• Pluggable I/O modules: I/O module exchange without
• Reuseability of existing applications (Excel 500, etc.)
• Fast wiring with state-of-the-art push-in terminals (screw-
• Wide range of sensors supported (NTC20kΩ, NTC10kΩ,
GENERAL
The Excel 800 System (consisting of the XCL8010A
Controller Module and connected Excel 800 Panel Bus and/or
Excel 800 L
highly cost-effective freely programmable control for heating,
ventilation, and air conditioning (HVAC) systems. It performs
a wide range of energy management functions, including
optimum start/stop, night purge, and max. load demand. The
Excel 800 System provides excellent value during installation
and long-term operation. Its modular design enables the
system to be expanded to meet growing needs.
The use of "plug & play" Excel 800 Panel Bus I/O modules
yields huge installation and commissioning cost-savings due
to new, patented technologies, while the Excel 800
L
ONWORKS Bus I/O modules employ the LONWORKS
communication standard.
The mixed Excel 800 Panel Bus I/O modules (XF830A and
XFU830A) consist of a terminal socket with an integrated
electronic module. The pluggable (i.e., non-mixed) Excel 800
Panel Bus (XF82x) or L
consist of a terminal socket and a removable electronic
module, allowing the socket to be mounted and wired before
the electronic module is installed. Such removable electronic
modules can be hot-swapped without disrupting the power
and bus connections. Software updates, configuration, and
commissioning are done automatically for all Excel 800 Panel
Bus I/O Modules.
The open L
rd
3
-party controllers and devices, and communication with
other CentraLine / Honeywell devices (e.g. Excel 10 and
Excel 12 room controllers).
Remote service can be done via a modem / ISDN terminal
adapter in connection with a building supervisor.
Direct Web is supported via Honeywell's OpenViewNet, which
may be connected via C-Bus to the Excel 800.
ONWORKS Bus input/output modules) provides
ONWORKS Bus (XFL82x) I/O modules
ONWORKS standard enables easy integration of
• Binary input LEDs can be configured for status display
• Configurable safety position for outputs, in case of loss of
• XCL8010A Controller Module with real-time clock.
• Max. wiring flexibility due to optional accessories like aux.
• Can be mounted in small installation housings.
• Flexible I/O module mix covering all your application
• Utmost flexibility to design and control your most complex
• State-of-the-art control of critical applications thanks to
• Fast firmware download (~90 sec) via serial connection.
• C-Bus to upgrade from and operate with existing
• Web access via optional OpenViewNet.
• Dedicated modem interface for remote operation.
• Human-Machine-Interface, Laptop connection.
Excel 800
SYSTEM
SPECIFICATION DATA
maintenance.
ONWORKS Bus I/O modules (FTT10-A, link power
compatible) for easy integration into any system.
rewiring the power and bus connections. Further, the
separate installation of terminal sockets and electronic
modules lower risk of damage and theft in the construction
phase.
type terminals also available) and bridge connectors.
PT1000-1/-2, NI1000TK5000, PT3000, Balco500,
0/2…10 V, 0/4…20 mA). NOTE: The mixed I/O modules
XF830A and XFU830A feature inputs suitable for signals
from NTC20kΩ sensors and 0/2…10 V, 0/4…20 mA, only!
(off/yellow) or alarm display (green / red) per channel.
NOTE: The mixed I/O modules XF830A and XFU830A
feature only non-configurable binary input LEDs!
communication with the Controller module.
terminals, manual disconnectors, and cross-connectors.
requirements.
applications through increased memory size.
short cycle times (30% faster than Excel 500).
Honeywell installations, thereby protecting your
investment.
The Excel 800 Controller Module (XCL8010A) can
communicate with a variety of other devices (see Fig. 4),
including any combination of up to sixteen Panel I/O
Modules and a large number of L
room controllers, L
ONWORKS I/O modules, 3
devices). The Excel 800 Panel Bus I/O Modules
communicate via the Panel Bus, while the Excel 800
L
ONWORKS Bus I/O modules utilize the LONWORKS
communication standard and can thus also communicate
with other L
ONWORKS controllers.
The pluggable I/O modules consist of a terminal socket
and a removable electronic module, allowing the socket to
be mounted and wired before the electronic module is
ONWORKS devices (e.g.
rd
-party
Internet
Browser
OVN = OpenViewNet
Web-enabled
via OVN
XLWeb
C-Bus
Existing
IO (XF8xx)
XFCxxxXFCLxxx
installed. All such electronic modules can be swapped out
without disrupting the power and bus connections: Simply
unplug the “old” and insert the “new” module.
Software updates, configuration, and commissioning are
all done automatically by the Excel 800 Controller Module
for all Panel Bus I/O Modules.
The Excel 800 Panel Bus I/O Modules are addressed
manually by adjusting their HEX switches.
The Excel 800 L
ONWORKS I/O Modules are configured
using CARE.
Alternatively, LonMaker and LNS plug-ins can also be
used for configuration.
XL500
Controllers
XL10/12
EN0B-0564GE51 R0709
2
EXCEL 800 SYSTEM – PRODUCT DATA
X
X
X
X
X
X
X
X
pluggable
FLOATING
OUTPUT
LonWorks
pluggable
ANALOG INPUT
pluggable
ANALOG OUTPUT
XFLR822A
pluggable
BINARY INPUT
pluggable
RELAY OUTPUT
XFLR824A
BUS MODULES
PANE L
XFL821A
XFL822AXFL823A
XFR822A
FL824A
FR824A
FR825A
BUS MODULES
XCL8010A
CONTROLLER MODULE
XF821A
XS821-22
XSU821-22
XF822AXF823A
S823
SU823
F824A
S824-25
SU824-25
LonWorks or Panel Bus
Fig. 2. Overview of Excel 800 Modules
Table 1. Overview of Excel 800 Modules
order number description
XCL8010A
Panel Bus I/O Modules
XF821A
XF822A
XFR822A
XF823A
XF824A
XFR824A
XFR825A
XF830A
XFU830A
LONWORKS Bus I/O Modules
XFL821A
XFL822A
XFLR822A
XFL823A
XFL824A
XFLR824A
Terminal Sockets (not needed for the mixed I/O modules XF830A and XFU830A)
XS821-22
XSU821-22
XS823
XSU823
XS824-25
XSU824-25
Excel 800 Controller Module
Pluggable Panel Bus Analog Input Module (with 8 analog inputs)
Pluggable Panel Bus Analog Output Module (with 8 analog outputs)
Pluggable Panel Bus Analog Output Module (with 8 analog outputs and manual overrides)
Pluggable Panel Bus Binary Input Module (with 12 binary inputs)
Pluggable Panel Bus Relay Output Module (with 6 relay outputs)
Pluggable Panel Bus Relay Output Module (with 6 relay outputs and manual overrides)
Pluggable Panel Bus Floating Output Module (with 3 floating outputs and manual overrides)
Mixed Panel Bus I/O Module (with 8 analog inputs, 8 analog outputs, 12 binary inputs, and 6 relay outputs), with
push-in terminals
Mixed Panel Bus I/O Module (with 8 analog inputs, 8 analog outputs, 12 binary inputs, and 6 relay outputs), with
screw terminals
ONWORKS Bus Analog Input module (with 8 analog inputs)
ONWORKS Bus Analog Output Module (with 8 analog outputs)
ONWORKS Bus Analog Output Module (with 8 analog outputs and manual overrides)
ONWORKS Bus Binary Input Module (with 12 binary inputs)
ONWORKS Bus Relay Output Module (with 6 relay outputs)
ONWORKS Bus Relay Output Module (with 6 relay outputs and manual overrides)
MIXED I/Os
XF830A, XFU830A
PANEL BUS I/O MODULES
3
EN0B-0564GE51 R0709
EXCEL 800 SYSTEM – PRODUCT DATA
Table 2. Overview of auxiliary parts and spare parts
order number description
XS812
Manual Disconnector Module for AI/AO/BI Modules (for manual disconnection of individual signals;
useful during start-up). Plugged between Terminal Socket and Electronic Module. For pluggable
I/O modules, only.
XS812RO
Manual Disconnector Module for Relay Output Modules (for manual disconnection of individual
signals; useful during start-up). Plugged between Terminal Socket and Electronic Module. Not
suitable for line voltage. For pluggable I/O modules, only.
XS814
Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block includes two
groups with seven internally-connected push-in terminals. For pluggable I/O modules, only.
Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block consists of
two groups of nine internally-connected push-in terminals. For XF830A and XFU830A, only.
Ten Auxiliary Terminal Blocks (for connection of 0…20 mA signals). Each terminal block supports
up to 8 current inputs. For XF830A and XFU830A, only.
20 Cross-Connectors for connection of six relay commons. One Cross-Connector is included in
the Terminal Socket package. For pluggable I/O modules, only.
XS817
40 Cross-Connectors for connection of three relay commons (if voltage in relay block 1 is different
from voltage in relay block 2). For pluggable I/O modules, only.
XS816
10 Bridge Connectors. One Bridge Connector is included in the Terminal Socket package / in the
mixed I/O module package.
XAL10
10 Swivel Labels Holders (for attaching the application-specific label printed with CARE). One
Swivel Label Holder is included in each Terminal Socket package. For pluggable I/O modules,
only.
XAL11
10 Swivel Label Holders for Mixed I/O modules. One Swivel Label Holder is included in each
mixed I/O module package. For mixed I/O modules, only.
XW586
RJ45
XW882
Modem cable for XCL8010A Controller Module.
Adapter cable for connection of XCL8010A Controller Module to XI582 Operator Interface
(alternatively, XW586 + XW582 can be used).
XW885
RJ45
NOTE: All Excel 800 I/O Modules (pluggable and mixed) are protected against short circuit, 24 Vac +20% and 30 Vdc.
Download cable (alternatively, XW586 + XW585 can be used).
be set per input
to OFF/yellow
or green/red
using CARE
relay outputs (default)
Features:
Changeover relays
Voltage: 19…250 Vac,
1…29 Vdc, P>50 mW
max. total current:
12 A
current per relay:
N.O.: 4(4) A ac. or
4(1) A dc,
N.C.: 2(1) A ac or
4(1) A dc
Safety position
(remain, 0%, 100%)
yellow LED per output
Version with manual
override (R):
1 switch per output
auto feedback signal
(mode + value)
blinking in manual
override position
Table 4. Mixed Excel 800 Panel Bus I/O module specifications
Number: 8
Characteristics:
Linear Graph 0..10 Vdc with
pull-up, 0(2)…10 Vdc without
pull-up
NTC20kΩ (-30…+110 °C,
default)
Features:
10-bit resolution
configurable offset per input
Number: 8
Characteristics:
0…11 Vdc / ± 1 mA, default
Also configurable as: binary
outputs (0 V / 10 V)
Features:
10-bit resolution (default)
Safety position (remain,
0%, 50%, 100%)
Number: 12
Characteristics:
static binary input (default:
dry contact)
ON: < 1.6 kΩ
OFF: > 90 kΩ
Also configurable as:
totalizers (15 Hz)
Features:
1 yellow LED per input
Number: 6
Characteristics:
relay outputs (default)
Features:
Voltage: 24 Vac/dc,
P>50 mW
max. total current: 3 A (ac
or dc)
current per relay: 500 mA
normally-open contacts: P
> 50 mW, voltage: 24 V (ac
or dc)
yellow LED per output
floating outputs
Features:
2 relays per
floating output
Voltage:
19…250 Vac,
1…29 Vdc,
P>50 mW
max. total current:
12 A
current per relay:
N.O.: 4(4) A ac or
4(1) A dc,
N.C.: 2(1) A ac or
4(1) A dc
1 potentiometer per
floating output
2 LEDs per output:
green: relay 1
closed, red: relay 2
closed
blinking in manual
override position
auto feedback sig-
nal (mode + value)
5
EN0B-0564GE51 R0709
EXCEL 800 SYSTEM – PRODUCT DATA
A
V
V
A
A
A
XCL8010A CONTROLLER MODULE
Fig. 3. XCL8010A Controller Module
The XCL8010A Controller Module can communicate with a
variety of other devices (see Fig. 4), including any combination of up to sixteen Panel I/O Modules and/or L
devices (e.g. room controllers).
A total of 381 data-points (of all types, e.g. internal virtual
data-points and hardware data-points) are permitted.
Typically, HVAC applications require an equal number of
internal virtual data-points and hardware data-points.
Up to 40 m distance between the XCL8010A and the Panel
I/O Modules.┴
The Excel 800 System (XCL8010 Controller Module and
connected Excel 800 I/O Modules together with field devices)
can be powered by one or more external transformers.
Memory
• 128 kB EPROM
• 512 kB RAM
• 2 MB Flash EPROM (firmware and application)
Watchdog
The watchdog output is active if the Excel 800 Controller
Module is not operating properly.
Microprocessor
16-bit processor (TMP 91 CY22). 22 MHz
Memory and Realtime Clock Backup
In case of power failure, the super capacitor saves RAM
content and real-time clock for 72 hours (environmentally
friendly; no problems disposing of dead batteries).
COM
75
A
COM
B
24
AC
24
V
78
C_
24
1
AC
24
V
2
C_
24
V
3
C_
*
4
NC
EN0B-0564GE51 R0709
6