Honeywell EXCEL 800 SPECIFICATION DATA

HONEYWELL EXCEL 5000 OPEN SYSTEM
FEATURES
Plug-and-play Panel Bus I/O modules for easy
L
Pluggable I/O modules: I/O module exchange without
Reuseability of existing applications (Excel 500, etc.)
Fast wiring with state-of-the-art push-in terminals (screw-
Wide range of sensors supported (NTC20k, NTC10kΩ,
The Excel 800 System (consisting of the XCL8010A Controller Module and connected Excel 800 Panel Bus and/or Excel 800 L highly cost-effective freely programmable control for heating, ventilation, and air conditioning (HVAC) systems. It performs a wide range of energy management functions, including optimum start/stop, night purge, and max. load demand. The Excel 800 System provides excellent value during installation and long-term operation. Its modular design enables the system to be expanded to meet growing needs. The use of "plug & play" Excel 800 Panel Bus I/O modules yields huge installation and commissioning cost-savings due to new, patented technologies, while the Excel 800 L
ONWORKS Bus I/O modules employ the LONWORKS
communication standard. The mixed Excel 800 Panel Bus I/O modules (XF830A and XFU830A) consist of a terminal socket with an integrated electronic module. The pluggable (i.e., non-mixed) Excel 800 Panel Bus (XF82x) or L consist of a terminal socket and a removable electronic module, allowing the socket to be mounted and wired before the electronic module is installed. Such removable electronic modules can be hot-swapped without disrupting the power and bus connections. Software updates, configuration, and commissioning are done automatically for all Excel 800 Panel Bus I/O Modules. The open L
rd
3
-party controllers and devices, and communication with other CentraLine / Honeywell devices (e.g. Excel 10 and Excel 12 room controllers). Remote service can be done via a modem / ISDN terminal adapter in connection with a building supervisor.
Direct Web is supported via Honeywell's OpenViewNet, which may be connected via C-Bus to the Excel 800.
ONWORKS Bus input/output modules) provides
ONWORKS Bus (XFL82x) I/O modules
ONWORKS standard enables easy integration of
Binary input LEDs can be configured for status display
Configurable safety position for outputs, in case of loss of
XCL8010A Controller Module with real-time clock.
Max. wiring flexibility due to optional accessories like aux.
Can be mounted in small installation housings.
Flexible I/O module mix covering all your application
Utmost flexibility to design and control your most complex
State-of-the-art control of critical applications thanks to
Fast firmware download (~90 sec) via serial connection.
C-Bus to upgrade from and operate with existing
Web access via optional OpenViewNet.
Dedicated modem interface for remote operation.
Human-Machine-Interface, Laptop connection.
Excel 800
SYSTEM
SPECIFICATION DATA
maintenance.
ONWORKS Bus I/O modules (FTT10-A, link power
compatible) for easy integration into any system.
rewiring the power and bus connections. Further, the separate installation of terminal sockets and electronic modules lower risk of damage and theft in the construction phase.
type terminals also available) and bridge connectors.
PT1000-1/-2, NI1000TK5000, PT3000, Balco500, 0/2…10 V, 0/4…20 mA). NOTE: The mixed I/O modules XF830A and XFU830A feature inputs suitable for signals from NTC20k sensors and 0/2…10 V, 0/4…20 mA, only!
(off/yellow) or alarm display (green / red) per channel. NOTE: The mixed I/O modules XF830A and XFU830A feature only non-configurable binary input LEDs!
communication with the Controller module.
terminals, manual disconnectors, and cross-connectors.
requirements.
applications through increased memory size.
short cycle times (30% faster than Excel 500).
Honeywell installations, thereby protecting your investment.
® U.S. Registered Trademark Copyright © 2009 Honeywell Inc. • All Rights Reserved EN0B-0564GE51 R0709
3.4
EXCEL 800 SYSTEM – PRODUCT DATA
SYSTEM OVERVIEW
EBI /
SymmetrE
Ethernet LAN/WAN
Modem
XI582 or XI882A
C-Bus
XCL8010 + XF8xx
Panel Interface (<40m)
LON
LON IO (XFL8xx)
BNA
for distribution within building
Fig. 1. Excel 5000 architecture (overview)
General
The Excel 800 Controller Module (XCL8010A) can communicate with a variety of other devices (see Fig. 4), including any combination of up to sixteen Panel I/O Modules and a large number of L room controllers, L
ONWORKS I/O modules, 3
devices). The Excel 800 Panel Bus I/O Modules communicate via the Panel Bus, while the Excel 800 L
ONWORKS Bus I/O modules utilize the LONWORKS
communication standard and can thus also communicate with other L
ONWORKS controllers.
The pluggable I/O modules consist of a terminal socket and a removable electronic module, allowing the socket to be mounted and wired before the electronic module is
ONWORKS devices (e.g.
rd
-party
Internet
Browser
OVN = OpenViewNet
Web-enabled
via OVN
XLWeb
C-Bus
Existing
IO (XF8xx)
XFCxxx XFCLxxx
installed. All such electronic modules can be swapped out without disrupting the power and bus connections: Simply unplug the “old” and insert the “new” module. Software updates, configuration, and commissioning are all done automatically by the Excel 800 Controller Module for all Panel Bus I/O Modules. The Excel 800 Panel Bus I/O Modules are addressed manually by adjusting their HEX switches. The Excel 800 L
ONWORKS I/O Modules are configured
using CARE. Alternatively, LonMaker and LNS plug-ins can also be used for configuration.
XL500
Controllers
XL10/12
EN0B-0564GE51 R0709
2
EXCEL 800 SYSTEM – PRODUCT DATA
X
X
X
X
X
X
X
X
pluggable
FLOATING
OUTPUT
LonWorks
pluggable
ANALOG INPUT
pluggable
ANALOG OUTPUT
XFLR822A
pluggable
BINARY INPUT
pluggable
RELAY OUTPUT
XFLR824A
BUS MODULES
PANE L
XFL821A
XFL822A XFL823A
XFR822A
FL824A
FR824A
FR825A
BUS MODULES
XCL8010A
CONTROLLER MODULE
XF821A
XS821-22
XSU821-22
XF822A XF823A
S823
SU823
F824A
S824-25
SU824-25
LonWorks or Panel Bus
Fig. 2. Overview of Excel 800 Modules
Table 1. Overview of Excel 800 Modules
order number description
XCL8010A
Panel Bus I/O Modules
XF821A
XF822A
XFR822A
XF823A
XF824A
XFR824A
XFR825A
XF830A
XFU830A
LONWORKS Bus I/O Modules
XFL821A
XFL822A
XFLR822A
XFL823A
XFL824A
XFLR824A
Terminal Sockets (not needed for the mixed I/O modules XF830A and XFU830A)
XS821-22
XSU821-22
XS823
XSU823
XS824-25
XSU824-25
Excel 800 Controller Module
Pluggable Panel Bus Analog Input Module (with 8 analog inputs)
Pluggable Panel Bus Analog Output Module (with 8 analog outputs)
Pluggable Panel Bus Analog Output Module (with 8 analog outputs and manual overrides)
Pluggable Panel Bus Binary Input Module (with 12 binary inputs)
Pluggable Panel Bus Relay Output Module (with 6 relay outputs)
Pluggable Panel Bus Relay Output Module (with 6 relay outputs and manual overrides)
Pluggable Panel Bus Floating Output Module (with 3 floating outputs and manual overrides)
Mixed Panel Bus I/O Module (with 8 analog inputs, 8 analog outputs, 12 binary inputs, and 6 relay outputs), with push-in terminals
Mixed Panel Bus I/O Module (with 8 analog inputs, 8 analog outputs, 12 binary inputs, and 6 relay outputs), with screw terminals
Pluggable L
Pluggable L
Pluggable L
Pluggable L
Pluggable L
Pluggable L
Push-in terminal socket for pluggable AI/AO modules (incl. connector bridge, swivel label)
Screw-type terminal socket for pluggable AI/AO modules (incl. connector bridge, swivel label)
Push-in terminal socket for pluggable BI modules (incl. connector bridge, swivel label)
Screw-type terminal socket for pluggable BI modules (incl. connector bridge, swivel label)
Push-in terminal socket for pluggable relay/floating output modules (incl. connector bridge, cross connector, swivel label)
Screw-type terminal socket for pluggable relay/floating output modules (incl. connector bridge, cross connector, swivel label)
ONWORKS Bus Analog Input module (with 8 analog inputs)
ONWORKS Bus Analog Output Module (with 8 analog outputs)
ONWORKS Bus Analog Output Module (with 8 analog outputs and manual overrides)
ONWORKS Bus Binary Input Module (with 12 binary inputs)
ONWORKS Bus Relay Output Module (with 6 relay outputs)
ONWORKS Bus Relay Output Module (with 6 relay outputs and manual overrides)
MIXED I/Os
XF830A, XFU830A
PANEL BUS I/O MODULES
3
EN0B-0564GE51 R0709
EXCEL 800 SYSTEM – PRODUCT DATA
Table 2. Overview of auxiliary parts and spare parts
order number description
XS812
Manual Disconnector Module for AI/AO/BI Modules (for manual disconnection of individual signals; useful during start-up). Plugged between Terminal Socket and Electronic Module. For pluggable I/O modules, only.
XS812RO
Manual Disconnector Module for Relay Output Modules (for manual disconnection of individual signals; useful during start-up). Plugged between Terminal Socket and Electronic Module. Not suitable for line voltage. For pluggable I/O modules, only.
XS814
Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block includes two groups with seven internally-connected push-in terminals. For pluggable I/O modules, only.
XS830
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9
XS831
A1 B1 A2 B2 A3 B3 A4 B4 G1 G2A5 B5 A6 B6 A7 B7 A8 B8
XS815
Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block consists of two groups of nine internally-connected push-in terminals. For XF830A and XFU830A, only.
Ten Auxiliary Terminal Blocks (for connection of 0…20 mA signals). Each terminal block supports up to 8 current inputs. For XF830A and XFU830A, only.
20 Cross-Connectors for connection of six relay commons. One Cross-Connector is included in the Terminal Socket package. For pluggable I/O modules, only.
XS817
40 Cross-Connectors for connection of three relay commons (if voltage in relay block 1 is different from voltage in relay block 2). For pluggable I/O modules, only.
XS816
10 Bridge Connectors. One Bridge Connector is included in the Terminal Socket package / in the mixed I/O module package.
XAL10
10 Swivel Labels Holders (for attaching the application-specific label printed with CARE). One Swivel Label Holder is included in each Terminal Socket package. For pluggable I/O modules, only.
XAL11
10 Swivel Label Holders for Mixed I/O modules. One Swivel Label Holder is included in each mixed I/O module package. For mixed I/O modules, only.
XW586
RJ45
XW882
Modem cable for XCL8010A Controller Module.
Adapter cable for connection of XCL8010A Controller Module to XI582 Operator Interface (alternatively, XW586 + XW582 can be used).
XW885
RJ45
NOTE: All Excel 800 I/O Modules (pluggable and mixed) are protected against short circuit, 24 Vac +20% and 30 Vdc.
Download cable (alternatively, XW586 + XW585 can be used).
EN0B-0564GE51 R0709
4
EXCEL 800 SYSTEM – PRODUCT DATA
Table 3. Pluggable Excel 800 I/O Module specifications
Module Analog Input Analog Output Binary Input Relay Output Floating Output
Panel XF821A XF822A, XFR822A XF823A XF824A, XFR824A XFR825A
LONWORKS
no. of I/Os 8 analog inputs 8 analog outputs 12 binary inputs 6 relay outputs 3 floating outputs charac­teristics
Module Analog Inputs Analog Outputs Binary Inputs Relay Outputs
XF830A / XFU830A
XFL821A XFL822A, XFLR822A XFL823A XFL824A, XFLR824A
Linear Graph 0..10 Vdc with pull-up, 0(2)…10 Vdc without pull-up NTC20k (-50…+150 °C, default) NTC10k (-30…+100 °C)
(-50…150°C)
PT
1000-1
(0…400°C)
PT
1000-2
NI1000TK5000 (-30…+130 °C)
(-50…150°C)
PT
3000
BALCO
(-30…120°C)
500
Also configurable as: binary inputs Linear graph (0…10 V with
pull-up)
Features:
16-bit resolution configurable offset per
input
auxiliary voltage: 10 Vdc,
= 5 mA
I
max
0…11 Vdc / ± 1 mA Also configurable as: floating outputs or binary outputs (0 V / 10 V)
Features:
8-bit resolution
(default)
Safety position
(remain, 0%, 50%, 100%)
red LED per output light intensity follows
output level in auto
Version with manual override (R):
1 potentiometer per
output
auto feedback signal
(mode + value)
blinking in manual
override position
static binary inputs (default: dry contact) Also configurable as: totalizers (20 Hz)
Features:
1 LED per input Color mode can
be set per input to OFF/yellow or green/red using CARE
relay outputs (default)
Features:
Changeover relays Voltage: 19…250 Vac,
1…29 Vdc, P>50 mW
max. total current:
12 A
current per relay:
N.O.: 4(4) A ac. or 4(1) A dc, N.C.: 2(1) A ac or 4(1) A dc
Safety position
(remain, 0%, 100%)
yellow LED per output
Version with manual override (R):
1 switch per output auto feedback signal
(mode + value)
blinking in manual
override position
Table 4. Mixed Excel 800 Panel Bus I/O module specifications
Number: 8
Characteristics:
Linear Graph 0..10 Vdc with pull-up, 0(2)…10 Vdc without pull-up NTC20k (-30…+110 °C, default)
Features:
10-bit resolution configurable offset per input
Number: 8
Characteristics:
0…11 Vdc / ± 1 mA, default
Also configurable as: binary outputs (0 V / 10 V)
Features:
10-bit resolution (default) Safety position (remain,
0%, 50%, 100%)
Number: 12
Characteristics:
static binary input (default: dry contact) ON: < 1.6 k OFF: > 90 k Also configurable as: totalizers (15 Hz)
Features:
1 yellow LED per input
Number: 6
Characteristics:
relay outputs (default)
Features:
Voltage: 24 Vac/dc,
P>50 mW
max. total current: 3 A (ac
or dc)
current per relay: 500 mA normally-open contacts: P
> 50 mW, voltage: 24 V (ac or dc)
yellow LED per output
floating outputs
Features:
2 relays per
floating output
Voltage:
19…250 Vac, 1…29 Vdc, P>50 mW
max. total current:
12 A
current per relay:
N.O.: 4(4) A ac or 4(1) A dc, N.C.: 2(1) A ac or 4(1) A dc
1 potentiometer per
floating output
2 LEDs per output:
green: relay 1 closed, red: relay 2 closed
blinking in manual
override position
auto feedback sig-
nal (mode + value)
5
EN0B-0564GE51 R0709
EXCEL 800 SYSTEM – PRODUCT DATA
A
V
V
A
A
A
XCL8010A CONTROLLER MODULE
Fig. 3. XCL8010A Controller Module
The XCL8010A Controller Module can communicate with a variety of other devices (see Fig. 4), including any com­bination of up to sixteen Panel I/O Modules and/or L devices (e.g. room controllers). A total of 381 data-points (of all types, e.g. internal virtual data-points and hardware data-points) are permitted. Typically, HVAC applications require an equal number of internal virtual data-points and hardware data-points.
Up to 40 m distance between the XCL8010A and the Panel I/O Modules.
HMI INTERFACE and LEDs
PANEL BUS / LonWorks
TERMINALS
71 COM a
72 COM b
73 24V
~
74 24V 0
~
LonWorks
INTERFACE
LonWorks
TERMINALS
C-BUS TERMINATION SWITCH
I/O BUS SELECTION SWITCH
MODEM INTERFACE and LEDs
87 65 43 21 87 65 43 21
LON
LON
LON SERVICE
BUTTON
LON SERVICE
LED
11 1
12 285
13 396
14 410 7
C-Bus
C-Bus
out
in
C-BUS
TERMINALS
C-BUS Tx LED
C-BUS Rx LED
C-BUS RESET PC/HMI
RESET
BUTTON
I/O Bus
Modem
Panel
21
LON
RxTx
S1 S2
9.6k all
76k
76k
C-Bus
mid
end
87 6543
Fig. 4. XCL8010 Controller Module features
ONWORKS
PANEL BUS / LonWorks
TERMINALS
COM a 75
COM b 76
24V 77
~
24V 0
~ 78
Honeywell
POWER
!
Power/
Alarm
LED
LARM LED
COM
71
A
COM
72 76
B
24
73 77
VAC 24
V
74
AC_
8 7 65 43
2 1
LON
11
1
12
13
14
LON
LON
LON
8
2
1
2
C+ C+
C- C-9 6
SHIELD SHIELD
10 7
5
*WATCHDOG
RELAY
Fig. 5. XCL8010A Controller Module, terminal assignment
Electrical Specifications
Operating Voltage
24 Vac, ± 20%, 21…30 Vdc
The Excel 800 System (XCL8010 Controller Module and connected Excel 800 I/O Modules together with field devices) can be powered by one or more external transformers.
Memory
128 kB EPROM
512 kB RAM
2 MB Flash EPROM (firmware and application)
Watchdog
The watchdog output is active if the Excel 800 Controller Module is not operating properly.
Microprocessor
16-bit processor (TMP 91 CY22). 22 MHz
Memory and Realtime Clock Backup
In case of power failure, the super capacitor saves RAM content and real-time clock for 72 hours (environmentally friendly; no problems disposing of dead batteries).
COM
75
A
COM
B
24 AC
24
V
78
C_
24
1
AC
24
V
2
C_
24
V
3
C_
*
4
NC
EN0B-0564GE51 R0709