possible corrupt EEPROM and bootstrap
mode
6
Anytime
Node is unconfigured but has an application
►
Proceed with commissioning
Table 70 CLLIONLC01 LONW
ORKS
service LED
EN1B-0375GE51 R0308
70
Page 71
Excel 800 LION
C-Bus Tx and Rx LEDs
case C-Bus LEDs Meaning Remedy
1
Both LEDs are flashing
2
3
Both LEDs are OFF
Both LEDs are flashing
If the C-bus is functioning properly, then the
CLLIONLC01 Controller is functioning properly
If the C-bus is not functioning properly, then
the termination can be wrong
No C-bus communication
No C-bus communication
No action necessary
►
Check C-bus termination switch S1
(location: see Fig. 46 on page 33)
►
Check C-bus settings
►
Check C-bus wiring
synchronously
Table 71 CLLIONLC01 C-Bus Tx and Rx LEDs
HMI Tx and Rx LEDs
case HMI LEDs Meaning Remedy
1
2
Both LEDs are flashing
Both LEDs are OFF
If the HMI Interface is functioning properly,
then the CLLIONLC01 Controller is functioning
properly
No HMI Interface communication
No action necessary
►
Check HMI Interface connection and
proper earthing of connected
hardware
Table 72 CLLIONLC01 HMI Tx and Rx LEDs
Modem Tx and Rx LEDs
case Modem LEDs Meaning Remedy
1
2
Both LEDs are flashing
Both LEDs are OFF
Table 73 CLLIONLC01 modem Tx and Rx LEDs
If the Modem Interface is functioning properly,
then the CLLIONLC01 Controller is functioning
properly
No Modem Interface communication
No action necessary
►
Check Modem Interface connection
71 EN1B-0375GE51 R0308
Page 72
Excel 800 LION
I/O Modules Troubleshooting
►
Check if the power supply voltage level is OK and that there is no high voltage (> 24 VAC or > 40 VDC) connected to the
inputs/outputs of the …821, …822, …823 I/O modules.
►
Replace the problem I/O module with another module of the same kind.
– If the problem persists, this is an indication that the problem is caused by the application or incorrect wiring.
– If the problem is solved, this is an indication that the I/O module was defective.
For troubleshooting purposes on all I/O modules the following features can be used:
• Power LED
• Service LED
• Service button
In addition, a module-specific troubleshooting may be necessary.
Power LED of I/O Modules
case Power LED Meaning Remedy
1 ON
2 OFF
3 Flashing continuously
I/O module is powered
No power
If the I/O module’s service LED is likewise
flashing, the I/O module is in the boot mode
No action necessary
►
Check power supply
►
Wait until rebooting (firmware
download) has been completed
Table 74 Power LED of I/O modules
EN1B-0375GE51 R0308
72
Page 73
Excel 800 LION
Service LED of I/O Modules
case Service LED Meaning Remedy
1
2
3
4
5
6
7
8
9
10
LED remains OFF after
power-up
LED is lit continuously after
first power-up
Alternating flash between
service LED and power LED
LED flashes at power up,
goes OFF, and then is lit
continuously
LED repeatedly blinks
ON for 1 sec and
OFF for 1 sec
LED remains OFF after a
short ON duration
LED flashes continuously in
following pattern:
4 x ON/OFF followed by
pause
LED flashes continuously in
following pattern:
5 x ON/OFF followed by
pause
LED flashes continuously in
following pattern:
6 x ON/OFF followed by
pause
LED flashes continuously in
following pattern:
7 x ON/OFF followed by
pause
If the power LED is also OFF, then
– Defective device hardware
– Possible power supply problems, clock
problems, defective processor
•
LONW
ORKS
Bus I/O modules:
– Defective hardware
•
Panel Bus I/O modules:
– I/O module has not yet been configured
by CLLIONLC01
– Boot loader is active
– Failure during last firmware download
– Checksum error
Panel Bus I/O modules, only:
Download error or application checksum error.
Boot loader is running
LONW
ORKS
LONW
LONW
LONW
Bus I/O modules, only:
ORKS
Bus I/O module lacks application
ORKS
Bus I/O modules, only:
ORKS
Bus I/O module is unconfigured, but
has an application
I/O module is configured and running normally
Sensor failure of analog input module
(in case of LONW
ORKS
Bus I/O modules, this
behavior can occur only if the appropriate NV
has been bound)
LONW
ORKS
Bus I/O modules, only: LONW
I/O Bus module has received the wink
command from network, physical outputs are
unaffected
Boot loader problem or hardware defect
Communications failure
►
Replace hardware
LONW
►
Replace hardware
Panel Bus I/O modules:
►
Set the hex address to the position configured
with CARE
►
Ensure that I/O Bus switch S2 of CLLIONLC01
Controller is set to position "Panel"
►
Check the Panel Bus wiring:
- Check for cable breaks
- Check for cable short-circuits
- If using separate transformers: Check ground
►
Eliminate any mixture of Panel Bus I/Os and
LonWorks I/Os on same wire
►
Allow CLLIONLC01 to configure I/O module
►
Unplug and replug the module
►
If problem persists, replace hardware
►
Panel Bus I/O modules, only:
Wait until rebooting (firmware download) has
been completed
►
Download application
►
Set module to configured mode
No action necessary
►
Check sensor or connection
►
Check sensor configuration
ORKS
No action necessary
►
Replace hardware
►
Check bus wiring
►
Ensure that I/O Bus switch S2 of CLLIONLC01
Controller is set to correct position
►
Ensure that LONW
Panel Bus I/O modules are not sharing same
bus
►
In case of Panel Bus I/O modules, only:
Check for incorrect HEX addresses (2 Panel Bus
I/O modules using same HEX address)
►
In case of LONW
Check heartbeat
ORKS
Bus I/O modules:
connection
ORKS
Bus I/O modules and
ORKS
Bus I/O modules, only:
Table 75 Service LED of I/O modules
73 EN1B-0375GE51 R0308
Page 74
Excel 800 LION
LED Test for I/O Modules
►
Press the service button S1 of the I/O module, e.g. using a paperclip.
– The service LED and all other LEDs of that Panel Bus I/O module light up for as long as the service button is pressed.
LED Correct behavior
Power LED ON continuously (if it flashes, check the 24 VAC power supply)
Service LED ON continuously
Analog output module status LEDs ON continuously
Relay output module status LEDs ON continuously
Digital input module status LEDs Red -> green -> yellow -> red -> green -> yellow, cyclically every 0.5 sec
Table 76 Effects of pressing and holding down service button of I/O modules
An LED is defective if it is not lit as shown above.
Analog Input Modules Troubleshooting
case Problem Possible causes Remedy
1
Incorrect sensor
measurement
2
Unstable sensor
measurements
3
a voltage of about
8.88 V(*) is measured
(with an external voltmeter) at an open analog
input configured for:
NTC20kΩ or
Pt1000-1/-2 or
Pt3000 or
Balco 500 or
NTC10kΩ or
NI1000TK5000.
4
a voltage of about
8.88 V(*) is measured
(with an external voltmeter) at an open analog
input configured for:
0…10V with pull-up or
slow Digital Input
Wrong sensor configuration
Incorrect wiring
Sensor failure
Negative voltage on at least one channel
Incorrect grounding of active sensors
Sensor is not connected
Normal value for open input that is configured
to listed types
►
Reconfigure sensor
►
Rewire
►
Replace sensor
►
Check polarity of active sensor
inputs.
►
Ground active sensors individually
(see Fig. 62 and Fig. 63 on page 43
and following)
►
Connect the configured sensor
►
No action necessary
(*): voltage may differ slightly depending on the input impedance of the used voltmeter
Table 77 Failure modes of analog input modules
EN1B-0375GE51 R0308
74
Page 75
Excel 800 LION
Analog Output Modules Troubleshooting
case Problem Possible causes Remedy
1
All outputs always have
zero voltage
Manual override settings
Outputs are in safety position
Software problem
Internal undervoltage detection has been
►
Check manual override settings
►
Check communication
►
Power down and then power up
►
If problem persists, replace hardware
►
Replace hardware
activated
2
Unstable output voltage
Incorrect grounding of actuators
►
Ground actuators individually (see
Fig. 66 on page 47)
Table 78 Failure modes of analog output modules
Binary Input Modules Troubleshooting
case Problem Possible causes Remedy
1
Unexpectedly, all status
LEDs are always OFF
Internal overload protection has been
activated
►
Power down and then power up
Table 79 Failure modes of binary input modules
Relay Output Modules Troubleshooting
case Problem Possible causes Remedy
1
Unexpectedly, all outputs
are in unpowered position
Improper manual override settings
Outputs are in safety position
Software problem
Internal undervoltage detection has been
activated
►
Check manual override settings
►
Check communication
►
Power down and then power up
►
If problem persists, replace hardware
►
Replace hardware
Table 80 Failure modes of relay output modules
Floating Output Modules Troubleshooting
case Problem Possible causes Remedy
1
Unexpectedly, all outputs
are in unpowered position
Table 81 Failure modes of floating output modules
A “Frequently Asked Questions and Troubleshooting” document is available via the Honeywell Technical Assistance Center
(TAC) or, for Honeywell employees, on the Intranet under:
75 EN1B-0375GE51 R0308
Improper manual override settings
Outputs are in safety position
Software problem
Internal undervoltage detection has been
activated
http://web.ge51.honeywell.de/tac
►
Check manual override settings to
check outputs
►
Check communication
►
Power down and then power up
►
If problem persists, replace hardware
►
Replace hardware
Page 76
Excel 800 LION
Appendix 1: System Protective Earth Grounding
Excel 800 LION Systems and SELV
In order to avoid distribution of noise or earth ground
potential differences over networks or other connections, the
CLLIONLC01 Controller Module is designed to be in
compliance with SELV (Safety Extra-Low Voltage).
Furthermore, SELV offers the greatest possible safety
against electrical impact.
To support SELV, all Honeywell external (CRT series) or
internal transformers comply with standard EN60742.
Earth grounding is therefore not recommended.
Excel 800 LION Systems and Standard
EN60204-1
However, if compliance with EN60204-1 is required, note
the following:
General Information about EN60204-1
EN60204-1 defines electrical safety for a complete
application/machine including controllers, sensors, actuators
and any connected/controlled electrical device.
EN60204-1 requires controllers to be powered by PELV
(Protective Extra-Low Voltage) and earth grounding of the
secondary side of the used transformers or earth grounding
of the system ground.
Earth grounding is prescribed to prevent unexpected startup of connected rotating/moving machines due to an
insulation fault and double earth grounding somewhere in
the plant.
The use of an earth leakage monitor is also possible to fulfill
PELV if earth grounding is prohibited.
When is EN60204-1 Applicable to Excel 800 LION
Systems?
•Safety against electrical impact
EN60204-1 is not mandatory; this is because electrical
safety is provided by the use of SELV and transformers
according to standard EN60742.
• Safety against unexpected start-up of
rotating/moving machines
– If the application/plant does not contain machines that
can be harmful to the operator due to an unexpected
start-up, the standard EN60204-1 is not applicable.
If such machines are encountered, then EN60204-1 must be
followed. Grounding is required.
Earth Grounding of EN60204-1 Applicable
Systems
►
If system protective earth grounding is planned, use a
cable as short as possible for grounding:
min. 1.5 mm² (16 AWG).
►
For connection details, refer to the following examples.
Example 1
Connecting a single transformer with multiple Excel 800
LION Systems earth-grounded as per EN60204-1
►
Connect earth ground to terminal 1 of the CLLIONLC01
Controllers
Connecting an Excel 800 LION System together with other
controllers earth-grounded as per EN60204-1
Notes
• Use a noise-free earth ground inside the cabinet.
• Use one star-point to split power for controllers and field
devices.
• If the transformer is used for several controllers, each
controller ground has to be wired separately to the starpoint.
• If a field device that prohibits earth grounding is
connected to the system ground, an isolation monitoring
device must be used instead of earth grounding.
• If the field device transformer is physically far away from
the controller, earth grounding must still be performed for
the controller.
►
Connect earth ground to the respective terminal of the
controllers, see figure below.
Example 3
Connecting a C-Bus with controllers earth-grounded as per
EN60204-1
Notes
• Use a noise-free earth ground inside the cabinet.
• Do not use the controller terminals which are normally
used for C-Bus shield connection.
• Be sure to wire the shield only once per bus connection
to the earth ground; this is to prevent any current draw
over the shield.
• A permanent earth ground potential difference of more
than 24 VAC may destroy the related controllers.
►
Connect earth ground to the respective terminal of the
controllers, see figure below.
XCL5010C
C+C+C+C+
C-C-C-C-
16
1517 18
XCL5010XCL8010AXL50
55
448
SHIELD
96610
Fig. 99 Connecting and earth grounding mixed
controllers (single transformer)
NOTICE
Equipment damage!
Terminals 1 and 2 are assigned differently on the XCL5010
and CLLIONLC01 Controllers.
►
Make sure that earth ground is connected to the correct
terminal according to Fig. 99 and the respective
connection diagrams.
The XL40, XL50, XL100C, Distributed IO, Smart IO, and the
Excel 800 LION System can share one transformer.
The XC5010C Controller always requires its own
transformer.
If EN60204-1 is applicable for the given type of controller,
the system ground has the same potential as one terminal
of the power supply.
Noise-Free Earth Ground
(only once per connection)
max. 24 VAC potential
difference allowed
between Earth Grounds
Fig. 100 Connecting C-Bus with multiple controllers earth-
grounded as per EN60204-1
If a system ground of the controller is connected to the earth
ground, the available terminals for shielding the C-Bus must
not be used. Instead, the C-Bus shield must be connected
to the earth ground, but only once per bus connection.
77 EN1B-0375GE51 R0308
Page 78
Excel 800 LION
Appendix 2: Remote Communications
For remote communications with up to three centrals, a
modem or ISDN terminal adapter can be connected directly
to the modem interface of the CLLIONLC01 Controller
Module.
Notes
Remote communication via modem or ISDN terminal
adapter requires firmware version V2.1.0 or higher.
XBSi building supervisors are not supported for remote
communication.
Approved Modems
The following modem has been approved for use with the
Excel 800 LION:
Type Model Comment
Standard
modem
Table 82 Approved modem
Westermo TD-33
Modem or ISDN Terminal Adapter
Connection
The modem interface of the CLLIONLC01 Controller Module
accepts a standard modem cable with a female 9-pin
connector.
Fig. 101 Modem interface
►
Connect the cable that is supplied with the modem/ISDN
terminal adapter to the modem interface of the
CLLIONLC01 Controller.
Modem Requirements
Modems to be connected to CLLIONLC01 must support the
following requirements:
• Hayes compatible command set (not V150 or V151 =
Microsoft command set)
• Alpha-numeric return codes
• Modem must follow serial baud rate of the controller CPU
• Auto-bauding (baud rate fall-back)
• When carrier detect (connect) is reported, the carrier
must be on simultaneously at both modems (on controller
CPU side and on side of the central) ⇒ use same
modem
• After a switch-ON of the DTR line by the CPU or the
central, the modem must accept a dial command after 3
seconds
• Modem must answer AT commands in less than
3 seconds
EN1B-0375GE51 R0308 78
Page 79
Excel 800 LION
Modem Set-up
Standard Modem Behavior
If no special modem behavior is required, there is no need
to set up or initialize the modem/ISDN terminal adapter.
The CLLIONLC01 will automatically
•detect the device (MMI or modem) attached to the
modem interface,
• set the appropriate communication speed,
• adapt to alphanumeric return codes used by the
modem.
This automatic detection and adjustment can take up to
5 seconds.
Note
It is highly recommended to use a state-of-the-art modem
and leave it in its factory settings.
Automatic Baudrate Synchronization
The default communication speed between the
CLLIONLC01 and the local modem/ISDN terminal adapter is
9600 baud.
The communication speed between the modem and
terminal adapter and the central's modems/ISDN terminal
adapters is automatically synchronized by the two devices
to the highest speed that both of the devices are capable of.
This feature is called auto-bauding and is a feature that all
state-of-the-art-modems/ISDN terminal adapters provide
when left in their factory default settings.
The communication speed between the central and its
modem/ISDN terminal adapter is part of the modem set-up
at the central.
Auto / Manual Answer Detection
The CLLIONLC01 will automatically detect whether the
modem/ISDN terminal adapter is initialized in auto-answer
or manu-answer mode, and it will set the modem to manual
answer mode (S0 = 0).
Resetting the Modem
For those cases where it is not clear if the modem to be
used is in its factory settings, the modem can be reset to its
factory setting by using the RESET MODEM command in
the start-up sequence or through the HW configuration part
of the system info. sequence on the MMI. This will allow a
quick and easy modem reset without the need to run the
modem set-up software or the Windows™ terminal program.
The RESET MODEM command causes the following
commands to be sent to the modem:
1. ATZ
executes hardware reset on modem
2. AT&FX3&W
resets modem to factory configuration settings, configures
the modem not to wait for the public phone system dial tone,
and writes this to nonvolatile memory.
Set-up for Special Modem Behavior
If special modem/ISDN terminal adapter behavior is
required, the communication device should be set up
according to the instructions provided with it. This typically
involves running a setup program on a computer with the
device connected to the computer serial port or using the
Windows™ terminal program.
Set-up for In-house Telephone Systems
A common case of special modem behavior is when the
modem is connected to an in-house telephone network
requiring a prefix to be dialed before the destination number
to provide access to the public telephone network.
There are two important aspects of the special initialization
of the modem to consider:
• Do not wait for the public network dial tone.
– Typically the init command ATX3 will trigger the
modem to dial without waiting for a public network dial
tone.
– Save this modem set-up in the modem EEPROM with
the command AT&W.
– Check the modem handbook to verify the correct
commands.
– Note that these commands are executed automatically
with the RESET MODEM command.
• Add the prefix required for access to the public telephone
network to the destination telephone number.
– Depending on the in-house telephone system, a
certain prefix may have to be added to the destination
number in the central system configuration/site
definition screen prior to sending the set-up to the
remote CLLIONLC01 Controller.
Set-up for Limited Communication Speed
The communication speed of the modem can be fixed to a
lower rate in case of data transmission errors due to telephone line limitations. See the XI581/582 Buswide Operator
Interface User Guide (EN2B-0126GE51) for the procedure
for fixing the baud rate.
79 EN1B-0375GE51 R0308
Page 80
Excel 800 LION
Westermo TD-33 Setup Parameters
The Westermo TD-33 modem is the standard modem for
use with the Excel 800 LION.
The following is the initialization string for Excel
50/100C/500 with O.S. 2.01.xx or newer and Excel 800
LION:
AT&FE0X0&D2S0=0\V0&W0
The ATX command should be adapted according to your
telephone system. See also section "Set-up for In-house
Telephone Systems" above.
The following dip switch setting is required for
communication with Excel 800 LION:
Dip Switch Setting Comment
Dip switch 1 = ON Enables internal modem
watchdog
Others 0 = OFF Default setting
Table 83 Westermo TD-33 switch settings
Troubleshooting
In case of any problems the handbook of the modem or
ISDN terminal adapter must be consulted.
A “Frequently Asked Questions and Troubleshooting”
document is available via the Honeywell Technical
Assistance Center (TAC) or, for Honeywell employees, on
the Intranet under:
http://web.ge51.honeywell.de/tac
►
Go there, and enter the catchword "modemfaq" in the
search field.
EN1B-0375GE51 R0308 80
Page 81
Excel 800 LION
Appendix 3: Sensor Characteristics
Note
The following sensor characteristics do not include failures
due to:
• Sensor failures
• Wiring resistance or wiring failures
• Missreadings due to a meter connected to measure
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative: