• Pluggable I/O modules: I/O module exchange without
• Reuseability of existing applications (Excel 500, etc.)
• Fast wiring with state-of-the-art push-in terminals (screw-
• Wide range of sensors supported (NTC20kΩ, NTC10kΩ,
GENERAL
The Excel 800 System (consisting of the XCL8010A
Controller Module and connected Excel 800 Panel Bus and/or
Excel 800 L
highly cost-effective freely programmable control for heating,
ventilation, and air conditioning (HVAC) systems. It performs
a wide range of energy management functions, including
optimum start/stop, night purge, and max. load demand. The
Excel 800 System provides excellent value during installation
and long-term operation. Its modular design enables the
system to be expanded to meet growing needs.
The use of "plug & play" Excel 800 Panel Bus I/O modules
yields huge installation and commissioning cost-savings due
to new, patented technologies, while the Excel 800
L
ONWORKS Bus I/O modules employ the LONWORKS
communication standard.
The mixed Excel 800 Panel Bus I/O modules (XF830A and
XFU830A) consist of a terminal socket with an integrated
electronic module. The pluggable (i.e., non-mixed) Excel 800
Panel Bus (XF82x) or L
consist of a terminal socket and a removable electronic
module, allowing the socket to be mounted and wired before
the electronic module is installed. Such removable electronic
modules can be hot-swapped without disrupting the power
and bus connections. Software updates, configuration, and
commissioning are done automatically for all Excel 800 Panel
Bus I/O Modules.
The open L
rd
3
-party controllers and devices, and communication with
other CentraLine / Honeywell devices (e.g. Excel 10 and
Excel 12 room controllers).
Remote service can be done via a modem / ISDN terminal
adapter in connection with a building supervisor.
Direct Web is supported via Honeywell's OpenViewNet, which
may be connected via C-Bus to the Excel 800.
ONWORKS Bus input/output modules) provides
ONWORKS Bus (XFL82x) I/O modules
ONWORKS standard enables easy integration of
• Binary input LEDs can be configured for status display
• Configurable safety position for outputs, in case of loss of
• XCL8010A Controller Module with real-time clock.
• Max. wiring flexibility due to optional accessories like aux.
• Can be mounted in small installation housings.
• Flexible I/O module mix covering all your application
• Utmost flexibility to design and control your most complex
• State-of-the-art control of critical applications thanks to
• Fast firmware download (~90 sec) via serial connection.
• C-Bus to upgrade from and operate with existing
• Web access via optional OpenViewNet.
• Dedicated modem interface for remote operation.
• Human-Machine-Interface, Laptop connection.
Excel 800
SYSTEM
SPECIFICATION DATA
maintenance.
ONWORKS Bus I/O modules (FTT10-A, link power
compatible) for easy integration into any system.
rewiring the power and bus connections. Further, the
separate installation of terminal sockets and electronic
modules lower risk of damage and theft in the construction
phase.
type terminals also available) and bridge connectors.
PT1000-1/-2, NI1000TK5000, PT3000, Balco500,
0/2…10 V, 0/4…20 mA). NOTE: The mixed I/O modules
XF830A and XFU830A feature inputs suitable for signals
from NTC20kΩ sensors and 0/2…10 V, 0/4…20 mA, only!
(off/yellow) or alarm display (green / red) per channel.
NOTE: The mixed I/O modules XF830A and XFU830A
feature only non-configurable binary input LEDs!
communication with the Controller module.
terminals, manual disconnectors, and cross-connectors.
requirements.
applications through increased memory size.
short cycle times (30% faster than Excel 500).
Honeywell installations, thereby protecting your
investment.
The Excel 800 Controller Module (XCL8010A) can
communicate with a variety of other devices (see Fig. 4),
including any combination of up to sixteen Panel I/O
Modules and a large number of L
room controllers, L
ONWORKS I/O modules, 3
devices). The Excel 800 Panel Bus I/O Modules
communicate via the Panel Bus, while the Excel 800
L
ONWORKS Bus I/O modules utilize the LONWORKS
communication standard and can thus also communicate
with other L
ONWORKS controllers.
The pluggable I/O modules consist of a terminal socket
and a removable electronic module, allowing the socket to
be mounted and wired before the electronic module is
ONWORKS devices (e.g.
rd
-party
Internet
Browser
OVN = OpenViewNet
Web-enabled
via OVN
XLWeb
C-Bus
Existing
IO (XF8xx)
XFCxxxXFCLxxx
installed. All such electronic modules can be swapped out
without disrupting the power and bus connections: Simply
unplug the “old” and insert the “new” module.
Software updates, configuration, and commissioning are
all done automatically by the Excel 800 Controller Module
for all Panel Bus I/O Modules.
The Excel 800 Panel Bus I/O Modules are addressed
manually by adjusting their HEX switches.
The Excel 800 L
ONWORKS I/O Modules are configured
using CARE.
Alternatively, LonMaker and LNS plug-ins can also be
used for configuration.
XL500
Controllers
XL10/12
EN0B-0564GE51 R0709
2
EXCEL 800 SYSTEM – PRODUCT DATA
X
X
X
X
X
X
X
X
pluggable
FLOATING
OUTPUT
LonWorks
pluggable
ANALOG INPUT
pluggable
ANALOG OUTPUT
XFLR822A
pluggable
BINARY INPUT
pluggable
RELAY OUTPUT
XFLR824A
BUS MODULES
PANE L
XFL821A
XFL822AXFL823A
XFR822A
FL824A
FR824A
FR825A
BUS MODULES
XCL8010A
CONTROLLER MODULE
XF821A
XS821-22
XSU821-22
XF822AXF823A
S823
SU823
F824A
S824-25
SU824-25
LonWorks or Panel Bus
Fig. 2. Overview of Excel 800 Modules
Table 1. Overview of Excel 800 Modules
order number description
XCL8010A
Panel Bus I/O Modules
XF821A
XF822A
XFR822A
XF823A
XF824A
XFR824A
XFR825A
XF830A
XFU830A
LONWORKS Bus I/O Modules
XFL821A
XFL822A
XFLR822A
XFL823A
XFL824A
XFLR824A
Terminal Sockets (not needed for the mixed I/O modules XF830A and XFU830A)
XS821-22
XSU821-22
XS823
XSU823
XS824-25
XSU824-25
Excel 800 Controller Module
Pluggable Panel Bus Analog Input Module (with 8 analog inputs)
Pluggable Panel Bus Analog Output Module (with 8 analog outputs)
Pluggable Panel Bus Analog Output Module (with 8 analog outputs and manual overrides)
Pluggable Panel Bus Binary Input Module (with 12 binary inputs)
Pluggable Panel Bus Relay Output Module (with 6 relay outputs)
Pluggable Panel Bus Relay Output Module (with 6 relay outputs and manual overrides)
Pluggable Panel Bus Floating Output Module (with 3 floating outputs and manual overrides)
Mixed Panel Bus I/O Module (with 8 analog inputs, 8 analog outputs, 12 binary inputs, and 6 relay outputs), with
push-in terminals
Mixed Panel Bus I/O Module (with 8 analog inputs, 8 analog outputs, 12 binary inputs, and 6 relay outputs), with
screw terminals
ONWORKS Bus Analog Input module (with 8 analog inputs)
ONWORKS Bus Analog Output Module (with 8 analog outputs)
ONWORKS Bus Analog Output Module (with 8 analog outputs and manual overrides)
ONWORKS Bus Binary Input Module (with 12 binary inputs)
ONWORKS Bus Relay Output Module (with 6 relay outputs)
ONWORKS Bus Relay Output Module (with 6 relay outputs and manual overrides)
MIXED I/Os
XF830A, XFU830A
PANEL BUS I/O MODULES
3
EN0B-0564GE51 R0709
EXCEL 800 SYSTEM – PRODUCT DATA
Table 2. Overview of auxiliary parts and spare parts
order number description
XS812
Manual Disconnector Module for AI/AO/BI Modules (for manual disconnection of individual signals;
useful during start-up). Plugged between Terminal Socket and Electronic Module. For pluggable
I/O modules, only.
XS812RO
Manual Disconnector Module for Relay Output Modules (for manual disconnection of individual
signals; useful during start-up). Plugged between Terminal Socket and Electronic Module. Not
suitable for line voltage. For pluggable I/O modules, only.
XS814
Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block includes two
groups with seven internally-connected push-in terminals. For pluggable I/O modules, only.
Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block consists of
two groups of nine internally-connected push-in terminals. For XF830A and XFU830A, only.
Ten Auxiliary Terminal Blocks (for connection of 0…20 mA signals). Each terminal block supports
up to 8 current inputs. For XF830A and XFU830A, only.
20 Cross-Connectors for connection of six relay commons. One Cross-Connector is included in
the Terminal Socket package. For pluggable I/O modules, only.
XS817
40 Cross-Connectors for connection of three relay commons (if voltage in relay block 1 is different
from voltage in relay block 2). For pluggable I/O modules, only.
XS816
10 Bridge Connectors. One Bridge Connector is included in the Terminal Socket package / in the
mixed I/O module package.
XAL10
10 Swivel Labels Holders (for attaching the application-specific label printed with CARE). One
Swivel Label Holder is included in each Terminal Socket package. For pluggable I/O modules,
only.
XAL11
10 Swivel Label Holders for Mixed I/O modules. One Swivel Label Holder is included in each
mixed I/O module package. For mixed I/O modules, only.
XW586
RJ45
XW882
Modem cable for XCL8010A Controller Module.
Adapter cable for connection of XCL8010A Controller Module to XI582 Operator Interface
(alternatively, XW586 + XW582 can be used).
XW885
RJ45
NOTE: All Excel 800 I/O Modules (pluggable and mixed) are protected against short circuit, 24 Vac +20% and 30 Vdc.
Download cable (alternatively, XW586 + XW585 can be used).
be set per input
to OFF/yellow
or green/red
using CARE
relay outputs (default)
Features:
Changeover relays
Voltage: 19…250 Vac,
1…29 Vdc, P>50 mW
max. total current:
12 A
current per relay:
N.O.: 4(4) A ac. or
4(1) A dc,
N.C.: 2(1) A ac or
4(1) A dc
Safety position
(remain, 0%, 100%)
yellow LED per output
Version with manual
override (R):
1 switch per output
auto feedback signal
(mode + value)
blinking in manual
override position
Table 4. Mixed Excel 800 Panel Bus I/O module specifications
Number: 8
Characteristics:
Linear Graph 0..10 Vdc with
pull-up, 0(2)…10 Vdc without
pull-up
NTC20kΩ (-30…+110 °C,
default)
Features:
10-bit resolution
configurable offset per input
Number: 8
Characteristics:
0…11 Vdc / ± 1 mA, default
Also configurable as: binary
outputs (0 V / 10 V)
Features:
10-bit resolution (default)
Safety position (remain,
0%, 50%, 100%)
Number: 12
Characteristics:
static binary input (default:
dry contact)
ON: < 1.6 kΩ
OFF: > 90 kΩ
Also configurable as:
totalizers (15 Hz)
Features:
1 yellow LED per input
Number: 6
Characteristics:
relay outputs (default)
Features:
Voltage: 24 Vac/dc,
P>50 mW
max. total current: 3 A (ac
or dc)
current per relay: 500 mA
normally-open contacts: P
> 50 mW, voltage: 24 V (ac
or dc)
yellow LED per output
floating outputs
Features:
2 relays per
floating output
Voltage:
19…250 Vac,
1…29 Vdc,
P>50 mW
max. total current:
12 A
current per relay:
N.O.: 4(4) A ac or
4(1) A dc,
N.C.: 2(1) A ac or
4(1) A dc
1 potentiometer per
floating output
2 LEDs per output:
green: relay 1
closed, red: relay 2
closed
blinking in manual
override position
auto feedback sig-
nal (mode + value)
5
EN0B-0564GE51 R0709
EXCEL 800 SYSTEM – PRODUCT DATA
A
V
V
A
A
A
XCL8010A CONTROLLER MODULE
Fig. 3. XCL8010A Controller Module
The XCL8010A Controller Module can communicate with a
variety of other devices (see Fig. 4), including any combination of up to sixteen Panel I/O Modules and/or L
devices (e.g. room controllers).
A total of 381 data-points (of all types, e.g. internal virtual
data-points and hardware data-points) are permitted.
Typically, HVAC applications require an equal number of
internal virtual data-points and hardware data-points.
Up to 40 m distance between the XCL8010A and the Panel
I/O Modules.┴
The Excel 800 System (XCL8010 Controller Module and
connected Excel 800 I/O Modules together with field devices)
can be powered by one or more external transformers.
Memory
• 128 kB EPROM
• 512 kB RAM
• 2 MB Flash EPROM (firmware and application)
Watchdog
The watchdog output is active if the Excel 800 Controller
Module is not operating properly.
Microprocessor
16-bit processor (TMP 91 CY22). 22 MHz
Memory and Realtime Clock Backup
In case of power failure, the super capacitor saves RAM
content and real-time clock for 72 hours (environmentally
friendly; no problems disposing of dead batteries).
COM
75
A
COM
B
24
AC
24
V
78
C_
24
1
AC
24
V
2
C_
24
V
3
C_
*
4
NC
EN0B-0564GE51 R0709
6
XI582 OPERATOR INTERFACE
The XCL8010A can be connected with an XI582 Operator
Interface or PC-based XL-Online operator and service
software.
Fig. 6. The XI582 Operator Interface
The XI582 Operator Interface is the command and information center of the Excel 800 System. With it, data can be
entered and displayed. Information such as current temperature values, control status, etc. can also be displayed.
The menu-driven, 6-line, backlit LCD graphic display with 34
characters per line, together with eight clearly marked keys,
makes the device easy to use.
The XI582 is connected to the HMI Interface on the front of
the Excel 800 Controller Module. The XI582 can be mounted
up to 15 m (48 ft.) away from the Controller Module. This can
be extended to 100 m (328 ft.) using line drivers.
Fig. 7. The XI882A Operator Interface
XI882A OPERATOR INTERFACE
The XI882A Operator Interface is an easy-to-operate and
robust operator unit for the entire EXCEL 5000 range of plant
controllers.
The touch-panel operation screens allow for easy and selfexplanatory operation by finger-tip or by touch-pen (supplied).
User-configurable fast-access lists can contain selected datapoints, time programs, and parameters, thus permitting plantoriented and customer-oriented operation.
EXCEL 800 SYSTEM – PRODUCT DATA
The XI882 Operator Interface can be connected to the HMI
interface of the XCL8010
XW882 cable or an XW586 cable together with an XW585
cable. Graphic trending of datapoints is supported.
Controller Module using either an
XL-ONLINE
The PC-based XL-Online is the local intelligent operating and
service software. It performs all the operating functions of the
XI582 as well as having the advantages of a PC. Not only can
the XL-Online make major modifications such as changing
setpoint values and time program switching points, it also
offers all service and commissioning functions.
XL-Online can be operated at five different access levels,
three of which are password-protected. A printer can be
connected to the parallel interface of the PC to log alarms and
error messages. As with the XI582, the PC with the XL-Online
operator and service software can be placed up to 15 meters
from the computer module. Line drivers allow distances of up
to 100 m (328 ft.).
Communication
Human-Machine Interface
The XCL8010A Controller Module is equipped with an HMI
Interface (RJ45 socket serving as a serial port) for the
connection of HMIs, e.g.:
• the XI582 Operator Interface or the XI882A Operator
Interface, or
• a laptop (with XL-Online / CARE).
C-Bus Interface
Up to 30 C-bus devices (e.g. controllers, etc.) can
communicate with one another and a PC central via the Cbus interface. The C-bus must be connected through the
individual controllers (open ring topology).
Web Interface
The optional OpenViewNet™ (OVN, see also Fig. 1 on page
2) is an intelligent BMS (Building Management System) that
interfaces Excel 800 Controller Modules on one end and
provides TCP/IP interface on the other. The device is then IPenabled and accessible from anywhere in the world. The
OpenViewNet’s processor and in-house memory hosts and
runs both the operating system and the application that
enables a user to monitor and supervise buildings remotely.
Notification of alarms and events are provided so that actions
can be taken accordingly. You can also generate reports,
schedule them to run periodically, use customized graphics
for monitoring, and trend important data off-line or online. The
processing of data between the device and the clients is
distributed to utilize the resources effectively and efficiently.
7
EN0B-0564GE51 R0709
EXCEL 800 SYSTEM – PRODUCT DATA
LONWORKS Interface
The LONWORKS bus is a 78-kilobit serial link that uses transformer isolation so that the bus wiring does not have a
polarity; that is, it is not important which of the two L
bus terminals are connected to each wire of the twisted pair.
The L
ONWORKS bus can be wired in daisy chain, star, loop or
any combination thereof as long as the max. wire length
requirements are met. The recommended configuration is a
daisy chain with two bus terminations. This layout allows for
max. L
ONWORKS bus length, and its simple structure presents
the least number of possible problems, particularly when
adding on to an existing bus.
ONWORKS
Modem Interface
The XCL8010A Controller Module is equipped with a Modem
Interface (RJ45 socket serving as a serial port) for the
connection of a modem or an ISND terminal adapter.
Panel Bus Interface
The XCL8010A Controller Module features a panel bus
interface (max. 40 m), polarity-insensitive for easy wiring.
Deterministic bus (cycle time: 250 ms to scan all connected
Panel I/O Bus Modules).
PROGRAMMING
The Excel 800 System includes the “CARE” software package
specially designed to meet the requirements of application
engineers. The easy-to-use, menu-driven software features
the following functions:
• data point description,
• time program,
• alarm handling,
• application program (DDC program),
• password protection,
• L
ONWORKS configuration.
Data Point Description
Data points are the basis of the Excel 800 System. They contain system-specific information such as values, status, limit
values, and default settings. The user has easy access to
data points and the information that they contain. The user
can recall and modify information in the data points.
Time Program
The time program can be used to enter the setpoint or status
at any time for any data point. The following time programs
are available:
• daily program,
• weekly program,
• annual program,
• TODAY function,
• special day list.
Daily programs are used to create a weekly program. The
annual program is created automatically by multiplying the
weekly program and then incorporating daily programs. The
TODAY function allows direct changes to the switching program. It allows you to allocate a setpoint or status to the
selected data point for a defined period of time.
Alarm Handling
The alarm handling facility offers system security. Alarm
signals can, for example, alert the operator to scheduled
maintenance work. All alarms that occur are stored in data
files and reported immediately. If your system configuration
allows, you can also list alarms on a printer or transmit alarms
to higher-level devices via the local bus or a modem.
There are two types of alarms, critical and non-critical. Critical
alarms (e.g. system alarms caused by communication
failures) have priority over non-critical alarms. To distinguish
between alarm types, you can generate your own alarm
messages or use pre-programmed system messages. The
following events all generate alarm messages:
• exceeding limit values,
• overdue maintenance work,
• totalizer readings,
• digital data point changes of state.
The alarm buffer can contain up to 99 alarms.
Application Program (DDC program)
You can use the Honeywell CARE programming tool to create
application programs for your system. A set of predefined
applications (MODAL) is available in order to provide state-ofthe-art applications without the need of programming.
Password Protection
The Excel 800 System is also protected by passwords. This
ensures that only authorized persons have access to system
data. There are four operator levels, each protected by its
own password.
Operator level 1: Read only. The operator can display information about setpoints, switching points, and operating hours.
Operator level 2: Read and make limited changes. The
operator can display system information and modify certain
pre-set values.
Operator level 3: Read and make changes. System
information can be displayed and modified.
Operator level 4: Access level for tools (e.g. CARE, XLOnline).
Trending
The Excel 800 System provides controller-based trending.
This feature allows historical values to be stored in the
Controller Module. Both time-based or value-hysteresis-based
trending are possible.
EN0B-0564GE51 R0709
8
EXCEL 800 I/O MODULES
A
A
XCL8010A Controller Module
I/O Bus
Panel
LON
S1 S2
2
31
32
33
PRESS
COM a
COM b
24V
~
24V 0
~
PRESS
Honeywell
21
8765 4 32 1
3
41
42
43
1234
!
21
AUX
GNDGND
Power/
Alarm
9
PRESS
Honeywell
1234
0
100
AUTO
AA
!
21
51
616261
52
62
AUX
53
6363
GNDGND
9
22 12345678
10 11 12 13 14 15 16 17 18 25 26
PRESS
22 12345678
10 11 12 13 14 15 16 17 18 25 26
876 543
Modem
Rx Tx
5
4
3
6
2
7
1
8
0
9
F
A
E
B
D
C
71 COM a
72 COM b
73 24V
~
74 24V 0
~
LON
C-BUS RESET PC/HMI
876543
21
111
12285
13396
144
LON
10 7
C-Bus
in
C-Bus
out
11
12
13
9.6k all
76k
76k
AAA
S1 S2
mid
end
C-Bus
71 COM a
72 COM b
73 24V
~
74 24V 0
~
1
21
22
23
144424543464 25
Fig. 8. Excel 800 Controller and I/O Modules on DIN rails
General
Each Excel 800 I/O Module is equipped with:
• one green power LED
• one yellow status LED
Overvoltage Protection
All inputs and outputs are protected against 24 Vac and
40 Vdc overvoltage as well as against short-circuiting.
Service LED
Each I/O Module is equipped with a yellow service LED for
easy diagnosis of failures.
Microprocessor
Each I/O Module is equipped with its own microprocessor.
Panel Bus I/O Modules
Up to 16 I/O modules in any combination of models may be
connected.
Addressing is performed using the HEX switch.
The Excel 800 Controller Module and Panel I/O Modules can
be separated by up to 40 m. Firmware maintenance is
automatically handled by the XCL8010A.
LonWorks Bus I/O Modules
The LONWORKS Bus I/O Modules can be used with any
L
ONWORKS controller.
In addition to the main microprocessor, the L
I/O Modules also have their own Neuron chip (3120). Each
LonWorks I/O Module is equipped with an FTT-10A
transceiver (linki power compatible).
A L
ONWORKS service button is located on each terminal
socket.
PRESS
S1 S2
5
4
3
6
2
7
1
8
0
9
F
A
E
B
D
C
Honeywell
5678
1 234
!
AI/AOV
BI
GND
Excel 800 I/O Modules
PRESS
S1 S2
5
4
3
6
2
7
1
8
0
9
F
A
E
B
D
C
Honeywell
5678
0
100
AUTO
AAAA
!
11
12
AI/AOV
13
S1 S2
5
4
3
6
2
7
1
8
0
9
F
A
E
B
D
C
PRESS
S1 S2
31
32
33
Honeywell
11 12
!
5
4
3
6
2
7
1
8
0
9
F
A
E
B
D
C
Honeywell
56
--1
--0
--AUTO
!
41
51
42
52
43
53
5 6 7 8 9 10
123456789101112
13 14 15 16 17 18 19 20 21 22 23 2 4 25 26
PRESS
1234
21
22
23
144424543464 25
ONWORKS Bus
616261
62
6363
EXCEL 800 SYSTEM – PRODUCT DATA
9
EN0B-0564GE51 R0709
EXCEL 800 SYSTEM – PRODUCT DATA
Analog Input Modules
Fig. 9. XF821A Panel Bus AI Module (shown with socket)
and XFL821A LonWorks Bus AI Module (shown without
socket)
The pluggable Excel 800 Analog Input Modules, with 8 analog
inputs, are available in the following versions:
• XF821A Panel Bus Analog Input Module
• XFL821A L
They are installed with the XS821-22 or XSU821-22 Terminal
Socket (incl. one connector bridge and one swivel label).
Accessory disconnector module: XS812 (see also Table 2 on
page 4).
ONWORKS Bus Analog Input Module
Features
• 0…10 Vdc, 2…10 Vdc without pull-up
• 0…10 Vdc with pull-up (linear graph, e.g. used for wall
module connection)
• 0/4…20 mA, needs 499 Ω resistor in parallel
• NTC20kΩ (-50…+150 °C, default)
• NTC10kΩ (-30…+100 °C)
• PT1000-1 (-50…+150 °C)
• PT1000-2 (0…+400 °C)
• NI1000TK5000 (-30…+130 °C)
• PT3000 (-50…+150 °C)
• BALCO500 (-30…+120 °C)
• Binary input
• 16-bit resolution
• Configurable offset per input
• Auxiliary voltage: 10 Vdc, I
• Sensor failure detection
MAX
= 5 mA
71
COM a
COM b
72
73
24V~
24V~0
74
Vaux Vau xAI4AI3AI2AI1AI5 AI6 AI7AI8
12123224
9 10
GND GNDGND GND GND GND GND GND GND GND
13121114 15 16 17 18
3
121222
5
4
S2S1
4
5
3
6
2
7
1
8
0
9
F
A
E
B
C
D
678
5
678
Vaux
COM a
COM b
24V~
24V~0
75
76
77
78
AI / AO
GNDGND
9 102513 14 15 16 17 1811 1226
Fig. 10. Excel 800 Analog Input Modules (schematic)
2625
EN0B-0564GE51 R0709
10
EXCEL 800 SYSTEM – PRODUCT DATA
V
A
Analog Output Modules
XF822AXFL822A
Fig. 11. XF822A Panel Bus AO Module and XFL822A
LonWorks Bus AO Module (both shown without socket)
71
COM a
COM b
72
73
24V~
24V~0
74
NC NCAO4AO3AO2AO1AO5 AO6 AO7 AO8
12123224
9 10
GND GNDGND GND GND GND GND GND GND GND
13121114 15 16 17 18
121222
3
5
4
S2S1
4
5
3
2
1
0
F
E
C
D
678
5
aux
GNDGND
COM a
6
7
COM b
8
9
A
B
24V~0
678
24V~
75
76
77
78
2625
I / AO
Fig. 12. XFR822A Panel Bus AO Module (shown with
socket) and XFLR822A LonWorks Bus AO Module
(shown without socket)
The pluggable Excel 800 Analog Output Modules, with 8
analog ouputs, are available in the following versions:
• XF822A Panel Bus Analog Output Module (without
manual overrides)
• XFR822A Panel Bus Analog Output Module (with manual
overrides)
• XFL822A L
ONWORKS Bus Analog Output Module (without
manual overrides)
• XFLR822A L
ONWORKS Bus Analog Output Module (with
manual overrides)
They are installed with the XS821-22 or XSU821-22 Terminal
Socket (incl. one connector bridge and one swivel label).
Accessory disconnector module: XS812 (see also Table 2 on
page 4).
9 102513 14 15 16 17 1811 1226
Fig. 13. Excel 800 Analog Output Modules (schematic)
Features
• 0…11 Vdc, +/-1 mA
• Floating actuator (requires MCD3)
• Binary output (0 V / 10 V)
• red LED per output (brightness according to signal level)
• Optional versions with manual override potentiometers
(Auto, 0…100%; LED flashes in override mode)
• Feedback on manual override signal
• 8-bit resolution
• Configurable safety position for outputs in case of
communication problems (remain, 0%, 50%, 100%)
11
EN0B-0564GE51 R0709
EXCEL 800 SYSTEM – PRODUCT DATA
Binary Input Modules
Fig. 14. XF823A Panel Bus BI Module (shown with XS823)
and XFL823A LonWorks Bus BI Module (shown without
socket)
The pluggable Excel 800 Binary Input Modules, with 12 binary
inputs, are available in the following versions:
• XF823A Panel Bus Binary Input Module
• XFL823A L
They are installed with the XS823 or XSU823 Terminal
Socket (incl. one connector bridge and one swivel label).
Accessory disconnector module: XS812 (see also Table 2 on
page 4).
ONWORKS Bus Binary Input Module
Features
• Static binary input (dry contact)
• Totalizer for up to 20 Hz
• LEDs per binary input supporting alarm display mode
(red/green) or status mode (off/yellow).
• Color mode of each LED can be set to OFF/yellow or
green/red in CARE.
Fig. 17. XFR824A Panel Bus Relay Output Module (shown
with socket) and XFLR824A LonWorks Bus Relay Output
Module (shown without socket)
The pluggable Excel 800 Relay Output Modules, with 6 relay
outputs, are available in the following versions:
• XF824A Panel Bus Relay Output Module (without manual
overrides)
• XFR824A Panel Bus Relay Output Module (with manual
overrides)
• XFL824A L
ONWORKS Bus Relay Output Module (without
manual overrides)
• XFLR824A L
ONWORKS Bus Relay Output Module (with
manual overrides)
They are installed with the XS824-25 or XSU824-25 Terminal
Socket (incl. one connector bridge, one cross connector, and
one swivel label).
Accessory disconnector module: XS812-RO (see also Table 2
on page 4).
- Optional versions with manual override switches (Auto, 0,
1; LED flashes in override mode)
- Feedback on manual override signal
- Configurable safety position for outputs in case of
communications problems (remain, OFF, ON)
- Permissible Load per Relay Output Module (Total)
•Max. load:
19…250 Vac: 12 A
1…24 Vdc: 12 A resistive, 3 A inductive
- Permissible Load per Normally-Open Contact:
•Max. load:
19…250 Vac: 4 A resistive or inductive
1…24 Vdc: 4 A resistive, 1 A inductive
•Min. load: P > 50 mW
- Permissible Load per Normally-Closed Contact:
•Max. load:
19…250 Vac: 2 A resistive, 1 A inductive
1…24 Vdc: 2 A resistive, 1 A inductive
•Min. load: P > 50 mW
13
EN0B-0564GE51 R0709
EXCEL 800 SYSTEM – PRODUCT DATA
Floating Output Module
Fig. 19. XFR825A Panel Bus Floating Output Module
(shown with socket)
The pluggable XFR825A Panel Bus Floating Output Module
(with manual overrides), with 3 floating outputs, is installed
with the XS824-25 or XSU824-25 Terminal Socket (incl. one
connector bridge, one cross connector, and one swivel label).
Accessory disconnector module: XS812-RO (see also Table 2
on page 4).
71
72
73
74
COM a
COM b
24V~
24V~0
COM a
S2S1
4
5
3
6
2
7
COM b
1
8
0
9
F
A
E
B
C
D
24V~
24V~0
75
76
77
78
Features
- Cross-Connecter
- 1 red LED (opening) and 1 green LED (closing) per
floating output
- Manual override potentiometers (Auto, 0%...100%; LED
flashes in override mode)
- Feedback on manual override signal
- Configurable safety position for outputs in case of
communication problems (remain, 0%, 50%, 100%)
- Permissible Load per Floating Output Module (Total)
•Max. load:
19…250 Vac: 12 A
1…24 Vdc: 12 A resistive, 3 A inductive
- Permissible Load per Normally-Open Contact:
•Max. load:
19…250 Vac: 4 A resistive or inductive
1…24 Vdc: 4 A resistive, 1 A inductive
•Min. load: P > 50 mW
- Permissible Load per Normally-Closed Contact:
•Max. load:
19…250 Vac: 2 A resistive, 1 A inductive
1…24 Vdc: 2 A resistive, 1 A inductive
Fig. 21. XF830A and XFU830A Mixed Panel Bus Modules
The mixed Excel 800 Panel Bus I/O modules, with 8 analog
inputs, 8 analog outputs, 12 binary inputs, and 6 relay
outputs, are available in the following versions:
• XF830A mixed Excel 800 Panel Bus I/O module, with
push-in terminals
• XFU830A mixed Excel 800 Panel Bus I/O module, with
screw terminals
Each features an integrated terminal socket and electronic
module and comes complete with one connector bridge and
one swivel label.
The XF830A can be equipped with up to two rows of (XS830
and/or XS831) auxiliary terminal blocks on the top and/or
bottom. The XFU830A can be equipped with up to two rows
of (XS830 and/or XS831) auxiliary terminal blocks on the top,
only.
Fig. 22. XF830A mixed Excel 800 Panel Bus I/O module,
shown with 4 optional aux. terminal blocks (top view)
71
COM a
COM b
72
73
24V~
24V~0
74
Install. Instr.
DI
EN1B-0375GE51
XFU830A
12 BI / 8 AI / 8 AO / 6 RO
24V, 15VA, T50
0706AX0001-XFU830A
8
Made in Germany
0532
1 234
4
5
3
6
2
7
24V for relay 1...5
1
8
0
9
S2
F
A
E
B
C
D
J1 J2 J3 J4 J5
10
11 12
Analog Inputs
AI5
AI6AI7 AI8
17
18 19 20
13 14 15 16
AI1 AI2AI3AI4 41
16 41 42
Analog Outputs
GND
AO5
25
G1 G2
21 22 23 24
42
AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
Binary Inputs
B7
B8 B9 B10 B11 B12
7
8 9 10 11 12
1 2 3 456
B1 B2 B3 B4 B5 B6
5 6 7 8 9
725 26 27 28 35 36 37 38 39 40
829310411512617131814191520
121 22 23 24 29 30 31 32 33 34
AO6 AO7 AO8
26 27 28 35
40
24V Relays
IN1 IN2 IN3 IN4 IN5 IN6
36 37 38 39 40
29 30 31 32 33 34
1 234
Fig. 23. XFU830A mixed Excel 800 Panel Bus I/O module,
shown without optional aux. terminal blocks (top view)
Features
- 1 yellow LED per output
- Configurable safety position for outputs in case of
communications problems (remain in last position, OFF,
ON)
- Permissible Load per mixed Excel 800 Panel Bus I/O
module (total)
•Max. load:
19…29 Vac: 3 A
1…24 Vdc: 3 A resistive, 3 A inductive
- Permissible Load per Normally-Open Contact:
•Max. load:
19…29 Vac: 0.5 A resistive or inductive
1…24 Vdc: 0.5 A resistive, 1 A inductive
•Min. load: P > 50 mW
15
EN0B-0564GE51 R0709
EXCEL 800 SYSTEM – PRODUCT DATA
Environmental Specifications
Ambient Temperature
Operation: 0...50 °C (32...122 °F)
Storage: -20...+70 °C (-4...+158 °F)
Ambient Humidity (Operation and Storage)
5 to 93% r.h. non-condensing
Table 5. Power consumption of XCL8010A
devices powered
XCL8010A* 190 mA 140 mA
watchdog load (terminal 4) < 500 mA < 500 mA
XF821A, XFL821A 130 mA 80 mA
XF822A, XFR822A 150 mA 90 mA
XFL822A, XFLR822A 160 mA 90 mA
XF823A, XFL823A 180 mA 130 mA
XF824A, XFR824A, XFR825A 140 mA 80 mA
XFL824A, XFLR824A 140 mA 90 mA
XF830A, XFU830A 200 mA 95 mA
supply voltage
24 Vac 24 Vdc
Mechanical
Housing Dimensions (H x W x D)
The XCL8010A Controller Module has the dimensions:
110 X 144 X 93 mm (see also Fig. 24 on page 17).
The pluggable Excel 800 I/O Modules (mounted on Terminal
Sockets) all have the dimensions: 110 X 90 X 93 mm (see
also Fig. 25 on page 17).
The mixed Excel 800 I/O Modules have the dimensions:
216 X 110 X 93 mm (see also Fig. 26 on page 18).
Housing Material
Plastic, flame-retardant
Mounting Methods
DIN-rail mounting (e.g. in control cabinet).
Calculated Lifetime of Weakest Components
MTBF ≥ 13.7 years (under typical operating conditions)
Protection Class
IP 20
Available Literature
• Mounting Instructions (EN1B-0359GE51);
• Installation Instructions (EN1B-0375GE51).
Norms, Standards
The Excel 800 System conforms to EN 60730-1:2005-12 and
EN 60730-2-9:2005-10.
EN0B-0564GE51 R0709
16
Dimensions
144
EXCEL 800 SYSTEM – PRODUCT DATA
92.75
110
45
28
32
Fig. 24. XCL8010A Controller Module, dimensions (in mm)
D = XS831 Aux. Terminal Package (optional)A, B, and C = XS830 Aux. Terminal Packages (optional)
Fig. 26. Mixed Excel 800 I/O Modules (example shows XF830A with 4 auxiliary terminal packages), dimensions (in mm)
External
40
24V
COM b
IN3
IN1 IN2
IN4
36 37 38 39 40
29 30 31 32 33 34
29 30 31 32 33 34
B
B1 B2B3B4
D
COM a
24V~
24V~0
IN5 IN6
DO
B5 B6 B7 B8 B9
76
77
78
Honeywell
!
110
69
28
15
SWIVEL LABEL HOLDER
51.5
92.5
38
SCREW-TYPE TERMINALS
(XFU830A)
45
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative: